EtherNet/IP Modules

Catalog Numbers 1756-ENBT, 1756-EN2F, 1756-EN2T, 1756-EN2TR, 1756-EN2TXT, 1756-EN3TR, 1756-EWEB, 1768-ENBT,
1768-EWEB
Installation Instructions
Important User Information
Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety
Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from
your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some
important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference,
and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment
must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
Allen-Bradley, CompactLogix, CompactLogix-XT, ControlFLASH, ControlLogix, ControlLogix-XT, FLEX I/O-XT, Logix5000, Logix-XT, RSLinx Classic, RSLogix, RSNetWorx for EtherNet/IP, Rockwell Software,
Rockwell Automation, RSLinx Classic, RSLogix 5000, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
Rockwell Automation Publication ENET-IN002B-EN-P - January 2012 3
Summary of Changes
This manual contains new and updated information. Changes throughout this
revision are marked by change bars, as shown to the right of this paragraph.
New and Updated
Information
This table contains the changes made to this revision.
Topic Page
Added new warnings for USB cable usage 29, 58
4 Rockwell Automation Publication ENET-IN002B-EN-P - January 2012
Summary of Changes
Notes:
Rockwell Automation Publication ENET-IN002B-EN-P - January 2012 5
Table of Contents
Preface Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Chapter 1
Install a 1756 EtherNet/IP
Communication Module
Installation Summary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Grounding Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Determine Module Slot Location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Set the Network IP Address on a Module . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Set the Network IP Address with the Rotary Switches . . . . . . . . . . . 15
Set the Network IP Address with the BOOTP/DHCP Server. . . . 16
Set the Network IP Address with RSLinx or
RSLogix 5000 Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Reset the Module IP Address to Factory Default Value . . . . . . . . . . 24
Install the Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Connect the Module to an EtherNet/IP Network via an
RJ45 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Connect the Module to an EtherNet/IP Network via a
Fiber Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Download the Add-on Profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Connect to the Module via the USB Port . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Apply Chassis Power and Check Status Indicators . . . . . . . . . . . . . . . . . . 30
Install or Remove the Module Under Power . . . . . . . . . . . . . . . . . . . . . . . . 31
Chapter 2
Install a 1768 EtherNet/IP
Communication Module
Installation Summary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Grounding Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Set the Network IP Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Set the Network IP Address with a BOOTP/DHCP Server. . . . . . 39
Set the Network IP Address with RSLinx or
RSLogix 5000 Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Reset the Module IP Address to Factory Default Value . . . . . . . . . . 46
Install the Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
If You Use Screws to Mount the Module . . . . . . . . . . . . . . . . . . . . . . . 46
Mount on a DIN Rail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Connect the Module to an EtherNet/IP Network via an
RJ45 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Download the Add-on Profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Apply Chassis Power and Check Status Indicators . . . . . . . . . . . . . . . . . . 50
Remove the Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
6 Rockwell Automation Publication ENET-IN002B-EN-P - January 2012
Table of Contents
Chapter 3
Configure a Workstation to
Operate on an EtherNet/IP
Network
Select the Driver. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Configure the Ethernet Communication Driver . . . . . . . . . . . . . . . . . . . . 54
Chapter 4
USB Communication Set Up the Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Configure a Module via the USB Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Set Up a USB Driver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Load Firmware through a USB Port. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Appendix A
1756 EtherNet/IP Status
Indicators
1756-ENBT, 1756-EN2F, 1756-EN2T, 1756-EN2TXT,
1756-EWEB EtherNet/IP Module Status Indicators . . . . . . . . . . . . . . . . 62
1756-EN2TR, 1756-EN3TR EtherNet/IP Module
Status Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Appendix B
1768 EtherNet/IP Module Status
Indicators
Link (LINK) Status Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Network (NET) Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
OK Status Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Appendix C
Fiber Cable and LC Connector Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Rockwell Automation Publication ENET-IN002B-EN-P - January 2012 7
Preface
This manual describes how to install and start up EtherNet/IP module systems
with Logix5000 controllers.
Use this manual if you program applications that use an EtherNet/IP network
with one of these Logix5000

controllers:
CompactLogix

controller
ControlLogix

controller
You should also understand the following:
Networking concepts
How to use RSLogix

5000 software
How to use RSLinx

Classic programming software


Additional Resources
For more information on the products described in this publication, use these
resources.
Resource Description
Ethernet Design Considerations
Reference Manual, publication
ENET-RM002
Provides details about how to use EtherNet/IP communication
modules with Logix5000 controllers and communicate with
other devices on the EtherNet/IP network.
EtherNet/IP Design
Considerations Reference
Manual, publication ENET-RM001
Provides details about how to use any EtherNet/IP network
EtherNet/IP Embedded Switch
Technology Application Guide,
publication ENET-AP005
Provides details about how to install, configure, and maintain
linear and Device-level Ring (DLR) networks using Rockwell
Automation EtherNet/IP devices equipped with embedded
switch technology.
EtherNet/IP Media Planning and
Installation Manual
This manual is available from the
Open DeviceNet Vendor
Association (ODVA) at:
http://www.odva.org.
Provides details about how to use the required media
components and how to plan for, install, verify, troubleshoot,
and certify your EtherNet/IP network.
8 Rockwell Automation Publication ENET-IN002B-EN-P - January 2012
Preface
Notes:
Rockwell Automation Publication ENET-IN002B-EN-P - January 2012 9
Chapter 1
Install a 1756 EtherNet/IP Communication
Module
Topic Page
Installation Summary 12
Determine Module Slot Location 12
Set the Network IP Address on a Module 13
Install the Module 24
Connect the Module to an EtherNet/IP Network via an RJ45
Connection
25
Connect the Module to an EtherNet/IP Network via a Fiber
Connector
27
Download the Add-on Profile 28
Connect to the Module via the USB Port 29
Apply Chassis Power and Check Status Indicators 30
Install or Remove the Module Under Power 31
ATTENTION: Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications
(as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11. Without appropriate
precautions, there may be difficulties with electromagnetic compatibility in residential and other environments due to
conducted and radiated disturbances.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for
those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting
from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the
spread of flame, complying with a flame spread rating of 5VA or be approved for the application if non-metallic. The interior
of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain
additional information regarding specific enclosure type ratings that are required to comply with certain product safety
certifications.
In addition to this publication, see the following:
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1, for additional installation requirements
NEMA Standard 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosures
10 Rockwell Automation Publication ENET-IN002B-EN-P - January 2012
Chapter 1 Install a 1756 EtherNet/IP Communication Module
North American Hazardous Location Approval
The following information applies when operating this
equipment in hazardous locations.
Informations sur lutilisation de cet quipement en
environnements dangereux.
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use
in Class I Division 2 Groups A, B, C, D, Hazardous Locations and
nonhazardous locations only. Each product is supplied with
markings on the rating nameplate indicating the hazardous
location temperature code. When combining products within a
system, the most adverse temperature code (lowest "T" number)
may be used to help determine the overall temperature code of
the system. Combinations of equipment in your system are
subject to investigation by the local Authority Having
Jurisdiction at the time of installation.
Les produits marqus "CL I, DIV 2, GP A, B, C, D" ne conviennent
qu' une utilisation en environnements de Classe I Division 2
Groupes A, B, C, D dangereux et non dangereux. Chaque produit
est livr avec des marquages sur sa plaque d'identification qui
indiquent le code de temprature pour les environnements
dangereux. Lorsque plusieurs produits sont combins dans un
systme, le code de temprature le plus dfavorable (code de
temprature le plus faible) peut tre utilis pour dterminer le
code de temprature global du systme. Les combinaisons
d'quipements dans le systme sont sujettes inspection par les
autorits locales qualifies au moment de l'installation.
WARNING: EXPLOSION HAZARD -
Do not disconnect equipment unless power has
been removed or the area is known to be
nonhazardous.
Do not disconnect connections to this
equipment unless power has been removed or
the area is known to be nonhazardous. Secure
any external connections that mate to this
equipment by using screws, sliding latches,
threaded connectors, or other means provided
with this product.
Substitution of components may impair
suitability for Class I, Division 2.
If this product contains batteries, they must
only be changed in an area known to be
nonhazardous.
AVERTISSEMENT: RISQUE DEXPLOSION
Couper le courant ou s'assurer que
l'environnement est class non dangereux
avant de dbrancher l'quipement.
Couper le courant ou s'assurer que
l'environnement est class non dangereux
avant de dbrancher les connecteurs. Fixer
tous les connecteurs externes relis cet
quipement l'aide de vis, loquets coulissants,
connecteurs filets ou autres moyens fournis
avec ce produit.
La substitution de composants peut rendre cet
quipement inadapt une utilisation en
environnement de Classe I, Division 2.
S'assurer que l'environnement est class non
dangereux avant de changer les piles.
Rockwell Automation Publication ENET-IN002B-EN-P - January 2012 11
Install a 1756 EtherNet/IP Communication Module Chapter 1
European Hazardous Location Approval
The following applies when the product bears the Ex Marking.
This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC and has been
found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment
intended for use in Zone 2 potentially explosive atmospheres, given in Annex II to this Directive.
Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 60079-15 and EN 60079-0.
ATTENTION: This equipment is not resistant to sunlight or other sources of UV radiation.
WARNING:
This equipment must be installed in an enclosure providing at least IP54 protection when applied in Zone 2
environments.
This equipment shall be used within its specified ratings defined by Rockwell Automation.
Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than
40% when applied in Zone 2 environments.
This equipment must be used only with ATEX certified Rockwell Automation backplanes.
Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors,
or other means provided with this product.
Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
ATTENTION: Prevent Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation.
Follow these guidelines when you handle this equipment:
Touch a grounded object to discharge potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
Use a static-safe workstation, if available.
Store the equipment in appropriate static-safe packaging when not in use.
ATTENTION: Safety-related Programmable Electronic Systems
Personnel responsible for the application of safety-related programmable electronic systems (PES) shall be aware of the
safety requirements in the application of the system and shall be trained in using the system.
12 Rockwell Automation Publication ENET-IN002B-EN-P - January 2012
Chapter 1 Install a 1756 EtherNet/IP Communication Module
Installation Summary
To install a communication module in a 1756 ControlLogix chassis, follow
these steps.
1. Set the Network IP Address on a Module.
2. Determine Module Slot Location.
3. Install the Module.
4. Connect the Module to an EtherNet/IP Network via an RJ45
Connection.
or
Connect the Module to an EtherNet/IP Network via a Fiber Connector.
5. Download the Add-on Profile.
6. Connect to the Module via the USB Port.
7. Apply Chassis Power and Check Status Indicators.
8. Install or Remove the Module Under Power. - Optional
Grounding Considerations
The grounding and bonding must be of equal potential between all devices in the
communication coverage area.
Determine Module Slot
Location
Install the communication module in any slot in a ControlLogix or
ControlLogix-XT chassis. You can install multiple communication modules in
the same chassis.
This example shows chassis slot numbering in a 4-slot ControLogix chassis and a
5-slot ControlLogix-XT chassis. Slot 0 is the first slot and is always the leftmost
slot in the chassis.
20806
Slot 2 Slot 0
Slot 1 Slot 3
ControlLogix Chassis ControlLogix-XT Chassis
31896
Slot 0 Slot 4 Slot 1 Slot 2 Slot 3
Rockwell Automation Publication ENET-IN002B-EN-P - January 2012 13
Install a 1756 EtherNet/IP Communication Module Chapter 1
Set the Network IP Address
on a Module
To operate an EtherNet/IP communication module on an EtherNet/IP network,
you must set a network IP address.
The IP address uniquely identifies the module. The IP address is in the form
xxx.xxx.xxx.xxx where each xxx is a number from 000254.
There are some reserved values that you cannot use as the first octet in the
address. These numbers are examples of values you cannot use:
001.xxx.xxx.xxx
127.xxx.xxx.xxx
223 to 255.xxx.xxx.xxx
The specific reserved values that cannot be used vary by application.
For more information about configuring an EtherNet/IP network, see
EtherNet/IP Network Configuration User Manual, publication ENET-UM001.
Depending on the 1756 EtherNet/IP communication module, you can use some
or all of these tools to set the network Internet Protocol (IP) address:
Rotary switches - The 1756-ENBT and 1756-EWEB modules do not offer
rotary switches. If you are using either of these modules, skip Set the
Network IP Address with the Rotary Switches on page 15 and go to Set
the Network IP Address with the BOOTP/DHCP Server on page 16.
Bootstrap Protocol (BOOTP)/Dynamic Host Configuration Protocol
(DHCP) server
RSLinx Classic software
RSLogix 5000 software
The module uses these tools sequentially to set the IP address.
The 1756 EtherNet/IP communication modules are shipped with this
configuration:
BOOTP/DHCP enabled
Rotary switches set to 999 - when applicable
14 Rockwell Automation Publication ENET-IN002B-EN-P - January 2012
Chapter 1 Install a 1756 EtherNet/IP Communication Module
This graphic shows the process used to set your modules IP address.
Figure 1 - How Your Modules IP Address Is Set
If you need to reset your modules settings to its factory default settings during
normal module operation, Reset the Module IP Address to Factory Default Value
on page 24.
The tools are used in this sequence to set the network IP address:
1. Set the Network IP Address with the Rotary Switches
2. Set the Network IP Address with the BOOTP/DHCP Server
3. Set the Network IP Address with RSLinx or RSLogix 5000 Software
Module Powerup
Module has an
IP address.
Switches
set from
001254?
Yes No
Is DHCP or
BOOTP
enabled?
Yes No
Module requests
address from DHCP/
BOOTP server.
Module uses IP
address stored in
nonvolatile memory.
Rockwell Automation Publication ENET-IN002B-EN-P - January 2012 15
Install a 1756 EtherNet/IP Communication Module Chapter 1
Set the Network IP Address with the Rotary Switches
This graphic shows the rotary switches on a 1756 EtherNet/IP communication
module. The switches are on the top of the module.
At powerup, the module reads the rotary switches to determine if they are set to a
valid number for the last portion of the IP address, that is, if the numbers are in
the range from 001254.
If the settings are a valid number, these conditions result:
IP address = 192.168.1.xxx (where xxx represents the switch settings)
Subnet mask = 255.255.255.0
Gateway address = 0.0.0.0
The module does not have a host name assigned, nor does it use any
Domain Name System
We recommend that you set the rotary switches to a valid number before
installing the module.
If either of these conditions exist, the module attempts to use the BOOTP/
DHCP server to set the IP address:
Rotary switches are not set to a valid number.
Module does not have rotary switches.
For more information on using the BOOTP/DHCP server to set the IP address,
see page 15.
Rotary Switches
Front of
Module
16 Rockwell Automation Publication ENET-IN002B-EN-P - January 2012
Chapter 1 Install a 1756 EtherNet/IP Communication Module
Set the Network IP Address with the BOOTP/DHCP Server
The BOOTP/DHCP server is a standalone server you can use to set an IP
address. When used, the BOOTP/DHCP server sets an IP address and other
Transport Control Protocol (TCP) parameters.
You can use the BOOTP/DHCP server to set the modules IP address if one of
these conditions exists at powerup:
The modules rotary switches are not set to a valid number and the module
is BOOTP/DHCP enabled.
The module does not have rotary switches and the module is BOOTP/
DHCP enabled.
Access the BOOTP/DHCP server from one of these locations:
Programs > Rockwell Software > BOOTP-DHCP Server
If you have not installed the server, you can download and install it from
http://www.ab.com/networks/ethernet/bootp.html.
Tools directory on the RSLogix 5000 software installation CD
To set the modules IP address with a BOOTP/DHCP server, follow these steps.
1. Start the BOOTP/DHCP software.
2. From the Tools menu, choose Network Settings.
IMPORTANT Before you start the BOOTP/DHCP server, make sure you have the
modules hardware (MAC) address. The hardware address is on a
sticker on the side of the communication module and uses an
address in a format similar to the following:
00-00-BC-14-55-35
Rockwell Automation Publication ENET-IN002B-EN-P - January 2012 17
Install a 1756 EtherNet/IP Communication Module Chapter 1
3. Type the Subnet Mask of the network.
The Gateway address, Primary and/or Secondary DNS address, and
Domain Name fields are optional.
4. Click OK.
The Request History panel appears with the hardware addresses of all
modules issuing BOOTP requests.
5. Select the appropriate module.
6. Click Add to Relation List.
The New Entry dialog box appears.
7. Type an IP Address, Hostname, and Description for the module.
8. Click OK.
18 Rockwell Automation Publication ENET-IN002B-EN-P - January 2012
Chapter 1 Install a 1756 EtherNet/IP Communication Module
9. To permanently assign this configuration to the module, wait for the
module to appear in the Relation List panel and select it.
10. Click Disable BOOTP/DHCP.
When power is recycled, the module uses the assigned configuration and
does not issue a BOOTP request.
Use DHCP Software
Dynamic Host Configuration Protocol (DHCP) software automatically assigns
IP addresses to client stations logging onto a TCP/IP network. DHCP is based
on BOOTP and maintains some backward compatibility. The main difference is
that BOOTP allows for manual configuration (static), while DHCP allows for
both static and dynamic allocation of network addresses and configurations to
newly attached modules.
Be cautious when using DHCP software to configure a module. A BOOTP
client, such as the EtherNet/IP communication modules, can start from a DHCP
server only if the DHCP server is specifically written to also handle BOOTP
queries. This is specific to the DHCP software package used. Consult your
system administrator to see if a DHCP package supports BOOTP commands
and manual IP allocation.
IMPORTANT If you do not click Disable BOOTP/DHCP, on a power cycle, the
host controller clears the current IP configuration and begins
sending BOOTP requests again.
ATTENTION: The EtherNet/IP communication module must be assigned
a fixed network address. The IP address of this module must not be
dynamically provided.
Failure to observe this precaution may result in unintended machine motion
or loss of process control.
Rockwell Automation Publication ENET-IN002B-EN-P - January 2012 19
Install a 1756 EtherNet/IP Communication Module Chapter 1
Set the Network IP Address with RSLinx or
RSLogix 5000 Software
This table describes when to set the network IP address with RSLinx or
RSLogix 5000 software.
Consider these factors when you determine how to set the network IP address:
Network isolation from or integration into the plant/enterprise network
Network size - For large networks, isolated networks, it might be more
convenient and safer to use a BOOTP/DHCP server rather than RSLogix
5000 or RSLinx software. The BOOTP/DHCP server also limits the
possibility of assigning duplicate IP addresses.
Company policies and procedures dealing with plant-floor network
installation and maintenance
Level of involvement by IT personnel in plant floor network installation
and maintenance
Type of training offered to control engineers and maintenance personnel
If you use the Rockwell Automation BOOTP or DHCP server in an uplinked
subnet where an enterprise DHCP server exists, a module may get an address
from the enterprise server before the Rockwell Automation utility even sees the
module. You might have to disconnect from the uplink to set the address and
configure the module to retain its static address before reconnecting to the
uplink. This is not a problem if you have node names configured in the module
and leave DHCP enabled.
Conditions Software to Use Page
A BOOTP server is not available.
The EtherNet/IP communication module is connected to
another NetLinx network.
RSLinx 20
The RSLogix 5000 project is online with a controller that
communicates to or through the EtherNet/IP communication
module.
RSLogix 5000 23
20 Rockwell Automation Publication ENET-IN002B-EN-P - January 2012
Chapter 1 Install a 1756 EtherNet/IP Communication Module
Set the Network IP Address with RSLinx Software
To use RSLinx software to set the communication modules IP address, follow
these steps.
1. From the Communications menu, choose RSWho.
The RSWho dialog box appears.
2. Navigate to the Ethernet network.
3. Right-click the EtherNet/IP module and choose Module Configuration.
The Module Configuration dialog box appears.
Rockwell Automation Publication ENET-IN002B-EN-P - January 2012 21
Install a 1756 EtherNet/IP Communication Module Chapter 1
4. Click the Port Configuration tab.
5. For Network Configuration Type, click Static to permanently assign this
configuration to the port.
6. Type this information in the appropriate fields:
In the IP Address field, type the IP address.
In the Network Mask field, type the network mask address.
In the Gateway Address field, type the gateway address.
In the Primary Name Server field, type the name of the primary server.
In the Secondary Name Server field, type the name of the secondary
server.
In the Domain Name field, type the domain name.
In the Host Name field, type the host name.
IMPORTANT If you select Dynamic, on a power cycle, the controller clears the
current IP configuration and resumes sending BOOTP requests.
22 Rockwell Automation Publication ENET-IN002B-EN-P - January 2012
Chapter 1 Install a 1756 EtherNet/IP Communication Module
7. Configure the port settings.
8. Click OK.
To Then
Use the default port speed
and duplex settings
Leave Auto-negotiate port speed and duplex checked.
This setting determines the actual speed and duplex
setting.
Manually configure your ports
speed and duplex settings
Follow these steps.
1. Clear the Auto-negotiate port speed and duplex
checkbox.
2. From the Current Port Speed pull-down menu, choose a
port speed.
3. From the Current Duplex pull-down menu, choose the
appropriate Duplex value, that is, Half Duplex or Full
Duplex.
IMPORTANT Consider the following when you configure the modules
port settings:
If the module is connected to an unmanaged switch, leave
Auto-negotiate port speed and duplex checked or the module
will fail.
If you are forcing the port speed and duplex with a managed
switch, the corresponding port of the managed switch must be
forced to the same settings or the module will fail.
Rockwell Automation Publication ENET-IN002B-EN-P - January 2012 23
Install a 1756 EtherNet/IP Communication Module Chapter 1
Set the Network IP Address with RSLogix 5000 Software
To use RSLogix 5000 software to set the communication modules IP address,
follow these steps.
1. In the Controller Organizer, right-click the EtherNet/IP module and
choose Properties.
The Module Properties dialog box appears.
2. Click the Port Configuration tab.
3. In the IP Address field, type the IP address.
4. In the other fields, type the other network parameters, if needed.
5. Click Set.
6. Click OK.
IMPORTANT The fields that appear vary from one EtherNet/IP module
to another.
24 Rockwell Automation Publication ENET-IN002B-EN-P - January 2012
Chapter 1 Install a 1756 EtherNet/IP Communication Module
Reset the Module IP Address to Factory Default Value
You can reset the modules IP address to its factory default value with the
following methods:
If the module has rotary switches, set the switches to 888 and cycle power.
If the module does not have rotary switches, use a MSG instruction to the
reset the IP address.
For more information on resetting the network IP address to its default
value with a MSG instruction, see KnowledgeBase article #55362, Reset
module to factory defaults. You can access the article at http://
rockwellautomation.custhelp.com/app/answers/list.
Install the Module
To install the module, follow these steps.
1. Align the circuit board with top and bottom guides in the chassis.
WARNING: When you insert or remove the module while backplane
power is on, an electrical arc can occur. This could cause an explosion in
hazardous location installations.
Be sure that power is removed or the area is nonhazardous before
proceeding. Repeated electrical arcing causes excessive wear to contacts
on both the module and its mating connector. Worn contacts may create
electrical resistance that can affect module operation.
31588-M
Rockwell Automation Publication ENET-IN002B-EN-P - January 2012 25
Install a 1756 EtherNet/IP Communication Module Chapter 1
2. Slide the module into the chassis, making sure the module backplane
connector properly connects to the chassis backplane and noting that the
module is properly installed when it is flush with the power supply or other
installed modules.
Connect the Module to an
EtherNet/IP Network via an
RJ45 Connection
These 1756 EtherNet/IP communication modules use an RJ45 connector to
connect to an EtherNet/IP network:
1756-ENBT - ControlLogix EtherNet/IP bridge module
1756-EN2T - ControlLogix EtherNet/IP bridge module
1756-EN2TR - ControlLogix EtherNet/IP 2-port module
1756-EN2TXT - ControlLogix-XT EtherNet/IP module
1756-EN3TR - ControlLogix EtherNet/IP 2-port module
1756-EWEB - ControlLogix EtherNet/IP Web Server module
Wire the RJ45 connector as shown.
31589-M
RJ 45
8
1
8 ------ NC
7 ------ NC
6 ------ RD-
5 ------ NC
4 ------ NC
3 ------ RD+
2 ------ TD-
1 ------ TD+
26 Rockwell Automation Publication ENET-IN002B-EN-P - January 2012
Chapter 1 Install a 1756 EtherNet/IP Communication Module
To connect the module to the network, follow these steps.
1. Attach the cable with the RJ45 connector to the Ethernet port on the
bottom of the module as shown.
This example graphic shows two cables attached to the Ethernet ports at
the bottom of a 2-port module.
2. Attach the other end of the cable to the devices in your network.
WARNING: If you connect or disconnect the communication cable with
power applied to this module or any device on the network, an electrical
arc can occur. This could cause an explosion in hazardous location
installations.
Be sure that power is removed or the area is nonhazardous before
proceeding.
Rockwell Automation Publication ENET-IN002B-EN-P - January 2012 27
Install a 1756 EtherNet/IP Communication Module Chapter 1
Connect the Module to an
EtherNet/IP Network via a
Fiber Connector
The 1756-EN2F ControlLogix EtherNet/IP module uses a fiber connector to
connect to an EtherNet/IP network.
Attach the LC2 multi-mode fiber cable to the Ethernet port on the bottom of the
module as shown.
ATTENTION: Do not look directly into the optical port. Under certain
conditions, viewing the optical port may expose the eye to hazard. When
viewed under some conditions, the optical port may expose the eye
beyond the maximum permissible exposure recommendations.
Class 1 laser product. Laser radiation is present when the system is open
and interlocks bypassed. Only trained and qualified personnel should be
allowed to install, replace, or service this equipment.
28 Rockwell Automation Publication ENET-IN002B-EN-P - January 2012
Chapter 1 Install a 1756 EtherNet/IP Communication Module
Download the Add-on
Profile
The module has a later firmware revision for the communication module than
recognized in the most current version of RSLogix 5000 software, you may need
to download the Add-on Profile (AOP) for the communication module so it can
be recognized in the Controller Organizer.
To download an AOP, follow these steps.
1. Locate the module AOP on http://support.rockwellautomation.com/
controlflash/LogixProfiler.asp.
2. Click the desired file to download it.
3. Enter your RSLogix 5000 software serial number and click Qualify for
Update.
4. Download and extract the zipped files to a temporary directory.
5. Shut down any instances of RSLogix 5000 software that are currently
running.
6. In the temporary directory, double-click the MPSetup.exe file and follow
the onscreen instructions to install the AOP.
IMPORTANT You need a Rockwell Automation MySupport account to download
the AOP. If you do not have one, follow the steps on the
MySupport website to obtain an account.
Rockwell Automation Publication ENET-IN002B-EN-P - January 2012 29
Install a 1756 EtherNet/IP Communication Module Chapter 1
Connect to the Module via
the USB Port
These 1756 EtherNet/IP communication modules have a USB device port:
1756-EN2F - ControlLogix EtherNet/IP bridge module
1756-EN2T - ControlLogix EtherNet/IP bridge module
1756-EN2TR - ControlLogix EtherNet/IP 2-port module
1756-EN2TXT - ControlLogix-XT EtherNet/IP module
1756-EN3TR - ControlLogix EtherNet/IP 2-port module
The module has a USB device port that uses a series B receptacle. To use the USB
port, you must have RSLinx Classic software, version 2.55 or later, installed on
your computer.
Use a USB cable to connect your computer to the USB port. You can download
programs to controllers and configure Ethernet modules directly from your
computer over a USB connection.
For more information about USB setup and configuration, see Chapter 4, USB
Communication on page 57.
WARNING: Do not use the USB port in hazardous locations.
ATTENTION: The USB port is intended for temporary local programming
purposes only and is not intended for permanent connection. The USB
cable is not to exceed 3.0 m (9.84 ft) and must not contain hubs.
30 Rockwell Automation Publication ENET-IN002B-EN-P - January 2012
Chapter 1 Install a 1756 EtherNet/IP Communication Module
Apply Chassis Power and
Check Status Indicators
Before you apply power, you must install and connect a ControlLogix chassis and
power supply.
To apply power, follow these steps.
1. Flip the switch to the ON position.
2. Check the power supply and module status indicators and alphanumeric
display to determine that the power supply and module are operating
properly.
The alphanumeric display should cycle through the following states:
TEST - PASS - OK - REV x.x, where x.x is the modules firmware revision.
The display then alternates between OK and port link status for both
ports.
LINK NET OK
Rockwell Automation Publication ENET-IN002B-EN-P - January 2012 31
Install a 1756 EtherNet/IP Communication Module Chapter 1
Install or Remove the
Module Under Power
You can install or remove this module while chassis power is applied.
Be sure that power is removed or the area is nonhazardous before proceeding.
Repeated electrical arcing causes excessive wear to contacts on both the module
and its mating connector. Worn contacts may create electrical resistance that can
affect module operation.
To remove or replace the module, follow these steps.
1. Push on the upper and lower module tabs to disengage them.
2. Slide the module out of the chassis.
WARNING: When you insert or remove the module while backplane
power is on, an electrical arc can occur. This could cause an explosion in
hazardous location installations.
Be sure that power is removed or the area is nonhazardous before
proceeding. Repeated electrical arcing causes excessive wear to contacts on
both the module and its mating connector. Worn contacts may create
electrical resistance that can affect module operation.
IMPORTANT If you want to replace an existing module with an identical one, and you
want to resume identical system operation, you must install the new
module in the same slot.
31590-M
31591-M
32 Rockwell Automation Publication ENET-IN002B-EN-P - January 2012
Chapter 1 Install a 1756 EtherNet/IP Communication Module
Notes:
Rockwell Automation Publication ENET-IN002B-EN-P - January 2012 33
Chapter 2
Install a 1768 EtherNet/IP Communication
Module
Topic Page
Installation Summary 36
Set the Network IP Address 37
Install the Module 46
Connect the Module to an EtherNet/IP Network via an RJ45
Connection
48
Download the Add-on Profile 49
Apply Chassis Power and Check Status Indicators 50
Remove the Module 51
ATTENTION: Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications
(as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11. Without appropriate
precautions, there may be difficulties with electromagnetic compatibility in residential and other environments due to
conducted and radiated disturbances.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for
those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting
from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the
spread of flame, complying with a flame spread rating of 5VA or be approved for the application if non-metallic. The interior
of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain
additional information regarding specific enclosure type ratings that are required to comply with certain product safety
certifications.
In addition to this publication, see the following:
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1, for additional installation requirements
NEMA Standard 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosures
34 Rockwell Automation Publication ENET-IN002B-EN-P - January 2012
Chapter 2 Install a 1768 EtherNet/IP Communication Module
North American Hazardous Location Approval
The following information applies when operating this
equipment in hazardous locations.
Informations sur lutilisation de cet quipement en
environnements dangereux.
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in
Class I Division 2 Groups A, B, C, D, Hazardous Locations and
nonhazardous locations only. Each product is supplied with
markings on the rating nameplate indicating the hazardous
location temperature code. When combining products within a
system, the most adverse temperature code (lowest "T" number)
may be used to help determine the overall temperature code of the
system. Combinations of equipment in your system are subject to
investigation by the local Authority Having Jurisdiction at the time
of installation.
Les produits marqus "CL I, DIV 2, GP A, B, C, D" ne conviennent
qu' une utilisation en environnements de Classe I Division 2
Groupes A, B, C, D dangereux et non dangereux. Chaque produit
est livr avec des marquages sur sa plaque d'identification qui
indiquent le code de temprature pour les environnements
dangereux. Lorsque plusieurs produits sont combins dans un
systme, le code de temprature le plus dfavorable (code de
temprature le plus faible) peut tre utilis pour dterminer le code
de temprature global du systme. Les combinaisons
d'quipements dans le systme sont sujettes inspection par les
autorits locales qualifies au moment de l'installation.
WARNING: EXPLOSION HAZARD -
Do not disconnect equipment unless power has
been removed or the area is known to be
nonhazardous.
Do not disconnect connections to this equipment
unless power has been removed or the area is
known to be nonhazardous. Secure any external
connections that mate to this equipment by using
screws, sliding latches, threaded connectors, or
other means provided with this product.
Substitution of components may impair suitability
for Class I, Division 2.
If this product contains batteries, they must only
be changed in an area known to be
nonhazardous.
WARNING: RISQUE DEXPLOSION
Couper le courant ou s'assurer que
l'environnement est class non dangereux avant
de dbrancher l'quipement.
Couper le courant ou s'assurer que
l'environnement est class non dangereux avant
de dbrancher les connecteurs. Fixer tous les
connecteurs externes relis cet quipement
l'aide de vis, loquets coulissants, connecteurs
filets ou autres moyens fournis avec ce produit.
La substitution de composants peut rendre cet
quipement inadapt une utilisation en
environnement de Classe I, Division 2.
S'assurer que l'environnement est class non
dangereux avant de changer les piles.
Rockwell Automation Publication ENET-IN002B-EN-P - January 2012 35
Install a 1768 EtherNet/IP Communication Module Chapter 2
European Hazardous Location Approval
The following applies when the product bears the Ex Marking.
This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC and has been
found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment
intended for use in Zone 2 potentially explosive atmospheres, given in Annex II to this Directive.
Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 60079-15 and EN 60079-0.
ATTENTION: This equipment is not resistant to sunlight or other sources of UV radiation.
WARNING:
This equipment must be installed in an enclosure providing at least IP54 protection when applied in Zone 2
environments.
This equipment shall be used within its specified ratings defined by Rockwell Automation.
Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than
40% when applied in Zone 2 environments.
This equipment must be used only with ATEX certified Rockwell Automation backplanes.
Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors,
or other means provided with this product.
Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
ATTENTION: Prevent Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation.
Follow these guidelines when you handle this equipment:
Touch a grounded object to discharge potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
Use a static-safe workstation, if available.
Store the equipment in appropriate static-safe packaging when not in use.
36 Rockwell Automation Publication ENET-IN002B-EN-P - January 2012
Chapter 2 Install a 1768 EtherNet/IP Communication Module
Installation Summary
To install a communication module in a 1768 CompactLogix system, follow
these steps.
1. Set the Network IP Address.
2. Install the Module.
3. Connect the Module to an EtherNet/IP Network via an RJ45
Connection.
4. Download the Add-on Profile.
5. Apply Chassis Power and Check Status Indicators.
6. Remove the Module. - Optional
Grounding Considerations
ATTENTION: This product is grounded through the DIN rail to chassis
ground. Use zinc-plated yellow-chromate steel DIN rail to assure proper
grounding. The use of other DIN rail materials (for example, aluminum or
plastic) that can corrode, oxidize, or are poor conductors, can result in
improper or intermittent grounding. Secure DIN rail to mounting surface
approximately every 200 mm (7.87 in.) and use end-anchors
appropriately.
Rockwell Automation Publication ENET-IN002B-EN-P - January 2012 37
Install a 1768 EtherNet/IP Communication Module Chapter 2
Set the Network IP Address
To operate an EtherNet/IP communication module on an EtherNet/IP network,
you must set a network IP address.
The IP address uniquely identifies the module. The IP address is in the form
xxx.xxx.xxx.xxx where each xxx is a number from 000254.
There are some reserved values that you cannot use as the first octet in the
address. These numbers are examples of values you cannot use:
001.xxx.xxx.xxx
127.xxx.xxx.xxx
223 to 255.xxx.xxx.xxx
The specific reserved values that cannot be used vary by application.
For more information about configuring an EtherNet/IP network, see
EtherNet/IP Network Configuration User Manual, publication ENET-UM001.
You can these tools to set the network Internet Protocol (IP) address on your
1768 EtherNet/IP communication module:
Bootstrap Protocol (BOOTP)/Dynamic Host Configuration Protocol
(DHCP) server
RSLinx Classic software
RSLogix 5000 software
The module uses these tools sequentially to set the IP address.
The 1768 EtherNet/IP communication modules are shipped with BOOTP/
DHCP enabled
38 Rockwell Automation Publication ENET-IN002B-EN-P - January 2012
Chapter 2 Install a 1768 EtherNet/IP Communication Module
This graphic shows the process used to set your modules IP address.
Figure 2 - How Your Modules IP Address is Set
If you need to reset your modules settings to its factory default settings during
normal module operation, Reset the Module IP Address to Factory Default Value
on page 46.
The tools are used in this sequence to set the network IP address:
1. Set the Network IP Address with a BOOTP/DHCP Server
2. Set the Network IP Address with RSLinx or RSLogix 5000 Software
Module Powerup
Module has an
IP address.
Is DHCP or
BOOTP
enabled?
Yes No
Module requests
address from DHCP/
BOOTP server.
Adapter uses IP
address stored in
nonvolatile memory.
Rockwell Automation Publication ENET-IN002B-EN-P - January 2012 39
Install a 1768 EtherNet/IP Communication Module Chapter 2
Set the Network IP Address with a BOOTP/DHCP Server
The BOOTP/DHCP server is a standalone server you can use to set an IP
address. When used, the BOOTP/DHCP server sets an IP address and other
Transport Control Protocol (TCP) parameters.
Access the BOOTP/DHCP server from one of these locations:
Programs > Rockwell Software > BOOTP-DHCP Server
If you have not installed the server, you can download and install it from
http://www.ab.com/networks/ethernet/bootp.html.
Tools directory on the RSLogix 5000 software installation CD
To set the modules IP address with a BOOTP/DHCP server, follow these steps.
To set the modules IP address with a BOOTP/DHCP server, follow these steps.
1. Start the BOOTP/DHCP software.
2. From the Tools menu, choose Network Settings.
3. Type the Subnet Mask of the network.
The Gateway address, Primary and/or Secondary DNS address, and
Domain Name fields are optional.
4. Click OK.
IMPORTANT Before you start the BOOTP/DHCP server, make sure you have the
modules hardware (MAC) address. The hardware address is on a
sticker on the side of the communication module and uses an
address in a format similar to the following:
00-0b-db-14-55-35
40 Rockwell Automation Publication ENET-IN002B-EN-P - January 2012
Chapter 2 Install a 1768 EtherNet/IP Communication Module
The Request History panel appears with the hardware addresses of all
modules issuing BOOTP requests.
5. Select the appropriate module.
6. Click Add to Relation List.
The New Entry dialog box appears.
7. Type an IP Address, Hostname, and Description for the module.
8. Click OK.
9. To permanently assign this configuration to the module, wait for the
module to appear in the Relation List panel and select it.
10. Click Disable BOOTP/DHCP.
When power is recycled, the module uses the assigned configuration and
does not issue a BOOTP request.
IMPORTANT If you do not click Disable BOOTP/DHCP, on a power cycle, the
host controller clears the current IP configuration and begins
sending BOOTP requests again.
Rockwell Automation Publication ENET-IN002B-EN-P - January 2012 41
Install a 1768 EtherNet/IP Communication Module Chapter 2
Use DHCP Software
Dynamic Host Configuration Protocol (DHCP) software automatically assigns
IP addresses to client stations logging onto a TCP/IP network. DHCP is based
on BOOTP and maintains some backward compatibility. The main difference is
that BOOTP allows for manual configuration (static), while DHCP allows for
both static and dynamic allocation of network addresses and configurations to
newly attached modules.
Be cautious when using DHCP software to configure a module. A BOOTP
client, such as the EtherNet/IP communication modules, can start from a DHCP
server only if the DHCP server is specifically written to also handle BOOTP
queries. This is specific to the DHCP software package used. Consult your
system administrator to see if a DHCP package supports BOOTP commands
and manual IP allocation.
ATTENTION: The EtherNet/IP communication module must be assigned
a fixed network address. The IP address of this module must not be
dynamically provided.
Failure to observe this precaution may result in unintended machine motion
or loss of process control.
42 Rockwell Automation Publication ENET-IN002B-EN-P - January 2012
Chapter 2 Install a 1768 EtherNet/IP Communication Module
Set the Network IP Address with RSLinx or
RSLogix 5000 Software
This table describes when to set the network IP address with RSLinx or
RSLogix 5000 software.
Consider these factors when you determine how to set the network IP address:
Network isolation from or integration into the plant/enterprise network
Network size - For large networks, isolated networks, it might be more
convenient and safer to use a BOOTP/DHCP server rather than RSLogix
5000 or RSLinx software. The BOOTP/DHCP server also limits the
possibility of assigning duplicate IP addresses.
Company policies and procedures dealing with plant floor network
installation and maintenance
Level of involvement by IT personnel in plant-floor network installation
and maintenance
Type of training offered to control engineers and maintenance personnel
If you use the Rockwell Automation BOOTP or DHCP server in an uplinked
subnet where an enterprise DHCP server exists, a module may get an address
from the enterprise server before the Rockwell Automation utility even sees the
module. You might have to disconnect from the uplink to set the address and
configure the module to retain its static address before reconnecting to the
uplink. This is not a problem if you have node names configured in the module
and leave DHCP enabled.
Conditions Software to Use Page
A BOOTP server is not available.
The EtherNet/IP communication module is connected to
another NetLinx network.
RSLinx 43
The RSLogix 5000 project is online with a controller that
communicates to or through the EtherNet/IP communication
module.
RSLogix 5000 45
Rockwell Automation Publication ENET-IN002B-EN-P - January 2012 43
Install a 1768 EtherNet/IP Communication Module Chapter 2
Set the Network IP Address with RSLinx Software
To use RSLinx software to set the communication modules IP address, follow
these steps.
1. From the Communications menu, choose RSWho.
The RSWho dialog box appears.
2. Navigate to the Ethernet network.
3. Right-click the EtherNet/IP module and choose Module Configuration.
The Module Configuration dialog box appears.
4. Click the Port Configuration tab.
44 Rockwell Automation Publication ENET-IN002B-EN-P - January 2012
Chapter 2 Install a 1768 EtherNet/IP Communication Module
5. For Network Configuration Type, click Static to permanently assign this
configuration to the port.
6. Type this information in the appropriate fields:
In the IP Address field, type the IP address.
In the Network Mask field, type the network mask address.
In the Gateway Address field, type the gateway address.
In the Primary Name Server field, type the name of the primary server.
In the Secondary Name Server field, type the name of the
secondary server.
In the Domain Name field, type the domain name.
In the Host Name field, type the host name.
7. Configure the port settings.
8. Click OK.
IMPORTANT If you click Dynamic, on a power cycle, the controller clears
the current IP configuration and resumes sending BOOTP
requests.
To Then
Use the default port speed
and duplex settings
Leave Auto-negotiate port speed and duplex checked.
This setting determines the actual speed and duplex
setting.
Manually configure your ports
speed and duplex settings
Follow these steps.
1. Clear the Auto-negotiate port speed and duplex
checkbox.
2. From the Current Port Speed pull-down menu, choose a
port speed.
3. From the Current Duplex pull-down menu, choose the
appropriate Duplex value, that is, Half Duplex or Full
Duplex.
Rockwell Automation Publication ENET-IN002B-EN-P - January 2012 45
Install a 1768 EtherNet/IP Communication Module Chapter 2
Set the Network IP Address with RSLogix 5000 Software
To use RSLogix 5000 software to set the communication modules IP address,
follow these steps.
1. In the Controller Organizer, right-click the EtherNet/IP module and
choose Properties.
The Module Properties dialog box appears.
2. Click the Port Configuration tab.
3. In the IP Address field, type the IP address.
4. In the other fields, type the other network parameters, if needed.
5. Click Apply.
6. Click OK.
IMPORTANT The fields that appear vary between EtherNet/IP
communication modules.
46 Rockwell Automation Publication ENET-IN002B-EN-P - January 2012
Chapter 2 Install a 1768 EtherNet/IP Communication Module
Reset the Module IP Address to Factory Default Value
You can reset the modules IP address to its factory default value by sending a
MSG instruction to the module.
For more information on resetting the network IP address to its default value
with a MSG instruction, see KnowledgeBase article #55362, Reset module to
factory defaults. You can access the article at
http://rockwellautomation.custhelp.com/app/answers/list.
Install the Module
To install the module, follow this procedure.
If You Use Screws to Mount the Module
The steps in these instructions show how to mount the modules on DIN rail. If
you are using screws instead of DIN rail, make these changes to the instructions.
1. Use the modules as a template and mark pilot holes on your panel.
2. Drill the pilot holes for M4 or #8 screws.
3. Use M4 or #8 screws to mount the modules to your panel, using 1.16 Nm
(10 lbin) of torque.
4. Ground the module on a ground bus with a dedicated earth ground stake.
5. Connect the ground bus to a functional earth ground on the DIN rail or
panel.
Refer to Industrial Automation Wiring and Grounding Guidelines, publication
1770-4.1, for additional information.
IMPORTANT Do not use screws and DIN rail to mount the modules. It is possible to
break the mounting tabs off if you screw the modules to the panel while
they are on DIN rail.
Rockwell Automation Publication ENET-IN002B-EN-P - January 2012 47
Install a 1768 EtherNet/IP Communication Module Chapter 2
Mount on a DIN Rail
To install the module on a DIN rail, follow these steps.
1. Mount the DIN rail in a suitable location.
2. Open the DIN rail latches on the module.
3. Align and press the module onto the DIN rail to the left of the controller.
4. Slide the module snugly against the controller.
ATTENTION: This product is grounded through the DIN rail to
chassis ground. Use zinc plated yellow-chromate steel DIN rail to
assure proper grounding. The use of other DIN rail materials (for
example, aluminum or plastic) that can corrode, oxidize, or are
poor conductors, can result in improper or intermittent grounding.
Secure DIN rail to mounting surface approximately every 200 mm
(7.8 in.) and use end-anchors appropriately.
31597-M
48 Rockwell Automation Publication ENET-IN002B-EN-P - January 2012
Chapter 2 Install a 1768 EtherNet/IP Communication Module
5. Close the DIN rail latches on the module.
In this example, the 1768 EtherNet/IP communication module is installed in slot
1 and the 1768 CompactLogix controller is installed in slot 0.
Connect the Module to an
EtherNet/IP Network via an
RJ45 Connection
Wire the RJ45 connector as shown.
8 ------ NC
7 ------ NC
6 ------ RD-
5 ------ NC
4 ------ NC
3 ------ RD+
2 ------ TD-
1 ------ TD+
Rockwell Automation Publication ENET-IN002B-EN-P - January 2012 49
Install a 1768 EtherNet/IP Communication Module Chapter 2
To connect the module to the network, follow these steps.
1. Attach the cable with the RJ45 connector to the Ethernet port on the
bottom of the module as shown.
2. Attach the other end of the cable to the devices in your network.
Download the Add-on
Profile
The module has a later firmware revision for the communication module than
recognized in the most current version of RSLogix 5000 software, you may need
to download the Add-on Profile (AOP) for the communication module so it can
be recognized in the Controller Organizer.
To download an AOP, follow these steps.
1. Locate the module AOP on http://support.rockwellautomation.com/
controlflash/LogixProfiler.asp.
2. Click the desired file to download it.
3. Enter your RSLogix 5000 software serial number and click Qualify for
Update.
WARNING: If you connect or disconnect the communication cable with
power applied to this module or any device on the network, an electrical
arc can occur. This could cause an explosion in hazardous location
installations.
Be sure that power is removed or the area is nonhazardous before
proceeding.
IMPORTANT You need a Rockwell Automation MySupport account to download
the AOP. If you do not have one, follow the steps on the
MySupport website to obtain an account.
50 Rockwell Automation Publication ENET-IN002B-EN-P - January 2012
Chapter 2 Install a 1768 EtherNet/IP Communication Module
4. Download and extract the zipped files to a temporary directory.
5. Shut down any instances of RSLogix 5000 software that are currently
running.
6. In the temporary directory, double-click the MPSetup.exe file and follow
the onscreen instructions to install the AOP.
Apply Chassis Power and
Check Status Indicators
Before you apply power, you must install and mount a CompactLogix controller
and Compact I/O power supply on the DIN rail.
To apply power, follow these steps.
1. Flip the switch to the ON position.
2. Check the power supply and module status indicators and alphanumeric
display to determine that the power supply and module are operating
properly.
Power Supply
Status Indicators
Module Status
Indicators
Rockwell Automation Publication ENET-IN002B-EN-P - January 2012 51
Install a 1768 EtherNet/IP Communication Module Chapter 2
Remove the Module
To remove the communication module, follow these steps.
1. Flip the switch to the OFF position.
2. Open the DIN rail latches of the communication module and the module
directly to the left of communication module.
3. Slide the communication module and other modules to the right.
IMPORTANT When you turn the CompactLogix power supply off, make sure you wait
for all status indicators on the power supply and controller to turn off
before disconnecting any part from the system.
If you disconnect the CompactLogix system while the controller is still
writing its program to memory, the program write will not be completed
and you will lose your program.
52 Rockwell Automation Publication ENET-IN002B-EN-P - January 2012
Chapter 2 Install a 1768 EtherNet/IP Communication Module
4. Open the DIN rail latches of the controller.
5. Slide the controller and other modules away from the communication
module.
6. Pull the communication module off the DIN rail.
Rockwell Automation Publication ENET-IN002B-EN-P - January 2012 53
Chapter 3
Configure a Workstation to Operate on an
EtherNet/IP Network
Before you begin, make sure the workstation is ready to connect to the
EtherNet/IP network:
The Ethernet communication card is already installed in the workstation.
The IP address and other network parameters are correctly configured for
the workstation.
The workstation is properly connected to the EtherNet/IP network.
Select the Driver
You can choose from any of three Ethernet drivers:
AB_ETHIP
AB_ETH
Topic Page
Select the Driver 53
Configure the Ethernet Communication Driver 54
54 Rockwell Automation Publication ENET-IN002B-EN-P - January 2012
Chapter 3 Configure a Workstation to Operate on an EtherNet/IP Network
Configure the Ethernet
Communication Driver
To configure the Ethernet communication driver in RSLinx Classic software,
follow these steps
1. From the Communications pull-down menu, choose Configure Drivers.
The Configure Drivers dialog box appears.
2. From the Available Driver Types pull-down menu, choose EtherNet/IP
Driver or Ethernet devices.
3. Click Add New.
The Add New RSLinx Classic Driver dialog box appears.
Rockwell Automation Publication ENET-IN002B-EN-P - January 2012 55
Configure a Workstation to Operate on an EtherNet/IP Network Chapter 3
4. Type a name for the new driver and click OK.
The Configure driver dialog box appears.
5. Click Browse Local Subnet.
6. Click Apply.
7. Click OK.
This new driver is now available.
56 Rockwell Automation Publication ENET-IN002B-EN-P - January 2012
Chapter 3 Configure a Workstation to Operate on an EtherNet/IP Network
Notes:
Rockwell Automation Publication ENET-IN002B-EN-P - January 2012 57
Chapter 4
USB Communication
These EtherNet/IP communication modules have a USB device port:
1756-EN2F - ControlLogix EtherNet/IP bridge module
1756-EN2T - ControlLogix EtherNet/IP bridge module
1756-EN2TR - ControlLogix EtherNet/IP 2-port module
1756-EN2TXT - ControlLogix-XT EtherNet/IP module
1756-EN3TR - ControlLogix EtherNet/IP 2-port module
Set Up the Hardware
In this example, the controller in the local chassis produces a tag that the
Logix5000 controller in the remote chassis consumes. The local controller can
also send a MSG instruction to the remote controller.
Figure 3 - Sharing Data and Transferring Messages
Topic Page
Set Up the Hardware 58
Configure a Module via the USB Port 58
Load Firmware through a USB Port 60
Logix5575 EtherNet/IP ControlNet
OK FORCE SD RUN
RUN REM PROG
1 2
LNK1 LNK2 OK
10/100 BASE T
EtherNet/IP
1 2
LNK1 LNK2 OK
10/100 BASE T
Local Chassis
USB Connection
EtherNet/IP
Remote Chassis with Logix5000 Controllers
58 Rockwell Automation Publication ENET-IN002B-EN-P - January 2012
Chapter 4 USB Communication
Configure a Module via
the USB Port
You can configure some EtherNet/IP communication modules via the USB port.
To use the USB port, you must have RSLinx Classic software, version 2.51 or
later, installed on your computer.
Use a USB cable to connect your computer to the USB port. You can download
programs to controllers and configure other devices accessible via the
communication module through this connection.
Set Up a USB Driver
To configure RSLinx Classic software to use a USB port, you need to first set up a
USB driver. To set up a USB driver, follow these steps.
1. With one end installed in the computer, install a USB cable in your
communication modules USB port.
The RSLinx Found New Hardware Wizard dialog box appears.
2. Click Install the software automatically (Recommended).
3. Click Next.
WARNING: Do not use the USB port in hazardous locations.
ATTENTION: The USB port is intended for temporary local
programming purposes only and is not intended for permanent
connection. The USB cable is not to exceed 3.0 m (9.84 ft) and must
not contain hubs.
Rockwell Automation Publication ENET-IN002B-EN-P - January 2012 59
USB Communication Chapter 4
These RSLinx dialog boxes appear consecutively.
4. Click Finish to set up your USB driver.
60 Rockwell Automation Publication ENET-IN002B-EN-P - January 2012
Chapter 4 USB Communication
5. In RSLinx Classic software, from the Communications menu,
choose RSWho.
The RSLinx Workstation organizer appears.
Your 1756-EN2T module appears under two different drivers, a virtual
chassis and the USB port.
Load Firmware through a
USB Port

Virtual Chassis Driver
USB Port Driver
IMPORTANT Do not simultaneously load firmware for more than one module at a
time through a USB port. If you do, one or more of the firmware loads
may fail in the middle of the loading process.
Rockwell Automation Publication ENET-IN002B-EN-P - January 2012 61
Appendix A
1756 EtherNet/IP Status Indicators
The 1756 EtherNet/IP communication modules support these status indicators.
Topic Page
1756-ENBT, 1756-EN2F, 1756-EN2T, 1756-EN2TXT, 1756-EWEB
EtherNet/IP Module Status Indicators
62
1756-EN2TR, 1756-EN3TR EtherNet/IP Module Status Indicators 64
Status Indicator Description
Module Status Display Alphanumeric display that scrolls messages. For example, when a
module is operating normally, the display scrolls the modules IP
address.
Link Status (LINK) Indicates the modules current state with respect to transmitting data on
the EtherNet/IP network.
OK Status (OK) Indicates the modules current state. For example, this status indicator
indicates if the module is executing power-up testing, in the process of a
firmware update or operating normally.
Network Status (NET) Indicates if CIP connections are established.
The 1756-EN2TR and 1756-EN3TR modules do not have a NET status
indicator.
62 Rockwell Automation Publication ENET-IN002B-EN-P - January 2012
Chapter A 1756 EtherNet/IP Status Indicators
1756-ENBT, 1756-EN2F,
1756-EN2T, 1756-EN2TXT,
1756-EWEB EtherNet/IP
Module Status Indicators
The 1756 EtherNet/IP communication modules listed in this section use the
same status indicators:
Module Status Display
Link Status Indicator (LINK)
Network Status Indicator (NET)
OK Status Indicator (OK)
This graphic shows the front of the module for all of these modules.
Table 1 - Link (LINK) Status Indicator
Status Description
Off The module is experiencing one of these conditions:
The module is not powered. Check all physical connections to the module.
The module is powered but does not have an IP address. Assign an IP
address to the module.
Flashing green The module has a valid IP address but has not established any CIP
connections.
Green The module has established at least 1 CIP connection and is operating
properly. The modules IP address scrolls across the Module Status display.
Table 2 - Network (NET) Status Indicator
Status Description
Off One of these conditions exists:
The module is not powered.
Verify there is chassis power.
Verify that the module is completely inserted into the chassis and
backplane.
Make sure the module has been configured.
The module is powered but does not have an IP address. Assign an IP
address to the module.
Module Status Display
OK Status Indicator
Network Status Indicator (NET)
Link Status
Indicator (LINK)
Rockwell Automation Publication ENET-IN002B-EN-P - January 2012 63
1756 EtherNet/IP Status Indicators Chapter A
Flashing green The controller has an IP address and one of these conditions exists:
The module has not established any CIP connections.
If connections are configured for this module, check the connection
originator for the connection error code.
One or more connections have timed out. For example, an HMI or I/O
connection has timed out.
Reestablish the connection.
Green The module has established at least 1 CIP connection and is operating
properly. The modules IP address scrolls across the Module Status display.
Red The module is in conflict mode. It shares an IP address with another device on
the network. The modules current IP address scrolls across the Module
Status display. The display scrolls: OK <IP_address_of_this_module>
Duplicate IP <Mac_address_of_duplicate_node_detected>
For example: OK 10.88.60.196 Duplicate IP - 00:00:BC:02:34:B4
Change the modules IP address.
Flashing green/
flashing red
The module is performing its power-up testing.
Table 3 - OK Status Indicator
Status Description
Off The module is not powered.
Verify there is chassis power.
Verify that the module is completely inserted into the chassis and
backplane.
Make sure the module has been configured.
Flashing green The module is not configured. The Module Status display scrolls: BOOTP or
DHCP<Mac_address_of_module>
For example: BOOTP 00:0b:db:14:55:35
Configure the module.
Green The module is operating correctly. The modules IP address scrolls across the
Module Status display.
Flashing red The module detected a recoverable minor fault. Check the module
configuration. If necessary, reconfigure the module.
Red The module detected an unrecoverable major fault. Cycle power to the
module. If this does not clear the fault, replace the module.
Flashing red/
flashing green
The module is performing its power-up testing.
Table 2 - Network (NET) Status Indicator
Status Description
64 Rockwell Automation Publication ENET-IN002B-EN-P - January 2012
Chapter A 1756 EtherNet/IP Status Indicators
1756-EN2TR, 1756-EN3TR
EtherNet/IP Module Status
Indicators
The 1756-EN2TR and 1756-EN3TR EtherNet/IP communication modules use
the same status indicators. This graphic shows the front of the module for both of
these modules.
Table 4 - Link Status Indicators (LNK1 and LNK2)
Status Description
Off One of these conditions exists:
The module is not powered.
Verify there is chassis power.
Verify that the module is completely inserted into the chassis and
backplane.
Make sure the module has been configured.
No link exists on the port.
The port is administratively disabled (LNK2).
The port is disabled due to rapid ring faults (LNK2).
Flashing green Activity exists on the port.
Green One of these conditions exists:
A link exists on the port.
The ring network is operating normally on active ring supervisor (LNK2).
A ring partial network fault was detected on the active ring
supervisor (LNK2).
Module Status Display
OK Status Indicator
Link 2 (LNK2) Status Indicator
Link 1 Status
Indicator (LNK1)
Rockwell Automation Publication ENET-IN002B-EN-P - January 2012 65
1756 EtherNet/IP Status Indicators Chapter A
Table 5 - OK Status Indicator
Status Description
Off The module is not powered.
Verify there is chassis power.
Verify that the module is completely inserted into the chassis and
backplane.
Make sure the module has been configured.
Flashing green The module is not configured. The Module Status display scrolls: BOOTP or
DHCP<Mac_address_of_module>
For example: BOOTP 00:0b:db:14:55:35
Configure the module.
Green The module is operating correctly. The Module Status display scrolls: OK
<IP_address_of_this_module>
For example: OK 10.88.60.160
Flashing red The module detected a recoverable minor fault.
Check the module configuration. If necessary, reconfigure the module.
Red The module detected an unrecoverable major fault.
Cycle power to the module. If this does not clear the fault, replace the
module.
Both of these
conditions exist:
Status Indicator
is Red
Module Status
Display is
scrolling: Image
Update Needed
The modules main firmware image needs to be updated. Follow these steps:
1. Update the firmware image.
2. Cycle power to the module.
3. If the status indicators remain the same, that is, red and scrolling Image
Update Needed, replace the module.
Flashing red and
green
The module is performing its power-up testing.
66 Rockwell Automation Publication ENET-IN002B-EN-P - January 2012
Chapter A 1756 EtherNet/IP Status Indicators
Notes:
Rockwell Automation Publication ENET-IN002B-EN-P - January 2012 67
Appendix B
1768 EtherNet/IP Module Status Indicators
The 1768-ENBT and 1768-EWEB EtherNet/IP communication modules
support these status indicators.
This graphic shows the front of the module for the modules.
Link (LINK) Status Indicator
This table describes the LINK status indicator.
Status Indicator Description
Module Status Display Alphanumeric display that scrolls messages. For example, when a
module is operating normally, the display scrolls the modules IP
address.
Link Status (LINK) Indicates the modules current state with respect to transmitting data on
the EtherNet/IP network.
OK Status (OK) Indicates the modules current state. For example, this status indicator
indicates if the module is executing power-up testing, in the process of a
firmware update or operating normally.
Network Status (NET) Indicates if CIP connections are established.
LINK NET OK
LINK NET OK
Module Status
Display
Network Status Indicator (NET)
Link Status
Indicator (LINK)
OK Status Indicator
Table 6 - Link (LINK) Status Indicator
Status Description
Off The module is experiencing one of these conditions:
The module is not powered. Check all physical connections to the module.
The module is powered but does not have an IP address. Assign an IP
address to the module.
Flashing green The module has a valid IP address but has not established any CIP
connections.
Green The module has established at least 1 CIP connection and is operating
properly. The modules IP address scrolls across the Module Status display.
68 Rockwell Automation Publication ENET-IN002B-EN-P - January 2012
Appendix B 1768 EtherNet/IP Module Status Indicators
Network (NET) Status
Indicators
This table describes the NET status indicator.
Table 7 - Network (NET) Status Indicator
Status Description
Off One of these conditions exists:
The module is not powered.
Verify there is chassis power.
Verify that the module is completely inserted into the chassis and
backplane.
Make sure the module has been configured.
The module is powered but does not have an IP address. Assign an IP
address to the module.
Flashing green The controller has an IP address and one of these conditions exists:
The module has not established any CIP connections.
If connections are configured for this module, check the connection
originator for a connection error code.
One or more connections have timed out. For example, an HMI or I/O
connection has timed out.
Reestablish the connection.
Green The module has established at least 1 CIP connection and is operating
properly. The modules IP address scrolls across the Module Status display.
Red The module is in conflict mode. It shares an IP address with another device on
the network. The modules current IP address scrolls across the Module
Status display. The display scrolls: OK <IP_address_of_this_module>
Duplicate IP <Mac_address_of_duplicate_node_detected>
For example: OK 10.88.60.196 Duplicate IP - 00:00:BC:02:34:B4
Change the modules IP address.
Flashing green/
flashing red
The module is performing its power-up testing.
Rockwell Automation Publication ENET-IN002B-EN-P - January 2012 69
1768 EtherNet/IP Module Status Indicators Appendix B
OK Status Indicator
This table describes the OK status indicator.
Table 8 - OK Status Indicator
Status Description
Off The module is not powered.
Verify there is chassis power.
Verify that the module is completely inserted into the chassis and
backplane.
Make sure the module has been configured.
Flashing green The module is not configured. The Module Status display scrolls: BOOTP or
DHCP<Mac_address_of_module>
For example: BOOTP 00:0b:db:14:55:35
Configure the module.
Green The module is operating correctly. The Module Status display scrolls: OK
<IP_address_of_this_module>
For example: OK 10.88.60.160
Flashing red The module detected a recoverable minor fault. Check the module
configuration. If necessary, reconfigure the module.
Red The module detected an unrecoverable major fault. Cycle power to the
module. If this does not clear the fault, replace the module.
Flashing red/
flashing green
The module is performing its power-up testing.
70 Rockwell Automation Publication ENET-IN002B-EN-P - January 2012
Appendix B 1768 EtherNet/IP Module Status Indicators
Notes:
Rockwell Automation Publication ENET-IN002B-EN-P - January 2012 71
Appendix C
Fiber Cable and LC Connector
This appendix provides specifications for the fiber cable and LC connector used
with the 1756-EN2F EtherNet/IP fiber module or the 1783-ETAP1F and 1783-
ETAP2F EtherNet/IP fiber taps.
Figure 4 - Fiber Cable
Specifications
The 1756-EN2F EtherNet/IP fiber module and the 1783-ETAP1F and 1783-
ETAP2F EtherNet/IP fiber taps use a fiber cable and LC connector. The fiber
cable is typically used in 1 m (3 ft), 2 m, (6 ft), 3 m (9 ft), 5 m (15 ft), and 100 m
(300 ft) lengths, but supports lengths up to 2 km (1.24 mi).
The fiber cable and LC connector supports these specifications.
IMPORTANT You can special order a fiber cable in any length up to 2 km (1.24 mi)
from your fiber cable vendor.
Table 9 - Fiber Cable and LC Connector Specifications
Attribute Value
Fiber transceiver type 100Base-FX IEEE802.3u
Optical wavelength 1310 nm no cap
Transmitter launch power at beginning of life
(BOL), min
Allow -1 dB at end of life (EOL)
-19 dBm into 62.5/125 m fiber, N/A = 0.275
-22.5 dBm into 50/125 m fiber, N/A = 0.20
Receiver sensitivity, Min -31.8 dBm
72 Rockwell Automation Publication ENET-IN002B-EN-P - January 2012
Appendix C Fiber Cable and LC Connector
Receiver sensitivity, Max -14 dBm
Fiber channel power budget at rated BER
(Two connected modules or taps, either the
1756-EN2F EtherNet/IP fiber module, or 1783-
ETAP1F or 1783-ETAP2F EtherNet/IP fiber taps)
12.8 dB for 62.5/125 m multimode fiber
9.3 dB for 50/125 m multimode fiber
Fiber type Glass
62.5/125 m and 50/125 m multimode fiber
Simplex or duplex
Jacket type and jacket diameter is dependent on
connector selection
Graded Index (GI) fiber
Per IEC 60794-1-1, IEC 60793-2-10 category A1
fibers
Connector type IEC 61754-20 LC connector, max. insertion loss
0.75 dB per connection
Channel length, Max 2 km (1.24 mi)
(1)
(1) The channel, that is, connectors and cable, must not exceed the allowable power budget.
IMPORTANT Allow at least 5.08 cm (2 in.) for the fiber cable bend radius. Contact
the cable manufacturer for more information on the recommended
cable bend radius.
Table 9 - Fiber Cable and LC Connector Specifications
Attribute Value
EXAMPLE In the example shown here, the channel insertion loss is calculated for an optical channel based on
these factors:
1 dB/km fiber
0.75 dB per adapter
Note that in this example, the end connectors are not factored in the calculations.
ATTENTION: The maximum power budget for this example is 12.8 dB for 62.5/125 m fiber. Therefore, the
channel insertion loss for the example of 3.5 dB is less than the maximum power budget.
Fiber 1 dB/km Fiber 1 dB/km Fiber 1 dB/km
0.75 dB 0.75 dB
1km 0.75km 0.25km
0.75 dB 0.75 dB 0.75dB 0.25 dB 1 dB + + + +
Total channel insertion loss = 3.5 db
Rockwell Automation Publication ENET-IN002B-EN-P - January 2012 73
Fiber Cable and LC Connector Appendix C
Notes:
74 Rockwell Automation Publication ENET-IN002B-EN-P - January 2012
Appendix C Fiber Cable and LC Connector
Notes:
Rockwell Otomasyon Ticaret A.., Kar Plaza Merkezi E Blok Kat:6 34752 erenky, stanbul, Tel: +90 (216) 5698400
Publication ENET-IN002B-EN-P - January 2012
Supersedes Publication ENET-IN002A-EN-P - June 2011 Copyright 2012 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products.
At http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and
application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the
best use of these tools.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect
support programs. For more information, contact your local distributor or Rockwell Automation representative,
or visit http://www.rockwellautomation.com/support/.
Installation Assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this manual.
You can contact Customer Support for initial help in getting your product up and running.
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility.
However, if your product is not functioning and needs to be returned, follow these procedures.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document,
complete this form, pSublication RA-DU002, available at http://www.rockwellautomation.com/literature/.
United States or Canada 1.440.646.3434
Outside United States or
Canada
Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact
your local Rockwell Automation representative.
United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain
one) to your distributor to complete the return process.
Outside United States Please contact your local Rockwell Automation representative for the return procedure.