Sie sind auf Seite 1von 1

PURCHASE ORDER NUMBER

Contractor Qc Supervisor
Name, Sign and Date:
Quality Record Approved
* Person Responsible for Completion of Quality work / Test
Contractor QC Inspector Y =YES N =NO F =FAILED
Name, Initials and Date:
Performed Inspection Work / Rework May Proceed
REMARKS:
Name, Initials and Date:
Work is Complete and Ready for Inspection:
Name, Initials and Date:
T&I Witnessed
Subcontractor / Contractor
1-RTSAES-S-060 -- Overlay of SAES-S-060 -- Saudi Aramco Plumbing Code, 28 J anuary, 2004
2-RTSAES-L-105-- Overlay of SAES-L-105 -- Piping Material Specifications, 30 September, 2003
Subcon QC Inspector PID Representative
Name, Initials and Date:
Performed Inspection Work / Rework May Proceed
Name, Initials and Date:
T&I Witnessed QC Record Reviewed Work Verified
A10
The flanged branch connection to the Copper-Nickel pipe shall be
isolated in accordance with Saudi Aramco Standard Drawing AA-036865.
Note: Copper-Nickel reducer may be used to obtain the desired pipe
size. Welding bosses shall not be used.
RTSAES-L-105
Para 12.2.3
QC Record Reviewed Work Verified
Company
REFERENCE DOCUMENTS:
A9
Connections between any dissimilar metals shall be by means of a
dielectric or insulating union.
RTSAES-S-060
Para 604.11.2(b)
A8
Connections between a larger cement-lined steel header and Copper-
Nickel pipe shall be accomplished with special cement-lined, flanged tees
with a 4-inch minimum size branch.
A6
Connections between Cement lined Carbon steel(12LC0U) and 12BD0U
or 12BC0U shall be made with an isolation gasket, such as Pikotek or
equal, or a dielectric union
Note:Cathodic protection, if provided, must be on separate circuits for the
different materials. Care must be taken to assure that the isolated joint is
not short-circuited by pipe supports
RTSAES-L-105
Para 12.2.1
RTSAES-L-105
Para 12.2.3
A7
Connections between cement-lined steel pipe and the same size Copper-
Nickel pipe shall be made with an isolated, flanged joint in accordance
with Saudi Aramco Standard Drawing AA-036865.
Note: The raised face of the cement-lined steel flange shall be
machined off to accommodate the connection to the flat-faced Copper-
Nickel flange.
RTSAES-L-105
Para 12.2.2
A5 Copper tube for water piping shall have a weight of not less than Type "L"
RTSAES-S-060
Para 604.2
A4 Copper tube below ground shall be type "K".
RTSAES-L-105
Section 12
Line Class Tables
A3
Copper tubing (Line Class 12BC0U) shall not be used for firewater
system in blast resistant control buildings
Note: 12 BD0U or approved equal shall be used for firewater system in
blast resistant control building
RTSAES-L-105
Para 12.2
A2
Fitting shall be in accordance with ASME B 16.22 for solder or brazed
joint.
RTSAES-L-105
Section 12
Line Class Tables
A1
Copper tube and fittings shall be joined (Soldered, Brazed, flared joint or
compression type) in accordance with the procedures and techniques
specified in Copper Tube Handbook of the Copper Development
Association, IAPMO IS 3-93
RTSAES-S-060
Para 316.1.7 b

ITEM
No.
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
SMITP-K-001-01 0 3.1
COMPANY INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL
W
SCHEDULED INSPECTION DATE &TIME ACTUAL INSPECTION DATE &TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
W
SMITP NUMBER REV. NO. SMITP ACTIVITY NUMBER WORK PERMIT REQUIRED?
LAYOUT DRAWING NUMBER REV. NO. EC / PMCC / MCC NO.
PROJ ECT TITLE WBS / BI / J O NUMBER CONTRACTOR / SUBCONTRACTOR
SADARA MFC PROJECT DAELIM /AMANA
EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.
SADARA MFC INSPECTION CHECKLIST
SMIC NUMBER DATE APPROVED QR NUMBER
Copper Pipe Installation SMIC-S-4050 PLUMBING
Page 1 of 1