Nano System
SECTION 5: page 1
Contents
Gent Panel Selector
System Architecture
Nano Control Panel
Compatible Loop
Devices
Nano Commissioning
Tool
by Honeywell
SECTION 5: page 3
5: NANO SYSTEM
Panel Selector
Nano-24 Compact-24 Vigilon-24 Vigilon-72
127 devices Upto 400 Upto 800 Upto 1200*
Loop length 1000M or less
16 zones or less 32** 32** 32**
Standalone system Network capability Network capability Network capability
24 hour standby capacity Up to 72hours
No on board printer requirement Integrated in Panel Integrated in Panel
Remote evacuation input at
panel

S-Quad / S-Cubed compatible
8 beam pairs or less 16 pairs per Loop 16 pairs per Loop 16 pairs per Loop
Customised / Voice Enhanced
Messaging

3400 / 34000 device
compatability

Simple or no repeat indication
requirement
Loop controlled repeats &
Mimics
Loop controlled repeats &
Mimics
Loop controlled repeats &
Mimics
One out all out
Complex cause and effect
(including command builds)

Simple linked 16 zone phased
evacuation

Simple linked 16 zone phased
evacuation with delay

Integral sounder mode
Simple interfacing requirements Upto 16 loop interfaces
Single area co-incidence
detection
Up to 128 groups Up to 128 groups Up to 128 groups
Day Night mode Via remote input Via system timer or
remote input
Via system timer or
remote input
Via system timer or
remote input
Integrated Voice Alarm system
3rd party Voice Alarm
connectivity

Head end management
requirement
Winmag Winmag Winmag
*Note all loop capacities subject to loop loading calculatations & max of 512 detection devices (EN54 requirement)
** Greater than 32 with Vigilon Mimic panel
Nano System
Vigilon System
by Honeywell
SECTION 5: page 4
5: NANO SYSTEM
System Architecture
Remote
LED
Conventional Sounders
(2 master alarm circuits)
Nano
Control Panel
24V supply
RS485
RS232
Printer Port
Printer
Repeat
Indicator
Panel
Loop
circuit
230V ac
Monitored Input
Fire relay change
over contacts rated
1A @ 24V dc
Fault relay change
over contacts rated
1A @ 24V dc
USB
MCP
Input output signals may be
used to control fire dampers
and plant equipment
S-Quad
Sensor/
Speech
Strobe
S-Cubed
S-Cubed
Beam
Receiver
Beam
Transmitter
S-Quad Sensor/Speech Strobe
S-Quad
Sensor/
Speech
Strobe
T-breaker
T-breaker
MCP
by Honeywell
SECTION 5: page 5
ORDER CODES
NANO SYSTEM CONTROL PANEL
Nano Single Loop Panel NANO-24
Nano is the latest fire detection
control panel from Gent by
Honeywell. Nano is a single loop
analogue addressable panel with
an intuitive user interface and
attractive appearance. Managing
up to 127 devices on the loop,
Nano is ideal for small systems.
Nano has been designed with
ease of use as a high priority. From
installation and commissioning to
everyday use, Nano delivers an
experience that makes the fire
alarm system easy to use and
safe to operate. The appearance
of the panel means that Nano
may be installed and look good
in any type of building.
Nano operates the latest range
of Vigilon loop devices from
Gent by Honeywell. This allows
a small system to benefit from
Gents advanced fire detection
technology and powered loop
performance with ranges such
as S-Quad and S-Cubed.
Designed for small buildings,
Nano offers a simple cause and
effect which can be configured
by a simple and easy to use PC
commissioning tool.
TECHNICAL SPECIFICATION
Type Control panel
Loop Capacity 127
Batteries 2 x 7Ah
Battery Standby 24 hours standby (subject to battery calculations)
Approx Weight 9 Kg (with batteries)
Operating Temperature 0C to +45C
Relevant Standard EN54 Parts 2 & 4
Cable Entry Top and rear knockouts
Approvals LPCB pending
5: NANO SYSTEM
Nano Control Panel
Nano control panel
347
4
1
9
85.5
Dimensions (mm)
by Honeywell
SECTION 5: page 6
5: NANO SYSTEM
Compatible Loop Devices
Nano is compatible with the full S-Quad range.
Reduce system costs by taking full advantage of
the S-Quads multi-function devices that combine
fire sensing with a sounder and/or a strobe. Fewer
devices means less cabling and therefore reduced
time spent on site.
Because all of the S-Quad devices are powered by
the loop each one requires just one pair of cables and one set of
terminations to provide all of its multi-sensor and sounder, strobe
and speech functionalities.
S
-
Q
U
A
D

C
O
M
P
A
T
I
B
L
E
S-QUAD SAVING YOU TIME AND MONEY
l
There is a built-in isolator in every single S-Quad saving
you more money whilst improving the integrity of the
system
l
Each S-Quad has a monitored line that can be configured
for a fire output or a fire input this may remove the need
and cost for a separate interface
S-QUAD ENSURING YOUR PEACE OF MIND
l
The capability and function of Nano with S-Quad ensures
that the system complies with the requirements of:
l The Disability Discrimination Act Part III 1995
l The Building Regulations Approved Document B&M
l The British Standard BS 5839-1:2002
by Honeywell
SECTION 5: page 7
5: NANO SYSTEM
Compatible Loop Devices
SPEECH MESSAGES
l
Sensors with voice capability can reduce the need
for speakers and traditional voice alarm amplifiers in
applications where background music or PA is not required
l
Up to 2 different standard messages are stored in each
device to allow different messages to be played in each
area for phased evacuation
l
A bell tone can be reproduced within the device required
for schools where the fire alarm sounders are used to
produce a class change signal
l
Voice messages are synchronised across the loop to ensure
clear instructions throughout the building
SENSOR
l
The combined power of Nano and S-Quad provides quick,
intelligent fire decisions
l
The S-Quad sensor can incorporate one or all of the
following sensing elements: optical, dual optical, heat and
CO. So depending on the environment, anything from an
Optical only to a Dual Optical Heat CO sensor can be used
l
S-Quads unique combination of sensing elements
eliminates a higher number of false alarms
l
Uniquely the S-Quad has a series of sensor states that are
designed to overcome the false alarm risks in different
types of rooms
STROBE
l
The built-in, high intensity flashing strobe helps alert
occupants in noisy environments as well as the hearing
impaired
l
The strobe function is built in to the centre of the sensor
this gives the whole device a low profile. Far better looking
than bulky layers of strobes and sounders that are fixed to
some sensor bases
l
Its very low power consumption means that the S-Quad
strobe can achieve the equivalent of a 3W Xenon strobe
whilst only using 1/20th of the power
l
Low power consumption and high output LED technology
ensures reliable and cost efficient units
l
All strobes are synchronized across the Nano loop
SOUNDER
l
The sensor sounder device allows an even distribution of
sound with only one device to install
l
Instead of three cables being needed to wire individual
sensors, strobes and sounders, these device innovations
can significantly reduce the cost of install by requiring just
one cable terminated to one device
l
As a result, eight S-Quad devices can be provided for the
same price of just one traditional wall-mounted sounder
and its own cabling and installation
l
Low current consumption means that more sensor
sounders can be supported on the Nano loop
Speech
Sensor
Sounder
Strobe
by Honeywell
SECTION 5: page 8
5: NANO SYSTEM
Compatible Loop Devices
l
Low current consumption means that more sounders can be supported on
the Nano loop
l
The S-Cubed sounder/strobes are fully compatible with the S-Quad range
and all are synchronised across the loop
l
Each S-Cubed requires just one pair of cables and one set of terminations to
provide all of its sounder, strobe and speech functionalities
l
The strobe option is equivalent to a 3W Xenon strobe but uses only 1/20th of
the power
l
The strobe and sound element is fully monitored for circuit failures
l
S-Cubed can help the Nano system meet the requirements of the Disability
Discrimination Act Part III
l
S-Cubed can be programmed to store customer messages
Gent by Honeywells patented S-Cubed Speech messages/Sounder/
Strobe devices are fully loop powered and do not require any
separate sounder circuits.
Sounder,
speech
messages,
strobe
Sounder
only
Sounder,
speech
messages
ORDER CODES
NANO SYSTEM CONTROL PANEL
Nano Single Loop Panel NANO-24
NANO CONTROL PANEL SPARES
Spare MCB for Nano NS-MCB
Spare PSU for Nano VCS-PSU-N
Spare Battery set for Nano NS-BATT
Spares Pack for Nano NS-SPARE
Spare Display for Nano NS-HMI
Spare Front Cover for Nano NS-DOOR
Spare Backbox for Nano NS-BACKBOX
Spare Nameplate / Screw Cover Pack of 5 Nano
NS-NPLATE
by Honeywell
SECTION 5: page 9
BEAM SENSORS
l
The beam sensors are connected to the same
circuit as all other devices, no additional wiring
is needed
l
The loop powered beam sensors do not
require any additional power supplies or
interfaces
l
This makes them the most economical solution
for beam detection
INTERFACES
l
Nano can support a high number of interfaces
on the loop, exceeding typical Nano system
requirements
l
Interfaces with output channels dont need
additional relays the Nano panel will monitor
for cable faults
l
The range includes low voltage and mains
switching variants to meet all application
needs
MANUAL CALL POINTS
l
The manual call point is available as a break
glass variant or with resettable elements
l
As well as saving on the cost of replacement
glasses, the resettable element is ideal where
glass could prove to be a safety hazard
l
Surface or flush mounted variants are available
- the call point flushes with a standard
installation back box
5: NANO SYSTEM
Compatible Loop Devices
The combination of powerful software in the Nano control panel
and Vigilons advanced range of loop powered devices delivers a
flexible, easy to use system for small buildings.
5
by Honeywell
SECTION 5: page 10
Designed for small buildings,
Nano offers a simple cause
and effect which can be
configured by an easy to use PC
commissioning tool.
The new commissioning tool has
been developed specifically to
improve the set up time for Nano.
Future configuration changes
can be managed through the
tool or directly via the interface
on the panel.
5: NANO SYSTEM
Nano Commissioning Tool