Sie sind auf Seite 1von 7

AGC of a Hydrothermal System with Thyristor

Controlled Phase Shifter in the Tie-Line


Rajesh Joseph Abraham, D. Das, and Amit Patra

Abstract--This paper presents the analysis of Automatic
Generation control (AGC) of a two-area interconnected
hydrothermal system considering a Thyristor Controlled Phase
Shifter (TCPS) in series with the tie-line. It is possible to stabilize
the system frequency and tie-power oscillations by controlling
the phase angle of TCPS which is expected to provide a new
ancillary service for the future power systems. A control strategy
using TCPS is proposed to provide active control of system
frequency. Gain settings of the Integral controllers without and
with TCPS are optimized using Integral Squared Error (ISE)
technique following a step load disturbance in either of the areas
by minimizing a quadratic performance index. Analysis reveals
that a TCPS is quite capable of suppressing the frequency and
tie-power oscillations effectively under the occurrence of sudden
load changes in any of the areas as compared to that obtained
without TCPS.
Index Terms-- AGC, Hydrothermal, TCPS, ISE technique.
I. NOMENCLATURE
T
P1
, T
P2
= Power System Time Constants
K
P1
, K
P2
= Power System Gains
T
T
= Turbine Time Constant
T
G
= Governor Time Constant of Thermal Area
T
W
= Water Time Constant
T
R
, T
1
, T
2
= Time Constants of the Hydro governor
R
1
, R
2
= Governor Speed Regulation parameter of Thermal
and Hydro areas respectively
P
R1
, P
R2
= Rated Area Capacities (a
12
= -P
R1
/P
R2
)
0
12
T = Synchronising coefficient without TCPS
T
12
= Synchronising Coefficient with TCPS
B
1
, B
2
= Frequency Bias Constant of Thermal and Hydro
areas respectively
K
I1
, K
I2
= Integral Gains of Thermal and Hydro areas
respectively
T
PS
= Time constant of the TCPS
K

= Gain constant of the TCPS


This work was supported by the All India Council for Technical Education
(A.I.C.T.E), New Delhi, India, in the form of National Doctoral Fellowship
(NDF 2003) awarded to Rajesh Joseph Abraham
The authors are with the Department of Electrical Engineering, Indian
Institute of Technology, Kharagpur 721 302, India (e-mail:
rja@ee.iitkgp.ernet.in, ddas@ee.iitkgp.ernet.in, amit@ee.iitkgp.ernet.in).
0-7803-9525-5/06/$20.00 2006 IEEE.
II. INTRODUCTION
N a practically interconnected power system, the generation
normally comprises of a mix of thermal, hydro, nuclear and
gas power generation. However, owing to their high
efficiency, nuclear plants are usually kept at base load close to
their maximum output. Gas power generation is ideal for
meeting the varying load demand and such plants form a very
small percentage of total system generation. Thus, the natural
choice of AGC falls on either thermal or hydro units. A
realistic situation may arise where an area regulated by hydro
generation is interconnected to another area regulated by
thermal generation.
The AGC of an interconnected power system has two
principal aspects: maintenance of frequency and power
exchange over inter area tie-lines on their respective
scheduled values. A lot of work [1][9] has been carried out
for the AGC of interconnected power systems. Now a days,
worldwide, the electric power industry is in a transition from
the Vertically Integrated Utility (VIU) scenario, where, a
single utility owned and operated the generation, transmission
and distribution systems and provided power at regulated
rates, to the Deregulated scenario, where, competitive
companies sell unbundled power at lower rates. The
proliferation of nonutility generation such as by Independent
Power Producers (IPPs) that do not possess sufficient
frequency control capabilities, tend to increase considerably.
Furthermore, various kinds of apparatus with large
capacity and fast power consumption such as testing plants for
nuclear fusion, steel factories etc increase significantly. When
these loads are concentrated in power systems, they may cause
a serious problem of frequency oscillations. Therefore, it is
very important to consider how the control services of system
frequency should be implemented. In a deregulated
environment, any power system control such as frequency,
will serve as an ancillary service. Thus, stabilization of
frequency oscillations in an interconnected power system
becomes challenging when implemented in the future
competitive environment. A new frequency stabilization
service which emphasises not only efficiency, reliability and
economics, but also, advanced and improved controls for
satisfying the requirements of power system operation, is
much in demand.
On the other hand, the concept of utilising power
electronic devices for power system control has been widely
accepted in the form of Flexible AC Transmission Systems
I
(FACTS) which provide more flexibility in power system
operation and control [10]. This extra flexibility permits the
independent adjustment of certain system variables such as
power flows, which are not normally controllable. A Thyristor
Controlled Phase Shifter (TCPS) is expected to be an effective
apparatus for the tie-line power flow control of an
interconnected power system
In the analysis of an interconnected power system, some
areas are considered as the channels of disturbances and in
this situation, the conventional frequency control i.e., the
governor may no longer be able to attenuate the large
frequency oscillations due to its slow response [1, 11]. On the
other hand, tie-line power flow control by a TCPS installed in
series with the tie-line in between two areas of an
interconnected power system has the possibility to control the
system frequency positively. The proposed control strategy
will be a new ancillary service for the stabilization of
frequency oscillations of an interconnected power system.
Literature survey shows ample applications of TCPS for the
improvement of dynamic and transient stabilities of power
systems [12][15]. However, no attempt has been made to
improve the performance of AGC of interconnected power
systems considering TCPS in series with the tie-line.
In the present work, analysis has been carried out for the
AGC of interconnected hydrothermal power system
considering a TCPS in series with the tie-line. An
interconnected hydrothermal system involves widely different
characteristics for the hydro and thermal subsystems. The
characteristics of hydro turbines differ from steam turbines in
that the relatively large water inertia used as a source of
energy causes a considerably greater time lag in the response
of the change in the prime mover torque to a change in gate
position, and also an initial tendency for the torque to change
in a direction opposite to that finally produced. The speed
governor characteristics of the hydro units are widely different
from that of the turbo governor. Moreover, the maximum
permissible generation rate constraint for the hydro units is
relatively much higher than the thermal units. Further, the
effects of different Generation Rate Constraints (fairly slow
response for the thermal plant and quite fast response for the
hydro plant) on the selection of optimum controller settings
for the thermal and hydro areas and on the system dynamic
performance considering a TCPS in series with the tie-line is
yet to be established.
In view of the above, the main objectives of the present
work are:
1) To study the effect of a Thyristor Controlled Phase
Shifter (TCPS) in a tie-line on the AGC dynamics of a
hydrothermal system
2) To develop a linearised model of a two area
interconnected hydrothermal system considering a TCPS
in series with the tie-line
3) To optimise the gain settings of the integral controllers
with and without considering TCPS and
4) To compare the dynamic responses with and without
considering the TCPS.
III. INCREMENTAL TIE LINE POWER FLOWMODEL
CONSIDERING TCPS
The recent advances in power electronics have led to the
development of the Flexible Alternating Current Transmission
Systems (FACTS). FACTS devices are designed to overcome
the limitations of the present mechanically controlled power
systems and enhance power system stability by using reliable
and high-speed electronic devices. One of the promising
FACTS devices is the Thyristor Controlled Phase Shifter
(TCPS). A TCPS is a device that changes the relative phase
angle between the system voltages. Therefore, the real power
flow can be regulated to mitigate the frequency oscillations
and enhance power system stability.
In this study, a two-area hydrothermal power system
interconnected by a tie-line is considered. Fig.1 shows the
schematic of the two-area interconnected hydrothermal system
considering a TCPS in series with the tie-line. TCPS is placed
near area 1. Resistance of the tie-line is neglected. Area 1 is
the thermal area comprising consists of a non reheat unit and
area 2 is the hydro area consisting of a hydro unit.
1
nonreheat
unit
1
hydro
unit
1 1
| V | Z ) ( | V |
1 1
| + Z
2 2
| V | Z
1' 1 2
12
jx
12
i
| Z 1 : 1
TCPS Line Tie
1
Area
2
Area
Fig. 1. A schematic of the two area interconnected hydrothermal power
system with TCPS in series with the Tie-Line.
Without TCPS, the incremental tie-line power flow from
area 1 to area 2 can be expressed as [1]
) f f (
s
2
P
2 1
0
12 0
tie12
= A
T t
(1)
When a TCPS is placed in series with the tie-line, as in
Fig.1, the current flowing from area 1 to area 2 can be written
as
12
2 2 1 1
12
jX
V ) ( V
i
Z + Z
= (2)
From Fig.1, we can also write,
(
(

Z + Z
+ Z =
12
2 2 1 1
1 1
tie12
tie12
jX
V ) ( V
) ( V jQ P (3)
Separating the real part of Eqn. (3), we get
) sin(
X
V V
P
2 1
12
2 1
tie12
+ = (4)
In Eqn. (4), perturbing
1
,
2
and from their nominal
values and respectively, we get
0
2
0
1
,
0

) )sin( cos(
X
V V
P
2 1
0 0
2
0
1
12
2 1
tie12
+ + = o (5)
But (
1
-
2
+ ) is very small and hence, sin (
1

2
+
) (
1

2
+ ). Therefore,
) )( cos(
X
V V
P
2 1
0 0
2
0
1
12
2 1
tie12
+ + = o (6)
Let
) cos(
X
V V
T
0 0
2
0
1
12
2 1
12
+ = (7)
Thus, Eqn. (6) reduces to
) ( T P
2 1 12 tie12
+ = o (8)
Therefore,
(9) T ) ( T P
12 2 1 12 tie12
+ A =
We also know that,

1
= 2f
1
dt and
2
= 2f
2
dt (10)
From Eqns.(9) and (10), we get,
(11)
) )
+ T = A T dt) f dt f ( 2 P
12 2 1 12 tie12
Laplace transform of Eqn.(11) is
(s) T (s)] F (s) F [
s
2
(s) P
12 2 1
12
tie12
+ A
T
= (12)
As per Eqn.(12), tie-line power flow can be controlled by
controlling the phase shifter angle . The phase shifter angle
(s) can be represented as [12-14]:
(s) Error
sT 1
K
(s)
1
PS

+
= (13)
where K

and T
PS
are the gain and time constants of the
TCPS. Thus, Eqn.(12) can be rewritten as
(s) Error
sT 1
K
T (s)] F (s) F [
s
2
(s) P
1
PS

12 2 1
12
tie12
+
+ A
T
=
(14)
IV. TCPS CONTROL STRATEGY
If the frequency deviation f
1
is sensed, it can be used as
the control signal (i.e., Error
1
= f
1
) to the TCPS unit to
control the TCPS phase shifter angle which in turn, controls
the tie-line power flow. Thus,
(s) F
sT 1
K
(s)
1
PS

+
= (15)
and the tie-line power flow perturbation becomes
(s) F
sT 1
K
T (s)] F (s) F [
s
2
(s) P
1
PS

12 2 1
12
tie12
+
+ A
T
=
(16)
V. SYSTEMINVESTIGATED
P1
P1
sT 1
K
+
T
sT 1
1
+ s
K
I1

B
1
1
R
1


+
+
+
s
T 2
12
H

+
T
12
+
PS

sT 1
K
+
+

+
P2
sT 1
P2
K
+
2
R
sT 1
sT 1
+
+
1
sT 1
1
+ s
K
I2

B
2
2
R
1
a
12 a
12
W
W
0.5sT 1
sT 1
+

+
+
+

d1
P
d2
P
1
f
2
f
tie12
P
1
f
g1
P
g2
P
t1
P
t2
P
2
u
1
u

G
sT 1
1
+
r1
P
Fig. 2. Two Area Interconnected Hydrothermal System considering TCPS in
series with the Tie-Line.
The AGC system investigated is composed of an
interconnection of two areas. Area 1 comprises of a non
reheat thermal system and area 2 comprises of a hydro system.
Typical generation rate constraints of 10%/min. for thermal
area and 4.5%/sec. (270%/min.) for raising generation and
6%/sec. (360%/min.) for lowering generation in the hydro
area are considered as in the IEEE Committee Report on
power plant response [16,17]. The detailed transfer function
models of speed governors and turbines are discussed and
developed in the IEEE Committee Report on Dynamic Models
for Steam and Hydro Turbines in Power System Studies [18].
The detailed small perturbation transfer function block
diagram model of the two-area hydrothermal system along
with the incremental model of the TCPS in series with the tie-
line is shown in Fig.2. A step load perturbation of 1% of the
nominal loading is considered in either of the areas. Nominal
parameters of the system are given in the Appendix.
VI. STATE SPACE REPRESENTATION
The power system model considered being a linear
continuous-time dynamic system, can be represented by the
standard state space model as
p BU AX X + + =

(17)
where X, U and p are the state, control and disturbance vectors
respectively and A, B and are the system, input and
disturbance matrices respectively which are constant and of
compatible dimensions associated with them which inturn
depend on the system parameters and the operating point. For
the system considered,
X = [f
1
f
2
P
tie12
P
g1
P
g2
P
t1
P
t2
P
r1
]
T
(18)
U = [u
1
u
2
]
T
(19)
and
p = [P
d1
P
d2
]
T
(20)
The state variables chosen are as shown in the power
system model given in Fig.2.
VII. OPTIMIZATION OF INTEGRAL GAIN SETTINGS
Integral Squared Error (ISE) technique is used for obtaining
the optimum integral gain settings. A performance index
)
+ + A =
t
0
)dt
2
P f f ( J
tie12
2
2
2
1
(21)
is minimized in the presence of GRCs to obtain the optimum
values of K
I1
and K
I2
. The controller settings of either thermal
or hydro area are optimized by considering the other area
uncontrolled following the approach of [19,20].
Optimum values of integral gain settings of area 1 and area
2 without and with TCPS in series with the tie-line are
tabulated in Table-1.
TABLE I
OPTIMUM VALUES OF INTEGRAL GAIN SETTINGS
Area Without
TCPS
With TCPS in series
with the tie-line
Thermal K
I1
= 0.0650 K
I1
= 0.0940
Hydro K
I2
= 0.0470 K
I2
= 0.2340
From Table-1, it is seen that the optimum values of the
integral gain settings in areas 1 and 2 considering TCPS are
higher than those obtained without TCPS.
VIII. DYNAMIC RESPONSES &DISCUSSIONS
Considering GRCs, simulation studies are performed to
investigate the performance of the two-area hydrothermal
system without and with TCPS in series with the tie-line and
near to the thermal area i.e., area 1. A step load disturbance of
0.01 pu MW is considered in either of the areas.
0 20 40 60 80
-0.06
-0.04
-0.02
0
0.02
0.04
Time (s)
D
e
l
t
a


f
1


(
H
z
)
Without TCPS
With TCPS
0 20 40 60 80
-0.06
-0.04
-0.02
0
0.02
0.04
Time (s)
D
e
l
t
a

f
2


(
H
z
)
0 20 40 60 80
-8
-6
-4
-2
0
2
4
x 10
-3
Time (s)
D
e
l
t
a

P
t
i
e
1
2
(
p
.
u

M
W
)
Fig. 3. Variations in area frequencies and tie-power with 1% step load
disturbance in thermal area.
It is seen from Fig.3 that, with the TCPS in series with the
tie-line, dynamic responses for f
1
, f
2
and P
tie12
have
improved significantly and it can be observed that the
oscillations in area frequencies and tie-line power deviations
have decreased to a considerable extent with the use of TCPS.
Fig.4 shows the variation of TCPS phase angle . From
Fig.4, it is seen that, with f
1
feedback, the maximum
negative variation is = - 0.1 rad = - 5.73
max
negative
A
0
approximately and on the positive side, the maximum phase
angle variation is = 0.02 rad = 1.146
max
positive
A
0
approximately.
0 20 40 60 80
-0.1
-0.08
-0.06
-0.04
-0.02
0
0.02
Time (s)
D
e
l
t
a

p
h
i


(
r
a
d
)
Fig. 4. Variation of TCPS phase angle with 1% step load disturbance in
thermal area.
0 20 40 60 80
-0.06
-0.04
-0.02
0
0.02
Time (s)
D
e
l
t
a


f
1

(
H
z
)
Without TCPS
With TCPS
0 20 40 60 80
-0.06
-0.04
-0.02
0
0.02
Time (s)
D
e
l
t
a

f
2
(
H
z
)
0 20 40 60 80
-5
0
5
10
x 10
-3
Time (s)
D
e
l
t
a

P
t
i
e
1
2


(
p
.
u
.

M
W
)
Fig. 5. Variations in area frequencies and tie-power with 1% step load
disturbance in hydro area.
Depicted in Fig.5 are the variations of area frequencies and
tie power deviations when the step load disturbance of 1%
occurs in area 2. Similar findings as in the case of Fig. 3 can
be observed in Fig. 5.
0 20 40 60 80
-0.08
-0.06
-0.04
-0.02
0
0.02
Time (s)
D
e
l
t
a

p
h
i


(
r
a
d
)
Fig. 6. Variation of TCPS phase angle with 1% step load disturbance in hydro
area.
The TCPS phase angle deviation with 1% step load
disturbance in area 2 has been plotted in Fig.6. It is found that
a maximum negative variation of about = - 0.095
rad = -5.445
max
negative
A
0
has occurred whereas, on the positive side, the
maximum phase angle variation is = 0.02 rad =
1.146
max
positive
A
0
approximately.
IX. CONCLUSIONS
In this paper, a tie-line power flow control technique by
TCPS has been proposed for a two-area interconnected
hydrothermal power system. Gain settings of the integral
controllers are optimized using ISE technique in the presence
of GRCs by minimizing a quadratic performance index. A
control strategy has been proposed to control the TCPS phase
angle which in turn controls the inter-area tie-line power flow.
Simulation results reveal that frequencies and tie-power
oscillations following sudden load disturbance in either of the
areas can be suppressed by controlling the phase angle of
TCPS. It may be therefore concluded that, the tie-line power
flow control by a TCPS can be expected to be utilized as a
new ancillary service for stabilization of frequencies and tie-
power oscillations in the deregulated environment of power
systems.
X. APPENDIX
All the notations carry the usual meanings
(a) System Data
P
R1
= P
R2
= 1200 MW
T
p1
=T
p2
=20 s
K
P1
= K
P2
= 120 Hz/p.u. MW
T
t
= 0.3 s
T
1
= 41.6 s
T
2
= 0.513 s
T
R
= 5 s
T
W
= 1 s
T
12
= 0.0866 s
T
G
= 0.08 s
R
1
= R
2
= 2.4 Hz/p.u. MW
D
1
= D
2
= 8.33 10
-3
p.u. MW/Hz
B
1
= B
2
= 0.4249 p.u. MW/Hz
(b) TCPS Data
T
PS
= 0.1 s
K

= 1.5 rad/Hz

max
= 10
0

min
= - 10
0
XI. APPENDIX
[1] O. I. Elgerd and C. Fosha, Optimum megawatt frequency control of
multi-area electric energy systems, IEEE Transactions on Power
Apparatus and Systems, vol. PAS-89, no. 4, pp. 556563, Apr. 1970.
[2] N. Cohn, Techniques for improving the control of bulk power transfers
on interconnected systems, IEEE Transactions on Power Apparatus and
Systems, vol. PAS-90, no. 6, pp. 24092419, 1971.
[3] S. M. Miniesy and E. V. Bohn, Two level control of interconnected
power plants, IEEE Transactions on Power Apparatus and Systems, vol.
PAS-90, pp. 27422748, June 1971.
[4] Y. L. Karnavas and D. P. Papadopoulos, Agc for autonomous power
system using combined intelligent techniques, International Journal of
Electric Power System Research, vol. 62, pp. 225239, 2002.
[5] R. K. Green, Transformed automatic generation control, IEEE
Transactions on Power Systems, vol. 11, no. 4, pp. 17991804, 1996.
[6] M. Reformat, E. Kuffel, D. Woodford, and W. Pedrycz, Application of
genetic algorithms for control design in power systems, Proc. IEE,
Generation, Transmission & Distribution, vol. 145, no. 4, pp. 345354,
1998.
[7] T. Hiyama, Design of decentralized load - frequency regulators for
interconnected power systems, Proc. IEE, vol. 129, Pt. C, no. 1, pp. 17
22, 1982.
[8] Y. H. Moon, H. S. Ryu, J. G. Lee, K. B. Song, and M. C. Shin, Extended
integral control for load - frequency control with the consideration of
generation rate constraints, International Journal of Electrical Power
and Energy Systems, vol. 24, pp. 263269, 2002.
[9] A. Bose and I. Atiyyah, Regulation Error in Load-Frequency Control,
IEEE Transactions on Power Apparatus and Systems, vol. PAS-99, no. 2,
pp. 650657, 1980.
[10] N. G. Hingorani, Flexible ac transmission, IEEE Spectrum, pp. 4045,
Apr. 1993.
[11] N. Jaleeli, L. S. Vanslycn, D. N. Ewart, L. H. Fink, and A. G. Hoffmann,
Understanding automatic generation control, IEEE Transactions on
Power Systems, vol. 7, pp. 11061122, 1999.
[12] K. Xing and G. Kusic, Application of thyristor controlled phase shifters
to minimize real power losses and augment stability of power systems,
IEEE Transactions on Energy Conversion, vol. 3, no. 4, pp. 792798,
1988.
[13] H. F. Wang, F. J. Shift, and M. Li, Analysis of thyristor controlled phase
shifter applied in damping power system oscillations, International
Journal of Electrical Power and Energy Systems, vol. 19, no. 1, pp. 19,
1997.
[14] R. Baker, G. Guth, W. Egli, and P. Eglin, Control algorithm for a static
phase shifting transformer to enhance transient and dynamic stability of
large power systems, IEEE Transactions on Power Apparatus and
Systems, vol. PAS-101, no. 9, pp. 35323542, 1982.
[15] Y. L. Tan and Y. Wang, Nonlinear excitation and phase shifter
controller for transient stability enhancement of power systems using
adaptive control law, International Journal of Electrical Power and
Energy Systems, vol. 18, no. 6, pp. 397403, 1996.
[16] I. W. G. on Power Plant Response to Load Changes, Mw response of
fossil fuelled steam units, IEEE Transactions on Power Apparatus and
Systems, vol. PAS-92, no. 2, pp. 455463, Mar/Apr 1973.
[17] I. P. W. group, Hydraulic turbine and turbine control models for system
dynamics, IEEE Transactions on Power Systems, vol. PWRS-7, no. 1,
pp. 167174, Feb 1992.
[18] I. C. Report, Dynamic models for steam and hydro turbines in power
system studies, IEEE Transactions on Power Apparatus and Systems,
vol. PAS-92, no. 6, pp. 19041915, Nov/Dec 1973.
[19] M. L. Kothari, P. S. Satsangi, and J. Nanda, Automatic generation
control of an interconnected hydrothermal system in continuous and
discrete mode considering generation rate constraints, Proc. IEE, vol.
130, Pt. C, no. D-1, pp. 1721, 1983.
[20] D. Das, J. Nanda, M. L. Kothari, and D. P. Kothari, Automatic
generation control of a hydrothermal system with new area control error
considering generation rate constraints, Electric Machines and Power
Systems, vol. 18, pp. 461471, 1990.
XII. BIOGRAPHIES
Rajesh Joseph Abraham graduated in Electrical &
Electronics Engineering from L. B. S College of Engineering,
Kasaragod, Kerala, India in 1998, and post graduated in
Guidance & Navigational Control from College of
Engineering, Thiruvananthapuram, Kerala, India in 2002.
Since July 2003, he is with the Department of Electrical
Engineering, Indian Institute of Technology, Kharagpur, India
working towards his Doctoral degree.
His special fields of interest include Power Control,
Robotic Control and Guidance & Navigational Control.
Debapriya Das has obtained his B. E. Degree from
Calcutta University in 1982. He obtained his M. Tech Degree
from Indian Institute of Technology, Kharagpur, India in 1984
and Ph. D Degree from Indian Institute of Technology, Delhi,
India in 1992. Presently, he is holding the position of
Associate Professor at the Department of Electrical
Engineering, Indian Institute of Technology, Kharagpur,
India. His research interests are in the area of Electric Power
Distribution System and Power System Operation and
Control.
Amit Patra received the B.Tech., M.Tech. and Ph.D.
Degrees from the Indian Institute of Technology, Kharagpur
in 1984, 1986 and 1990 respectively. He joined the
Department of Electrical Engineering, Indian Institute of
Technology, Kharagpur in 1987 as a faculty member, and is
currently a Professor. His current research interests include
design and testing of VLSI circuits, power management
circuits, analog CAD and fault tolerant control of industrial
processes.
He has published more than 100 research papers and is the
co-author of a research monograph entitled General Hybrid
Orthogonal Functions and Their Applications in Systems and
Control, published by the Springer Verlag in 1996. He has
carried out a number of sponsored projects in the areas of
fault detection and diagnosis, fault tolerant control, and is
currently involved with several projects on power
management circuits, analog layout automation, sensor signal
processing and Built-in Self Test circuits.
Dr. Patra received the Young Engineer Award of the Indian
National Academy of Engineering in 1996 and the Young
Teachers Career Award from the All India Council for
Technical Education in 1995. He has been a Young
Associate of the Indian Academy of Sciences during 1992-97.
He is a member of IEEE (USA), Institution of Engineers
(India) and a life member of the Systems Society of India.

Das könnte Ihnen auch gefallen