Scope of this proposal



This offer covers the design, manufacturing, testing and commissioning of Singapore Jurong Refinery
Relay & Metering panels.

Some necessary detail information related to SCADA system has not yet been confirmed. All the Relion 600
IED provide the optical Ethernet port and IEC61850 protocol. The Ethernet switches are not in our scope.

2. Summary

This document describes ABBs proposal for Singapore Jurong Refinery Relay & Metering panels.

ABBs Protection and Control solutions are future proof as they are compliant to international standards
like IEC 61850, and by that simplify maintenance and enable interoperability.

A. Scope of supply
1. Relay and Metering panels Qty. 8 Nos.
2. Line protection panel Qty. 1 no.
3. Synchronizing panel Qty. 1 no.
4. Marshalling panel for above R&M panels Qty. 1 No.
5. SPPG Metering panel Qty. 2 Nos.
6. Generator metering panel Qty. 1 Nos. (Optional)
7. Transducers panel Qty. 0 no.(Transducer will be mounted in relay and metering
panels)


3. Configuration Introduction

We recommend to use ABB Relion IED in bay level solution.The Relion

product family offers widest


range of products for protection, control, measurement and supervision for power systems. To
ensure interoperable and future-proof solutions, Relion products have been designed to implement
the core values of the IEC 61850 standard. With ABBs leading-edge technology, global application
knowledge and experienced support network, you can be completely confident that your system
performs reliably - in any situation.

3.1. Relay and Metering Panel
No Item Type
Qt
y
Total Brand Description
1.
1
Relay and Metering Panel 8
1
Bus bar Diff.
Relay
REB670
(12I,16BI+24BO,1*IRIG-
B,1*IEC61850)
2 16 ABB
87B1-1,87B1-2 - - -
87B8-1,87B8-2
2
Directional OC
and overvoltage
Relay
REF615F
(4I+4U,16BI+10BO,1*IRIG-
B,1*IEC61850)
1 8 ABB 67/67N,59V0.1-0.8
3
Current Backup
relay
REF615D
(4I,12BI+10BO,1*IRIG-
B,1*IEC61850)
1 8 ABB Current
4
Breaker failure
relay
REF615D
(4I,12BI+10BO,1*IRIG-
B,1*IEC61850)
1 8 ABB 50BF.1-8
5 Lock-out Relay RXMD2 4 32 ABB
6 Test block RTXP24 5 40 ABB
7
Measurement
transducers
3V,3I,f,P,Q,cos 10 80 SAC
8 Protection Panel 2260*800*800 1 8 SAC






3.1.1. Bus bar protection REB670

The numerical, low-impedance differential protection function is designed for fast and selective
protection for faults within protected zone. All connected CT inputs are provided with a restraint
feature. The minimum pick-up value for the differential current is set to give a suitable sensitivity for
all internal faults. For busbar protection applications typical setting value for the minimum differential
operating current is from 50% to 150% of the biggest CT. This setting is made directly in primary
amperes. The operating slope for the differential operating characteristic is fixed to 53% in the
algorithm.
The fast tripping time of the low-impedance differential protection function is especially advantages
for power system networks with high fault levels or where fast fault clearance is required for power
system stability.
The advanced open CT detection algorithm detects instantly the open CT secondary circuits and
prevents differential protection operation without any need for additional check zone.
Main feature of REB670:
Typically operate time:12ms
The low CT requirements guarantee stability and correct operation as long as the CT is
not saturated for at least two milliseconds during each power system cycle
maintain complete stability for external faults, even when heavy CT saturation occurs.
No limit for the CT ratio of each bays
Open CT check and indications
Dynamic linking of measured CT currents, Efficient merging of the two differential zones, and
Disconnector and/or circuit breaker status supervision
Complete Back-up Protection: breaker failure protection and 4-step overcurrent protection.
REB670 IED provides selective, reliable and fast fault clearance for all types of internal phase-
to-phase and phase-to earth faults in solidly earthed or low impedance earthed power systems.
REB670 IED continues ABBs strong track record in busbar protection


3.1.2. Directional OC and overvoltage/Current Backup/Breaker Failure relay REF615

REF615 is a dedicated feeder IED (intelligent electronic device) designed for the protection, control,
measurement and supervision of utility substations and industrial power systems including radial,
looped and meshed distribution networks with or without distributed power generation.
REF615 D is non-directional overcurrent and non-directional earth-fault protection, CB condition
monitoring, CB control and with the optional I/O module control of two network objects.

Main protection: 3I>, I
0
>
Non-dir E/F protection, residual connection
Phase discontinuity protection
Breaker failure protection
Auto-reclosing
Arc protection for reduced cubicle damage and increased personnel safety
Harmonics based E/F protection available as an option for std. conf. D

REF615 F is directional overcurrent and directional earth-fault protection with phase-voltage
based measurements, undervoltage and overvoltage protection, CB condition monitoring and
CB control.


Main protection: 3I> , I0>
Directional E/F protection, sensitive E/F protection, transient/intermittent E/F protection,
core-balance CT connection
Admittance, wattmetric or harmonics based E/F protection is available as an option
Phase discontinuity protection
Auto-reclosing
Thermal overload protection
Breaker failure protection
Fuse failure supervision
Current circuit supervision
Arc protection for reduced cubicle damage and increased personal safety
Including phase voltage, energy, power and power factor measurements



3.2. Line Protection Panel:
66kV Line protection configuration is as below
1.2 Line Protection Panel for 66kV PG Cubicle 1
1
66kV Cable
Differential
Protection Relay
RED670
(6I+6U,16BI+24BO,1*IRIG-
B,1*LDCM SM
65kM,1*IEC61850)
4 4 ABB
87L.4-1,87L.4-2
87L.7-1,87L.7-2
2 Test block RTXP24 4 4 ABB
3 Protection Panel 2260*800*800 1 1 SAC

3.2.1. Line Differential Relay RED670

RED670 is used for the protection, control and monitoring of overhead lines and cables in all types
of networks. The IED can be used from distribution up to the highest voltage levels. It is suitable for
the protection of heavily loaded lines and multi-terminal lines where the requirement for tripping is
one-, two-, and/or three-phase. Meanwhile, RED670 is capable of transferring 8 high-speed signal.


Protection for two to five line terminal applications
Power transformer in the protected zone
Tapped lines
With transformers
Short lines
Long lines with charging current compensation
Control and interlocking
Monitoring
3.3. Synchronization Panel
1.3 synchronization check panel Cubicle 1
1
Digital Auto
Synchronize
SYN5201 1 1 ABB Up to 7*Sync-check point
2
Backup and manual
Synchronize
DT-1/220+MZ-
10+Auxiliary Relay
1 1 SAC Up to 7*Sync-check point
3 Panel 2260*800*800 1 1 SAC

3.3.1. Digital Auto Synchronize SYN5201


The SYNCHROTACT 5 digital synchronizer is used for automatic synchronizing and paralleling
of generators with lines and for the paralleling of already synchronous lines. The device is
designed for system frequencies of either 50/60 Hz or 16 2/3 Hz.

SYN 5201 is a single-channel synchronizing device whose component choice and software
design provides the highest security against incorrect paralleling.


3.4. Marshaling Panel
1.4 Marshalling Panel 1
1 Panel 2260*800*800 1 1 SAC

Marshaling Panel will meet requirement as below
a. Marshalling panel wired with terminals for all external cables and communication cables.
b. One marshalling panels shall be provided to facilitate the interface between the GIS equipment
and the auxiliary panels and external systems (e.g. Alarm Panel, etc.).
c. Minimum I/O signals number to be managed by the marshaling panel is 100.
d. Terminals strips shall be realized with voltage free contacts.
e. Contacts on the outgoing terminal strip towards external systems shall be knife type.
f. All terminal strips shall be duplicated and installed face to face, eventual cross-wiring shall be
realized on the faced sides while the other two sides shall be dedicated one for interconnection with
Vendor systems and the other one for the interconnection with external systems. At least 20 % of
spare terminals shall be guaranteed.
3.5. SPPG Metering Panel
1.5 SPPG Metering Panel 2
1 Main Meter from PG Provided by Power Grid 1 2 /
2 Check Meter from PG Provided by Power Grid 1 2 /
3 Check Metering CEWE Prometer 0.2S 1 2 CEWE
4 Panel 2260*800*800 1 2 SAC

3.5.1. CEWE Pro eter


Cewe Prometer Energy meter in class 0.2S.
Three serial communication ports alternatives
More than one year logging memory
Instantaneous values with high accuracy
Shows harmonics and power quality
Easy to configure
Open protocol, IEC 62056-21 and DLMS
Built in terminal
Supported by Cewe Cetrics, Grlitz, Itron, Rejlers, Kamstrup, Frschel, nergy
ICT and ELIN softwares

3.6. Generator Metering Panel (Optional)
1.6 GeneratorMetering Panel (Optional) 1
1 Meter CEWE Prometer 0.2S 4 4 CEWE
2 Protection Panel 2260*800*800 1 1 SAC

3.7. Auto Voltage Regular (Optional)
Automatic voltage control for tap changer TR8ATCC and Tap changer control and supervision, 6
binary inputs TCMYLTC are used for control of power transformers with a on-load tap changer. The
functions provide automatic regulation of the voltage on the secondary side of transformers or
alternatively on a load point further out in the network.
Control of a single transformer, as well as control of up to two transformers within a single RET650,
or parallel control of up to four transformers in two or even four separate RET650 is possible. Note
that the last alternative is achieved by using the GOOSE interbay communication on the IEC 61850-
8-1 protocol. For parallel control of power transformers, three alternative methods are available, the
master-follower method, the circulating current method and the reverse reactance method.
In RET650 a local HMI page with voltage control status and manual control possibilities is available.
Manual control is under authority control if so defined.
Voltage control includes many extra features such as possibility of to avoid simultaneous tapping of
parallel transformers, extensive tap changer monitoring including contact wear and hunting
detection, monitoring of the power flow in the transformer so that for example, the voltage control
can be blocked if the power reverses etc.
In manual operating mode it is possible to give raise- or lower-commands to the load tap changer
from the local HMI. Such facilities are premade in the factory.
4. Scope of supply
No
.
Item Type Qty
Tota
l
Brand Description
1.
1
Relay and Metering Panel 8
1
Bus bar
Protection
relay
REB670
(12I,16BI+24BO,1*IRIG-
B,1*IEC61850)
2 16 ABB
87B1-1,87B1-2 - - -
87B8-1,87B8-2
2
TR. HV
Protection
relay
REF615F
(4I+4U,16BI+10BO,
1*IRIG-B,1*IEC61850)
1 8 ABB 67/67N,59V0.1-0.8
3
Current HV
Protection
relay
REF615D
(4I,12BI+10BO,1*IRIG-
B,1*IEC61850)
1 8 ABB Current
4
Breaker
failure
Protection
relay
REF615D
(4I,12BI+10BO,1*IRIG-
B,1*IEC61850)
1 8 ABB 50BF.1-8
5
Lock-out
Relay
RXMD2 4 32 ABB
6 Test block RTXP24 5 40 ABB
7
Measureme
nt
transducers
3V,3I,f,P,Q,cos 10 80 SAC
8
Protection
Panel
2260*800*800 1 8 SAC
1.
2
Line Protection Panel for 66kV PG
Cubicl
e
1
1
66kV Cable
Differential
Protection
Relay
RED670
(6I+6U,16BI+24BO,1*IRI
G-B,1*LDCM SM
65kM,1*IEC61850)
4 4 ABB
87L.4-1,87L.4-2
87L.7-1,87L.7-2
2 Test block RTXP24 4 4 ABB
3
Protection
Panel
2260*800*800 1 1 SAC
1.
3
synchronization check panel
Cubicl
e
1
1
Digital Auto
Synchronize
SYN5201 1 1 ABB
Up to 7*Sync-check
point
2
Backup and
manual
Synchronize
DT-1/220+MZ-
10+Auxiliary Relay
1 1 SAC
Up to 7*Sync-check
point
3 Panel 2260*800*800 1 1 SAC
1.
4
Marshalling Panel 1
1 Panel 2260*800*800 1 1 SAC
1.
5
SPPG Metering Panel 2
1
Main Meter
from PG
Provided by Power Grid 1 2 /
2
Check Meter
from PG
Provided by Power Grid 1 2 /
3
Check
Metering
CEWE Prometer 0.2S 1 2
CEW
E

4 Panel 2260*800*800 1 2 SAC
1.
6
GeneratorMetering Panel (Optional) 1
1 Meter CEWE Prometer 0.2S 4 4
CEW
E

2
Protection
Panel
2260*800*800 1 1 SAC
1.
7
Auto Voltage Regular (Optional) 1
1 AVR RET650 A07 1 1 ABB