GENERATOR PROTECTION RELAY FOR PRIMARY DISTRIBUTION

Dimensions (mm)
Connection & Functions
The SL-G is a relay for the protection of generators which is able to protect a generator by
means of current, voltage and frequency functions.
t is normally used in Cogeneration in power stations from gas, steam, hydraulic turbine, or
diesel driven generators.
SL-G monitors differences in voltage magnitudes, phase angles, and frequencies to perform
synchronism checks across the circuit breaker. This function can be coordinated with the
auto-reclose function (up to five recloses).
SL-G is used with auxiliary power supply (110-230 Vac/ 90-300 Vdc and optionally 24-48 Vdc).
Protection functions available in SL-G are the following:
81R, 78, 81 U/O, 27P, 32/40, 59P, 59N, 25, 79, 50P, 50N/G, 67P, 67N, 46, 79, 50BF, 52, 49, 86,
CLP, 49T, 74TCS, 37 and RG-B.
SL-G has metallic box with high electromagnetic compatibility level (EMC) and wide range of
operating temperature.
ts reduced size makes the SL-G relay easy to install and its light weight helps the customer to
save costs in transport.
1
7
7
.8
241.3
1
7
7
.8
1
6
1
.8
241.3
216.36
116.75
103
1
6
1
.8
229
1
0
1
.6
1
0
1
.6
1
6
5
3
1
.7
3
1
.75

6
6

6
219 5
CUTOUT
Dimensions (mm)
Functions diagram
SIL-G
74TCS Events (1000)
RTC (1ms)
Oscillography (2)
Setting table (3)
Fault report (20)
Leds cong. (6)
Out cong. (7)
Test
Inputs cong. (8)
SIL-G
32/40
CLP
G
50N/G
(2)
50N/G
(2)
67N
(2)
67N
(2)
59N
27P 59P
59N
27P 59P
50BF 46 49
32/40 32/40 32/40
50P 50P 67P
(1)
67P
(1)
52
Hmi
6 keys+52+79+Reset
LCD 20x2
79
81 U/O 81 U/O 81 U/O 81 U/O
52
25 81R 78
37 37
ModBus RTU
RS485
IEC 60870-5-103*
IEC 61850*
IEC 60870-5-104*
DNP3.0*
RS485
IRIG-B
Ethernet
67P 50/51P
67N 50/51 N/G
USB
SICom
67P
(1)
ModBus
RTU.
Tx
Rx
67N
(2)
86
49T
t
Model list
Tel.: (+34) 94 471 14 09 - Fax.: (+34) 94 471 05 92 - www.fanox.com - fanox@fanox.com 03/2014/Rev1
Fanox reserves the right to modify technical of products
contained within this document without previous notice.
Selection & Ordering data
Technical parameters
SILG 1 5 6 B 4 3 0 1 D A SILG156B4301DA

SILG 1 5 6
Example of ordering code:
Function Description
81R Frequency rate of change protection 4
78 Out of step protection (Vector Shift) 2
81 U/O Under / over frequency protection 4
27P Phase undervoltage protection 2
32/40
Dened time directional overpower
protection
4
59P Dened time phase overvoltage protection 2
59N Dened time neutral overvoltage protection 2
25 Synchronism check 1
79 Autorecloser 1
37 Phase undercurrent protection 2
50P Instantaneous phase overcurrent protection 2
50N/G
Instantaneous neutral overcurrent
protection
2
67P Inverse time phase overcurrent protection 2
67N Inverse time neutral overcurrent protection 2
46
Negative sequence inverse time overcurrent
protection
1
49T /
External trip
Overtemperature protection 1
49 Thermal overload protection 1
52 Control & monitoring of circuit breaker 1
50BF Circuit breaker failure 1


Function Description
86 Latching 1
CLP Cold Load Pickup 1
74TCS Trip Circuit Supervision 1
Auxiliary
Supply
Single-powered at 24-48 Vdc Optional
Single-powered at 90-300 Vdc / 110-230 Vac Optional
Measures
Neutral and phase measure accuracy 2% over
band of 20% of rated current and 4% over the
rest of the range. Neutral and phase voltage
measure from 4V to 130V

Inputs &
Outputs
Auxiliary inputs 8
Auxiliary outputs 7
Communi-
cation
Local port: USB (ModBus RTU, 19200)
Remote port RS485: ModBus RTU


Remote port RS485: IEC 60870-5-103
Remote port RJ45: IEC 61850, DNP3.0 or IEC
60870-5-104
Optional
Records
Events 1000
Oscillography (10 cycles pre-fault & 128 post-fault) 2
Fault Report 20
RTC (Real Time Clock)
Signalling
HMI: LCD, 20x2 and 10 keys
LEDs Indicators 8

Optional
SILG SELECTION & ORDERING CODES PROTECTION FUNCTIONS
81R(4) + 78(2) + 81U/O(4) + 59P(2) + 59N(2) + 27P(2)
+ 32/40(4) + 25 + 79 + 37(2) + 50P(2) + 67P(2) +
50N/G(2) + 67N(2) + 46 + 52 + 50BF + 74TCS + CLP
+ 49 + 86 + 49T

1
5
PHASE MEASUREMENT
In = 1 A; (0.10 30.00 A)
In = 5 A; (0.50 150.00 A)

1
5
NEUTRAL MEASUREMENT
In = 1 A; (0.10 30.00 A)
In = 5 A; (0.50 150.00 A)

5
6
NET FREQUENCY
50 Hz
60 Hz

A
B
POWER SUPPLY
24 - 48Vdc
90 300Vdc / 110 230Vac

4
ADDITIONAL FUNCTIONS
+ IRIG-B

0
1
2
3
4
5
REAR COMMUNICATIONS
IEC 60870-5-103 + ModBus (RS485)
IEC 60870-5-103 + ModBus (FOP)
IEC 60870-5-103 + ModBus (FOC-ST)
IEC61850 + ModBus (RS485)
DNP3.0 (TCP/IP) + ModBus (RS485)
IEC 60870-5-104 + ModBus (RS485)

0
INPUTS-OUTPUTS
7 outputs + 8 inputs

1
MECHANICS
Compact: 4U x rack

A
B
D
LANGUAGE
English, Spanish, French and German