DYNALINE Packaged Terminal Air Conditioner with Gas Heat

SUGGESTED ID SPECI!ICATI"NS
The supplier will provide packaged terminal gas heat/electric air conditioner of the sizes and
capacities shown on the schedule and listed in the specifications. Each unit shall consist of a
chassis, wall case/sleeve, outside grille and room cabinet.
Units shall be UL listed and/or C..!. design certified and shall be uburban "anufacturing
Compan# $%&!L'&E( ) models. The units shall be located as shown on the drawings.
Unit*s stead# state efficienc# shall be rated at +,- nominal and the EE. of the air conditioner
shall not be less than /,., EE..
Units shall be designed to operate on 0,+/0), volts, 1, 2z, single phase power.
Unit dimensions shall not e3ceed 405 wide and /15 high without optional air discharge package in
place, and not more than 00607/)05 from face of room cabinet to face of standard e3terior grille.
Units shall be designed to operate on &atural or L8 gas for the heating c#cle.
CHASSIS#
Unit chassis shall be a standard product of the manufacturer and shall be packed to prevent
damage when reasonable care is e3ercised during shipment. 9arnings on packaging shall alert
handlers to the hazards of improper handling or stacking.
Chassis shall slide into a standard6sized wall case and, after installation and testing, be read# to
operate. Each chassis shall consist of the following s#stem and components:
$ %e&rigeration s'stem constructed to isolate the hermeticall# sealed rotar#6t#pe compressor
from e3ternal vibration. The s#stem shall include copper/aluminum condenser and evaporator
coils with capillar# refrigerant control.
$ Air &low s#stem consists of a two6speed room air motor ;for 2i < Low !/C and 2i < Low heat
speeds= and a fan c#cle switch to permit continuous indoor fan operation. ! separate condenser
fan operates in the !/C c#cle onl#. The condenser fan, not operating in the heating mode,
eliminates the potential for e3haust gases to be drawn back and freezing in the chassis
compartment. The room air s#stem incorporates a tangential blower wheel for reduced noise and
increased efficienc#.
$ Condenser coils, with not less than /) fins per inch, and evaporator coils, with not less than //
fins per inch. Coils shall be constructed of copper/aluminum and fins shall be bonded to tubes to
prevent electrol#tic action.
$ Indoor and o(tdoor air&low which match the coil capacit# for efficient transfer of heat. $esign
of the unit shall prevent water blow6off on the indoor evaporator coil. 'ndoor suppl# air grille,
constructed of e3truded aluminum, shall discharge air at >0 degrees off vertical pattern.
$ Electrostatic ret(rn air &ilter, constructed of washable media, that installs and removes without
tools.
$ Gas)&ired heat e*changer, factor# installed with electronic controlled, pilotless ignition s#stem
and a ?draw6through@ negative draft combustion air s#stem. Aas ignition shall occur b# energizing
hot surface ignitor, which lights the burner on each thermostaticall# controlled heating c#cle. 2eat
e3changer shall be located in indoor air stream so as not to be visible or accessible through
indoor suppl# air grille.
$ To(ch +ad digital control for selecting temperature set point, heating, cooling and manual fan
operation. Control s#stem to incorporate computerized self6diagnostics to facilitate
troubleshooting.
$ "(tside air dam+er, positive closing and located within the chassis. !n accessible manual
control shall operate the damper.
$ Com+ressor ,lock)o(t- interface for use with standb# emergenc# power generator.
.ALL CASE#
9all case shall be insulated and constructed of /+6gauge galvanized and shall have a protective
baked6on enamel finish. Base pan shall be /+6gauge galvanized steel. Cases shall be installed
through e3terior walls where shown on the plans and shall be level from side to side and slope
//45 from front to rear to ensure proper operation of condensate s#stem. Case shall be secured to
the wall at both sides as shown in installation instructions. 'n no instance shall fasteners be used
through the base pan so as to protect the water integrit# of the base pan.
"UTSIDE G%ILLE#
pecial grilles to be supplied b# others must be submitted to the 8T!C manufacturer for feasibilit#
and air flow characteristics.
%""/ CAINET#
Each room chassis shall be eCuipped with a removable, wrap6around room cabinet constructed of
0,6gauge steel with a protective baked6on enamel finish similar to the wall case.
GAS TYPE#
&atural gas units shall be eCuipped with a gas valve having a built6in regulator set to operate at
the gas inlet suppl# pressure, minimum >5 9.C., ma3imum D5 9.C. Units burning L8 gas shall be
eCuipped with a gas valve having a built6in regulator set to operate at gas inlet suppl# pressures
of //5 9.C. minimum and /)5 9.C. ma3imum.
SE%0ICE#
Bidders shall submit complete information regarding service availabilit#, including address;es=
and phone number;s=, along with complete information of manufacturer address and phone
number to cover service information pertinent to installed eCuipment.
%ESP"NSIILITY !"% INSTALLATI"N1 STA%T)UP1 TESTING1 DE/"NST%ATI"N#
Units shall be installed in full accordance to the manufacturer*s recommendation. The
manufacturer shall not be liable for unit failure resulting from improper installation, which
invalidates the warrant#. Bidders shall specif# their responsibilities for the initial starting of units,
performing necessar# tests and adEustments to place units in proper operating condition and
demonstrating heating and cooling operations to the owner or the owner*s representative.
.A%%ANTY#
There shall be a one6#ear limited warrant# on parts and labor and a five6#ear limited warrant# on
the compressor and heat e3changer.
"PTI"NS
FFFF /1>D tamped Louver G clear anodized aluminum
FFFF /4/+ !rchitectural !luminum Louver 6 $ark Bronze Hinish
FFFF /40, !rchitectural !luminum Louver G !luminum Hinish
FFFF /1>/ !ir $ischarge !dapter G with grille 40@ Length
FFFF /10) E3tension for /1>/ G with grille 40@ Length
FFFF /104 Connector G 40@ duct goes between adapter and e3tension
FFFF /114! .ectangular Hront for use with /1>/ G $L)6,7/0 < $l)6/00,
FFFF /11>! .ectangular Hront for use with/1>/ G $L)6/100
FFFF >0,>4D 0 lb &atural Aas .egulator
FFFF /1//7+ 2eat/Cool "anual Changeover Thermostat
FFFF >0,+D) 4@ 2igh $ecorative Base 8anel
FFFF >0,11, !dEustable Legs ;0=
FFFF >0,770 Condensate $rain Iit