Sie sind auf Seite 1von 2

5/48

5
Characteristics (continued) 5
TeSys contactors 5
TeSys d
Contactor type LC1 D09
(3P)
DT20
D098
D12
(3P)
DT25
D128
D18
(3P)
DT32
D188
D25
(3P)
DT40
D258
Pole characteristics
Rated operational current (Ie)
(Ue y 440 V)
In AC-3, y 60 C A 9 12 18 25
In AC-1, y 60 C A 25 (1) 20 25 (1) 25 32 (1) 32 40 (1) 40
Rated operational voltage (Ue) Up to V 690 690 690 690
Frequency limits Of the operating current Hz 25400 25400 25400 25400
Conventional thermal current
(Ith)
y 60 C A 25 (1) 20 25 (1) 25 32 (1) 32 40 (1) 40
Rated making capacity
(440 V)
Conforming to IEC 60947 250 250 300 450
Rated breaking capacity
(440 V)
Conforming to IEC 60947 250 250 300 450
Permissible short time rating
No current flowing for preceding
15 minutes with y 40 C
For 1 s A 210 210 240 380
For 10 s A 105 105 145 240
For 1 min A 61 61 84 120
For 10 min A 30 30 40 50
Protection by fuses
against short-circuits
(U y 690 V)
Without thermal
overload relay, gG fuse
type 1 A 25 40 50 63
type 2 A 20 25 35 40
With thermal overload relay A See pages 6/16 and 6/17, for aM or gG fuse ratings corresponding to the associated
thermal overload relay
Average impedance per pole At Ith and 50 Hz m 2.5 2.5 2.5 2
Power dissipation per pole for
the above operational currents
AC-3 W 0.20 0.36 0.8 1.25
AC-1 W 1.56 1.56 2.5 3.2
Control circuit characteristics, a.c. supply
Rated control circuit voltage
(Uc)
50/60 Hz V 12690
Control voltage limits
50 or 60 Hz coils Operational
Drop-out
50/60 Hz coils Operational 0.81.1 Uc on 50 Hz and
0.851.1 Uc on 60 Hz at 60 C
Drop-out 0.30.6 Uc at 60 C
Average
consumption
at 20 C and at Uc
a 50 Hz Inrush 50 Hz coil VA
Cos 0.75
50/60 Hz coil VA 70
Sealed 50 Hz coil VA
Cos 0.3
50/60 Hz coil VA 7
a 60 Hz Inrush 60 Hz coil VA
Cos 0.75
50/60 Hz coil VA 70
Sealed 60 Hz coil VA
Cos 0.3
50/60 Hz coil VA 7.5
Heat dissipation 50/60 Hz W 23
Operating time
(2)
Closing "C" ms 1222
Opening "O" ms 419
Mechanical durability
in millions of operating cycles
50 or 60 Hz coil
50/60 Hz coil on 50 Hz 15
Maximum operating rate
at ambient temperature y 60 C
In operating cycles per hour 3600
(1) Versions with spring terminal connections:
16 A for LC1 D093 and LC1 D123 (20 A possible with 2 x 2.5 mm
2
cables in parallel),
25 A for LC1 D183 to LC1 D323 (32 A possible for LC1 D183 connected with 2 x 4 mm2
cables in parallel; 40 A possible for LC1 D253 and LC1 D323 connected with 2 x 4 mm2
cables in parallel).
(2) The closing time "C" is measured from the moment the coil supply is switched on to initial
contact of the main poles. The opening time "O" is measured from the moment the coil supply
is switched off to the moment the main poles separate.
Selection :
pages 5/160 to 5/191
References :
pages 5/58 to 5/61
Dimensions :
pages 5/82 to 5/85
Schemes :
pages 5/86 and 5/87
3/6
3
Characteristics 3
TeSys protection components 3
Thermal-magnetic motor circuit-breakers

Environment
Circuit-breaker type GV2 ME GV2 P GV3 ME GV7 R
Conforming to standards IEC 60947-1, 60947-2, 60947-4-1,
EN 60204, UL 508,
CSA C22-2 n 14,
NF C 63-650, 63-120, 79-130,
VDE 0113, 0660
IEC 60947-2,
60947-4-1,
NF EN, BS EN,
DIN EN 60 947.
IEC 60947-1,
60947-2, 60947-4-1,
EN 60947-1, 60947-2,
EN 60947-4-1,
NF C 63-650,
NF C 63-120, 79-130,
VDE 0113, 0660
Product certifications CSA, CEBEC,
GOST, TSE, UL,
BV, GL, LROS ,
DNV, PTB, EZU,
SETI, RINA,
CSA, UL, PTB,
EZU, GOST, TSE,
DNV, LROS, GL,
BV, RINA
CSA, UL, LROS DNV, UL
Protective treatment TH TC TC
Degree of protection
conforming to IEC 60529
Open-
mounted
IP 20 IP 20 IP 405
with terminal shields
In enclosure GV2 Mp01: IP 41
GV2 Mp02: IP 55
GV3 CE01: IP 55
Shock resistance
conforming to IEC 60068-2-27
30 gn -11 ms 22 gn -20 ms 30 gn -11 ms
Vibration resistance
conforming to IEC 60068-2-6
5 gn (5150 Hz) 2.5 gn (025 Hz) 2.5 gn (25 Hz)
Ambient air temperature Storage C - 40+ 80 - 40+ 80 - 40+ 80 - 55+ 95
Operation Open-
mounted
C - 20+ 60 - 20+ 60 - 20+ 60 - 25 + 70
In enclosure C - 20+ 40 - 20+ 40
Temperature compensation Open-
mounted
C - 20+ 60 - 20+ 60 - 20+ 60 - 25 + 55 (1)
In enclosure C - 20+ 40 - 20+ 40
Flame resistance
conforming to IEC 60695-2-1
C 960 960 960
Maximum operating altitude m 2000 3000 2000
Suitable for isolation
conforming to IEC 60947-1 7-1-6
Yes Yes
Resistance to mechanical impact J 0.5 0.5 0.5 0.5
In enclosure: 6
Sensitivity to phase failure Yes, conforming to IEC 60947-4-1 7-2-1-5-2
Technical characteristics
Circuit-breaker type GV2
ME
GV2
P
GV2
RT
GV3
ME06
ME25
GV3
ME40
ME63
GV3
ME80
GV7
Rp20...
Rp100
GV7
Rp150
GV7
Rp220
Utilisation category Conforming to IEC 60947-2 A A A
Conforming to IEC 60947-4-1 AC-3 AC-3 AC-3
Rated operational voltage (Ue)
conforming to IEC 60947-2
V 690 690 690
Rated insulation voltage
(Ui)
Conforming to IEC 60947-2 V 690 690 750
Conforming to CSA C22-2 n 14,
UL 508
V 600 600 (B600) 600
Rated operational frequency
conforming to IEC 60947-2
Hz 50/60 50/60 50/60
Rated impulse withstand voltage (U imp)
conforming to IEC 60947-2
kV 6 6 8
Total power dissipated per pole W 2.5 3 6 8 5 8.7 14.5
Mechanical durability
(C.O.: Closing - Opening)
C.O. 100 000 100 000 50 000 30 000 50 000 40 000 20 000
Electrical durability
for AC-3 duty
440 V In/2 C.O. 100 000 100 000 50 000 30 000 50 000 40 000 20 000
440 V In C.O. 30 000 20 000 10 000
Duty class (maximum operating rate) C.O./h 25 25 25
Maximum conventional rated thermal current (Ith)
conforming to IEC 60947-4-1
A 0.16
32
0.16
32
0.40
23
1.6
25
40
63
80 12
100
150 220
Rated duty conforming to IEC 947-4-1 Continuous duty
(1) For operation up to 70 C, please consult your Regional Sales Office.
References :
pages 3/44 to 3/49
Dimensions :
pages 3/62 to 3/67
Schemes :
pages 3/68 and 3/69

Das könnte Ihnen auch gefallen