Improving Efficiency With Variable-Primary Flow
Michigan utility constructs new chilled-water plant as part of redevelopment
JAMES J. NONNENMANN, PE, Stanley Consultants Inc., Muscatine, Iowa, and
DANIEL J. FLYNN, PE, Lansing Board of Water & Light, Lansing, Mich.
In 2007, a partnership was formed by the city of Lansing,
Mich.; the state of Michigan; Accident Fund Insurance
Co. of America and its parent company, Blue Cross Blue
Shield of Michigan; developer and construction manager
The Christman Co.; Lansing Economic Development
Corp.; and Lansing Board of Water & Light (LBWL) to
renovate the decommissioned Ottawa Street Power
Station in Lansing into Accident Fund's new world
headquarters. The partnership required LBWL to construct a separate plant to provide
chilled water, which previously was supplied by equipment in the Ottawa Street Power
Station's basement.
LBWL contracted with Stanley Consultants to provide engineering and construction
services for the new Roy E. Peffley Chilled Water Plant. The consulting firm used four
new 2,000-ton electric centrifugal chillers in the Peffley plant, which replaced the
Ottawa Street Power Station's four 2,000-ton steam-turbine centrifugal chillers.
Additionally, one of the Ottawa facilitys 2,000-ton electric units was relocated to the
new plant.
Several goals were established for the new plant's construction:
Chiller Selection
First, the number and size of the chillers for the Peffley plant had to be determined. To
Advertisement
Blogs & Opinions
The Customer Isnt Always Right
by Lawrence (Larry) Clark, CEA,
GGP, LEED AP O+M
Posted 1 week ago
in Clark's Remarks
HVAC and Cloud Computing: More
Similar Than You Think
by Lawrence (Larry) Clark, CEA,
GGP, LEED AP O+M
Posted 3 weeks ago
in Clark's Remarks
Getting What You Pay For
by Lawrence (Larry) Clark, CEA,
GGP, LEED AP O+M
Posted 5 weeks ago
in Clark's Remarks
HOME > AIR CONDITIONING > IMPROVING EFFICIENCY WITH VARIABLE-PRIMARY FLOW
SHARE SHARE 0 Recommend Recommend
Improved energy and operational efficiency. To save energy, several environmentally
friendly, yet economical, choices were made by the plant's project team.
Complementary architecture. The new plant is visible in downtown Lansing, so the exterior
design was of critical importance.
Budget control and building information modeling (BIM). It was important to maintain costs
throughout the project and keep change orders to a minimum with the use of BIM.
Improved maintenance operations. Because maintenance access to equipment at the Ottawa
Street Power Station was extremely tight, LBWL sought to improve maintenance operations
at the new plant.
Blogs Columns
Comfortech Show
Subscribe Contact Us Newsletters Advertise With Us About Us Info-Dex RSS
Air Conditioning Building Controls Fire / Smoke Heating Humidity Control IAQ & Ventilation Motors / Drives Piping / Pumping Resources
REGISTER LOG IN
Improving Efficiency With Variable-Primary Flow | Air Conditioning conte...http://hpac.com/air-conditioning/improving-efficiency-variable-primary-0410
1 of 7 4/21/2014 3:57 PM
aid the chiller-selection process prior to design, the project team evaluated recent
historical data for the production and utilization of chilled water.
A historical review of chilled-water loads for the buildings to be served was completed,
and a load-duration curve was created (Figure 1). The curve indicated the chilled-water
system had a peak load just short of 5,000 tons. Although loads of 1,000 tons or less
occurred during most operational hours, LBWL expected loads to increase when new
buildings were added to the loop. As a result, 2,000-ton chillers were utilized and
part-load performance was maximized for the initial years of operation. Three chillers
were installed to meet peak load, and a fourth unit provided "N+1" redundancy.
Although the 2,000-ton electric motor-driven chiller was relocated to the new plant, it
was not placed into operation. It will be connected and placed into service after load
growth has occurred.
Energy/Operational Efficiency
Chilled-water pumping. The Ottawa Street Power Station's chilled-water plant utilized
a primary-secondary pumping scheme to deliver chilled water. A primary-secondary
system consists of two circuits: a constant-volume production loop (primary) and a
variable-volume distribution loop (secondary). The primary loop circulates chilled
water through chillers, and the secondary loop circulates chilled water through a
distribution system (Figure 2).1
Page 2 of 3
In the past, chiller manufacturers required a constant chilled-water flow rate through
evaporator tubes, necessitating a constant-flow loop. A secondary loop operated with
variable flow by utilizing variable-speed drives on pump motors. This allowed a system
to vary flow rate with cooling load via the positioning of two-way control valves. A
neutral bridge or decoupler was used to hydraulically separate the primary and
secondary loops. The hydraulic independence of each loop prevented variable flow in
E-MAIL:
COUNTRY:
J ohnson Controls recently announced it reached a
definitive agreement to acquire Canada Pension
Plan Investment... fb.me/2U5BNmIfE
HPAC Engineering
@HPACEng
@johnsoncontrols to acquire Air Distribution
Technologies: hpac.com/iaq-ventilatio #HVAC
Retweeted by HPAC Engineering
Scott Arnold
@ScottArnoldHPAC
E d
19 Apr
19 Apr
Tweets
Follow
Tweet to @HPACEng
Newsletter Signup
Si gn-up to r ecei ve our fr ee newsletter s
By clicking below, I acknowledge and agree to Penton's
Terms of Service and to Penton's use of my contact
information to communicate with me about Penton's or
its third-party partners' products, services, events and
research opportunities. Penton's use of the information
I provide will be consistent with Penton's Privacy
Policy.
SUBSCRIBE
Connect With Us
Improving Efficiency With Variable-Primary Flow | Air Conditioning conte...http://hpac.com/air-conditioning/improving-efficiency-variable-primary-0410
2 of 7 4/21/2014 3:57 PM
the secondary loop from influencing constant flow in the primary loop.2
With advances in chiller-control technology, chiller manufacturers now can allow flow
variation through an evaporator. As a result, the neutral bridge can be eliminated, and
a single set of pumps (with variable-speed drives) can be used to deliver chilled water.
Known as a variable primary-flow system, this allows flow to be varied according to
cooling load.
The constant-flow primary pumps within a primary-secondary system represent a large
energy user that remains constant as long as the pumps are in operation. No reduction
in this type of pump energy is possible with a decreasing cooling load. A variable-
primary-flow system has a single set of pumps that use only enough electrical energy
needed for the corresponding load. However, there is a limitation to the savings.
Chiller manufacturers typically limit the range of evaporator-tube velocities from 5 to
10 fps (although some chiller manufacturers allow a wider range), thereby limiting how
much flow and pump energy can be reduced. To protect chillers, a bypass is used to
prevent chilled-water flow from dropping below a set limit (Figure 3).
By converting from a primary-secondary to variable-primary-flow system, the project
team estimated pump energy was reduced by 10 to 20 percent. Variable-primary-flow
systems also can save energy by mitigating the effects of low-delta-T syndrome.
Low-delta-T syndrome. Chilled-water-plant performance is not simply the sum of a
plant's rated capacity; it must include the performance of the chilled-water-distribution
system. Inefficient use of chilled water results in a lower return-water temperature,
which, in turn, decreases chiller temperature differential (delta-T).3
Because a chiller's usable capacity is directly proportional to evaporator flow rate and
temperature differential, it follows that as delta-T decreases, so does a chiller's
capacity, unless there is a corresponding increase in chilled-water flow rate.
The causes of low-delta-T syndrome primarily are related to building operation and, in
many cases, cannot be controlled by chilled-water-plant operators. However, a
chilled-water plant can combat lower-than-desired delta-T using a variable-
primary-flow system to allow variable flow through a chiller evaporator.
The Peffley plant's variable primary flow. The Peffley plant's project team reviewed
hourly historical data from fiscal year 2007 (the most recent data at the time) to
determine the range of chilled-water delta-T. To complete the analysis, histograms and
data plots were developed. The histograms allowed the team to determine how much
the delta-T varied during the year and what delta-T the system experienced during the
majority of its operating hours.
Improving Efficiency With Variable-Primary Flow | Air Conditioning conte...http://hpac.com/air-conditioning/improving-efficiency-variable-primary-0410
3 of 7 4/21/2014 3:57 PM
The initial analysis revealed that the average annual delta-T for 2007 was 6.8F, but
the temperature had been lowered by the number of hours the system had operated on
free cooling. When these hours were disregarded, the average delta-T improved to
7.6F. Figure 4 shows the distribution of chilled-water temperature differential during
the "chiller season." For just over 60 percent of the chiller season, the delta-T was
8.0F or lower; this jumped to almost 80 percent for temperatures lower than 11.0F.
Because the Ottawa Street Power Station's chillers originally were designed for 14F,
there still was a significant amount of time during which the system experienced
low-delta-T syndrome.
LBWL's long-term goal is to operate the chilled-water system at a high delta-T.
Although this is not likely to occur for a while, the variable primary-flow system can
help the plant handle periods of low delta-T in the interim.
Design temperature differential and operating range. Because of the range of
operating delta-Ts, the project team's next challenge was to determine the plant's
design temperature differential. To make this determination, the team investigated the
performance, flow range, and costs of several 2,000-ton chillers optimized at delta-Ts
within the range described in Figure 4. First, chiller performance was evaluated for a
range of chilled-water temperature differentials. Selections were solicited from multiple
manufacturers, and it was determined that chiller performance (non-standard
part-load value) was comparable at differing delta-Ts with only a 2-percent difference
over the range considered. Because energy performance was not a deciding factor in
selecting design delta-T, other factors were considered to evaluate performance at
off-design conditions.
Page 3 of 3
With delta-Ts of 5F to 14F, the flow rate of the 2,000-ton chillers varied from 9,600
to 3,430 gpm. Upon further consideration, the delta-T range was changed to 7F to
16F (6,800 to 3,000 gpm) to stay below the maximum flow rate allowed by chiller
manufacturers and allow the desired 16F delta-T to develop over time.
Finally, the chillers' capital costs were considered; they did not vary significantly until
a delta-T of 8F was reached. The cost of the chiller then increased, resulting in a
premium for design optimization up to this point.
Based on these factors, the project team selected a design delta-T of 10F, with an
operating range between 7F and 16F. The Peffley plant is capable of handling lower
delta-Ts without limiting its ability to operate at a higher delta-T in the future. With
the implementation of a variable primary-flow system and the selected operational
delta-T range, the project team estimated a chiller energy savings of 2 to 4 percent.
Free cooling. Another energy-saving measure included the use of a 2,000-ton
free-cooling heat exchanger. It allows chillers to be shut down when it is cool outside
and the building cooling load is low. The system transfers heat directly from chilled
Improving Efficiency With Variable-Primary Flow | Air Conditioning conte...http://hpac.com/air-conditioning/improving-efficiency-variable-primary-0410
4 of 7 4/21/2014 3:57 PM
water to condenser water, offsetting the need for operating chillers. Relocated from
Ottawa, the heat exchanger utilizes the same chilled-water distribution pumps and
condenser water pumps that the chillers employ. Therefore, the additional cooling
system required a minimal capital investment for piping, valves, and controls.
LBWL uses the free-cooling system instead of a centrifugal chiller from December
through February. The free-cooling system allows LBWL to meet most of the daily
chilled-water demand in periodic service runs during late fall and early spring, weather
permitting. At a design temperature of 44F, the system is capable of producing an
amount of chilled water equivalent to that produced by an electric centrifugal chiller.
The free-cooling system's number of operational hours offsets the need for electrically
generated chilled water, saving energy and reducing the building's carbon footprint.
Architectural Considerations
The Peffley plant is located near the heart of downtown Lansing on the Capitol Loop
highway, near the state capitol building and several state office buildings. A primary
project objective was to integrate the plant into the surrounding architecture.
Because of site space considerations, eight cooling-tower cells were located on the
plant's roof. To conceal them, the project team used architectural louver screens, but
the screens made the building mass too large. Horizontal and vertical exterior-
insulation-finishing-system accents were added to break up the mass. The vertical
accents provided an opportunity to include colored light-emitting diodes to accentuate
these features during night hours. A combination of decorative masonry block, brick,
and glass was used to construct the building.
Budget Control and BIM
The project operated under a very tight budget. To help minimize the possibility of
change orders during construction, the project was designed utilizing BIM. This design
approach integrates current technology with the design process to improve
communication, identify potential problems early, and provide engineers and designers
with vital resources.
BIM software modeled the plant in 3D with an interference manager to identify
potential conflicts early in the design process. The software produced structural models
with analytical features; architectural models for uses such as space planning;
mechanical models of equipment, piping, and HVAC systems; electrical models of
equipment and cable tray; and a database linked to piping and instrumentation
diagrams with information on valves and instruments. The models then were used to
produce traditional construction drawings, specifications, and data sheets. The
resulting BIM model provided LBWL personnel and the project construction manager
with valuable information on the project design and assisted in resolving clarifications.
Change orders totaled less than 2.4 percent of the project contract value, and the
project was completed within its $20 million budget.
Maintenance Operations
Despite limited site space, another project objective was to improve accessibility for
equipment maintenance. To this end, equipment was arranged to preserve an
open-access aisle on the operating floor, which allows equipment removal without
interruption of plant operations. Additionally, the operating floor was designed so
chillers and heavy electrical equipment could be moved without the need for floor
shoring.
To further facilitate maintenance, monorails were provided over each chiller driveline
and for each row of pumps. For equipment removal/installation in the basement, a
floor access hatch was included. Lastly, piping and equipment design included valve
operators at accessible locations wherever practical and ensured those out of reach
Improving Efficiency With Variable-Primary Flow | Air Conditioning conte...http://hpac.com/air-conditioning/improving-efficiency-variable-primary-0410
5 of 7 4/21/2014 3:57 PM
Tweet
E-MAIL:
COUNTRY:
could be accessed by a lift.
Summary
The redevelopment of downtown Lansing provided LBWL with an opportunity to
improve the operation and maintenance performance of its chilled-water system. The
project converted the primary-secondary system to a variable primary system and
maintained the free-cooling system, reducing energy consumption and carbon
footprint. Additionally, LBWL constructed an industrial facility without compromising
the aesthetics of the downtown area.
References
1) Nonnenmann, J. (2006, February). Chilled water plant pumping schemes. Paper
presented at the International District Energy Association Campus Energy Conference,
Albuquerque, N.M. 2) McCauley, G., & Strause, R. (1996, September). Chilled water
distribution pumping schemes. Paper presented at the Central Association of Physical
Plant Administrators (CAPPA) Annual Meeting, San Antonio, Texas. 3) Durkin, T.
(2005). Evolving design of chiller plant. ASHRAE Journal, 47, 40-46.
A senior mechanical engineer and project principal for Stanley Consultants Inc., James
J. Nonnenmann, PE, is responsible for business development, mechanical design, and
evaluation related to central energy plants, power generation, and building mechanical
systems. He holds a bachelor's degree in mechanical engineering from the University of
Illinois, Urbana-Champaign. He can be contacted at
nonnenmannjim@stanleygroup.com. A principal mechanical engineer and project
manager for Lansing Board of Water & Light, Daniel J. Flynn, PE, is responsible for
consulting, project management, and design related to the utilities' production and
distribution facilities. He holds a bachelor's degree in mechanical engineering from
Michigan Technological University. He can be contacted at djf@lbwl.com.
Low-Delta-T Syndrome
Causes of low-delta-T syndrome include:
Did you find this article useful? Send comments and suggestions to Associate Editor
Megan White at mailto://megan.white@penton.com.
Newsletter Signup
Si gn-up to r ecei ve our fr ee newsletter s
By clicking below, I acknowledge and agree to Penton's Terms of Service and to Penton's use of my contact
information to communicate with me about Penton's or its third-party partners' products, services, events and
Improper coil or control-valve selection.
Dirty coils.
Mismatched design conditions.
Three-way control valves, which allow bypass of chilled water around a coil at part-load
conditions, result in lower return-water temperatures for all conditions except design. The
mixing of the chilled-water supply and return water results in a lower-than-design delta-T,
contributing to low delta-T syndrome.
Supply/return mixing at building decoupler.
Arbitrary lowering of supply-air-temperature set point.
Coil piping configuration. Coils must be piped so water is counterflow to air. If coils are piped
in reverse, the coil's heat-transfer efficiency will decrease, resulting in lower chilled-water
return temperatures.
SHARE SHARE 0 Recommend Recommend
Improving Efficiency With Variable-Primary Flow | Air Conditioning conte...http://hpac.com/air-conditioning/improving-efficiency-variable-primary-0410
6 of 7 4/21/2014 3:57 PM
Site Features
Media Center
RSS
Sitemap
Site Archive
Newsletters
View Mobile Site
HPAC Engineering Corporate
Privacy Policy
Terms of Service
Contact
Follow Us
Search HPAC.com
Contracting Business Contractor HVAC-Talk Comfortech 2013 Show HVACR Distribution Business Radiant Living
Fire Protection Engineering
HPAC.com
Air Conditioning Building Controls Fire / Smoke Heating Humidity Control IAQ & Ventilation Motors / Drives Piping /
Pumping
Mechanical Systems Sites
Copyright 2014 Penton
research opportunities. Penton's use of the information I provide will be consistent with Penton's Privacy Policy.
SUBSCRIBE
Please Log In or Register to post comments.
Related Articles
Improving Efficiency With Variable-Primary Flow
Converting From Primary/Secondary to All-Variable Flow
AERCO Named Manufacturer of the Year by Rockland Economic Development Corp.
Primary/Secondary-Loop vs. Primary-Loop-Only Systems
Design Criteria for Primary/Secondary and Primary-Loop-Only Systems
Improving Efficiency With Variable-Primary Flow | Air Conditioning conte...http://hpac.com/air-conditioning/improving-efficiency-variable-primary-0410