Clad or jacketed steel tank (FRP or urethane outer tank, e.g. ACT-100 or Glasteel).
Bare metal in non-corrosive environment (certified by a corrosion expert).
2. Piping Design (10 CSR 20-10.020(1)(B)1. 6.)
Fiberglass reinforced plastic piping.
Dielectrically coated steel with cathodic protection.
Flexible thermoplastic piping.
Double-walled thermoplastic piping.
Bare metal in non-corrosive environment (certified by a corrosion expert).
3. Spill Protection (10 CSR 20-10.020(1)(C)1.A.)
Spill bucket at fill pipe.
Spill catchment basin.
Not required if filling less than 25 gallons at a time (e.g., used oil tanks).
4. Overfill Protection (10 CSR 20-020(1)(C)1.B.)
Automatic shut off device.
Overfill alarm.
Ball float valve.
Not required if filling less than 25 gallons at a time (e.g., used oil tanks).
5. Release Detection for Tanks (10 CSR 20-10.043)
Inventory control and tightness testing (may be used for only 10 years after new tank is
brought on line. Tank tightness test required every five years).
Manual tank gauging (tanks up to 2,000 gallons capacity).
Statistical inventory reconciliation, or SIR.
Automatic tank gauge, or ATG.
Interstitial monitoring (for double walled tanks).
Groundwater monitoring.
Vapor monitoring.
Not required only for emergency generator tanks.
Other method that meets requirements of 10 CSR 20-10.043(H).
3
6. Release Detection for Piping (10 CSR 20-10.044)
Pressurized Piping
Automatic line leak detector (required for pressurized systems) and at least one of the following:
Annual 0.1 gallon/hour line tightness testing.
Monthly 0.2 gallon/hour electronic line tightness testing.
Groundwater monitoring.
Vapor monitoring.
Interstitial monitoring (for double walled piping).
Statistical inventory reconciliation.
Suction Piping
Not required Safe Suction (meeting 10 CSR 20-10.041(1)(B)2.A-E).
Suction with three-year line tightness testing.
Suction with a2 through a6, listed under Pressurized Piping.
7. Corrosion Protection (10 CSR 20-10.020)
For all metal system components, including, but not limited to tanks, piping, flexible connectors
and ancillary equipment.
Meets corrosion protection by design.
Sacrificial anode system.
Impressed current system.
8. Installation per Industry Standard (10 CSR 20-10.020(1)(D))
Installed per American Petroleum Institute RP 1615.
Installed per Petroleum Equipment Institute RP 100.
9. Certification of Installation (10 CSR 20-10.020(1)(E) and 10.022(4))
Installer certified by tank and piping manufacturer.
Installation inspected and certified by a professional engineer.
Manufacturers checklists completed.
10. Post Installation Tightness Testing
Must be conducted in accordance with manufacturers requirements and the industry
recommended practice (see 8 above).
Single wall tanks and piping tightness tested.
Double wall tanks and piping tightness tested.
Double wall tanks and piping interstice tested.
Other as approved by the department.
All ancillary equipment must be tested in accordance with manufacturers requirements
(e.g., automatic tank gauge, line leak detector).
11. Financial Responsibility Coverage (10 CSR 20-11)
Petroleum Storage Tank Insurance Fund.
Financial test of self-insurance.
Guarantee.
Insurance or risk retention group.
Surety bond.
Letter of credit.
Trust fund.
Local government mechanism.
4
12. Registration within 30 days (10 CSR 20-10.022(2))
Must include all of the following:
Registration form completed.
Registration form signed by owner.
Registration (with original signature) mailed within 30 days of bringing tank into use.
13. Stage I and II Vapor Recovery Construction Permits
Permits must be issued before construction begins. In the St. Louis and Kansas City areas
contact one of the following offices:
State-wide Assistance
Air Pollution Control Program 573-751-6415.
Kansas City Area (Stage I only)
Kansas City Metro Area Kansas City Dept. of Health Air Quality 816-513-6314.
Clay, Jackson and Platte counties Kansas City Regional Office 816-622-7000.
St. Louis Area (Stage I and II)
St. Louis City Air Pollution 314-613-7300.
Franklin, Jefferson or St. Charles counties St. Louis Regional Office 314-416-2960.
St. Louis County Air Pollution 314-615-8923.
Summary
The above checklist is a summary of the regulatory requirements for petroleum underground
storage tank systems. If a system meets these requirements, it should be in compliance.
However, the checklist may not cover every aspect of an installation. A five-day notice to the
departments Jefferson City office, prior to beginning on-site activities, is requested in order for
the department to provide technical assistance.
Note: Vapor recovery equipment, suction piping systems and pressurized deliveries may affect
the functionality of some overfill prevention equipment, therefore, certain overfill prevention
devices may not be used in these situations
For questions or further assistance concerning the notification requirements, contact the Tanks
Section at 573-751-6822. For questions concerning the tank system and equipment installation,
contact the Tanks Compliance and Enforcement Unit at 573-522-5665.
State Insurance Fund
Missouri Petroleum Storage Tank Insurance Fund
P.O. Box 836
Jefferson City, MO 65102
800-765-2765 or 573-522-2352
Fax: 573-522-2354
www.pstif.org
Industry Standards
Underwriters Laboratory, or UL, Standard 1316 Standard for Glass-Fiber-Reinforced Plastic
Underground Storage Tanks for Petroleum Products.
American Society for Testing and Materials, or ASTM, Standard D4021-86 Standard
Specification for Glass-Fiber-Reinforced Polyester Underground Petroleum Storage Tanks.
5
Steel Tank Institute, or STI, Specification for STI-P3 System of External Corrosion Protection
of Underground Steel Storage Tanks.
Underwriters Laboratory Standard 1746 Corrosion Protection Systems for Underground
Storage Tanks.
National Association of Corrosion Engineers, or NACE, Standard RP-02-85 Control of
External Corrosion on Metallic Buried, Partially Buried or Submerged Liquid Storage Systems.
Underwriters Laboratory Standard 58 Standard for Steel Underground Tanks for Flammable
and Combustible Liquids.
Association for Composite Tanks ACT-100 Specification for the Fabrication of FRP Clad
Underground Storage Tanks.
Underwriters Laboratory Subject 971 UL Listed Non-Metal Pipe.
Underwriters Laboratory Standard 567 Pipe Connectors for Flammable and Combustible
and LP Gas.
National Fire Protection Association, or NFPA, Standard 30 Flammable and Combustible
Liquids Code.
American Petroleum Institute, or API, Publication 1615 Installation of Underground Petroleum
Storage Systems.
American Petroleum Institute Publication 1632 Cathodic Protection of Underground Petroleum
Storage Tanks and Piping Systems.
National Association of Corrosion Engineers Standard RP-01-69 Control of External Corrosion
on Submerged Metallic Piping Systems.
Petroleum Equipment Institute, or PEI, Publication RP100 Recommended Practices for
Installation of Underground Liquid Storage Systems.
American Petroleum Institute Publication 1626 Storing and Handling Ethanol and
Gasoline-Ethanol Blends at Distribution Terminals and Service Stations.
American Petroleum Institute Publication 1627 Storage and Handling of Gasoline-
Methanol/Cosolvent Blends at Distribution Terminals and Service Stations.
American Petroleum Institute Publication 1621 Recommended Practice for Bulk Liquid Stock
Control at Retail Outlets.
Petroleum Equipment Institute Publication RP300 Recommended Practices for Installation and
Testing of Vapor Recovery Systems.
6
Standards Contact Information
American Petroleum Institute
1220 L St., NW
Washington, DC 20005
202-682-8000
Publications: 202-682-8375
www.api.org
American Society for Testing and Materials
100 Barr Harbor Dr.
West Conshohocken, PA 19428-2959
610-832-9585
Fax: 610-832-9555
www.astm.org
National Association of Corrosion Engineers
1440 South Creek Dr.
Houston, TX 77084-4906
281-228-6200
Fax: 281-228-6300
www.nace.org/nace/index.asp
National Fire Protection Association
1 Batterymarch Park
Quincy, MA 02169-7471
800-344-3555 or 617-770 3000
Fax: 617-770-0700
www.nfpa.org/catalog/home/index.asp
For more information
Missouri Department of Natural Resources
Hazardous Waste Program
Tanks Section
P.O. Box 176
Jefferson City, MO 65102-0176
800-361-4827 or 573-751-6822
www.dnr.mo.gov/env/hwp/tanks/tanks.htm
www.dnr.mo.gov/env/hwp/index.html
Petroleum Equipment Institute
P.O. Box 2380
Tulsa, OK 74101-2380
918-494-9696
Fax: 918-491-9895
www.pei.org
Steel Tank Institute
570 Oakwood Rd.
Lake Zurich, IL 60047
847-438-8265
Fax: 847-438-8766
www.steeltank.com
Underwriters Laboratories Inc.
333 Pfingsten Rd.
Northbrook, IL 60062-2096
847-272-8800
Fax: 847-272-8129
www.ul.com
Missouri Department of Natural Resources
Hazardous Waste Program
Tanks Compliance and Enforcement Unit
P.O. Box 176
Jefferson City, MO 65102-0176
800-361-4827 or 573-522-5665
tanks-compliance@dnr.mo.gov