Correction Factor Chart

Shell-and-Tube Heat exchanger


Analysis
Crossflow Heat Exchanger Analysis

RB Astillero 1
CORRECTION FACTOR CHART
Multiple pass heat exchanger analysis is quite complicated
than single-pass ones. In doing the analysis for multi-pass
heat exchangers, correction factors for LMTD must be
inserted in the heat-transfer formula. The correction factors
are presented in chart form by Bowman, Mueller, and
Nagle and by the Tubular Exchanger Manufacturers
Association (TEMA). Such chart can be found in Heat
Transfer, 10th ed. by JP Holman on pages 534 536.
With the correction factor F, q will now be calculated as
follows:
q = UAF(LMTD or or T
m
)
Where F = appropriate correction factor
RB Astillero 2
Correction-factor plot for exchanger with one
shell pass and two, four, or any multiple of
tube passes.

RB Astillero 3
Correction-factor plot for exchanger with one
shell pass and three, six, or any multiple of
tube passes.


RB Astillero 4
Correction-factor plot for exchanger with two
shell passes and four, eight, or any multiple
of tube passes
RB Astillero
5
Correction-factor plot for single-pass cross-
flow exchanger, both fluids unmixed
RB Astillero
6

Correction-factor plot for single-pass cross-
flow exchanger, one fluid mixed, the other
unmixed.

RB Astillero 7
EXAMPLE #1
Water at the rate of 68 kg/min is heated from
35 to 75C by an oil having a specific heat of
1.9 kJ/kg C. The fluids use a shell-and-
tube exchanger with the water making one
shell pass and the oil making two tube
passes. The oil enters the exchanger at
110C and leaves at 75C. The overall heat-
transfer coefficient is 320 W/m
2
C.
Calculate the heat-exchanger area.
RB Astillero
8
EXAMPLE #1
Solution:


Solving for LMTD, or T
m


Solving for the parameters P and R:
RB Astillero
9
EXAMPLE #1
Solving for the parameters P and R:


Estimating the correction factor F:

F = 0.81

RB Astillero
10
EXAMPLE #1
Solving for heat transfer area:











RB Astillero 11
EXAMPLE #2
RB Astillero
12
EXAMPLE #2
RB Astillero
13
EXAMPLE #2








RB Astillero
14
EXAMPLE #3
RB Astillero
15
EXAMPLE #3
RB Astillero
16
EXAMPLE #3
RB Astillero
17
EXAMPLE #3
RB Astillero
18
EXERCISES
1. A shell-and-tube heat exchanger is used for the heating of oil from 20 to
30C; the oil flow rate is 12 kg/s (Cc = 2.2 kJ/kg K). The heat exchanger has
one shell pass and two tube passes. Hot water (C
H
= 4.18 kJ/kg K) enters the
shell at 75C and leaves the shell at 55C. The overall heat-transfer coefficient
based on the outside surface of the tubes is estimated to be 1080 W/m
2
K.
Determine(a) the corrected logarithmic-mean temperature difference, and (b)
the required surface area in the exchanger.

2. A finned-tube crossflow heat exchanger with both fluids unmixed is used to
heat water (Cc = 4.2 kJ/kg K) from 20 to 75C. The mass flow rate of the water
is 2.7 kg/s. The hot stream (C
H
= 1.2 kJ/kg K) enters the heat exchanger at
280C and leaves at 120C. The overall heat-transfer coefficient is 160
W/m
2
K. Determine (a) the mass flow rate of the heat stream, and (b) the
exchanger surface area.

RB Astillero
19
EXERCISES
3. A shell-and-tube heat exchanger is used to cool oil (C
H
= 2.2 kJ/kg K) from
110 to 65C. The heat exchanger has two shell passes and four tube passes.
The coolant (Cc = 4.20 kJ/kg K) enters the shell at 20C and leaves the shell
at 42C. For an overall tube-side heat-transfer coefficient of 1200 W/m
2
K and
an oil flow of 11 kg/s, determine (a) the coolant mass flow rate; (b) the required
surface area in the exchanger.

4. A shell-and-tube exchanger having one shell pass and eight tube passes is
to heat kerosene from 80 to 130F. The kerosene enters at a rate of 2500 lb
m
/h.
Water entering at 200F and at a rate of 900 lb
m
/h is to flow on the shell side.
The overall heat-transfer coefficient if 260 Btu/h ft
2
F. Determine the
required heat-transfer area.

RB Astillero 20
EXERCISES
5. A shell-and-tube heat exchanger operates with two shell passes and four
tube passes. The shell fluid is ethylene glycol, which enters at 140C and
leaves at 80C with a flow rate of 4500 kg/h. Water flows in the tubes, entering
at 35C and leaving at 85C. The overall heat-transfer coefficient for this
arrangement is 850 W/m
2
C. Calculate the flow rate of water required and the
area of the heat exchanger.

6. The flow rate of glycol to the exchanger in Problem 5 is reduced in half with
the entrance temperatures of both fluids remaining the same. What is the water
exit temperature under these new conditions, and by how much is the heat-
transfer rate reduced?

RB Astillero
21