Sie sind auf Seite 1von 18

TECHNICAL REPORT

MKV / 6FA COMBINED CYCLE UPGRADE


&
DLN TUNING

UNITS: GTG-9, 10 & 11


prepared for


SULZER TURBO SERVICES ARGENTINA, SA
(Guaracachi)
Santa Cruz, Bolivia



Issued: October 26, 2010

Project No. 2010-65-1435






Prepared by: William Stewart

Turbine Technology Services
12661 Challenger Parkway, Suite 250
Orlando, FL 32826






Sulzer Turbo Services Argentina, SA Project No. 2010-65-1435
EGSA Guaracachi / Santa Cruz, Bolivia Page 2

General Information .................................................................................................................. 1
Site Background & Purpose of Visit ........................................................................................ 2
Objectives. ................................................................................................................................. 3
Conclusions & Recommendations .......................................................................................... 4
Attachments
Simple To Combined Cycle MKV Control Changes
Turbine Boiler Protection Flowchart








Sulzer Turbo Services Argentina, SA Project No. 2010-65-1435
EGSA Guaracachi / Santa Cruz, Bolivia Page 3
1. GENERAL INFORMATION
Customer: Sulzer Turbo Services Argentina, SA
Site / Location: EGSA Guaracachi / Santa Cruz, Bolivia
Customer Reps: Augusto Valdivia, Antonio Lanza, Esteban Aguayo

TTS Site Personnel: William Stewart
Timeline: 12
th
thru 20
th
October 2010

2. SITE BACKGROUND & PURPOSE OF VISIT
The first subject turbine is a gas fuelled 6FA unit at Guaracachi, Santa Cruz, Bolivia. The unit being
identified as GCH-11 was installed with a Mark V TMR Speedtronic control system.

The other subject turbines are also gas fuelled 6FA units at Guaracachi, Santa Cruz, Bolivia. The units
being identified as GCH-10 and GCH-11 Mark V TMR Speedtronic control systems. These units have
recently been converted from simple cycle to combined cycle modes of operation.

The first purpose of this Turbine Technology Services Corporation (TTSC) visit was to perform a DLN
tuning exercise after mechanical rework of the unit GCH-11. The second purpose of this visit was to
make the controls modifications to the combined cycle units (GCH-09 and GCH-10) followed by
testing and DLN tuning as per an agreed scope of work proposed by Sulzer/TTS.

3. OBJECTIVES
3.1. Mechanical Objectives
Install and configure the customers DLN tuning kit.
3.2. Control & Instrumentation Objectives
The control and instrumentation objective was to perform a DLN tuning exercise after
mechanical rework of the unit GCH-11. The second purpose of this visit was to make the
controls modifications to the combined cycle units (GCH-09 and GCH-10) followed by testing
and DLN tuning as per an agreed scope of work proposed by Sulzer/TTS.
3.3. Time Line of Works Carried Out
Monday 11th October 2010
Started travel from Orlando to Santa Cruz, Bolivia.
Tuesday 12th October 2010
Arrived at Santa Cruz airport at 8:30AM. Arrived at site around 1PM. Had a quick meeting with
the customer and Sulzer rep to confirm the scope of work on unit 11. Began installation of the






Sulzer Turbo Services Argentina, SA Project No. 2010-65-1435
EGSA Guaracachi / Santa Cruz, Bolivia Page 4
DLN tuning kit on unit 11 around 2:30PM. After installation it was seen that no dynamics were
being received from the unit. Changed the configuration from the default system left by the
previous GTE engineer (equipment manufacturer) to the new conversion factors for the
installed tubing length. Still no dynamics were being transmitted to the DLN computer.

Left site at 6:30PM

Contacted TTS DLN expert to confirm that the numbers in the configuration were correct.
Wednesday 13th October 2010
Arrived at site at 8:00AM. Tried several other program configurations but in every case no
dynamics were seen by the system. The tuning purge box has 7 channels with 7 transmiiters.
The 6FA only has six combustors so the spare from channel 7 was swapped with the
transmitter in channel 6. Still no dynamics were seen. The correct nitrogen bottle and
regulator became available at 3PM. All channels were purged with 200 psi Nitrogen, but still
no dynamics were present.

A frequency source was requested and this was used to inject all of the channels. The test
signal was set to 300mV pk-pk @ 100Hz and was injected directly into the signal conditioner.
All channels were working and displayed between 4 and 5 psi at 100 Hz. The same signal was
injected at the other end of the sensor cables at the purge box and again all 6 channels
showed 4-5 psi @ 100Hz. Next the connectors were removed from the sensors and the same
signal injected and the system again displayed the correct numbers. This proved that the
tuning equipment was fully functional from the transmitter outputs to the monitoring
computer. All connectors on the transmitters were removed, cleaned, and replaced. Still no
unit dynamics were being sensed. The conclusion is that either all sensors are non-functional
or the DLN tubing is incorrectly installed. Developed the DLN spreadsheet in preparation for
the tuning process.

Left site at 6:45PM
Thursday 14th October 2010
Arrived at site at 8:00AM. Moved the complete DLN tuning kit to Unit 9 and purged all the
PCBs and tubes with 200 psi Nitrogen. Again no dynamics were being sensed on this unit so
still neither bad sensors or bad tubing installations can be ruled out. It was decided that the
Sulzer rep would travel to Brazil and take 7 sensors from another tuning kit. It is expected that
his return will be around Saturday.

Started working on the combined cycle control code change requirements for unit 9. Had a
meeting with the Customer/DCS engineer (Esteban) to discuss how the interface should work.
A list of interconnections was generated together with a list of extra signals that the customer
would like to receive from the MKV controller.

Left site at 6:00PM






Sulzer Turbo Services Argentina, SA Project No. 2010-65-1435
EGSA Guaracachi / Santa Cruz, Bolivia Page 5
Friday 15th October 2010
Arrived at site at 8:00AM. Reviewed an old DLN tuning kit that the customer had in their
stores, however it was only a wave-guide purging system and contained no PCB sensors.
Continued working on engineering modification documents for units 9 and 10. Transmitted a
standard boiler high temperature protection algorithm for review and incorporation into the
customers DCS system. Created a flowchart showing how the unit will initially react to the DCS
signals mentioned in the high temperature protection algorithm and transmitted this to the
customer. Created a MKV connection list for DCS interface and transmitted to the customer.

Left Site At 6:00PM
Saturday 16th October 2010
Arrived at site at 8:00AM. Sulzer rep returned with replacement pressure sensors for the
tuning kit. Replaced two of the sensors but still no dynamics were being sensed. Moved the
tuning kit to the last unit (GCH10) and although a very small signal was being detected by the
tuning kit on channel 5, there was no real improvement. Called the equipment supplier GTE
(John Brooks) and discussed the issues we were having and what local testing we had
performed. He is also of the opinion that the tuning kit is operational and that the issue
appears to lie between the PCB sensors and the combustion chamber. Initial discussions with
site/Sulzer mechanical personnel indicated that the DLN waveguide sensors may be installed
flush with the liner and not recessed by 0.062 as required. It is anticipated that the next step
will be to shut down one of the units to check the probe insertions.

Left site at 2:00PM.
Monday 18th October 2010
Arrived at site at 8:00AM. Meeting with customer highlighted several points that would inhibit
the continuation of the work. Customer advised that they wanted a new exhaust temperature
control curve generated. This task required the services of external sources. Data was
requested from TTS engineering in order to generate this new exhaust temperature control
curve. All data was provided from site with the exception of the exhaust pressure/ambient
temperature data when the the units were running at base load. Currently due to the non
completion of the heat recovery system, running at base load is currently not possible. This
information will be required to be forwarded by the customer to TTS engineering at a future
date. Also, no DLN tuning is currently possible due to the non-functionality of the tuning
equipment/probe installation. Due to these reasons, the customer has no intentions to shut
down the unit to only partially complete the scope of work.

Left site at 6:00PM






Sulzer Turbo Services Argentina, SA Project No. 2010-65-1435
EGSA Guaracachi / Santa Cruz, Bolivia Page 6
Tuesday 19th October 2010
Awaiting demobilization details from Sulzer/Guaracachi. Continued working on the
engineering documents for the future MKV changes required to support the combined cycle
operation.
Wednesday 20th October 2010
Awaiting demobilization details from Sulzer/Guaracachi. Continued working on and completed
the engineering documents for the future MKV changes required to support the combined
cycle operation. This document was transmitted to TTS engineering for review and comment.
Wrote the site visit report and transmitted this to TTS.
Thursday 21st October 2010
Demobilization from assignment and travel back to Orlando.


4. CONCLUSIONS AND RECOMMENDATION
4.1. Obtain a replacement DLN tuning kit and/or verify insertion depths of all sensors installed in
the units.
4.2. Obtain the following information from site :
a) Exhaust gas pressure and ambient temperature when units GCH-09 and GCH-10 can
achieve base load.
b) Volume of previous exhaust duct and volume of newly installed boiler duct to calculate
new purge times.
4.3. Obtain the following from TTS engineering :
a) New exhaust temperature control curves.
b) New values for turbine start-up purge constants.
c) New values for exhaust pressure switches 63EA-1, 63ET-1 and 63ET-2.






Sulzer Turbo Services Argentina, SA Project No. 2010-65-1435
EGSA Guaracachi / Santa Cruz, Bolivia Page 1
Simple to Combined Cycle MKV Control Changes

UNIT GCH09 and GCH10

MKV Modification Requirements
OTSG High Temperature Protection and Addition of Customer Requested Outputs.

IO.ASG
L4CT already exists. Ensure any required OTSG/steam turbine trips are incorporated into this signal.
LCA4_FSNL Reset unit to FSNL Trip 52G (CIM) <Q_QD1_CI50>
LCA70_RB Runback Command From OTSG Protection (CIM) <Q_QD1_CI51>
S3 Turbine Complete Sequence To DCS N.O. <C_CD_CO50>
S52GX1 Generator Breaker Status To DCS N.O. <C_CD_CO51>

SITE.ASG
:Added for OTSG High Temperature Protection (November 2010)
?LQ L52GT_TRIP3 LOG ; High-High Steam Temperature - Trip Gen Breaker
?LQ L70L_RB LOG ; High Steam Temperature - Load Runback Required
?LQ LTTGT_RB LOG ; Exhaust Gas Temperature Runback Required
?VQCC TTKGT_RB TC ; Exhaust Gas Temperature Runback Set-point
?LQ L83AMX LOG ; Auxiliary to L83AM
?VQ TTXM_OUT MWATT ; Exhaust Temperature Signal To DCS
?VQ TNH_RPM_OUT RPM ; Turbine Speed In RPM To DCS
?VQCC K3IGVTC_OFF DGA ; IGV Position Set-point For IGV Control OFF
?LQ L3IGVTC_OFF LOG ; IGV Position Permissive For IGV Control OFF

CONST_Q.SRC
: Added for OTSG High Temperature Protection (November 2010)
TTKGT_RB 900 deg F ; Exhaust Gas Temperature Runback Set-point
K3IGVTC_OFF 100.0 DGA ; IGV Position Set-point For IGV Control OFF

Change TNKR1_5 as shown below
TNKR1_5 0.67 %/min ; HIGH STEAM TEMP LOAD RUNBACK RATE

Modify Purge Time Constants K2TV_1 (Hot Start) and K2TV_2 (Cold Start) to compensate for the
larger volume in the OTSG duct. Currently set to 4.0 minutes and 2.0 minutes respectively.
This needs information from customer. Need data on volume of old duct and volume of new duct.
NOTE : Customer should have changed before now as the unit is running in combined cycle mode.

Modify exhaust temperature control constants (TTKn_I, TTKn_C, TTKn_S and TTKRXBP) after the
engineering study is complete.

ALARM.LST
475 |LRB_ALM| GAS TURBINE LOAD RUNBACK
476 |L52GT_T3_ALM| GEN BREAKER TRIP FROM OTSG PROTECTION





Simple to Combined Cycle MKV Control Changes


Sulzer Turbo Services Argentina, SA Project No. 2010-65-1435
EGSA Guaracachi / Santa Cruz, Bolivia Page 2
ALARM.DAT
QP 475 GAS TURBINE LOAD RUNBACK
QP 476 GEN BREAKER TRIP FROM OTSG PROTECTION

MAOUT_Q.SRC
TTXM_OUT Q_C_MAO01 512 23551 ; 0 800 Deg C
TNH_RPM_OUT Q_C_MAO02 0 23999 ; 0 6000 RPM


Control Code Changes

Add New Rungs
OTSG High Temperature Protection

CMP
LTRUE Enable


TTXM 0a
LTTGT_RB
( )
TTKGT_RB 1b a>b




LTTGT_RB -- Exhaust gas temp runback required LOGIC
TTKGT_RB -- Exhaust gas temperature runback setpoint deg F
TTXM -- Ex Temp Median Corrected by Average deg F


LCA70_RB LTTGT_RB L52GX L70L_RB
( )

LRB_ALM
( )

L52GX -- Generator breaker closed LOGIC
L70L_RB -- High Steam Temperature - Load Runback Required LOGIC
LCA70_RB -- Runback Command From OTSG Protection LOGIC
LRB_ALM -- ALMTXT:'GAS TURBINE LOAD RUNBACK' LOGIC
LTTGT_RB -- Exhaust gas temp runback required LOGIC


L70L_RB L70LX3
( )

L70LX3 -- Shutdown Lower LOGIC
L70L_RB -- High Steam Temperature - Load Runback Required LOGIC










Simple to Combined Cycle MKV Control Changes


Sulzer Turbo Services Argentina, SA Project No. 2010-65-1435
EGSA Guaracachi / Santa Cruz, Bolivia Page 3
Modify Existing Rung
ADD
L70RX5 L83MSPD L83MLOAD L83JD10 L83JD5 L83JD4
////( )


L70LX5


L83SCI_
CMD


L70HT
SOK_L




L84TL L70L_RB L3PMSV_TS
/

(Note L84TL Completely on Liquid Fuel - may be deleted for gas only units)

L3PMSV_TS -- Primary GCV ref less than PGCV in PPM LOGIC
L70HTSOK_L -- LOGIC
L70LX5 -- High Temperature Spread Lower LOGIC
L70L_RB -- High Steam Temperature - Load Runback Required LOGIC
L70RX5 -- Governor Raise Control Logical LOGIC
L83JD10 -- FAST FIRED SHUTDOWN RATE SELECT LOGIC
L83JD4 -- Auto Load Rate LOGIC
L83MLOAD -- Manual Load LOGIC
L83MSPD -- Manual Speed LOGIC
L83SCI_CMD -- LOGIC COMMAND Isoch control LOGIC


Add New Rung

L70L_RB L3PMSV_TS L83JD10 L83JD5
//( )

L84TL


(Note L84TL Completely on Liquid Fuel - may be deleted for gas only units)
L3PMSV_TS -- Primary GCV ref less than PGCV in PPM LOGIC
L70L_RB -- High Steam Temperature - Load Runback Required LOGIC
L83JD5 -- High Steam Temperature Runback Rate LOGIC
L83JD10 -- FAST FIRED SHUTDOWN RATE SELECT LOGIC














Simple to Combined Cycle MKV Control Changes


Sulzer Turbo Services Argentina, SA Project No. 2010-65-1435
EGSA Guaracachi / Santa Cruz, Bolivia Page 4
Modify Existing Rungs


L70LX2 L83SCI_CMD L33CDMN L70L
//( )


L70LX3
(add L70LX3)


L70LX4



L70LX5


L70LX6



L70LDLN



L83SCI_CMD L60IL


L70HT
SOK_L L3HTSOKP
/



L33CDMN -- Droop Speed Setpoint at Min Limit LOGIC
L3HTSOKP -- Comp heat soak perm to sync LOGIC
L70HTSOK_L -- LOGIC
L70L -- Lower Speed Setpoint LOGIC
L70LDLN -- DLN Lower Load Signal LOGIC
L70LX2 -- Base to Peak Transient Lower LOGIC
L70LX3 -- Shutdown Lower LOGIC
L70LX4 -- Local Manual Lower LOGIC
L70LX5 -- High Temperature Spread Lower LOGIC
L70LX6 -- Auto Synch Load Logical LOGIC
L70TKL -- DWDROOP Setpoint Tracking Lower LOGIC
L83SCI_CMD -- LOGIC COMMAND Isoch control LOGIC


















Simple to Combined Cycle MKV Control Changes


Sulzer Turbo Services Argentina, SA Project No. 2010-65-1435
EGSA Guaracachi / Santa Cruz, Bolivia Page 5


L83SCI_
L70RX4 L30TXA CMD L70L L33CDMX LFSRCPR LCA70_RB L70R
//////( )


L70RX5



L70RX6


L83SCI_
CMD L70TKR



L30TXA -- ALMTXT:'EXHAUST TEMPERATURE HIGH' LOGIC
L33CDMX -- Droop Speed Setpoint at Max Limit LOGIC
L70L -- Lower Speed Setpoint LOGIC
L70R -- Raise Speed Setpoint LOGIC
L70RX4 -- Local Manual Raise LOGIC
L70RX5 -- Governor Raise Control Logical LOGIC
L70RX6 -- Load Rate #6 Logic Signal LOGIC
L70TKR -- DWDROOP Setpoint Tracking Raise LOGIC
L83SCI_CMD -- LOGIC COMMAND Isoch control LOGIC
LCA70_RB -- Runback Command From OTSG Protection LOGIC
LFSRCPR -- Comp Oper Limit Control Backup FSR Active LOGIC





Simple to Combined Cycle MKV Control Changes


Sulzer Turbo Services Argentina, SA Project No. 2010-65-1435
EGSA Guaracachi / Santa Cruz, Bolivia Page 6
L1S L94Y L14HS L83AM
/ ( )

L83SCI_
CMD


L70R4L_R


L83C L86MR1_
APCAN L83AM L94Z CPB
/

L70LDLN

L3TN
RERRX


L30LTA


L30GJL


L70L_RB


Break rung up and drive L83AMX with bottom 3 signals and use L83AMX in this rung.

L14HS -- HP Speed - Min operating speed LOGIC
L1S -- Auxiliary to Start Signal LOGIC
L30GJL -- LOGIC
L30LTA -- ALMTXT:'LOAD TUNNEL TEMPERATURE HIGH' LOGIC
L3TNRERRX -- ALMTXT:'DWATT TOO LOW TO SUPPORT TNR-TNR LOWER' LOGIC
L70LDLN -- DLN Lower Load Signal LOGIC
L70L_RB -- High Steam Temperature - Load Runback Required LOGIC
L70R4L_R -- Operator Input Raise or Lower Speed Setpoint LOGIC
L83AM -- Auto to Manual Load Transfer LOGIC
L83CAPCAN -- Load Selection Cancel Logic LOGIC
L83SCI_CMD -- LOGIC COMMAND Isoch control LOGIC
L86MR1_CPB -- COMMAND PB Master reset LOGIC
L94Y -- Time Delay Normal Shutdown LOGIC
L94Z -- 4'S Up with No Shutdown LOGIC


Add New Rung

LCA4_FSNL L52GT_TRIP3
( )

L52GT_T3_ALM
( )


L52GT_TRIP3 -- High-High steam temp trip gen breaker LOGIC
L52GT_T3_ALM -- ALMTXT:GEN BREAKER TRIP FROM OTSG PROTECTION LOGIC
LCA4_FSNL -- Reset unit to FSNL Trip 52G (DCS) [CA4-FSNL] LOGIC






Simple to Combined Cycle MKV Control Changes


Sulzer Turbo Services Argentina, SA Project No. 2010-65-1435
EGSA Guaracachi / Santa Cruz, Bolivia Page 7
Modify Existing Rungs

L14HS L52GT
/( )


L32DW



L52GT_ TRIP


Add to
L52GT_TRIP3 Existing Rung



L14HS -- HP Speed - Min operating speed LOGIC
L32DW -- Reverse Power - Generator Breaker Trip LOGIC
L52GT -- Generator breaker trip [52GT-1] LOGIC
L52GT_TRIP -- Mark V manual synch 52G breaker trip PB LOGIC
L52GT_TRIP3 -- High-High steam temp trip gen breaker LOGIC


L83PPBM_
L3FG_P2X L83FXPMZ L84TL L14HS CMD
// ( )


L70L_RB L83FXP2


L83SCI_
CMD


L83PPBM_
CMD


L14HS -- HP Speed - Min operating speed LOGIC
L3FG_P2X -- T.D. Above Estimated P3 Margin LOGIC
L70L_RB -- High Steam Temperature - Load Runback Required LOGIC
L83FXP2 -- Premix Steady State Mode Selected LOGIC
L83FXPMZ -- Not in Any Premix Mode LOGIC
L83PPBM_CMD -- Piloted Premix Base Command LOGIC
L83SCI_CMD -- LOGIC COMMAND Isoch control LOGIC
L84TL -- Completely on Liquid Fuel LOGIC
















Simple to Combined Cycle MKV Control Changes


Sulzer Turbo Services Argentina, SA Project No. 2010-65-1435
EGSA Guaracachi / Santa Cruz, Bolivia Page 8
Should the response of the load runback not be fast enough with IGV temperature control selected
ON, then there is the further option to select IGV temperature control off. This selection can only be
made at a very low load or when the IGVs are fully open. To prevent having to shut down the unit
several times for test purposes, add the following rung and modify L43TVOFF as shown below. Prior
to utilizing this function, full DLN mapping in IGV Temp Control OFF mode should be performed. Set
the constant K3IGVTC_OFF initially to 100 DGA. If this IGV Temp Control OFF function is required,
then this value can be reduced to 86 DGA.




CMP
LTRUE Enable


CSGV 0a L3IGVTC_OFF

( )
K3IGVTC_OFF 1b a>b




CSGV -- Position feedback IGV (high value selected) DGA
K3IGVTC_OFF -- IGV Position Set-point For IGV Control OFF DGA
L3IGVTC_OFF -- IGV Position Permissive For IGV Control OFF LOGIC


L69T L43TVOF_
VOFDW CPB L43TVOFF
( )

L3IGV
L60GVMAX TC_OFF L70L_RB


L3IGVTC_OFF -- IGV Position Permissive For IGV Control OFF LOGIC
L70L_RB -- High Steam Temperature - Load Runback Required LOGIC
L43TVOFF -- IGV Temperature Control Off Select LOGIC
L43TVOF_CPB -- IGV Temperature Control Off Pushbutton LOGIC
L60GVMAX -- IGV at Maximum Position LOGIC
L69TVOFDW -- Load Permissive to Turn IGV Temp Control Off LOGIC






















Simple to Combined Cycle MKV Control Changes


Sulzer Turbo Services Argentina, SA Project No. 2010-65-1435
EGSA Guaracachi / Santa Cruz, Bolivia Page 9

Add New Rungs For Customer Requested Output Signals




COPY
LTRUE Enable Copy Analog LZZ
( )

TTXM 1input output0 TTXM_OUT



TTXM -- Ex Temp Median Corrected by Average deg F
TTXM_OUT -- Exhaust Temperature Signal To DCS deg F



COPY
LTRUE Enable Copy Analog LZZ
( )

TNH_RPM 1input output0 TNH_RPM_OUT



TNH_RPM -- HP Turbine Speed (RPM) rpm
TNH_RPM_OUT -- Turbine Speed In RPM To DCS rpm


L3 S3
( )

L3 -- Turbine Complete Sequence LOGIC
S3 -- Turbine Complete Sequence To DCS LOGIC



L52GX1 S52GX1
( )

L52GX1 -- QD1-DTBB-027 Generator breaker status [52GX-1] LOGIC
S52GX1 -- Generator Breaker Status To DCS LOGIC






















Simple to Combined Cycle MKV Control Changes


Sulzer Turbo Services Argentina, SA Project No. 2010-65-1435
EGSA Guaracachi / Santa Cruz, Bolivia Page 10
MK5 WIRING CONNECTIONS

SIGNAL NAME CORE CARD TERMINAL DESCRIPTION
4CT <QD1> DTBB 75/76 CUSTOMER TRIP (already connected)
CA4_FSNL <QD1> DTBB 07/08 TRIP GEN BREAKER FROM DCS
CA70_RB <QD1> DTBB 09/10 LOAD RUNBACK FROM DCS
S3 <CD> DTBD 76/77 COMPLETE SEQUENCE TO DCS
S52GX1 <CD> DTBD 79/80 GEN BREAKER STATUS TO DCS
TTXM_OUT <C> CTBA 01/02 EXHAUST TEMPERATURE TO DCS
TNH_RPM_OUT <C> CTBA 03/04 TURBINE SPEED IN RPM TO DCS



RECALIBRATIONS REQUIRED

Recalibration of the following devices will be required following the conversion to combined cycle
mode and base load exhaust pressure data is available to Sulzer/TTS:

63EA-1 : Current device summary setting of 16 InH2O. (New Setting Required)
63ET-1 : Current device summary setting of 20 InH2O. (New Setting Required)
63ET-2 : Current device summary setting of 20 InH2O. (New Setting Required)








Simple to Combined Cycle MKV Control Changes


Sulzer Turbo Services Argentina, SA Project No. 2010-65-1435
EGSA Guaracachi / Santa Cruz, Bolivia Page 11
Standard HRSG High Temperature Protection



UnitAtHighLoad
InPremix
BoilerRunback
(CA70_RB)
No Yes
TransferTo
PPM
PilotedPremix
TransferComplete
ReduceLoad
ToTTXM<482C
At0.67%/Min
ReduceLoad
ToTTXM<482C
At0.33%/Min
UnitRunningWith
TTXM<482C
ResetToFSNL
(CA70_FSNL)
TripGeneratorBreaker
TripGasTurbine
TripGasTurbine
(4CT)
D
C
S

B
O
I
L
E
R

A
N
D

S
T
E
A
M

T
U
R
B
I
N
E

P
R
O
T
E
C
T
I
O
N
IGVTemp
ControlOFF
AlternativeOption
BasedOnBoiler
Requirements

Das könnte Ihnen auch gefallen