Technical note ndeg3 is issued in order to give general information about the foreseen Nd3800 RCCP for intake and discharge offshore pipes. The intention of BONNA to suggest the realization of offshore water intake with two pipes lines but with reduced diameters at ND3800 internal diameter.
Originalbeschreibung:
Originaltitel
101129 MES Central Java - BONNA Technical (ND3800 Pipes for Offshore Installation)
Technical note ndeg3 is issued in order to give general information about the foreseen Nd3800 RCCP for intake and discharge offshore pipes. The intention of BONNA to suggest the realization of offshore water intake with two pipes lines but with reduced diameters at ND3800 internal diameter.
Technical note ndeg3 is issued in order to give general information about the foreseen Nd3800 RCCP for intake and discharge offshore pipes. The intention of BONNA to suggest the realization of offshore water intake with two pipes lines but with reduced diameters at ND3800 internal diameter.
Rev Modifications Date Made by Checked by Approved by Titre :
KARANG GENENG Coal Fired Power Plant Project Central Java
OFFSHORE
Technical note n3
Diffusion :
E. LASTENNET (BONNA INDONESIE)
BET.E
Doc n: Technical note n3
Project n: 5389-X
31 place Ronde, Quartier Valmy 92986 PARIS LA DEFENSE CEDEX : 33(0)1 46 53 24 00, : 33 (0)1 46 53 28 11
Doc n: Technical note n3 Rev. Date Lang. Sheet
Technical note n 3 00 29/11/2010 EN Page 2 of 4
S Su um mm ma ar ry y
1 Subject of this note .......................................................................................................................3 2 Input data ....................................................................................................................................3 3 ND 3800 geometrical and mechanical data .......................................................................................3 3.1 Geometrical data ..................................................................................................................3 3.2 Mechanical data....................................................................................................................4
Doc n: Technical note n3 Rev. Date Lang. Sheet
Technical note n 3 00 29/11/2010 EN Page 3 of 4
1 Subject of this note This note is issued in order to give general information about the foreseen Nd3800 RCCP for Intake and discharge offshore pipes. 2 Input data Project data Flow rate for one 1000 MW unit 160 000 m3/h 44.44 m3/s 2 Units supplied by the sea water intake 88.88 m3/s Actual design diameter of the Offshore water intake 1 = 5210 mm One line It is the intention of BONNA to suggest the realization of offshore water intake with two pipes lines but with reduced diameters at ND3800 internal diameter. 3 ND 3800 geometrical and mechanical data 3.1 Geometrical data
About End ring "L" About End ring "S" Joint S-L coupe type Typical S-L joint section Coffrage Coffering Embotement thorique Theoretical fitting depth 78 +0/-10 mm (-20 possible) (sauf pour, except for 300 and 250; voir, see NT216 3) Longueur utile Effective length Procdure d'embotement: voir NT 216 3 Deviation angulaire admissible: voir NT 216 3 Procdure de soudage:voir NT 216 4.1 et NT216-1 Procdure de contrle des soudures: voir NT416 Procdure de rejointoiement: voir NT216 4.2 et 4.3 Fitting instructions: refers to NT 216 3 Allowable angular deflection: refers to NT 216 3 Welding instructions: refers to NT 216 4.1 and NT216-1 Welding testing procedure: refers to NT416 Grouting instruction: refers to NT 216 4.2 and 4.3 Soudure extrieure pour diamtres: external welding for diameters: 250 <=<=1200 Soudure intrieure pour diamtres: external welding for diameters: 800 <= e i e e e p Doc n: Technical note n3 Rev. Date Lang. Sheet
Technical note n 3 00 29/11/2010 EN Page 4 of 4
tuyaux Bton arm me en tle a joints souds S-L Internal diameter: 3800 mm internal thickness 55 mm (*) External thickness 245 mm (*) Wall thickness: 300 mm External diameter: 4400 mm Average specific weight 25 kN/m3 (concrete and steel contents)
(*) subject to modification upon request. Depending on installation method the external concrete thickness can be reduced by several centimeter (max reduction value to be stated further) 3.2 Mechanical data
During installation: Maximal allowable flexure moment (longitudinal beam): Ml = 11 500 m.kN Relevant minimum local curvature radius Rmin = 4400 m Allowable traction (without curvature) Ft = 4400 kN Allowable jacking force (supposed applied on half external concrete face) Fj = 20 000 kN (non deviated) (2000 tons)
Section pre-assembled, according to the following sketch: Bearing with: effective supporting arch: 90 Bearing length >= 0.50 m L possible value: checked up to 40 m
Once laid on sea bottom: Allowable free span: Pipe immerged and full of water, without backfill 47 m