Bare Copper
Solid Conductor
Bare or Tinned,
Soft (Annealed), Medium
Hard, Hard Drawn
Applications:
For use in electrical grounding systems, and on insulators for
overhead transmission and distribution applications.
Standards:
ASTM B-1 (Hard Drawn)
ASTM B-2 (Medium Hard Drawn)
ASTM B-3 (Soft or Annealed)
ASTM B-33 (Tinned Soft or Annealed)
REA/RUS Approved
Federal standard QQ-W-343
RoHS Compliant
* Per NEC Table 310-21. Based on conductor temperature of 80 C; ambient temperature of 40 C; 2 ft./sec. wind.
NOTE: The data shown is approximate and subject to standard industry tolerances. 2011
Part
Number
Size
AWG or
MCM
BSOS18 18 .0403 4.985 85 6.6400 67 6.6100 6.3900 6.6400 -
BSOS16 16 .0508 7.800 135 4.1800 106 4.1600 4.0200 4.1800 -
BSOS14 14 .0641 12.400 214 2.6300 167 2.6100 2.5200 2.6200 -
BSOS12 12 .0808 19.800 337 1.6500 262 1.6400 1.5900 1.6500 -
BSOS10 10 .1019 31.400 529 1.0390 410 1.0330 .9988 1.0430 -
BSOS8 8 .1285 50.000 826 .6532 644 .6498 .6281 .6426 98
BSOS6 6 .1620 79.400 1,280 .4110 1010 .4088 .3952 .4109 124
BSOS4 4 .2043 126.400 1,970 .2584 1584 .2571 .2485 .2528 155
BSOS2 2 .2576 200.900 3,002 .1625 2450 .1617 .1563 .1580 209
BSOS1 1 .2893 253.300 3,688 .1289 3024 .1282 .1239 - -
BSOS1/0 1/0 .3249 319.500 4,518 .1011 3731 .1016 .0982 - 282
BSOS2/0 2/0 .3648 402.800 5,519 .0802 4600 .0798 .0779 - 329
BSOS3/0 3/0 .4096 507.800 6,720 .0636 5666 .0633 .0618 - 382
BSOS4/0 4/0 .4600 640.500 8,143 .0504 6980 .0502 .0490 - 444
Nominal
Dia.
(inch)
S
O
L
I
D

B
A
R
E

C
O
P
P
E
R
DC Resistance
(Ohms/1000 ft.)
@ 20 C
Min. Breaking
Strength (lbs.)
DC Resistance
(Ohms/1000ft.)
@ 20 C
Min. Breaking
Strength (lbs.)
Approx.
Net Weight
per 1000ft.
(lbs.)
Medium Hard Drawn Hard Drawn Soft (Annealed)
Ampacity*
Tinned Bare
DC Resistance
(Ohms/1000ft.)
@ 20 C
B
a
r
e

C
o
p
p
e
r
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
3
Made in the USA
Bare Copper
Stranded Conductor
Bare or Tinned,
Soft (Annealed), Medium Hard,
Hard Drawn
Applications:
For use in electrical grounding systems, and on insulators for over-
head transmission and distribution applications. Stranded conduc-
tors offer greater exibility than solid.
Standards:
ASTM B-1 (Hard Drawn)
ASTM B-2 (Medium Hard Drawn)
ASTM B-3 (Soft or Annealed)
ASTM B-8 (Concentric Lay Stranded)
ASTM B-33 (Tinned Soft or Annealed)
ASTM B-787 (Combination strand)
REA/RUS Approved
Federal standard QQ-W-343
RoHS Compliant
Size
AWG
or
MCM
Stranding
Class
Strand
(no.)
Hard Drawn
Minimum
Breaking
Strength
(lbs.)
DC Res.
(ohms/1000 ft.)
@20C
Minimum
Breaking
Strength
(lbs.)
DC Res.
(ohms/1000 ft.)
@20C
Soft Drawn
Bare Tinned
Ampacity*
16 26 K .0576 7.9 124.7 4.259 100.4 4.237 4.096 4.110 --
14 7 B .0726 12.7 197.1 2.679 157.7 2.665 2.5800 2.6800 --
12 7 B .0915 20.2 311.1 1.685 247.7 1.676 1.6200 1.6900 --
10 7 B .1160 32.0 491.7 1.060 388.9 1.054 1.0200 1.0600 --
8 7 B .1460 50.9 777 .6663 610 .6629 .6408 .6654 98
6 7 B .1840 81.0 1,228 .4191 959 .4169 .4030 .4196 124
4 7 A,B .2320 128.9 1,938 .2636 1,505 .2622 .2540 .2637 155
3 7 A,B .2600 162.5 2,433 .2090 1,885 .2079 .2010 .2086 --
2 3 AA .3200 202.9 2,912 .1641 2,298 .1633 .1578 -- 209
7 A,B .2920 204.9 3,050 .1660 2,360 .1650 .1594 .1657 209
1 7 A,AA .3280 258.4 3,801 .1316 2,955 .1309 .1265 .1302 --
19 B** .3320 258.4 3,902 .1316 3,039 .1309 .1265 .1313 --
1/0 7 A,AA .3680 325.8 4,752 .1042 3,705 .1037 .1002 .1031 282
19 B** .3730 325.8 4,897 .1042 3,802 .1037 .1003 .1043 282
2/0 7 A,AA .4140 410.9 5,927 .0826 4,640 .0822 .0795 .0818 329
19 B** .4190 410.9 6,153 .0826 4,765 .0822 .0795 .0826 329
3/0 7 A,AA .4640 518.1 7,366 .0655 5,812 .0652 .0631 .0649 382
19 B** .4700 518.1 7,702 .0655 5,973 .0652 .0631 .0655 382
4/0 7 A,AA .5220 653.3 9,154 .0519 7,278 .0517 .0499 -- 444
19 B** .5280 653.3 9,617 .0519 7,479 .0517 .0500 .0515 444
61 D .5300 653.3 9,903 .0519 7,728 .0517 .0500 .0520 444
Medium Hard Drawn
DC Res.
(Ohms/1000ft.)
@ 20 C
Nominal Diameter
Overall
(inch)
Approx.
Net
Weight
per 1000
ft. (lbs.)
S
T
R
A
N
D
E
D

B
A
R
E

C
O
P
P
E
R
*Per NEC Table 310-21. Based on conductor temperature of 80 C; ambient temperature of 40 C; 2 ft./sec. wind.
** Ref ASTM B-787 NOTE: The data shown is approximate and subject to standard industry tolerance 2011
Part
Number
BST26S16
BST7S14
BST7S12
BST7S10
BST7S8
BST7S6
BST7S4
BST7S3
BST3S2
BST7S2
BST7S1
BST19S1
BST7S1/0
BST19S1/0
BST7S2/0
BST19S2/0
BST7S3/0
BST19S3/0
BST7S4/0
BST19S4/0
BST61S4/0
B
a
r
e

C
o
p
p
e
r
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
4
Made in the USA
Bare Copper
Stranded Conductor
Bare or Tinned,
Soft (Annealed), Medium Hard,
Hard Drawn
Standards:
ASTM B-1 (Hard Drawn)
ASTM B-2 (Medium Hard Drawn)
ASTM B-3 (Soft or Annealed)
ASTM B-8 (Concentric Lay Stranded)
ASTM B-33 (Tinned Soft or Annealed)
REA/RUS Approved
Federal standard QQ-W-343
RoHS Compliant
Applications:
For use in electrical grounding systems, and on insulators for over-
head transmission and distribution applications. Stranded conduc-
tors offer greater exibility than solid.
250 19 A .574 771.9 11,360 .0440 8,836 .0438 .0423 .0435 494
37 B .575 771.9 11,600 .0440 8,952 .0438 .0423 .0440 494
300 19 A .629 926.3 13,510 .0366 10,530 .0365 .0352 .0363 556
37 B .630 926.3 13,855 .0366 10,732 .0365 .0353 .0367 556
350 19 A .678 1,081.0 15,590 .0314 12,200 .0313 .0302 .0311 -
37 B .681 1,081.0 16,070 .0314 12,462 .0313 .0302 .0314 -
400 19 A,AA .726 1,235.0 17,810 .0275 13,950 .0273 .0264 .0272 -
37 B .728 1,235.0 18,331 .0275 14,144 .0273 .0264 .0272 -
500 19 AA .811 1,544.0 21,942 .0220 17,313 .0219 .0212 .0218 773
37 A,B .813 1,544.0 22,495 .0220 17,517 .0219 .0212 .0218 773
600 61 B .893 1,853.0 27,530 .0183 21,350 .0182 .0176 .0181 -
750 37 AA .997 2,316.0 33,411 .0146 26,162 .0146 .0141 .0145 1,000
61 A,B .998 2,316.0 34,090 .0146 26,510 .0146 .0141 .0145 1,000
1000 37 AA 1.152 3,088.0 43,826 .0110 34,396 .0109 .0106 .0109 1,193
61 A,B 1.152 3,088.0 45,030 .0110 35,100 .0109 .0106 .0109 1,193
Size
AWG
or
MCM
Stranding
Class
Strand
(no.)
Nominal Diameter
Overall
(inch)
Approx.
Net
Weight
per 1000
ft. (lbs.)
Hard Drawn
Minimum
Breaking
Strength
(lbs.)
DC Res.
(ohms/1000 ft.)
@20C
Minimum
Breaking
Strength
(lbs.)
DC Res.
(ohms/1000 ft.)
@20C
Soft Drawn
DC Res.
(Ohms/1000ft.)
@ 20 C
Bare Tinned
Ampacity*
Medium Hard Drawn
S
T
R
A
N
D
E
D

B
A
R
E

C
O
P
P
E
R
* Per NEC Table 310-21. Based on conductor temperature of 80 C; ambient temperature of 40 C; 2 ft./sec. wind.
NOTE: The data shown is approximate and subject to standard industry tolerances. 2011
Part
Number
BST19S250
BST37S250
BST19S300
BST37S300
BST19S350
BST37S350
BST19S400
BST37S400
BST19S500
BST37S500
BST61S600
BST37S750
BST61S750
BST37S1000
BST61S1000
B
a
r
e

C
o
p
p
e
r
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
5
Made in the USA
2/0 AWG .392 9.956 137,900 .1083 69.9 417.4 2,204 621 50,200 35.3 .07741 .40872 .25402 5,437 2,466
3/0 AWG .430 10.922 167,300 .1314 84.8 506.4 2,674 753 48,500 34.1 .06380 .33686 .20936 6,373 2,891
4/0 AWG .482 12.243 212,000 .1665 107.4 641.7 3,388 955 46,600 32.8 .05035 .26585 .16523 7,759 3,519
300 MCM .574 14.580 299,800 .2355 151.9 907.5 4,792 1,350 44,200 31.1 .03560 .18797 .11682 10,410 4,722
350 MCM .620 15.748 351,200 .2758 177.9 1063.0 5,613 1,582 42,800 30.1 .03039 .16046 .09973 11,810 5,357
1/0 AWG .420x.312 10.7x7.9 105,600 .0829 53.5 319.7 1,687 475 51,800 36.4 .1011 .53381 .33177 4,296 1,949
2/0 AWG .480x.352 12.2x8.9 133,100 .1045 67.4 402.9 2,127 599 50,200 35.3 .08020 .42346 .26318 5,248 2,380
3/0 AWG .510x.400 13.7x10.2 167,800 .1318 85.0 507.9 2,682 755 48,500 34.1 .06361 .33586 .20874 6,392 2,899
4/0 AWG .600x.450 15.2x11.1 211,600 .1662 107.2 640.5 3,382 953 46,600 32.8 .05045 .26638 .16556 7,744 3,513
350 MCM .754x.570 19.2x14.5 350,100 .2750 177.4 1060.0 5,595 1,577 42,800 30.1 .03049 .16099 .10001 11,770 5,339
G
R
O
O
V
E
D
F
I
G
U
R
E

8
F
I
G
.

9
NOTE: The data shown is approximate and subject to standard industry tolerances. 2011
350 MCM .707x.496 17.9x12.6 348,900 .2740 176.8 1056.0 5,576 1,571 42,800 30.1 .03059 .16152 .10039 11,730 5,321
400 MCM .715x.522 18.9x14.0 397,200 .3120 201.3 1202.0 6,348 1,789 41,300 29.0 .02687 .14187 .08817 12,880 5,842
BGRV2/0CU
BGRV3/0CU
BGRV4/0CU
BGRV300CU
BGRV350CU
BFIG81/0CU
BFIG82/0CU
BFIG83/0CU
BFIG84/0CU
BFIG8350CU
BFIG9350CU
BFIG9400CU
Contact Wire for
Electried Rail Systems
Standards:
ASTM B-47
ASTM B-116
RoHS Compliant
Applications:
Trolley wire is used as an overhead power source for electric
railroad locomotives, cranes, light rail transit systems, and
underground mining motor cars.
Description:
Single conductor, solid copper, having a hard drawn temper, made
in the conguration of: grooved, gure 8, or gure 9.
Nominal
Conductor
Size
Overall Diameter
Inches
Area
Circular
Mils
Square
Inches
Square
MM
Weight
Pounds
Per
1,000 Ft.
KG
Per
KM
Pounds
Per
Mile
KGF
Per
Sq. MM
Lbs. Per
Square
Inch
Tensile Strength
(Minimum)
Ohms
Per
1000 Ft.
Ohms
Per KM
Min. Breaking
Strength
Kilo-
grams
Ohms
Per Mi.
Pounds
Resistance (68 F/20C)
Milli-
meters
Part
Number
B
a
r
e

C
o
p
p
e
r
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
6
Made in the USA
Bronze Contact Wire for
Electried Rail Systems
Standards:
ASTM B-9
Applications:
Trolley wire is used as an overhead power source for electric
railroad locomotives, cranes, light rail transit systems, and under-
ground mining motor cars.
Description:
Single conductor, solid bronze, having a hard drawn temper, made
in the conguration of: grooved, or gure 9.
2/0 AWG .392 9.957 137,900 .1083 69.9 417.4 2,204 621 73,000 51.3 .1367 .72178 .44859 7,906 3,586
3/0 AWG .430 10.922 167,300 .1314 84.8 506.4 2,674 753 71,000 49.9 .1127 .59506 .36983 9,329 4,232
4/0 AWG .482 12.243 212,000 .1665 107.4 641.7 3,388 955 69,000 48.5 .0889 .46966 .29190 11,490 5,212
300 MCM .574 14.580 299,800 .2355 151.9 907.5 4,792 1,350 64,800 45.6 .0629 .33211 .20641 15,260 6,922
350 MCM .620 15.748 351,200 .2758 166.3 1063.0 5,613 1,582 62,500 43.9 .0536 .28348 .17618 17,240 7,820
A
L
L
O
Y

5
5
G
R
O
O
V
E
D
BGRV2/0CD55
BGRV3/0CD55
BGRV4/0CD55
BGRV300CD55
BGRV350CD55
F
I
G
.

9

5
5
8
0
335 MCM .680x.482 17.3x12.2 336,400 .2642 170.4 1018.0 5,377 1,515 61,500 43.2 .05605 .29594 .18393 16,250 7,371
335 MCM .680x.482 17.3x12.2 336,400 .2642 170.4 1018.0 5,377 1,515 56,800 39.9 .03854 .20349 .12647 15,010 6,809
NOTE: The data shown is approximate and subject to standard industry tolerances. 2011
BFIG9335CD55
BFIG9335CD80
2/0 AWG .392 9.957 137,900 .1083 69.9 417.4 2,204 621 69,000 48.5 .0940 .49637 .30850 7,473 3,390
3/0 AWG .430 10.922 167,300 .1314 84.8 506.4 2,674 753 67,000 47.1 .0774 .40915 .25429 8,804 3,993
4/0 AWG .482 12.243 212,000 .1665 107.4 641.7 3,388 955 65,000 45.7 .0611 .32287 .20067 10,820 4,908
300 MCM .574 14.580 299,800 .2355 151.9 907.5 4,792 1,350 61,500 43.2 .0432 .22831 .14190 14,480 6,568
350 MCM .620 15.748 351,200 .2758 166.3 1063.0 5,613 1,582 59,500 41.8 .0369 .19488 .12112 16,410 7,414
A
L
L
O
Y

8
0
G
R
O
O
V
E
D
BGRV2/0CD80
BGRV3/0CD80
BGRV4/0CD80
BGRV300CD80
BGRV350CD80
Overall Diameter
Milli-
meters
Area
Circular
Mils
Square
Inches
Square
MM
Weight
Pounds
Per
1,000 Ft.
KG
Per
KM
Pounds
Per
Mile
KG
Per
Sq. MM
Lbs. Per
Square
Inch
Tensile Strength
(Minimum)
Resistance
(68 F/20C)
Ohms
Per
1000 Ft.
Ohms
Per KM
Min. Breaking
Strength
Ohms
Per Mi.
Pounds
Kilo-
grams
Nominal
Conductor
Size
Inches
Part
Number
S
i
n
g
l
e

C
o
n
d
u
c
t
o
r
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
7
Made in the USA
Standards:
ASTM B3 and B8
UL 44, ICEA S-95-658/NEMA WC-70
Federal spec A-A-59544, 90 C Wet/Dry
CT use 1/0 and larger
Gasoline and Oil Resistant II
C(UL)US: CSA/UL Listed
Sunlight Resistant
-40 C rated
Suitable for use in 105 C Dry System
RoHS Compliant
Applications:
Type XHHW-2, CT is suitable for general purpose wiring, for power dis-
tribution and branch circuit wiring, where a cable having superior ame
retardance is required. Also suitable for use in low leakage circuits
requiring a dielectric constant of 3.5 or less (Hospital Grade).
Description:
Single copper conductor, stranded, insulated with moisture, heat,
and ame resistant, chemically cross-linked polyethylene insula-
tion. Temperature rating 90 C in wet and dry locations. Colors
available.
XHHW-2
CT Rated
600 Volt Copper
*Per NEC-Table 310-17.
The overcurrent protection for items marked with an obelisk () shall not exceed 15 amps for 14 AWG, 20 amps for 12 AWG, and 30 amps for 10
AWG per NEC 310-17 footnote.
NOTE: The data shown is approximate and subject to standard industry tolerances. 2011
Strand
(no.)
Insulation
Thickness
(mils)
Nominal
Diameter
Overall
(inch)
Ampacity*
90C
Wet/Dry
Approx. Net
Weight
per 1000 feet (lbs.)
X
H
H
W
-
2
,

C
T
Size
AWG
or
MCM
XHHW14BK
XHHW12BK
XHHW10BK
XHHW8BK
XHHW6BK
XHHW4BK
XHHW3BK
XHHW2BK
XHHW1BK
XHHW1/0BK
XHHW2/0BK
XHHW3/0BK
XHHW4/0BK
XHHW250BK
XHHW300BK
XHHW350BK
XHHW400BK
XHHW500BK
XHHW600BK
XHHW750BK
Part
Number
14 7 30 .133 17 35
12 7 30 .152 26 40
10 7 30 .176 39 55
8 7 45 .236 63 80
6 7 45 .274 96 105
4 7 45 .322 147 140
3 7 45 .350 182 165
2 7 45 .382 226 190
1 19 55 .431 287 220
1/0 19 55 .470 360 260
2/0 19 55 .514 449 300
3/0 19 55 .564 560 350
4/0 19 55 .620 700 405
250 37 65 .705 833 455
300 37 65 .759 993 505
350 37 65 .811 1,153 570
400 37 65 .858 1,311 615
500 37 65 .943 1,628 700
600 61 80 1.053 1,968 780
750 61 80 1.158 2,443 885
S
i
n
g
l
e

C
o
n
d
u
c
t
o
r
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
8
Made in the USA
Standards:
ASTM B3 and B8
UL 44, ICEA S-95-658/NEMA WC-70
Federal spec A-A-59544, 90 C Wet/Dry
For CT Use / IEEE 1202 1/0 AWG and larger
Gasoline and Oil Resistant II
C(UL) US RW90:CSA/UL Listed
Sunlight Resistant (Black only)
-40 C rated
Suitable for use in 105 C Dry System
RoHS Compliant
Description:
Single copper conductor, stranded, insulated with moisture, heat,
and ame resistant, chemically cross-linked polyethylene insula-
tion. Temperature rating 90 C in wet and dry locations. All sizes
pass the vertical ame test (VW-1). Colors available.
Applications:
Type XHHW-2, VW-1 is suitable for general purpose wiring, for power
distribution and branch circuit wiring, where a cable having superior
ame retardance is required. Also suitable for use in low leakage
circuits requiring a dielectric constant of 3.5 or less (Hospital Grade).
XHHW-2
VW-1, CT Rated
600 Volt Copper
14 7 30 .133 18 35
12 7 30 .152 27 40
10 7 30 .176 40 55
8 7 45 .236 66 80
6 7 45 .274 99 105
4 7 45 .322 151 140
3 7 45 .350 187 165
2 7 45 .382 232 190
1 19 55 .431 295 220
1/0 19 55 .470 367 260
2/0 19 55 .514 456 300
3/0 19 55 .564 568 350
4/0 19 55 .620 709 405
250 37 65 .705 846 455
300 37 65 .759 1,007 505
350 37 65 .811 1,167 570
400 37 65 .858 1,327 615
500 37 65 .943 1,645 700
600 61 80 1.053 1,991 780
750 61 80 1.158 2,469 885
*Per NEC-Table 310-17.
The overcurrent protection for items marked with an obelisk () shall not exceed 15 amps for 14 AWG, 20 amps for 12 AWG, and 30 amps for 10
AWG per NEC 310-17 footnote.
NOTE: The data shown is approximate and subject to standard industry tolerances. 2011
Strand
(no.)
Insulation
Thickness
(mils)
Nominal
Diameter
Overall
(inch)
Ampacity*
90C
Wet/Dry
Approx. Net
Weight
per 1000 feet (lbs.)
X
H
H
W
-
2
,

V
W
-
1
Size
AWG
or
MCM
XHHW14VW1
XHHW12VW1
XHHW10VW1
XHHW8VW1
XHHW6VW1
XHHW4VW1
XHHW3VW1
XHHW2VW1
XHHW1VW1
XHHW1/0VW1
XHHW2/0VW1
XHHW3/0VW1
XHHW4/0VW1
XHHW250VW1
XHHW300VW1
XHHW350VW1
XHHW400VW1
XHHW500VW1
XHHW600VW1
XHHW750VW1
S
i
n
g
l
e

C
o
n
d
u
c
t
o
r
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
9
Made in the USA
Description:
Single copper conductor, tinned stranded insulated with moisture
and heat resistant, chemically cross-linked polyethylene insulation
(VW-1). Temperature rating 90C in wet and dry locations.

Switchboard Wire
UL Type SIS
600 Volt Copper
STANDARDS:
UL 44
C(UL) US: CSA/UL Listed (#14 AWG and Larger)
Flame Rated: UL 1581 Vertical Flame (VW1) (#14 and larger)
Dual Rated Type XHHW-2 (#14 & larger)
(UL 66 Fixture Wire for #16 AWG)
Per ICEA S-95-658 / NEMA WC-70
Gasoline and Oil Resistant II
Sunlight Resistant (Black only)
Excellent crush and abrasion resistance
-40C rated
Federal Spec AA-59544
Suitable for use in 105 C Dry System
RoHS Compliant
Stranding
Flex-Strand
Catalog
Number
Size
AWG or
KCMIL
SIS16KT 16 26 7 19 30 0.121 12 8
SIS14KTVW 14 41 7 19 30 0.139 19 25
SIS12KTVW 12 65 7 19 30 0.158 27 30
SIS10KTVW 10 105 7 19 30 0.182 40 40
SIS8HTVW 8 133 7 19 45 0.238 67 55
SIS6HTVW 6 133 7 19 45 0.274 100 75
Flex-Strand
Stock
Insulation
Thickness
(mils)
Nominal
Diameter
Overall (inch)
Ampacity*
(30C
Ambient)
90CWet/Dry
Approx. Net Wt.
per 1000 ft.
(lbs.)
Class B
Stock
Class C
***
**
**
**
COLOR CHART
Size Blue Black Brown Green Gray Orange Red White Yellow
16 X X X X X X X X X
14 X X X X X X X X
12 X X X X X X X
10 X X X
8 X
*Per NEC Table 310-16
** The overcurrent protection for items marked ** shall not exceed 15
amps for 14 AWG, 20 amps for 12 AWG, and 30 amps for 10 AWG per NEC 310-16 footnote.
***#16 AWG is FFH-2.
NOTE: Copper Conductor available Non-Tinned.
NOTE: The data shown is approximate and subject to standard industry tolerances. 2011
S
i
n
g
l
e

C
o
n
d
u
c
t
o
r
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
10
Made in the USA
Description:
Single copper conductor, stranded, insulated with moisture and
heat resistant, chemically cross-linked polyethylene insulation.
Temperature rating 90 C in wet and dry applications. Colors
available.
Standards:
ASTM B3 and B8
UL 44 and UL 854, ICEA S-95-658/NEMA WC-70
C(UL) US RW90 1kV:CSA/UL Listed
#14 - 4/0 Rated L-824C
Federal spec. A-A-59544
For CT Use 1/0 and Larger
Gasoline and Oil Resistant II
-40 C rated
Direct Burial/Sunlight Resistant
Suitable for use in 105 C Dry System
RoHS Compliant
XLP USE-2 or RHH/RHW-2
CT Rated
600 Volt, Copper
* Per NEC-Table 310-17.
The overcurrent protection for items marked with an obelisk () shall not exceed 15 amps for 14 AWG, 20 amps for 12 AWG, and
30 amps for 10 AWG per NEC 310-17 footnote.
NOTE: The data shown is approximate and subject to standard industry tolerances. 2011
Size
AWG
or
MCM
Strand
(no.)
Insulation
Thickness
(mils)
Approx.
Diameter
Overall
(inch)
Approx. Net
Weight
per 1000 feet (lbs.)
Ampacity*
90C
Wet/Dry
X
L
P

U
S
E
-
2
,

R
H
H
/
R
H
W
-
2

C
T
14 7 45 .163 20 35
12 7 45 .182 29 40
10 7 45 .206 42 55
8 7 60 .266 68 80
6 7 60 .304 102 105
4 7 60 .352 153 140
3 7 60 .380 189 165
2 7 60 .412 234 190
1 19 80 .481 303 220
1/0 19 80 .520 378 260
2/0 19 80 .564 468 300
3/0 19 80 .614 581 350
4/0 19 80 .670 723 405
250 37 95 .765 866 455
300 37 95 .819 1,028 505
350 37 95 .871 1,190 570
400 37 95 .918 1,350 615
500 37 95 1.003 1,671 700
600 61 110 1.113 2,015 780
750 61 110 1.218 2,496 885
XLP14BK
XLP12BK
XLP10BK
XLP8BK
XLP6BK
XLP4BK
XLP3BK
XLP2BK
XLP1BK
XLP1/0BK
XLP2/0BK
XLP3/0BK
XLP4/0BK
XLP250BK
XLP300BK
XLP350BK
XLP400BK
XLP500BK
XLP600BK
XLP750BK
Part
Number
Application:
Types USE-2, RHH/RHW-2 CT are suitable for use in general
purpose wiring applications and may be installed in raceway,
conduit, direct burial and aerial installations where a cable having
superior ame retardance is required.
S
i
n
g
l
e

C
o
n
d
u
c
t
o
r
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
11
Made in the USA
Description:
Single copper conductor, stranded, insulated with moisture and
heat resistant, chemically cross-linked polyethylene insulation.
Temperature rating 90 C in wet and dry applications. All sizes pass
the vertical ame test (VW-1). Colors available.
Application:
Types USE-2, RHH/RHW-2 VW-1 are suitable for use in general
purpose wiring applications and may be installed in raceway,
conduit, direct burial and aerial installations where a cable having
superior ame retardance is required.
Standards:
ASTM B3 & B8
UL 44 and UL 854, ICEA S-95-658/NEMA WC-70
Federal spec. A-A-59544
#14-4/0 rated L-824C
For CT Use / IEEE 1202 1/0 AWG and larger
Gasoline and Oil Resistant II
-40 C rated
Direct Burial
C(UL) US RW90 1kV:CSA/UL Listed
Sunlight Resistant (Black only)
Suitable for use in 105 C Dry System
RoHS Compliant
XLP USE-2 or RHH/RHW-2
VW-1, CT Rated,
600 Volt, Copper
* Per NEC-Table 310-17.
The overcurrent protection for items marked with an obelisk () shall not exceed 15 amps for 14 AWG, 20 amps for 12 AWG, and
30 amps for 10 AWG per NEC 310-17 footnote.
NOTE: The data shown is approximate and subject to standard industry tolerances. 2011
Size
AWG
or
MCM
Strand
(no.)
Insulation
Thickness
(mils)
Approx.
Diameter
Overall
(inch)
Approx. Net
Weight
per 1000 feet (lbs.)
Ampacity*
90C
Wet/Dry
X
L
P

U
S
E
-
2
,

R
H
H
/
R
H
W
-
2
14 7 45 .163 22 35
12 7 45 .182 31 40
10 7 45 .206 45 55
8 7 60 .266 73 80
6 7 60 .304 107 105
4 7 60 .352 160 140
3 7 60 .380 197 165
2 7 60 .412 243 190
1 19 80 .481 316 220
1/0 19 80 .520 389 260
2/0 19 80 .564 480 300
3/0 19 80 .614 594 350
4/0 19 80 .670 737 405
250 37 95 .765 885 455
300 37 95 .819 1,049 505
350 37 95 .871 1,212 570
400 37 95 .918 1,374 615
500 37 95 1.003 1,697 700
600 61 110 1.113 2,049 780
750 61 110 1.218 2,532 885
XLP14VW1
XLP12VW1
XLP10VW1
XLP8VW1
XLP6VW1
XLP4VW1
XLP3VW1
XLP2VW1
XLP1VW1
XLP1/0VW1
XLP2/0VW1
XLP3/0VW1
XLP4/0VW1
XLP250VW1
XLP300VW1
XLP350VW1
XLP400VW1
XLP500VW1
XLP600VW1
XLP750VW1
Part
Number
S
i
n
g
l
e

C
o
n
d
u
c
t
o
r
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
12
Made in the USA
Type RHH/RHW-2
CT Rated
2000 Volt, Copper
Description:
Single copper conductor, stranded, insulated with moisture and
heat resistant cross-linked polyethylene.
Temperature rating is 90 C in wet and dry applications.
Application:
Type RHH, RHW-2 is suitable for wiring in raceways, conduit, etc.
Applications include general purpose wiring for power distribution,
services, feeders, and branch circuit wiring in residential, industrial,
and commercial buildings.
Standards:
ASTM B3 & B8
UL 44
C(UL) US RW90 1kV:CSA/UL Listed
Federal Spec. A-A-59544
ICEA S-95-658/NEMA WC-70
For CT rated 1/0 and larger
Sunlight Resistant
#14-4/0 Rated L-824C
-40 C rated
Suitable for use in 105 C Dry System
Gasoline and Oil Resistant II
RoHS Compliant
Size
AWG
or
MCM
Strand
(no.)
Insulation
Thickness
(mils)
Nominal
Diameter
Overall
(inch)
Approx. Net
Weight
(lbs./mft)
Ampacity*
90C
Wet/Dry
2
K
V

R
H
H

/

R
H
W
-
2
/
R
W
U
9
0
*Based on ambient temperature of 30C per NEC-Table 310-17
The overcurrent protection for items marked with an obelisk () shall not exceed 15 amps for 14 AWG, 20 amps for 12 AWG, and 30
amps for 10 AWG per NEC 310-17 footnote.
NOTE: The data shown is approximate and subject to standard industry tolerances. 2011
14 7 60 .193 24 35
12 7 60 .212 33 40
10 7 60 .236 47 55
8 7 80 .306 76 80
6 7 80 .344 111 105
4 7 80 .392 164 140
3 7 80 .420 200 165
2 7 80 .452 246 190
1 19 95 .511 313 220
1/0 19 95 .550 390 260
2/0 19 95 .594 481 300
3/0 19 95 .644 595 350
4/0 19 95 .700 738 405
250 37 110 .795 883 455
300 37 110 .849 1,046 505
350 37 110 .901 1,209 570
400 37 110 .948 1,371 615
500 37 110 1.033 1,694 700
600 61 125 1.143 2,041 780
750 61 125 1.248 2,523 885

2K14XLPBK
2K12XLPBK
2K10XLPBK
2K8XLPBK
2K6XLPBK
2K4XLPBK
2K3XLPBK
2K2XLPBK
2K1XLPBK
2K1/0XLPBK
2K2/0XLPBK
2K3/0XLPBK
2K4/0XLPBK
2K250XLPBK
2K300XLPBK
2K350XLPBK
2K400XLPBK
2K500XLPBK
2K600XLPBK
2K750XLPBK
Part
Number
S
i
n
g
l
e

C
o
n
d
u
c
t
o
r
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
13
Made in the USA
600 Volt Single
Conductor
Power Cable
XHHW-2/PVC
Standards:
Conductors UL 44
UL Listed Construction
Per ICEA S-95-658 / NEMA WC-70
Federal Spec A-A-59544
Temperature Rating: 90C Wet/Dry
Sunlight Resistant
For CT Use (1/0 and Larger)
RoHS Compliant
Description:
Single copper conductor, stranded insulated with moisture
and heat resistant, chemically cross-linked polyethylene
insulation, covered with a sunlight resistant, PVC jacket.

Jacket available in colors.

14 7 30 30 0.193 27 25+
12 7 30 30 0.212 36 30+
10 7 30 30 0.236 40 40+
8 7 45 30 0.296 78 55
6 7 45 30 0.34 117 75
4 7 45 30 0.39 172 95
2 7 45 30 0.45 256 130
1 19 55 45 0.54 331 150
1/0 19 55 45 0.57 405 170
2/0 19 55 45 0.61 498 195
3/0 19 55 45 0.66 613 225
4/0 19 55 45 0.72 758 260
250 37 65 65 0.84 941 290
350 37 65 65 0.95 1276 350
500 37 65 65 1.08 1770 430
750 61 80 65 1.30 2620 535
Size
AWG
or
MCM
Strand
(no.)
Insulation
Thickness
(mils)
Nominal
Diameter
Overall
(inch)
Ampacity*
30 C Ambient
90 C Wet/Dry
*Per NEC-Table 310-16.
The overcurrent protection for items marked with an obelisk (+) shall not exceed 15 amps for 14 AWG, 20 amps for 12 AWG and 30 amps for 10 AWG
NOTE: The data shown is approximate and subject to standard industry tolerances.
2011
Approx. Net
Weight
per 1000 feet (lbs.)
Jacket
Thickness
(mils)
XHPVC14
XHPVC12
XHPVC10
XHPVC8
XHPVC6
XHPVC4
XHPVC2
XHPVC1
XHPVC1/0
XHPVC2/0
XHPVC3/0
XHPVC4/0
XHPVC250
XHPVC350
XHPVC500
XHPVC750
Part
Number
S
i
n
g
l
e

C
o
n
d
u
c
t
o
r
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
14
Made in the USA
600 Volt Single
Conductor
Power Cable
XHHW-2/CPE
Standards:
Conductors UL 44
UL Listed Construction
Per ICEA S-95-658 / NEMA WC-70
Federal Spec A-A-59544
Temperature Rating: 90C Wet/Dry
Sunlight Resistant
For CT Use (1/0 and Larger)
RoHS Compliant
Description:
Single copper conductor, stranded insulated with moisture
and heat resistant, chemically cross-linked polyethylene
insulation, covered with a sunlight resistant, CPE jacket.

14 7 30 30 0.193 28 25+
12 7 30 30 0.212 37 30+
10 7 30 30 0.236 45 40+
8 7 45 30 0.296 80 55
6 7 45 30 0.34 119 75
4 7 45 30 0.39 178 95
2 7 45 30 0.45 260 130
1 19 55 45 0.54 334 150
1/0 19 55 45 0.57 409 170
2/0 19 55 45 0.61 501 195
3/0 19 55 45 0.66 615 225
4/0 19 55 45 0.72 761 260
250 37 65 65 0.84 945 290
350 37 65 65 0.95 1280 350
500 37 65 65 1.08 1775 430
750 61 80 65 1.30 2626 535
Size
AWG
or
MCM
Strand
(no.)
Insulation
Thickness
(mils)
Nominal
Diameter
Overall
(inch)
Ampacity*
30 C Ambient
90 C Wet/Dry
*Per NEC-Table 310-16.
The overcurrent protection for items marked with an obelisk (+) shall not exceed 15 amps for 14 AWG, 20 amps for 12 AWG and 30 amps for 10 AWG
NOTE: The data shown is approximate and subject to standard industry tolerances.
2011
Approx. Net
Weight
per 1000 feet (lbs.)
Jacket
Thickness
(mils)
XHCPE14
XHCPE12
XHCPE10
XHCPE8
XHCPE6
XHCPE4
XHCPE2
XHCPE1
XHCPE1/0
XHCPE2/0
XHCPE3/0
XHCPE4/0
XHCPE250
XHCPE350
XHCPE500
XHCPE750
Part
Number
S
i
n
g
l
e

C
o
n
d
u
c
t
o
r
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
15
Made in the USA
EnviroPlusTM
Power Cable
600 Volt Single Conductor Power Cable
XHHW-2
Zero Halogen, Limited Smoke Jacket
Standards:
LS and CT Rated 1/0 and larger per UL1685
Conductors UL44
ICEA S-95-658/NEMA WC-70
IEEE 383 70,000 BTU ame test 1/0 and larger
Federal spec A-A-59544
UL Listed construction
Temperature Rating: 90 C Wet/Dry
Sunlight resistant; superior water resistance
Excellent crush and abrasion resistance
Zero Halogen, Limited Smoke Jacket
RoHS Compliant
Description:
Single conductor, stranded copper, insulated with heat and
moisture resistant, cross-linked polyethylene insulation, (Type
XHHW-2), with an overall ame and sunlight resistant, Zero Halo-
gen, Limited Smoke, Zero Lead Jacket.
Available with tinned conductors.
14 7 30 30 .193 29 25
12 7 30 30 .212 38 30
10 7 30 30 .236 53 40
8 7 45 30 .296 83 55
6 7 45 30 .334 114 75
4 7 45 30 .382 168 95
2 7 45 30 .442 252 130
1 19 55 45 .521 331 150
1/0 19 55 45 .596 412 170
2/0 19 55 45 .643 505 195
3/0 19 55 45 .690 620 225
4/0 19 55 45 .746 765 260
250 37 65 65 .871 943 290
350 37 65 65 .977 1,275 350
500 37 65 65 1.111 1,770 430
750 61 80 65 1.324 2,610 535
Size
AWG
or
MCM
Strand
(no.)
Insulation
Thickness
(mils)
Nominal
Diameter
Overall
(inch)
Ampacity*
30 C Ambient
90 C Wet/Dry
*Per NEC-Table 310-16.
The overcurrent protection for items marked with an obelisk () shall not exceed 15 amps for 14 AWG, 20 amps for 12 AWG and 30 amps for 10
NOTE: The data shown is approximate and subject to standard industry tolerances.
2011
Approx. Net
Weight
per 1000 feet (lbs.)
Jacket
Thickness
(mils)
XHENV14
XHENV12
XHENV10
XHENV8
XHENV6
XHENV4
XHENV2
XHENV1
XHENV1/0
XHENV2/0
XHENV3/0
XHENV4/0
XHENV250
XHENV350
XHENV500
XHENV750
Part
Number
S
i
n
g
l
e

C
o
n
d
u
c
t
o
r
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
16
Made in the USA

2
K
V

R
H
H

/

R
H
W
-
2
Photovoltaic Wire
for use with Solar Panels
600 Volt Single Conductor Power Cable
USE-2 or RHH or RHW-2
Description:
Single copper conductor, stranded, insulated with moisture and
heat resistant cross-linked polyethylene. Rated 600V to meet the
challenging requirements of transformerless inverters on
photovoltaic (solar) panel installations.
Temperature rating is 90 C in wet and dry applications.
Standards:
ASTM B3 & B8
UL 44, UL 854, UL 4703,
Flame Rated: VW-1 per UL 1685
Federal Spec. A-A-59544
ICEA S-95-658/NEMA WC-70
CT rated 1/0 and larger
Sunlight Resistant
#14-4/0 Rated L-824C
-40 C rated
Suitable for use in 105 C Dry System
RoHS Compliant
*Based on ambient temperature of 30C per NEC-Table 310-17
The overcurrent protection for items marked with an obelisk () shall not exceed 15 amps for 14 AWG, 20 amps for 12 AWG, and 30 amps for 10
AWG per NEC 310-17 footnote. NOTE: The data shown is approximate and subject to standard industry tolerances.
NOTE: Photovoltaic module interconnection wire for use with or without a raceway in accordance wiht wiring systems Article 690 in the National
Electrical Code (NEC), NFPA 70. 2011
14 7 60 .193 27 35
12 7 60 .212 37 40
10 7 60 .236 51 55
8 7 75 .296 81 80
6 7 75 .334 116 105
4 7 75 .382 170 140
3 7 75 .410 207 165
2 7 75 .412 254 190
1 19 95 .511 329 220
1/0 19 95 .520 402 260
2/0 19 95 .594 495 300
3/0 19 95 .644 611 350
4/0 19 95 .700 755 405
250 37 110 .795 906 455
300 37 110 .849 1,071 505
350 37 110 .901 1,235 570
400 37 110 .948 1,399 615
500 37 110 1.033 1,724 700
600 61 125 1.143 2,079 780
750 61 125 1.248 2,565 885
Size
AWG
or
MCM
Strand
(no.)
Insulation
Thickness
(mils)
Nominal
Diameter
Overall
(inch)
Approx. Net
Weight
(lbs./mft)
Ampacity*
90C
Wet/Dry
6
0
0

V

R
H
H

/

R
H
W
-
2

PV600V14VW1
PV600V12VW1
PV600V10VW1
PV600V8VW1
PV600V6VW1
PV600V4VW1
PV600V3VW1
PV600V2VW1
PV600V1VW1
PV600V1/0VW1
PV600V2/0VW1
PV600V3/0VW1
PV600V4/0VW1
PV600V250VW1
PV600V300VW1
PV600V350VW1
PV600V400VW1
PV600V500VW1
PV600V600VW1
PV600V750VW1
Part
Number
Applications:
Photovoltaic wire (600 Volt) for use as interconnection wiring on
solar panels in grounded or ungrounded systems as dened in
applicable parts of the National Electrical Code (NEC) NFPA 70,
such as article 690.31(A).
S
i
n
g
l
e

C
o
n
d
u
c
t
o
r
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
17
Made in the USA

2
K
V

R
H
H

/

R
H
W
-
2
Photovoltaic Wire
for use with Solar Panels
2000 Volt Single Conductor Power Cable
USE-2 or RHH or RHW-2
Description:
Single copper conductor, stranded, insulated with moisture and
heat resistant cross-linked polyethylene. Rated 2KV to meet the
challenging requirements of transformerless inverters on
photovoltaic (solar) panel installations.
Temperature rating is 90 C in wet and dry applications.
Standards:
ASTM B3 & B8
UL 44, UL 854, UL 4703,
Flame Rated: VW-1 per UL 1685
Federal Spec. A-A-59544
ICEA S-95-658/NEMA WC-70
CT rated 1/0 and larger
Sunlight Resistant
#14-4/0 Rated L-824C
-40 C rated
Suitable for use in 105 C Dry System
RoHS Compliant
*Based on ambient temperature of 30C per NEC-Table 310-17
The overcurrent protection for items marked with an obelisk () shall not exceed 15 amps for 14 AWG, 20 amps for 12 AWG, and 30 amps for 10
AWG per NEC 310-17 footnote. NOTE: The data shown is approximate and subject to standard industry tolerances.
NOTE: Photovoltaic module interconnection wire for use with or without a raceway in accordance wiht wiring systems Article 690 in the National
Electrical Code (NEC), NFPA 70. 2011
14 7 75 .223 33 35
12 7 75 .242 43 40
10 7 75 .266 58 55
8 7 85 .316 86 80
6 7 85 .354 122 105
4 7 85 .402 177 140
3 7 85 .430 215 165
2 7 85 .432 262 190
1 19 105 .531 338 220
1/0 19 105 .570 413 260
2/0 19 105 .614 506 300
3/0 19 105 .664 623 350
4/0 19 105 .720 768 405
250 37 120 .815 920 455
300 37 120 .869 1,086 505
350 37 120 .921 1,252 570
400 37 120 .968 1,416 615
500 37 120 1.053 1,743 700
600 61 135 1.163 2,099 780
750 61 135 1.268 2,587 885
Size
AWG
or
MCM
Strand
(no.)
Insulation
Thickness
(mils)
Nominal
Diameter
Overall
(inch)
Approx. Net
Weight
(lbs./mft)
Ampacity*
90C
Wet/Dry
2
K
V

R
H
H

/

R
H
W
-
2

PV2K14VW1
PV2K12VW1
PV2K10VW1
PV2K8VW1
PV2K6VW1
PV2K4VW1
PV2K3VW1
PV2K2VW1
PV2K1VW1
PV2K1/0VW1
PV2K2/0VW1
PV2K3/0VW1
PV2K4/0VW1
PV2K250VW1
PV2K300VW1
PV2K350VW1
PV2K400VW1
PV2K500VW1
PV2K600VW1
PV2K750VW1
Part
Number
Applications:
Photovoltaic wire (2,000 Volt) for use as interconnection wiring on
solar panels in grounded or ungrounded systems as dened in
applicable parts of the National Electrical Code (NEC) NFPA 70,
such as article 690.31(A).
S
i
n
g
l
e

C
o
n
d
u
c
t
o
r
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
18
Made in the USA
Standards:
UL 4703 (PV Wire)
Conductors UL854 (#16 per UL 66)
ICEA S-95-658/NEMA WC-70
Flame Rated: VW-1 per UL 1685
Temperature Rating: 90 C Wet and Dry
Sunlight Resistant; Superior Water Resistance
Excellent crush and abrasion resistance
Zero Halogen, Limited Smoke Jacket
RoHS Compliant
Description:
Single conductor insulated with heat and moisture resistant,
cross-linked polyethylene insulation, (Type USE-2), with an
overall ame and sunlight resistant, Zero Halogen, Limited
Smoke, Zero Lead Jacket. Tinned conductors available.
Applications:
Photovoltaic wire (600 Volt) for use as interconnection wiring on
solar panels in grounded or ungrounded systems as dened in
applicable parts of the National Electrical Code (NEC) NFPA 70,
such as article 690.31(A).

PVENV16 16 26 45 30 .210 27 8
PVENV14 14 7 45 30 .223 32 25
PVENV12 12 7 45 30 .242 42 30
PVENV10 10 7 45 30 .266 57 40
PVENV8 8 7 60 30 .326 87 55
PVENV6 6 7 60 45 0.394 134 75
PVENV4 4 7 60 45 0.442 190 95
PVENV3 3 7 60 45 0.470 228 110
PVENV2 2 7 60 45 0.502 276 130
PVENV1 1 19 80 60 0.601 369 150
PVENV1/0 1/0 19 80 60 0.640 446 170
PVENV2/0 2/0 19 80 60 0.684 541 195
PVENV3/0 3/0 19 80 60 0.734 660 225
PVENV4/0 4/0 19 80 60 0.790 808 260
PVENV250 250 37 95 80 0.925 998 290
PVENV300 300 37 95 80 0.979 1186 320
PVENV350 350 37 95 80 1.031 1338 350
PVENV400 400 37 95 80 1.078 1526 380
PVENV500 500 37 95 80 1.163 1840 430
PVENV600 600 61 110 80 1.271 2200 475
PVENV750 750 61 110 80 1.378 2696 535
Size
AWG
or
MCM
Strand
(no.)
Insulation
Thickness
(mils)
Nominal
Diameter
Overall
(inch)
Ampacity*
30 C Ambient
90 C Wet/Dry
*Per NEC-Table 310-16.
The overcurrent protection for items marked with an obelisk () shall not exceed 15 amps for 14 AWG, 20 amps for 12 AWG and 30 amps for 10
NOTE: The data shown is approximate and subject to standard industry tolerances.
2011
Approx. Net
Weight
per 1000 feet (lbs.)
Jacket
Thickness
(mils)
Part
Number
Photovoltaic Wire
for use with Solar Panels
600 Volt Single Conductor Power Cable
USE-2 or RHH or RHW-2
Zero Halogen, Limited Smoke Jacket
S
i
n
g
l
e

C
o
n
d
u
c
t
o
r
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
19
Made in the USA
Standards:
Conductors UL 1072 - MV-90
ICEA S-96-659/NEMA WC-71
Conductors Rated at 90 C Dry
Flame Retardant, Track Resistant
Sunlight Resistant
Zero Halogen, Limited Smoke Jacket
RoHS Compliant
EnviroPlusTM Power Cable
2400 Volt MV-90
Non-shielded
Description:
Conductor is stranded bare copper, with semi-conducting strand
shield, heat and moisture resistant EPR insulation per ICEA
S-96-659, with an extruded ame and sunlight resistant, Zero
Halogen, Limited Smoke, Zero Lead jacket.
Size
AWG
or
MCM
Insulation
Thickness
(mils)
Copper Conductor Nominal
Diameter
Over Insul.
(inches)
Jacket
Thickness
(mils)
Nominal O.A.
Diameter
(inches)
Approx.
Net Wgt.
Lbs/1000'
Conduit
Ampacity*
No. of
Strands
8 7 125 .58 80 .75 293 61 93
6 7 125 .62 80 .79 340 84 120
4 7 125 .67 80 .84 413 110 160
2 7 125 .73 80 .90 518 145 215
1/0 19 125 .80 80 .97 679 200 290
2/0 19 125 .85 80 1.02 788 225 330
4/0 19 125 1.01 95 1.21 1,215 305 445
250 37 140 1.09 110 1.32 1,405 355 495
350 37 140 1.19 110 1.42 1,778 430 615
500 37 140 1.32 110 1.55 2,322 530 775
750 61 155 1.56 125 1.82 3,371 665 1,000
Air
* Ampacity: Refer to NEC Article 310.
NOTE: The data shown is approximate and subject to standard industry tolerances. 2011
ENV2.4K8E
ENV2.4K6E
ENU2.4K4E
ENV2.4K2E
ENV2.4K1/0E
ENV2.4K2/0E
ENV2.4K4/0E
ENV2.4K250E
ENV2.4K350E
ENV2.4K500E
ENV2.4K750E
Part
Number
S
i
n
g
l
e

C
o
n
d
u
c
t
o
r
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
20
Made in the USA
Description:
Single copper conductor, stranded, insulated with moisture and
ame retardant, sunlight resistant polyvinyl chloride compound.
Suitable for use in wet or dry locations where conductor tempera-
tures do not exceed 75 C. Available in colors.
Application:
Type THW is suitable for use in conduit or other recognized race-
ways for services, feeders and branch circuit wiring. Applications
also include general purpose grounding for power and distribution
circuits in residential, industrial and commercial buildings.
Standards:
ASTM B3 & B8
UL 83
All sizes carry the VW-1 Flame test designation
Federal Spec. A-A-59544
CT-use 1/0 and larger
Sunlight Resistant
Oil Resistant I
NEMA WC-5 / ICEA S-61-402
C(UL)US: CSA/UL Listed (#14-500)
RoHS Compliant
THW
600 Volt, Copper
Size
AWG
or
MCM
Strand
(No.)
Insulation
Thickness
(mils)
Nominal
Diameter
Overall
(inch)
Approx. Net
Weight
(lbs/Mft)
*Based on ambient temperature of 30C per NEC-Table 310-17 **Available with 30 mil Insulation
The overcurrent protection for items marked with an obelisk () shall not exceed 15 amps for 14 AWG, 20 amps for 12 AWG, and 30
amps for 10 AWG per NEC 310-17 footnote.
NOTE: The data shown is approximate and subject to standard industry tolerances. 2011
14** 1 45 .154 22 30
12** 1 45 .171 31 35
10** 1 45 .192 44 50
8 1 45 .219 65 70
14 7 30 .133 19 30
12 7 30 .152 28 35
10 7 30 .176 41 50
8 7 45 .236 68 70
6 7 60 .304 109 95
4 7 60 .352 163 125
3 7 60 .380 199 145
2 7 60 .412 245 170
1 19 80 .481 320 195
1/0 19 80 .520 393 230
2/0 19 80 .564 485 265
3/0 19 80 .614 599 310
4/0 19 80 .670 743 360
250 37 95 .765 893 405
300 37 95 .819 1,057 445
350 37 95 .871 1,221 505
400 37 95 .918 1,384 545
500 37 95 1.003 1,708 620
600 61 110 1.113 2,062 690
750 61 110 1.218 2,547 785
1,000 61 110 1.372 3,351 935
Ampacity*
75 C
Wet/Dry
THW14SOL
THW12SOL
THW10SOL
THW8SOL
THW14
THW12
THW10
THW8
THW6
THW4
THW3
THW2
THW1
THW1/0
THW2/0
THW3/0
THW4/0
THW250
THW300
THW350
THW400
THW500
THW600
THW750
THW1000
Part
Number
S
i
n
g
l
e

C
o
n
d
u
c
t
o
r
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
21
Made in the USA
Description:
Single copper conductor, stranded, insulated with moisture and
ame retardant, sunlight resistant polyvinyl chloride compound.
Suitable for use in wet or dry locations where conductor tempera-
tures do not exceed 90 C. Available in colors.
Application:
Type THW-2 is suitable for use in conduit or other recognized
raceways for services, feeders and branch circuit wiring. Applica-
tions also include general purpose grounding for power and distri-
bution circuits in residential, industrial and commercial buildings.
Standards:
ASTM B3 & B8
UL 83
All sizes carry the VW-1 Flame test designation
Federal Spec. A-A-59544
CT-use 1/0 and larger
Sunlight Resistant (Black only)
Oil Resistant I
NEMA WC-5 / ICEA S-61-402
RoHS Compliant
THW-2
600 Volt, Copper
Insulation
Thickness
(mils)
Nominal
Diameter
Overall
(inch)
Approx. Net
Weight
(lbs/Mft)
*Based on ambient temperature of 30C per NEC-Table 310-17 **Available with 30 mil Insulation
The overcurrent protection for items marked with an obelisk () shall not exceed 15 amps for 14 AWG, 20 amps for 12 AWG, and 30
amps for 10 AWG per NEC 310-17 footnote.
NOTE: The data shown is approximate and subject to standard industry tolerances. 2011
T
H
W
14** 1 45 .154 22 35
12** 1 45 .171 31 40
10** 1 45 .192 44 55
14 7 30 .133 19 35
12 7 30 .152 28 40
10 7 30 .176 41 55
8 7 45 .236 68 80
6 7 60 .304 109 105
4 7 60 .352 163 140
3 7 60 .380 199 165
2 7 60 .412 245 190
1 19 80 .481 320 220
1/0 19 80 .520 393 260
2/0 19 80 .564 485 300
3/0 19 80 .614 599 350
4/0 19 80 .670 743 405
250 37 95 .765 893 455
300 37 95 .819 1,057 505
350 37 95 .871 1,221 570
400 37 95 .918 1,384 615
500 37 95 1.003 1,708 700
600 61 110 1.113 2,062 780
750 61 110 1.218 2,547 885
1,000 61 110 1.372 3,351 1,055
Ampacity*
90 C
Wet/Dry
Size
AWG
or
MCM
Strand
(No.)
THW2-14BKSOL
THW2-12BKSOL
THW2-10BKSOL
THW2-14BK
THW2-12BK
THW2-10BK
THW2-8BK
THW2-6BK
THW2-4BK
THW2-3BK
THW2-2BK
THW2-1BK
THW2-1/0BK
THW2-2/0BK
THW2-3/0BK
THW2-4/0BK
THW2-250BK
THW2-300BK
THW2-350BK
THW2-400BK
THW2-500BK
THW2-600BK
THW2-750BK
THW2-1000BK
Part
Number
S
i
n
g
l
e

C
o
n
d
u
c
t
o
r
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
22
Made in the USA
Description:
Copper conductor, solid or stranded, soft (annealed),
medium hard, or hard drawn, covered with black high molecular
weight polyethylene (HMW-PE).
Application:
For use in overhead distribution systems where protection from
environmental elements is required.
Weatherproof Line Wire
HMW-PE / Copper
Solid/Stranded
Soft, Medium Hard,
Hard Drawn
Standards:
Service Wire line conforms to ASTM standards:
B-1 (Hard Drawn)
B-2 (Medium Hard Drawn)
B-3 (Soft or Annealed)
B-8 (Concentric Stranded Copper)
Strand Class A, AA (1 - 4/0)
Service Wire line wire conforms to ANSI C8.35 / ICEA S-70-547
RoHS Compliant
Size
AWG
or
MCM
W
E
A
T
H
E
R
P
R
O
O
F

L
I
N
E

W
I
R
E
Covering
Thickness
(mils)
DC Resistance (Ohms
per 1000 ft.) @ 20 C
Nominal
Diameter
Overall
(inch)
Approx. Net
Weight per
1000 feet
(lbs.)
Hard
Drawn
Medium
Drawn
Soft
(Annealed)
Ampacity*
(Amps)
Stranding
*Per NEC Table 310-21. Based on conductor temperature of 80 C; ambient temperature of 40 C; 2 ft./sec. wind.
NOTE: The data shown is approximate and subject to standard industry tolerances. 2011
6 Solid 30 .22 86.7 .4110 4088 .3952 130
4 Solid 30 .26 135.2 .2584 .2571 .2485 163
4 7 30 .29 138.6 .2636 .2622 .2540 163
2 Solid 45 .35 218.3 .1625 .1617 .1563 219
2 7 45 .38 223.6 .1660 .1650 .1590 219
1 7 45 .42 283.6 .1316 .1309 .1265 --
1/0 7 60 .49 357.5 .1042 .1037 .1002 297
2/0 7 60 .53 446.1 .0826 .0822 .0795 344
3/0 7 60 .58 556.9 .0655 .0652 .0630 401
4/0 7 60 .64 696.4 .0519 .0517 .0499 466
250 37 60 .70 818.8 .0440 .0438 .0423 519
350 37 60 .80 1,136.1 .0314 .0313 .0302 --
500 37 80 .97 1,626.2 .0220 .0219 .0212 812
750 61 80 1.16 2,415.2 .0146 .0146 .0141 1,050
1000 61 95 1.34 3,234.0 .0110 .0109 .0106 1,253
PESOS6
PESOS4
PEST7S4
PESOS2
PEST7S2
PEST7S1
PEST7S1/0
PEST7S2/0
PEST7S3/0
PEST7S4/0
PEST37S250
PEST37S350
PEST37S500
PEST37S750
PEST37S1000
Part
Number
S
i
n
g
l
e

C
o
n
d
u
c
t
o
r
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
23
Made in the USA
Description & Features:
Cathodic Protection Cable is a stranded copper conductor insu-
lated with a black high molecular weight polyethylene (HMW-PE)
compound that provides excellent abrasion, crush, chemical, oil
and moisture resistance.
Application:
Suitable for direct burial for use in cathodic protection systems
for pipelines, storage tanks, pilings, well casings, cables, water
storage tanks and other buried or water-submerged metallic
structures.
Cathodic Protection Cable
Soft Drawn Bare Copper
600V
Construction:
Conductor: Soft annealed stranded copper per ASTM B-8
Insulation: Black high molecular weight polyethylene (HMW-PE)
per ASTM D-1248
Temperature: 75 C
Voltage: 600 volts
Specications & Standards:
ICEA S-61-402/NEMA WC-5
Suitable for Direct Burial
Chemical, Oil and Moisture Resistant
Crush and Abrasion Resistant
Sunlight Resistant
RoHS Compliant
8 7 .143 .110 .37 2,500', 5,000' .652 87
6 7 .182 .110 .40 5,000' .411 122
4 7 .229 .110 .45 5,000' .258 175
2 7 .290 .110 .51 1,000', 5,000' .162 260
1 19 .326 .125 .58 2,500' .129 330
1/0 19 .367 .125 .62 2,000' .102 400
2/0 19 .410 .125 .66 2,000' .081 495
4/0 19 .526 .125 .77 2,000' .051 750
250 37 .575 .140 .86 1,000' .043 900
350 37 .681 .140 .96 1,000' .031 1229
All diameters are nominal values; all weights are product weights exclusive of packaging. All diameters and weights are subject
to normal manufacturing tolerances.
All sales are subject to Standard Terms & Conditions of Sale. 2011
CATHODIC PROTECTION CABLE/600V
AWG Strand Cond. O.D. Insul. O.D. (Reels) OHMS/1000 Ft. @25C (Lbs./Mft.)
Conductor Nominals (In.)
Product Wgt. Standard Put-up Nominal DC Resistance
CATH8
CATH6
CATH4
CATH2
CATH1
CATH1/0
CATH2/0
CATH4/0
CATH250
CATH350
Part
Number
S
i
n
g
l
e

C
o
n
d
u
c
t
o
r
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
24
Made in the USA
Description & Features:
Transformer Riser Wire is a copper conductor covered with a
black, high molecular weight polyethylene (HMW-PE) jacket that
provides excellent abrasion, crush, chemical, oil, and moisture
resistance.
Application:
A heavy-walled, covered cable for use in uninsulated transformer
wire applications. Intended to eliminate faults due to atmospheric
conditions, vibrations, and faulting caused by objects crossing the
leads.
Transformer
Riser Wire
Specications & Standards:
ICEA S-61-402 / NEMA WC-5
Suitable for Direct Burial
Chemical, Oil, and Moisture Resistant
Crush and Abrasion Resistant
Sunlight Resistant
RoHS Compliant
Construction:
Conductor: Soft annealed copper per ASTM B-3
Covering: Black high molecular weight polyethylene (HMW-PE) per
ASTM D-1248
NOTE: All diameters are nominal values; all weights are product exclusive of packaging. All diameters are subject to standard
manufacturing tolerances.
All sales are subject to Standard Terms & Conditions of Sale. 2011
Transformer Riser Wire
8 .129 110 .349 .6532 83
8 .146 110 .366 .6532 87
6 .162 110 .382 .4110 118
6 .184 110 .404 .4109 122
4 .204 110 .424 .2590 171
4 .232 110 .452 .2584 177
2 .258 110 .478 .1625 253
2 .292 110 .512 .1625 261
Conductor
Product Wgt.
Nominal DC
Resistant OHMS
1000 @ .25
Nominals (In.)
AWG O.D. Insulation O.D. (Lbs./Mft.)
RISER8
RISER8-7
RISER6
RISER6-7
RISER4
RISER4-7
RISER2
RISER2-7
Part
Number
T
w
i
s
t
e
d

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
25
Made in the USA
Copper
Service Drop
600 Volt
XHHW-2
Description:
The conductors are stranded, bare soft drawn copper insulated
with heat, moisture, and sunlight resistant cross-linked polyethyl-
ene. The neutral is solid or stranded, bare, hard drawn copper.
Standards:
ASTM B-1 (Hard Drawn)
ASTM B-3 (Soft Drawn or Annealed)
ASTM B-8 (Concentric-lay strand)
ICEA S-95-658/NEMA WC-70
Conductor rated at 90 C.
Single conductors per UL 44
RoHS Compliant
Insulated Conductors
2

I
N
S
U
L
A
T
E
D

-

1

B
A
R
E
Code
Name
Strand
(no.)
Size
(AWG)
Approx.
Net Wt.
per 1000 ft.
(lbs.)
Ampacity*
(40 C Ambient)
Bodoni 8 7 45 8 1 180 66
Garamond 8 7 45 8 7 181 66
Futura 6 7 45 6 1 276 89
Gothic 6 7 45 6 7 277 89
Ionic 4 7 45 4 1 427 117
Caslon 4 7 45 4 7 430 117
Century 2 7 45 2 7 670 158
Corinthian 1/0 19 55 1/0 7 1,062 214
Doric 2/0 19 55 2/0 7 1,329 247
Tuscan 3/0 19 55 3/0 7 1,664 287
Composite 4/0 19 55 4/0 7 2,100 335
Roman 250 37 65 250 37 2,479 374
Helvetica 350 37 65 350 37 3,444 464
Deville 500 37 65 500 37 4,885 580
Hard Drawn
Size (AWG)
Strand
(no.)
Neutral - Messenger

Insul.
Thick.(mils)
Huntington 8 7 45 8 7 245 66
Atlanta 6 7 45 6 1 373 89
Tallahassee 6 7 45 6 7 375 89
Baton Rouge 4 7 45 4 1 576 117
Richmond 4 7 45 4 7 579 117
Jackson 2 7 45 2 1 896 158
Seattle 2 7 45 2 7 900 158
Nashville 1/0 19 55 1/0 7 1,426 214
Lincoln 2/0 19 55 2/0 7 1,783 247
Raleigh 3/0 19 55 3/0 7 2,232 287
Denver 4/0 19 55 4/0 7 2,810 335
Pittsburgh 250 37 65 250 37 3,325 374
Houston 350 37 65 350 37 4,615 464
Culloden 500 37 65 500 37 6,540 580
3

I
N
S
U
L
A
T
E
D

-

1

B
A
R
E
*Per NEC Table 310-20. Ampacity gures are based on conductor temperature of 90 C, ambient temperature of 40 C.
NOTE: The data shown is approximate and subject to standard industry tolerances. 2011
TRI8CUSOL
TRI8CU
TRI6CUSOL
TRI6CU
TRI4CUSOL
TRI4CU
TRI2CU
TRI1/0CU
TRI2/0CU
TRI3/0CU
TRI4/0CU
TRI250CU
TRI350CU
TRI500CU
Part
Number
QUAD8CU
QUAD6CUSOL
QUAD6CU
QUAD4CUSOL
QUAD4CU
QUAD2CUSOL
QUAD2CU
QUAD1/0CU
QUAD2/0CU
QUAD3/0CU
QUAD4/0CU
QUAD250CU
QUAD350CU
QUAD500CU
T
w
i
s
t
e
d

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
26
Made in the USA
Description:
The cable conductor shall consist of soft drawn copper, stranded,
insulated with cross-linked polyethylene, type XHHW-2. These
conductors are rated for 600 volts and carry a maximum tempera-
ture rating of 90 C wet/dry. The conductors are twisted in a six
around one construction, commonly known as planetary wrap.
Conductors will be striped per customer specications.
Application:
400 Hz cable (6 around 1 XHHW-2) is used as a power source for
mainframe computers, TV and radio station output power supply,
aircraft ground power supplies at airport terminals, plus many other
applications.
400 Hz Cable
XHHW-2 Copper
Standards:
UL 44, ICEA S-95-658/NEMA WC-70
ASTM B3, B8
RoHS Compliant
Features:
Lowers overall impedance of circuit, using multiple smaller
conductors, which minimize voltage drop; a critical factor for 400
Hz computer power.
Readily available in the commonly used sizes with minimal
delivery times.
*Has the same ratings and is handled in the same manner as
any building wire.
Geometrically balanced construction allows for a minimum of
phase to phase unbalance.
The cabled conductors allow for a single, easy, conduit pull.
4 7 45 .966 1,050
2 7 45 1.146 1,620
1 19 55 1.293 2,059
1/0 19 55 1.410 2,577
2/0 19 55 1.551 3,212
3/0 19 55 1.692 4,007
4/0 19 55 1.860 5,006
250 37 65 2.115 5,992
350 37 65 2.433 8,285
500 37 65 2.835 11,702

2
K
V

R
H
H

/

R
H
W
-
2
Approx.
Diameter
(inch)
Insulation
Thickness
(mils)
Strand
(no.)
Size
AWG
or
MCM
Approx. Net
Weight
per 1000 feet (lbs.)
4
0
0

H
z

C
A
B
L
E
*Ampacity is derated due to the fact that this is a multi-conductor assembly.
NOTE: The data shown is approximate and subject to standard industry tolerances. 2011
SPLEX4/7
SPLEX2/7
SPLEX1/7
SPLEX1/07
SPLEX2/07
SPLEX3/07
SPLEX4/07
SPLEX250/7
SPLEX350/7
SPLEX500/7
Part
Number
T
w
i
s
t
e
d

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
27
Made in the USA
Description:
The cable conductor shall consist of soft drawn copper, stranded,
insulated with cross-linked polyethylene, type USE-2. These con-
ductors are rated for 600 volts and carry a maximum temperature
rating of 90 C wet/dry. The conductors are twisted in a six around
one construction, commonly known as planetary wrap. Conduc-
tors will be striped per customer specications.
Application:
400 Hz cable (6 around 1 USE-2) is used as a power source for
mainframe computers, TV and radio station output power supply,
aircraft ground power supplies at airport terminals, plus many other
applications.
400 Hz Cable
XLP USE-2 or RHH/RHW-2
Standards:
UL44/UL854, ICEA S-95-658/NEMA WC-70
ASTM B3, B8
RoHS Compliant
Features:
Lowers overall impedance of circuit, using multiple smaller
conductors, which minimize voltage drop; a critical factor for 400
Hz computer power.
Readily available in the commonly used sizes with minimal
delivery times.
*Has the same ratings and is handled in the same manner as
any building wire.
Geometrically balanced construction allows for a minimum of
phase to phase unbalance.
The cabled conductors allow for a single, easy, conduit pull.
4 7 60 1.056 1,093
2 7 60 1.236 1,671
1 19 80 1.443 2,171
1/0 19 80 1.560 2,708
2/0 19 80 1.692 3,354
3/0 19 80 1.842 4,163
4/0 19 80 2.010 5,177
250 37 95 2.295 6,180
350 37 95 2.613 8,493
500 37 95 3.009 11,931


2
K
V

R
H
H

/

R
H
W
-
2
Approx.
Diameter
(inch)
Insulation
Thickness
(mils)
Strand
(no.)
Size
AWG
or
MCM
Approx. Net
Weight
per 1000 feet (lbs.)
4
0
0

H
z

C
A
B
L
E
*Ampacity is derated due to the fact that this is a multi-conductor assembly.
NOTE: The data shown is approximate and subject to standard industry tolerances. 2011
SPLEX4/7U
SPLEX2/7U
SPLEX1/7U
SPLEX1/07U
SPLEX2/07U
SPLEX3/07U
SPLEX4/07U
SPLEX250/7U
SPLEX350/7U
SPLEX500/7U
Part
Number
T
w
i
s
t
e
d

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
28
Made in the USA
Preassembled
Aerial Cable
600 Volt
Copper XHHW-2
Standard:
ICEA S-95-658/NEMA WC-70
Single CDRS are UL 44 Listed
RoHS Compliant
NOTE: Optional constructions include: galvanized or stainless
steel messengers, PVC coated copper, stainless steel strap.
Description:
3 or 4 conductors, stranded, bare annealed copper, insulated
with heat and moisture resistant cross-linked polyethylene. The
conductors shall be cabled with a left hand lay and a messenger
of 30% EHS copperweld shall be laid parallel and bound with a at
bare copper binding strap. Available with aluminum conductors.
8 7 45 1/4 7 # 12 .751 425 66
6 7 45 1/4 7 # 12 .832 527 89
4 7 45 1/4 7 # 12 .936 690 117
2 7 45 1/4 7 # 12 1.065 939 158
1 19 55 1/4 7 # 12 1.171 1,131 185
1/0 19 55 1/4 7 # 12 1.255 1,357 214
2/0 19 55 5/16 7 # 10 1.420 1,711 247
3/0 19 55 5/16 7 # 10 1.521 2,056 287
4/0 19 55 3/8 7 # 8 1.721 2,613 335
250 37 65 3/8 7 # 8 1.904 3,043 374
350 37 65 1/2 7 # 6 2.234 4,231 464
500 37 65 9/16 7 # 5 2.582 5,845 580
750 61 80 9/16 7 # 5 3.041 8,375 747
Size
AWG
or
MCM
Strand
(no.)

Insulation
Thickness
(mils)
Approx.
Diameter
Overall
(inch)
Approx.
Net Wt.
per 1000 ft.
(lbs.)
Ampacity*
(40 C
Ambient)
Messenger Size **
(inch) (strand)
T
H
R
E
E

C
O
N
D
U
C
T
O
R
F
O
U
R

C
O
N
D
U
C
T
O
R
*Per NEC 310-20.
**Messenger size based on 150' span with sag of 2.5 ft.
NOTE: The data shown is approximate and subject to standard industry tolerances.
NOTE: 4-Conductor ampacity assumes all four conductors are hot. If three are hot and one is a neutral, use the three conductor ampacity.
2011
8 7 45 1/4 7 # 12 .812 491 53
6 7 45 1/4 7 # 12 .904 627 71
4 7 45 1/4 7 # 12 1.019 843 94
2 7 45 1/4 7 # 12 1.164 1,174 126
1 19 55 1/4 7 # 12 1.283 1,429 148
1/0 19 55 5/16 7 # 10 1.441 1,808 171
2/0 19 55 5/16 7 # 10 1.554 2,175 198
3/0 19 55 3/8 7 # 8 1.747 2,759 230
4/0 19 55 3/8 7 # 8 1.882 3,335 268
250 37 65 1/2 7 # 6 2.188 4,102 299
350 37 65 1/2 7 # 6 2.444 5,423 371
500 37 65 9/16 7 # 5 2.827 7,526 464
750 61 80 9/16 7 # 5 3.342 10,895 598
AER1/4C8/3
AER1/4C6/3
AER1/4C4/3
AER1/4C2/3
AER1/4C1/3
AER1/4C1/03
AER5/16C2/03
AER5/16C3/03
AER3/8C4/03
AER3/8C250/3
AER1/2C350/3
AER9/16C500/3
AER9/16C750/3
Part
Number
AER1/4C8/4
AER1/4C6/4
AER1/4C4/4
AER1/4C2/4
AER1/4C1/4
AER5/16C1/04
AER5/16C2/04
AER3/8C3/04
AER3/8C4/04
AER1/2C250/4
AER1/2C350/4
AER9/16C500/4
AER9/16C750/4
T
w
i
s
t
e
d

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
29
Made in the USA
Preassembled
Aerial Cable
2.4kV Nonshielded
Copper EPR
Standards:
ICEA S-96-659/NEMA WC-71
Single CDRS are UL-1072 Listed
RoHS Compliant
NOTE: Optional constructions include: galvanized or stainless
steel messengers, stainless steel strap, PVC coated strap.
Description:
Class B stranded copper, extruded conductor shield, insulated with
heat and moisture resistant EPR.
The conductors shall be cabled with a left hand lay and laid parallel
to a 30% EHS copperweld messenger then bound with a at cop-
per binding strap.
Applications:
Where NEC jurisdiction applies: 2,400 volt nonshielded
power cable, Type MV-90, for conductor temperatures not
exceeding 90 C.

8 7 125 1/4 7 # 12 1.50 774 66
6 7 125 1/4 7 # 12 1.58 898 88
4 7 125 1/4 7 # 12 1.69 1,100 115
2 7 125 1/4 7 # 12 1.82 1,393 154
1/0 19 125 1/4 7 # 12 1.97 1,856 205
2/0 19 125 5/16 7 # 10 2.14 2,242 240
4/0 19 125 3/8 7 # 8 2.57 3,490 320
250 37 140 3/8 7 # 8 2.74 3,907 355
350 37 140 1/2 7 # 6 3.06 5,178 440
500 37 140 9/16 7 # 5 3.40 6,898 545
750 61 155 9/16 7 # 5 3.91 9,786 685
Strand
(no.)
Approx.
Diameter
Overall
(inch)
Approx.
Net Wt.
per 1000 ft.
(lbs.)
Ampacity*
(40 C
Ambient)
Messenger Size **
Size
AWG
or
MCM

Insulation
Thickness
(mils) (inch) (strand)
N
O
N
-
S
H
I
E
L
D
E
D
*Per NEC 310-71
**Messenger size based on 150' span with sag of 2.5 ft.

NOTE: The data shown is approximate and subject to standard industry tolerances. 2011

AR1/4C2.4K8/3E
AR1/4C2.4K6/3E
AR1/4C2.4K4/3E
AR1/4C2.4K2/3E
AR1/4C2.4K1/03E
AR5/16C2.4K2/03E
AR3/8C2.4K4/03E
AR3/8C2.4K250/3E
AR1/2C2.4K350/3E
AR9/16C2.4K500/3E
AR9/16C2.4K750/3E
Part
Number
T
w
i
s
t
e
d

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
30
Made in the USA
Preassembled
Aerial Cable
5kV Shielded
Copper EPR
Standards:
ICEA S-93-639/NEMA WC-74
Single CDRS are UL-1072 Listed
RoHS Compliant
NOTE: Optional constructions include: galvanized or stainless
steel messengers, PVC coated stainless steel strap.
Description:
Class B stranded copper, extruded conductor shield, insulated
with heat and moisture resistant EPR, semi-conducting insulation
shield, copper shield (stranded or tape), overall PVC jacket.
The conductors shall be cabled with a left hand lay and laid paral-
lel to a 30% EHS copperweld messenger then bound with a at
PVC coated copper binding strap.
6 7 115 60 5/16 7#10 1.76 1,250 88
4 7 115 60 5/16 7#10 1.88 1,500 115
2 7 115 60 5/16 7#10 1.99 1,795 154
1/0 19 115 80 5/16 7#10 2.27 2,418 205
2/0 19 115 80 3/8 7# 8 2.46 2,883 240
4/0 19 115 80 1/2 7# 6 2.75 3,975 320
250 37 115 80 9/16 7# 5 2.94 4,592 355
350 37 115 80 9/16 7# 5 3.16 5,687 440
500 37 115 80 9/16 7# 5 3.48 7,382 545
750 61 115 80 9/16 7# 5 3.89 10,137 685
Messenger Size **
(strand) (inch)
Approx.
Diameter
Overall
(inch)
Strand
(no.)
Size
AWG
or
MCM
Jacket
Thickness
(mils)
Approx.
Net Wt.
per 1000 ft.
(lbs.)
Ampacity*
(40 C
Ambient)
S
H
I
E
L
D
E
D
Insulation
Thickness
(mils)
*Per NEC 310-71
**Messenger size based on 150' span with sag of 2.5 ft.
NOTE: The data shown is approximate and subject to standard industry tolerances. 2011
AR5/16C5KS6/3E
AR5/16C5KS4/3E
AR5/16C5KS2/3E
AR5/16C5KS1/03E
AR3/8C5KS2/03E
AR1/2C5KS4/03E
AR9/16C5KS250/3E
AR9/16C5KS350/3E
AR9/16C5KS500/3E
AR9/16C5KS750/3E
Part
Number
T
w
i
s
t
e
d

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
31
Made in the USA
Standards:
ICEA S-93-639/NEMA WC-74
Single CDRS are UL 1072 Listed
RoHS Compliant
NOTE: Optional constructions include: galvanized or stainless
steel messengers, PVC coated, stainless steel strap.
Preassembled
Aerial Cable
15 kV MV-105
133% 15,000 Volt
Copper EPR
Description:
3 copper conductors, Class B strand, annealed copper, heat and
moisture resistant ethylene polypropylene rubber, semi-conducting
insulation shield, (wire or tape) conductor shield, type EPR, 133%
insulation level, polyvinyl chloride jacket. The conductors shall be
cabled with a left hand lay and laid parallel to the 30% EHS cop-
perweld messenger, bound with a rounded-edge at PVC coated
copper binding strap.
Size
AWG
or
MCM
Strand
(no.)

Insulation
Thickness
(mils)
Approx.
Net Wt.
per 1000 ft.
(lbs.)
(inch) (strand)
Jacket
Thickness
(mils)
Messenger Size **
1
3
3
%

E
P
R

I
N
S
U
L
A
T
I
O
N
2 7 220 80 3/8 7 # 8 2.63 2,599 185
1 19 220 80 1/2 7 # 6 2.82 3,029 210
1/0 19 220 80 1/2 7 # 6 2.93 3,370 240
2/0 19 220 80 1/2 7 # 6 3.03 3,756 275
4/0 19 220 80 9/16 7 # 5 3.27 4,758 360
250 37 220 80 9/16 7 # 5 3.44 5,346 400
350 37 220 80 9/16 7 # 5 3.65 6,502 490
500 37 220 80 9/16 7 # 5 3.93 8,211 600
750 61 220 110 9/16 7 # 5 4.47 11,353 745
Ampacity*
(40 C
Ambient)
Approx.
Diameter
Overall
(inch)
*Per NEC 310-71
**Messenger size based on 150' span with sag of 2.5 ft.
NOTE: The data shown is approximate and subject to standard industry tolerances. 2011
AR3/8C15K2/3E
AR1/2C15K1/3E
AR1/2C15K1/03E
AR1/2C15K2/03E
AR9/16C15K4/03E
AR9/16C15K250/3E
AR9/16C15K350/3E
AR9/16C15K500/3E
AR9/16C15K750/3E
Part
Number
T
r
a
y

a
n
d

P
o
w
e
r

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
32
Made in the USA
Description:
3 conductors, stranded, insulated with heat and moisture
resistant cross-linked polyethylene (type XHHW-2), phase
identied. Cabled together with bare copper ground con-
ductor. Cable core covered with berglass binder tape and
overall ame and sunlight resistant grey PVC jacket. Surface
printed. Jacket available in colors.
Standards:
UL 44
UL 854
Temperature Rating: 90 C Wet/Dry
Color Code: Black and numbered
RoHS Compliant
SER Copper Cable
XHHW-2 PVC
600 Volt Copper XHHW-2
Approx.
Diameter
Overall (inch)
Approx. Net Wt.
per 1000 ft.
(lbs.)
PVC Jacket
Thickness
(mils)
Grounding
Conductor
(AWG)
Insulation
Thickness
(mils)
Strand
(no.)
Size
Ampacity*
(30 C
Ambient)
90CWet/Dry
T
H
R
E
E

C
O
N
D
U
C
T
O
R
* PER NEC TABLE 310-16
NOTE: The data shown is approximate and subject to standard industry tolerances. 2011
SER6666 7 45 1- #6 30 .746 432 75
SER4446 7 45 1- #6 30 .823 597 95
SER3335 7 45 1- #5 30 .923 716 110
SER2224 7 45 1- #4 30 .974 901 130
SER1113 19 55 1- #3 30 1.090 1,122 150
SER1/01/01/02 19 55 1- #2 30 1.189 1,387 170
SER2/02/02/01 19 55 1- #1 30 1.293 1,719 195
SER3/03/03/01/0 19 55 1- 1/0 30 1.417 2,138 225
SER4/04/04/02/0 19 55 1- 2/0 30 1.557 2,661 260

SER6/3G6
SER4/3G6
SER3/3G5
SER2/3G4
SER1/3G3
SER1/03G2
SER2/03G1
SER3/03G1/0
SER4/03G2/0
Part
Number
T
r
a
y

a
n
d

P
o
w
e
r

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
33
Made in the USA
SEU Copper Cable
XHHW-2 /PVC
600 Volt Copper XHHW-2
Description:
2 conductors, stranded, insulated with heat and moisture
resistant cross-linked polyethylene (type XHHW-2), phase
identied. Cabled together with Served bare copper ground
conductor. Cable core covered with berglass binder tape
and overall ame and sunlight resistant grey PVC jacket. Sur-
face printed. Jacket available in colors.
Standards:
UL 44
UL 854
Temperature Rating: 90 C Wet/Dry
Color Code: Black and numbered (Except #8 - K2)
RoHS Compliant
Diameter
Overall
(inch)
Approx. Net Wt.
per 1000 ft.
(lbs.)
Jacket
Thickness
(mils)
Grounding
Conductor
(AWG)
Insulation
Thickness
(mils)
Strand
(no.)
Size
Ampacity*
(30 C
Ambient)
90CWet/Dry
T
W
O

C
O
N
D
U
C
T
O
R
* PER NEC TABLE 310-16
NOTE: The data shown is approximate and subject to standard industry tolerances. 2011
SEU888 7 45 1- #8 30 .670 226 55
SEU668 7 45 1- #8 30 .750 300 75
SEU666 7 45 1- #6 30 .770 330 75
SEU446 7 45 1- #6 30 .870 442 95
SEU444 7 45 1- #4 30 .900 492 95
SEU334 7 45 1- #4 30 .960 560 110
SEU333 7 45 1- #3 30 .970 595 110
SEU224 7 45 1- #4 30 1.020 664 130
SEU222 7 45 1- #2 30 1.060 744 130
SEU111 19 55 1- #1 30 1.100 920 150
SEU1/01/01/0 19 55 1- 1/0 30 1.200 1,238 170
SEU2/02/02/0 19 55 1- 2/0 30 1.320 1,413 195
SEU3/03/03/0 19 55 1- 3/0 30 1.420 1,757 225
SEU4/04/04/04/0 19 55 1- 4/0 30 1.61 2,175 260
SEU8/2G8
SEU6/2G8
SEU6/2G6
SEU4/2G6
SEU4/2G4
SEU3/2G4
SEU3/2G3
SEU2/2G4
SEU2/2G2
SEU1/2G1
SEU1/02G1/0
SEU2/02G2/0
SEU3/02G3/0
SEU4/02G4/0
Part
Number
T
r
a
y

a
n
d

P
o
w
e
r

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
34
Made in the USA
Part
Number
Number
of Conductors
Overall Jacket
(mils)
Nominal Diameter
(inches)
Approx. Net Weight
(lb/1000)
TCFFH16/2FL 2 (at) 45 .328 x .209 49
TCFFH16/3 3 45 .347 63
TCFFH16/4 4 45 .378 79
TCFFH16/5 5 45 .412 94
TCFFH16/7 7 45 .479 126
TCFFH16/9 9 60 .588 174
TCFFH16/12 12 60 .652 219
TCFFH16/19 19 60 .744 318
TCFFH16/25 25 80 .877 465
TCFFH16/37 37 80 1,032 653
TCXH14/2FL 2 (at) 45 .36 X .22 61
TCXH14/3 3 45 .376 80
TCXH14/4 4 45 .410 101
TCXH14/5 5 45 .448 121
TCXH14/7 7 60 .554 179
TCXH14/9 9 60 .636 223
TCXH14/12 12 60 .707 298
TCXH14/19 19 80 .859 472
TCXH14/25 25 80 .952 600
TCXH14/37 37 80 1.13 850
TCXH12/2FL 2 (at) 45 .40 X .24 82
TCXH12/3 3 45 .416 109
TCXH12/4 4 45 .456 138
TCXH12/5 5 45 .499 168
TCXH12/7 7 60 .611 255
TCXH12/9 9 60 .704 321
TCXH12/12 12 60 .786 411
TCXH12/19 19 80 .954 652
TCXH12/25 25 80 1.060 833
TCXH12/37 37 80 1.257 1,190
TCXH10/2FL 2 (at) 45 .44 X .27 115
TCXH10/3 3 45 .469 158
TCXH10/4 4 60 .545 203
TCXH10/5 5 60 .595 264
TCXH10/7 7 60 .684 357
TCXH10/9 9 60 .793 451
TCXH10/12 12 80 .927 618
TCXH10/19 19 80 1.076 925
TCXH10/25 25 80 1.20 1,191
TCXH10/37 37 80 1.43 1,715
Tray Cable
XHHW-2 / PVC
UL Type TC
600 Volt/Multi-Conductor
Description:
Conductors, Class B stranded, annealed copper, insulated with 30
mils heat and moisture resistant cross-linked polyethylene (Type
XHHW-2,VW-1), phase identied. Cabled together with llers and
binders (where necessary). Overall ame and sunlight resistant
black PVC jacket. Surface printed. Jacket available in colors.
Standards:
UL 1277, IMSA 19-1
Flame Rated: IEEE-383 (70,000 BTU),
ICEA T-29-520 (210,000 BTU),
IEEE 1202/CSA FT-4, Two-hour Firewall rated,
Sunlight Resistant for CT Use; Direct Burial,
Oil Resistant II Jacket
Color Code: K-2 (Optional color codes available) (#16 Black and
numbered)
Conductors rated 90 Wet/Dry
ICEA S-95-658/NEMA WC-70
Conductors rated VW-1 (#14-#10),
Exposed Runs rated (TC-ER)
Features:
Suitable for use in NEC Hazardous locations:
Class I, Div. 2; Class II, Div. 2; RoHS Compliant
#
1
6

A
W
G
#
1
4

A
W
G
#
1
2

A
W
G
#
1
0

A
W
G
NOTE: The data shown is approximate and subject to standard industry tolerances.
NOTE: #16 AWG per UL 66 Fixture Wire type FFH-2 2011
T
r
a
y

a
n
d

P
o
w
e
r

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
35
Made in the USA
14 7 30 1-#14 45 .412 101 25
14 7 30 1-#14 45 .414 106 25
12 7 30 1-#12 45 .452 138 30
12 7 30 1-#12 45 .456 144 30
10 7 30 1-#10 45 .505 196 40
10 7 30 1-#10 45 .515 203 40
8 7 45 1-#10 60 .665 306 55
8 7 45 1-#10 60 .690 315 55
6 7 45 1- #8 60 .746 446 75
6 7 45 1- #8 60 .802 480 75
4 7 45 1- #8 80 .890 657 95
3 7 45 1- #6 80 .950 809 110
2 7 45 1- #6 80 1.019 963 130
1 19 55 1- #6 80 1.125 1,181 150
1/0 19 55 1- #6 80 1.209 1,421 170
2/0 19 55 1- #6 80 1.310 1,724 195
3/0 19 55 1- #4 80 1.411 2,142 225
4/0 19 55 1- #4 80 1.532 2,611 260
250 37 65 1- #4 110 1.775 3,185 290
300 37 65 1- #3 110 1.891 3,756 320
350 37 65 1- #3 110 2.004 4,296 350
400 37 65 1- #3 110 2.105 4,824 380
500 37 65 1- #2 110 2.292 5,933 430
600 61 80 1- #2 110 2.525 7,091 475
750 61 80 1- #1 140 2.811 8,880 535
Approx.
Diameter
Overall (inch)
Approx. Net Wt.
per 1000 ft.
(lbs.)
PVC Jacket
Thickness
(mils)
Grounding
Conductor
(AWG)
Insulation
Thickness
(mils)
Strand
(no.)
Size
AWG
or MCM
Description:
3 conductors, stranded, insulated with heat and moisture resistant cross-linked
polyethylene (type XHHW-2), phase identied. Cabled together with llers
(where necessary) and bare copper ground conductor. Cable core covered
with binder tape, and overall ame and sunlight resistant black PVC jacket.
Surface printed. Jacket available in colors. Also available with aluminum
conductors.
Features:
Suitable for use in NEC Hazardous locations: Class I, Div. 2; Class II, Div. 2;
RoHS Compliant
Ampacity*
(30 C
Ambient)
90CWet/Dry
T
H
R
E
E

C
O
N
D
U
C
T
O
R
* PER NEC TABLE 310-16 ** ER Rated all sizes with green ground or with no ground.
The overcurrent protection for items marked with an obelisk () shall not exceed 15 amps for 14 AWG, 20 amps for 12 AWG and 30 amps for 10
AWG per NEC 310-16 footnote.
NOTE: The data shown is approximate and subject to standard industry tolerances.
2011
Tray Cable
XHHW-2/PVC
UL Type TC
600 Volt Copper XHHW-2
Standards:
UL 1277, IMSA 19-1
Flame Rated: IEEE-383 (70,000 BTU),
ICEA T-29-520 (210,000 BTU) on 1/0 and larger: Available upon request
IEEE 1202/CSA FT-4: Available upon request
Two-hour Firewall rated, (2/0 AWG and smaller)
Sunlight Resistant for CT Use; Direct Burial,
Oil Resistant II Jacket
Color Code: Black and numbered(#14 - #8 AWG K-2 (Optional color
codes available)
Conductors rated 90 C Wet/Dry
ICEA S-95-658/NEMA WC-70
Exposed runs rated #4 AWG and larger (TC-ER)**
TCXH14/3G
TCXH14/3GG
TCXH12/3G
TCXH12/3GG
TCXH10/3G
TCXH10/3GG
TCXH8/3G
TCXH8/3GG
TCXH6/3G
TCXH6/3GG
TCXH4/3G
TCXH3/3G
TCXH2/3G
TCXH1/3G
TCXH1/03G
TCXH2/03G
TCXH3/03G
TCXH4/03G
TCXH250/3G
TCXH300/3G
TCXH350/3G
TCXH400/3G
TCXH500/3G
TCXH600/3G
TCXH750/3G
Part
Number
T
r
a
y

a
n
d

P
o
w
e
r

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
36
Made in the USA
14 7 30 1-#14 45 .448 127 20
14 7 30 1-#14 45 .446 123 20
12 7 30 1-#12 45 .492 169 24
12 7 30 1-#12 45 .499 175 24
10 7 30 1-#10 60 .581 256 32
10 7 30 1-#10 60 .595 264 32
8 7 45 1-#10 60 .726 381 44
8 7 45 1-#10 60 .757 390 44
6 7 45 1- #8 60 .818 554 60
6 7 45 1- #8 60 .920 628 60
4 7 45 1- #8 80 .973 823 76
3 7 45 1- #6 80 1.041 1,013 88
2 7 45 1- #6 80 1.118 1,215 104
1 19 55 1- #6 80 1.237 1,498 120
1/0 19 55 1- #6 80 1.331 1,814 136
2/0 19 55 1- #6 80 1.444 2,210 156
3/0 19 55 1- #4 80 1.558 2,745 180
4/0 19 55 1- #4 110 1.755 3,459 208
250 37 65 1- #4 110 1.958 4,089 232
300 37 65 1- #3 110 2.088 4,829 256
350 37 65 1- #3 110 2.214 5,538 280
400 37 65 1- #3 110 2.327 6,238 304
500 37 65 1- #2 110 2.537 7,675 344
600 61 80 1- #2 140 2.858 9,353 380
750 61 80 1- #1 140 3.112 11,497 428
Approx.
Diameter
Overall (inch)
Approx. Net Wt.
per 1000 ft.
(lbs.)
PVC Jacket
Thickness
(mils)
Grounding
Conductor
(AWG)
Insulation
Thickness
(mils)
Strand
(no.)
Size
AWG
or MCM
Description:
4 conductors, stranded, insulated with heat and moisture resistant cross-linked
polyethylene (type XHHW-2), phase identied. Cabled together with llers
(where necessary) and bare copper ground conductor. Cable core covered
with binder tape, and overall ame and sunlight resistant black PVC jacket.
Surface printed. Jacket available in colors. Also available with aluminum
conductors.
Features:
Suitable for use in NEC Hazardous locations: Class I, Div. 2; Class II, Div. 2;
RoHS Compliant
Ampacity*
(30 C
Ambient)
90CWet/Dry
F
O
U
R

C
O
N
D
U
C
T
O
R
* PER NEC TABLE 310-16 ** ER Rated all sizes with green ground or with no ground.
The overcurrent protection for items marked with an obelisk () shall not exceed 15 amps for 14 AWG, 20 amps for 12 AWG and 30 amps for 10
AWG per NEC 310-16 footnote.
NOTE: The data shown is approximate and subject to standard industry tolerances.
NOTE: 4-Conductor ampacity assumes all four conductors are hot. If three are hot and one is a neutral, use the three conductor ampacity. 2011
Tray Cable
XHHW-2/PVC
UL Type TC
600 Volt Copper XHHW-2
Standards:
UL 1277, IMSA 19-1
Flame Rated: IEEE-383 (70,000 BTU),
ICEA T-29-520 (210,000 BTU) on 1/0 and larger: Available upon request
IEEE 1202/CSA FT-4: Available upon request
Two-hour Firewall rated, (2/0 AWG and smaller)
Sunlight Resistant for CT Use; Direct Burial,
Oil Resistant II Jacket
Color Code: Black and numbered (#14 - #8 AWG K-2 (Optional color
codes available)
Conductors rated 90 C Wet/Dry
ICEA S-95-658/NEMA WC-70
Exposed runs rated #4 AWG and larger (TC-ER)**
TCXH14/4G
TCXH14/4GG
TCXH12/4G
TCXH12/4GG
TCXH10/4G
TCXH10/4GG
TCXH8/4G
TCXH8/4GG
TCXH6/4G
TCXH6/4GG
TCXH4/4G
TCXH3/4G
TCXH2/4G
TCXH1/4G
TCXH1/04G
TCXH2/04G
TCXH3/04G
TCXH4/04G
TCXH250/4G
TCXH300/4G
TCXH350/4G
TCXH400/4G
TCXH500/4G
TCXH600/4G
TCXH750/4G
Part
Number
T
r
a
y

a
n
d

P
o
w
e
r

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
37
Made in the USA
Tray Cable
FR-XLP/CPE
UL Type TC
600 Volt/Multi-Conductor
Standards:
UL 1277, IMSA 19-1
Flame Rated: IEEE 383 (70,000 BTU), T-29-520 (210,000 BTU),
IEEE 1202 / CSA FT-4
Two-hour Firewall rated
Sunlight Resistant for CT Use; Direct Burial,
Oil Resistant II Jacket
Color Code: K-2 (Optional color codes available)
Conductors rated 90 Wet/Dry
ICEA S-95-658/NEMA WC-70
Exposed runs rated (TC-ER)
Conductors rated VW-1 (#14 - #10)
Description:
Conductors, Class B stranded, annealed copper, insulated with 30
mils heat and moisture resistant cross-linked polyethylene (Type
XHHW-2 VW-1,), phase identied. Cabled together with llers and
binders (where necessary). Overall ame and sunlight resistant
black CPE jacket. Surface printed. Available with tinned conductors.
Features:
Suitable for use in NEC Hazardous locations:
Class I, Div. 2; Class II, Div. 2; RoHS compliant
Number
of
Conductors
Overall
Jacket
(Mils)
Approximate
Net Weight
(lbs./1000)
2 45 .333 52
3 45 .347 67
4 45 .378 83
5 45 .412 100
7 45 .448 130
9 60 .588 185
12 60 .652 233
19 60 .753 341
25 80 .877 465
37 80 1.032 653
2 45 .396 68
3 45 .412 88
4 45 .446 110
5 45 .484 132
7 60 .554 188
9 60 .636 235
12 60 .710 299
19 80 .860 474
25 80 .952 600
37 80 1.130 850
2 45 .434 89
3 45 .452 118
4 45 .492 148
5 60 .565 195
7 60 .611 255
9 60 .704 320
12 60 .786 417
19 80 .954 653
25 80 1.060 833
37 80 1.257 1190
2 45 .478 120
3 45 .505 163
4 60 .581 224
5 60 .631 270
7 60 .684 358
9 60 .793 452
12 80 .927 620
19 80 1.080 928
25 80 1.200 1191
37 80 1.430 1715
NOTE: The data shown is approximate and subject to standard industry tolerances.
NOTE: #16 AWG per UL 66 Fixture Wire type FFH-2 2011
#
1
0

A
W
G













#
1
2

A
W
G













#
1
4

A
W
G













#
1
6

A
W
G















Nominal
Diameter
(inches)
Part
Number
TCCPE16/2FL
TCCPE16/3
TCCPE16/4
TCCPE16/5
TCCPE16/7
TCCPE16/9
TCCPE16/12
TCCPE16/19
TCCPE16/25
TCCPE16/37
TCCPE14/2FL
TCCPE14/3
TCCPE14/4
TCCPE14/5
TCCPE14/7
TCCPE14/9
TCCPE14/12
TCCPE14/19
TCCPE14/25
TCCPE14/37
TCCPE12/2FL
TCCPE12/3
TCCPE12/4
TCCPE12/5
TCCPE12/7
TCCPE12/9
TCCPE12/12
TCCPE12/19
TCCPE12/25
TCCPE12/37
TCCPE10/2FL
TCCPE10/3
TCCPE10/4
TCCPE10/5
TCCPE10/7
TCCPE10/9
TCCPE10/10
TCCPE10/19
TCCPE10/25
TCCPE10/37
T
r
a
y

a
n
d

P
o
w
e
r

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
38
Made in the USA
14 7 30 1-#14 45 .42 102 25
14 7 30 1-#14 45 .42 108 25
12 7 30 1-#12 45 .46 139 30
12 7 30 1-#12 45 .46 147 30
10 7 30 1-#10 45 .51 196 40
10 7 30 1-#10 45 .52 206 40
8 7 45 1-#10 60 .67 307 55
8 7 45 1-#10 60 .69 321 55
6 7 45 1- #8 60 .75 459 75
6 7 45 1- #8 60 .81 487 75
4 7 45 1- #8 80 .89 672 95
3 7 45 1- #6 80 .96 813 110
2 7 45 1- #6 80 1.02 982 130
1 19 55 1- #6 80 1.15 1217 150
1/0 19 55 1- #6 80 1.24 1462 170
2/0 19 55 1- #6 80 1.34 1768 195
3/0 19 55 1- #4 80 1.45 2193 225
4/0 19 55 1- #4 80 1.57 2668 260
250 37 65 1- #4 110 1.78 3236 290
350 37 65 1- #3 110 2.01 4356 350
500 37 65 1- #2 110 2.29 6003 430
600 61 80 1- #2 110 2.54 7112 475
750 61 80 1- #1 140 2.82 8986 535
Tray Cable
FR-XLP/CPE
UL Type TC
600 Volt Copper XHHW-2
* PER NEC TABLE 310-16 ** ER Rated all sizes with green ground or with no ground.
The overcurrent protection for items marked with an obelisk () shall not exceed 15 amps for 14 AWG, 20 amps for 12 AWG and 30 amps for 10
AWG per NEC 310-16 footnote.
NOTE: The data shown is approximate and subject to standard industry tolerances. 2011
Standards:
UL 1277, IMSA 19-1
Flame Rated: IEEE 383 (70,000 BTU), T-29-520 (210,000 BTU):
Available upon request, IEEE 1202 / CSA FT-4: Available upon request
Sunlight Resistant for CT Use; Direct Burial,
Oil Resistant II Jacket
Color Code: Black and numbered (#14 - #8 AWG K-2 (Optional color
codes available)
Conductors rated 90 C Wet/Dry
ICEA S-95-658/NEMA WC-70
Exposed runs rated #4 AWG and larger (TC-ER)**
Description:
3 conductors, stranded, insulated with heat and moisture resis-
tant crosslinked polyethylene (type XHHW-2), phase identied.
Cabled together with llers (where necessary) and bare copper
ground conductor. Cable core covered with binder tape, and over-
all ame and sunlight resistant black CPE jacket. Surface printed.
Jacket available in colors. Also available with tinned conductors.
Approx.
Diameter
Overall (inch)
Approx. Net Wt.
per 1000 ft.
(lbs.)
Jacket
Thickness
(mils)
Grounding
Conductor
(AWG)
Insulation
Thickness
(mils)
Strand
(no.)
Size
AWG
or MCM
Ampacity*
(30 C
Ambient)
90CWet/Dry
T
H
R
E
E

C
O
N
D
U
C
T
O
R
Features:
Suitable for use in NEC Hazardous locations: Class I, Div. 2; Class
II, Div. 2, RoHS compliant
TCCPE14/3G
TCCPE14/3GG
TCCPE12/3G
TCCPE12/3GG
TCCPE10/3G
TCCPE10/3GG
TCCPE8/3G
TCCPE8/3GG
TCCPE6/3G
TCCPE6/3GG
TCCPE4/3G
TCCPE3/3G
TCCPE2/3G
TCCPE1/3G
TCCPE1/03G
TCCPE2/03G
TCCPE3/03G
TCCPE4/03G
TCCPE250/3G
TCCPE350/3G
TCCPE500/3G
TCCPE600/3G
TCCPE750/3G

Part
Number
T
r
a
y

a
n
d

P
o
w
e
r

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
39
Made in the USA
14 7 30 1-#14 45 .45 123 20
14 7 30 1-#14 45 .45 130 20
12 7 30 1-#12 45 .49 169 24
12 7 30 1-#12 45 .50 178 24
10 7 30 1-#10 60 .58 257 32
10 7 30 1-#10 60 .60 269 32
8 7 45 1-#10 60 .75 390 44
8 7 45 1-#10 60 .76 397 44
6 7 45 1- #8 60 .89 618 60
6 7 45 1- #8 60 .92 638 60
4 7 45 1- #8 80 .99 850 76
3 7 45 1- #6 80 1.08 1038 88
2 7 45 1- #6 80 1.15 1254 104
1 19 55 1- #6 80 1.25 1513 120
1/0 19 55 1- #6 80 1.34 1830 136
2/0 19 55 1- #6 80 1.45 2225 156
3/0 19 55 1- #4 80 1.57 2764 180
4/0 19 55 1- #4 110 1.77 3480 208
250 37 65 1- #4 110 1.96 4158 232
350 37 65 1- #3 110 2.22 5618 280
500 37 65 1- #2 110 2.54 7769 344
600 61 80 1- #2 140 2.87 9378 380
750 61 80 1- #1 140 3.12 11639 428
Tray Cable
FR-XLP/CPE
UL Type TC
600 Volt Copper XHHW-2
* PER NEC TABLE 310-16 ** ER Rated all sizes with green ground or with no ground.
The overcurrent protection for items marked with an obelisk () shall not exceed 15 amps for 14 AWG, 20 amps for 12 AWG and 30 amps for 10
AWG per NEC 310-16 footnote.
NOTE: The data shown is approximate and subject to standard industry tolerances.
NOTE: 4-Conductor ampacity assumes all four conductors are hot. If three are hot and one is a neutral, use the three conductor ampacity. 2011
Standards:
UL 1277, IMSA 19-1
Flame Rated: IEEE 383 (70,000 BTU), T-29-520 (210,000 BTU):
Available upon request, IEEE 1202 / CSA FT-4: Available upon request
Sunlight Resistant for CT Use; Direct Burial,
Oil Resistant II Jacket
Color Code: Black and numbered (#14 - #8 AWG K-2 (Optional color
codes available)
Conductors rated 90 C Wet/Dry
ICEA S-95-658/NEMA WC-70
Exposed runs rated #4 AWG and larger (TC-ER)**
Description:
4 conductors, stranded, insulated with heat and moisture resis-
tant crosslinked polyethylene (type XHHW-2), phase identied.
Cabled together with llers (where necessary) and bare copper
ground conductor. Cable core covered with binder tape, and over-
all ame and sunlight resistant black CPE jacket. Surface printed.
Jacket available in colors. Also available with tinned conductors.
Approx.
Diameter
Overall (inch)
Approx. Net Wt.
per 1000 ft.
(lbs.)
Jacket
Thickness
(mils)
Grounding
Conductor
(AWG)
Insulation
Thickness
(mils)
Strand
(no.)
Size
AWG
or MCM
Ampacity*
(30 C
Ambient)
90CWet/Dry
F
O
U
R

C
O
N
D
U
C
T
O
R
Features:
Suitable for use in NEC Hazardous locations: Class I, Div. 2; Class
II, Div. 2; RoHS compliant
TCCPE14/4G
TCCPE14/4GG
TCCPE12/4G
TCCPE12/4GG
TCCPE10/4G
TCCPE10/4GG
TCCPE8/4G
TCCPE8/4GG
TCCPE6/4G
TCCPE6/4GG
TCCPE4/4G
TCCPE3/4G
TCCPE2/4G
TCCPE1/4G
TCCPE1/04G
TCCPE2/04G
TCCPE3/04G
TCCPE4/04G
TCCPE250/4G
TCCPE350/4G
TCCPE500/4G
TCCPE600/4G
TCCPE750/4G

Part
Number
T
r
a
y

a
n
d

P
o
w
e
r

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
40
Made in the USA
EnviroPlusTM Control Cable
Factory Mutual Group 1 listed
UL Type TC
600 Volt Control Cable
Zero Halogen, Limited Smoke
Number
of
Conductors
Overall
Jacket
(Mils)
Approximate
Net Weight
(lbs./1000)
2 45 .391 71 25
3 45 .412 92 25
4 45 .446 113 20
5 45 .484 135 20
7 60 .554 192 17
9 60 .636 242 17
12 60 .707 306 12+
19 60 .819 449 12+
37 80 1.13 863 10+
2 45 .429 92 30
3 45 .452 121 30
4 45 .492 152 24
5 60 .565 202 24
7 60 .611 262 21
9 60 .704 328 21
12 60 .786 419 15+
19 80 .954 665 15+
37 80 1.260 1,205 12+
2 45 .478 124 40
3 45 .505 167 40
4 60 .581 231 32
5 60 .631 278 32
7 60 .684 365 28+
9 60 .793 460 28+
12 80 .927 631 20+
19 80 1.076 941 20+
37 80 1.430 1,732 16+
* Per NEC Table 310-16. (Ampacity derated in accordance with note 8a).
*The overcurrent protection shall not exceed 15 amps for 14 AWG, and 20 amps for 12 AWG and 30 amps for 10 AWG per NEC 310-16 footnote.
NOTE: The data shown is approximate and subject to standard industry tolerances 2011

#
1
0

A
W
G

#
1
2

A
W
G

#
1
4

A
W
G
Nominal
Diameter
(inches)
Ampacity*
30 C Ambient
90 C Wet/Dry
Standards:
UL1277, IMSA 19-1
Flame Rated IEEE 1202/CSA FT-4, IEEE 383, UL1685, UL 1581
Factory Mutual Group 1 listed
Two-hour Firewall rated
Conductors rated VW-1 (#14 - #10)
Sunlight resistant for CT use; Direct Burial
Temperature Rating: 90 C Wet/Dry
ICEA S-95-658/NEMA WC-70
Color Code: K-2 (Optional color codes available)
Exposed runs rated (TC-ER)
Zero Halogen, Limited Smoke Jacket

Description:
Conductors are stranded, annealed copper, insulated with 30 mils
heat and moisture resistant cross-linked polyethylene (type
XHHW-2 VW-1), phase identied. Cabled together with llers
(where necessary). Cable core is covered with binder tape, and an
overall ame and sunlight resistant black Zero Halogen, Limited
Smoke, Zero Lead Jacket.
Available with tinned conductors.
Features:
Suitable for use in NEC Hazardous locations:
Class I, Div. 2; Class II, Div. 2; RoHS Compliant
TCNH14/2
TCNH14/3
TCNH14/4
TCNH14/5
TCNH14/7
TCNH14/9
TCNH14/12
TCNH14/19
TCNH14/37
TCNH12/2
TCNH12/3
TCNH12/4
TCNH12/5
TCNH12/7
TCNH12/9
TCNH12/12
TCNH12/19
TCNH12/37
TCNH10/2
TCNH10/3
TCNH10/4
TCNH10/5
TCNH10/7
TCNH10/9
TCNH10/12
TCNH10/19
TCNH10/37
Part
Number
T
r
a
y

a
n
d

P
o
w
e
r

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
41
Made in the USA
8 7 45 1-#10 60 .665 314 55
8 7 45 1-#10 60 .726 329 55
6 7 45 1- #8 60 .746 454 75
6 7 45 1- #8 60 .818 486 75
4 7 45 1- #8 80 .890 670 95
3 7 45 1- #6 80 .950 822 110
2 7 45 1- #6 80 1.019 978 130
1 19 55 1- #6 80 1.125 1,196 150
1/0 19 55 1- #6 80 1.209 1,439 170
2/0 19 55 1- #6 80 1.310 1,743 195
3/0 19 55 1- #4 80 1.411 2,163 225
4/0 19 55 1- #4 80 1.532 2,633 260
250 37 65 1- #4 110 1.775 3,219 290
350 37 65 1- #3 110 2.004 4,333 350
500 37 65 1- #2 110 2.292 5,977 430
600 61 80 1- #2 110 2.525 7,138 475
750 61 80 1- #1 140 2.811 8,946 535
8 7 45 1-#10 60 .726 389 44
8 7 45 1-#10 60 .793 405 44
6 7 45 1- #8 60 .818 563 60
6 7 45 1- #8 80 .936 640 60
4 7 45 1- #8 80 .973 836 76
3 7 45 1- #6 80 1.041 1,027 88
2 7 45 1- #6 80 1.118 1,230 104
1 19 55 1- #6 80 1.237 1,516 120
1/0 19 55 1- #6 80 1.331 1,832 136
2/0 19 55 1- #6 80 1.444 2,232 156
3/0 19 55 1- #4 80 1.558 2,768 180
4/0 19 55 1- #4 110 1.753 3,492 208
250 37 65 1- #4 110 1.958 4,125 232
350 37 65 1- #3 110 2.214 5,579 280
500 37 65 1- #2 140 2.597 7,880 344
600 61 80 1- #2 140 2.858 9,419 380
750 61 80 1- #1 140 3.112 11,571 428
EnviroPlusTM Tray Cable
Factory Mutual Group 1 listed
UL Type TC
600 Volt Tray Cable
Zero Halogen, Limited Smoke
*Per NEC-Table 310-16. ** ER Rated all sizes with green ground or with no ground.
NOTE: The data shown is approximate and subject to standard industry tolerances.
NOTE: 4-Conductor ampacity assumes all four conductors are hot. If three are hot and one is a neutral, use the three conductor ampacity. 2011
Standards:
UL1277, IMSA 19-1
FlameRated IEEE 1202/CSA FT-4, IEEE 383, UL1685, UL 1581
Factory Mutual Group 1 listed
Two-hour Firewall rated, (2/0 AWG and smaller)
Sunlight resistant for CT use; Direct Burial
Conductors rated 90 C Wet/Dry
ICEA S-95-658/NEMA WC-70
Color Code: Black and numbered (#14 - #8 K-2)
Zero Halogen, Limited Smoke
Exposed Runs rated #6 AWG and larger (TC-ER)**

Description:
3 or 4 conductors, stranded copper, insulated with heat and mois-
ture resistant cross-linked polyethylene (Type XHHW-2), phase
identied. Cabled together with llers and bare copper ground
conductor. Cable core is covered with binder tape and overall
ame and sunlight resistant black Zero Halogen, Limited Smoke,
Zero Lead Jacket.
Approx.
Diameter
Overall (inch)
Approx. Net Wt.
per 1000 ft.
(lbs.)
Jacket
Thickness
(mils)
Grounding
Conductor
(AWG)
Insulation
Thickness
(mils)
Strand
(no.)
Size
AWG
or MCM
Ampacity*
(30 C
Ambient)
90CWet/Dry
T
H
R
E
E

C
O
N
D
U
C
T
O
R
F
O
U
R

C
O
N
D
U
C
T
O
R
Available with tinned conductors.
Features:
Suitable for use in NEC Hazardous locations:
Class I, Div. 2; Class II, Div. 2; RoHS Compliant
TCNH8/3G
TCNH8/3GG
TCNH6/3G
TCNH6/3GG
TCNH4/3G
TCNH3/3G
TCNH2/3G
TCNH1/3G
TCNH1/03G
TCNH2/03G
TCNH3/03G
TCNH4/03G
TCNH250/3G
TCNH350/3G
TCNH500/3G
TCNH600/3G
TCNH750/3G
TCNH8/4G
TCNH8/4GG
TCNH6/4G
TCNH6/4GG
TCNH4/4G
TCNH3/4G
TCNH2/4G
TCNH1/4G
TCNH1/04G
TCNH2/04G
TCNH3/04G
TCNH4/04G
TCNH250/4G
TCNH350/4G
TCNH500/4G
TCNH600/4G
TCNH750/4G
Part
Number
T
r
a
y

a
n
d

P
o
w
e
r

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
42
Made in the USA
8 7 45 3-#14 60 .665 320 55
6 7 45 3-#12 60 .746 463 75
4 7 45 3-#10 80 .890 712 95
2 7 45 3- #8 80 1.019 1,044 130
1 19 55 3- #8 80 1.125 1,263 150
1/0 19 55 3- #6 80 1.209 1,590 170
2/0 19 55 3- #6 80 1.310 1,894 195
3/0 19 55 3- #4 80 1.411 2,403 225
4/0 19 55 3- #4 80 1.532 2,873 260
250 37 65 3- #4 110 1.775 3,459 290
350 37 65 3- #2 110 2.004 4,754 350
500 37 65 3- #1 110 2.292 6,511 430
750 61 80 3-2/0 140 2.811 9,857 535

8 7 45 3-#14 60 .726 395 44
6 7 45 3-#12 60 .818 572 60
4 7 45 3-#10 80 .973 879 76
2 7 45 3- #8 80 1.118 1,297 104
1 19 55 3- #8 80 1.237 1,583 120
1/0 19 55 3- #6 80 1.331 1,983 136
2/0 19 55 3- #6 80 1.444 2,383 156
3/0 19 55 3- #4 80 1.558 3,007 180
4/0 19 55 3- #4 110 1.753 3,732 208
250 37 65 3- #4 110 1.958 4,365 232
350 37 65 3- #2 110 2.214 6,000 280
500 37 65 3- #1 140 2.597 8,414 344
750 61 80 3-2/0 140 3.122 12,482 428
EnviroPlusTM Tray Cable
Factory Mutual Group 1 listed
UL Type TC, 50% Ground
600 Volt Tray Cable, Tinned Copper
Zero Halogen, Limited Smoke
*Per NEC-Table 310-16. ** ER Rated all sizes with green ground or with no ground.
NOTE: The data shown is approximate and subject to standard industry tolerances.
NOTE: 4-Conductor ampacity assumes all four conductors are hot. If three are hot and one is a neutral, use the three conductor ampacity. 2011
Standards:
UL1277, IMSA 19-1
Cable passes IEEE 1202/CSA FT-4, IEEE 383, UL1685, UL 1581
Factory Mutual Group 1 listed
Two-hour Firewall rated, (2/0 AWG and smaller)
Sunlight resistant for CT use; Direct Burial
Conductors rated 90 C Wet/Dry
ICEA S-95-658/NEMA WC-70
Color Code: Method 4 (Except #8 is K-2)
Zero Halogen, Limited Smoke
Exposed Runs rated #6 AWG and larger (TC-ER)**
Description:
3 or 4 conductors, stranded copper, insulated with heat and mois-
ture resistant cross-linked polyethylene (Type XHHW-2), phase
identied. Cabled together with llers and bare copper ground
conductor(s). Cable core is covered with binder tape and overall
ame and sunlight resistant black Zero Halogen, Limited Smoke,
Zero Lead Jacket.
Approx.
Diameter
Overall (inch)
Approx. Net Wt.
per 1000 ft.
(lbs.)
Jacket
Thickness
(mils)
Grounding
Conductor
(AWG)
Insulation
Thickness
(mils)
Strand
(no.)
Size
AWG
or MCM
Ampacity*
(30 C
Ambient)
90CWet/Dry
T
H
R
E
E

C
O
N
D
U
C
T
O
R
F
O
U
R

C
O
N
D
U
C
T
O
R
Available with tinned conductors.
Features:
Suitable for use in NEC Hazardous locations:
Class I, Div. 2; Class II, Div. 2; RoHS Compliant
TCNH8/3G3#14
TCNH6/3G3#12
TCNH4/3G3#10
TCNH2/3G3#8
TCNH1/3G3#8
TCNH1/03G3#6
TCNH2/03G3#6
TCNH3/03G3#4
TCNH4/03G3#4
TCNH250/3G3#4
TCNH350/3G3#2
TCNH500/3G3#1
TCNH750/3G3-2/0
TCNH8/4G3#14
TCNH6/4G3#12
TCNH4/4G3#10
TCNH2/4G3#8
TCNH1/4G3#8
TCNH1/04G3#6
TCNH2/04G3#6
TCNH3/04G3#4
TCNH4/04G3#4
TCNH250/4G3#4
TCNH350/4G3#2
TCNH500/4G3#1
TCNH750/4G3-2/0
Part
Number
T
r
a
y

a
n
d

P
o
w
e
r

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
43
Made in the USA
Tray Cable Shielded
XHHW-2 / PVC
UL Type TC
600 Volt Copper XHHW-2
Description:
Conductors, Class B stranded, annealed copper, insulated with 30
mils heat and moisture resistant cross-linked polyethylene (Type
XHHW-2), phase identied. Cabled together with llers, where
necessary. Cable core covered with mylar binder tape, longitudi-
nally applied corrugated copper tape shield, and an overall ame
and sunlight resistant black PVC jacket. Surface printed. Jacket
available in colors.
Standards:
UL 1277, IMSA 19-1
Flame Rated: IEEE-383 (70,000 BTU),
IEEE 1202/CSA FT-4
Two-hour Firewall rated
Sunlight Resistant for CT Use; Direct Burial,
Oil Resistant II Jacket
Color Code: K-2 (Optional color codes available)
Conductors rated 90 Wet/Dry
ICEA S-95-658/NEMA WC-70
Exposed runs rated (TC-ER)
Features:
Suitable for use in NEC Hazardous locations:
Class I, Div. 2; Class II, Div. 2; RoHS Compliant
Part
Number
Number
of Cond
Overall Jacket
(mils)
Nominal Diameter
(inches)
Approx. Net Weight
(lb/1000)
Ampacity* (30C Ambient
Wet/Dray) 90C
TCXHSHC14/2 2 45 .461 106 25
TCXHSHC14/3 3 45 .482 125 25
TCXHSHC14/4 4 60 .546 163 20
TCXHSHC14/5 5 60 .584 187 20
TCXHSHC14/7 7 60 .624 229 17
TCXHSHC14/9 9 60 .706 279 17
TCXHSHC14/12 12 60 .777 345 12
TCXHSHC14/19 19 80 .929 523 12
TCXHSHC12/2 2 45 .499 129 30
TCXHSHC12/3 3 60 .552 172 30
TCXHSHC12/4 4 60 .592 205 24
TCXHSHC12/5 5 60 .635 238 24
TCXHSHC12/7 7 60 .681 301 21
TCXHSHC12/9 9 60 .774 369 21
TCXHSHC12/12 12 80 .896 492 15
TCXHSHC12/19 19 80 1.024 706 15
TCXHSHC10/2 2 60 .578 178 40
TCXHSHC10/3 3 60 .605 223 40
TCXHSHC10/4 4 60 .651 269 32
TCXHSHC10/5 5 60 .701 317 32
TCXHSHC10/7 7 60 .754 404 28
TCXHSHC10/9 9 80 .903 540 28
TCXHSHC10/12 12 80 .997 675 20
TCXHSHC10/19 19 80 1.146 983 20
#
1
4

A
W
G
#
1
2

A
W
G
#
1
0

A
W
G
*Per NEC Table 310-16 (Ampacity derated in accordance with note 8a)
*The overcurrent protection for items marked with an () shall not exceed 15 amps for 14 AWG, 20 amps for 12 AWG and
30 amps for 10 AWG per NEC 310-16 footnote.
NOTE: The data shown is approximate and subject to standard industry tolerances. 2011
T
r
a
y

a
n
d

P
o
w
e
r

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
44
Made in the USA
Part
Number
Number
of Cond
Overall Jacket
(mils)
Nominal Diameter
(inches)
Approx. Net Weight
(lb/1000)
Ampacity* (30C Ambient
Wet/Dray) 90C
TCNHSHC14/2 2 45 .461 108 25
TCNHSHC14/3 3 45 .482 128 25
TCNHSHC14/4 4 60 .546 167 20
TCNHSHC14/5 5 60 .584 192 20
TCNHSHC14/7 7 60 .624 234 17
TCNHSHC14/9 9 60 .706 285 17
TCNHSHC14/12 12 60 .777 351 12
TCNHSHC14/19 19 80 .929 533 12
TCNHSHC12/2 2 45 .499 132 30
TCNHSHC12/3 3 60 .552 176 30
TCNHSHC12/4 4 60 .592 210 24
TCNHSHC12/5 5 60 .635 243 24
TCNHSHC12/7 7 60 .681 306 21
TCNHSHC12/9 9 60 .774 375 21
TCNHSHC12/12 12 80 .896 501 15
TCNHSHC12/19 19 80 1.024 718 15
TCNHSHC10/2 2 60 .578 162 40
TCNHSHC10/3 3 60 .605 197 40
TCNHSHC10/4 4 60 .651 235 32
TCNHSHC10/5 5 60 .701 272 32
TCNHSHC10/7 7 60 .754 339 28
TCNHSHC10/9 9 80 .903 459 28
TCNHSHC10/12 12 80 .997 565 20
TCNHSHC10/19 19 80 1.146 803 20
#
1
4

A
W
G
#
1
2

A
W
G
#
1
0

A
W
G
*Per NEC Table 310-16 (Ampacity derated in accordance with note 8a)
*The overcurrent protection for items marked with an () shall not exceed 15 amps for 14 AWG, 20 amps for 12 AWG and
30 amps for 10 AWG per NEC 310-16 footnote.
NOTE: The data shown is approximate and subject to standard industry tolerances. 2011
EnviroPlusTM Control Cable
Factory Mutual Group 1 listed
UL Type TC
600 Volt Control Cable
Zero Halogen, Limited Smoke
Standards:
UL1277, IMSA 19-1
Flame rated IEEE 1202/CSA FT-4, IEEE 383, UL1685, UL 1581
Factory Mutual Group 1 listed
Two-hour Firewall rated
Conductors rated VW-1 (#14 - #10)
Sunlight resistant for CT use; Direct Burial
Conductors Rated 90 C Wet/Dry
ICEA S-95-658/NEMA WC-70
Color Code: K-2 (Optional color codes available)
Exposed runs rated (TC-ER)
Zero Halogen, Limited Smoke Jacket
Description:
Conductors are stranded, annealed copper, insulated with 30
mils heat and moisture resistant cross-linked polyethylene (type
XHHW-2 VW-1), phase identied. Cabled together with llers
(where necessary). Cable core is covered with binder tape, lon-
gitudinally applied corrugated copper tape shield, and an overall
ame and sunlight resistant black Zero Halogen, Limited Smoke,
Zero Lead Jacket.
Features:
Suitable for use in NEC Hazardous locations:
Class I, Div. 2; Class II, Div. 2; RoHS Compliant
Available with tinned conductors.
T
r
a
y

a
n
d

P
o
w
e
r

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
45
Made in the USA
Approx.
Diameter
Overall (inch)
Approx. Net
Wt. per
1000 ft. (lbs.)
PVC Jacket
Thickness
(mils)
Grounding
Conductor
(AWG)
Insulation
Thickness
(mils)
Strand
(no.)
Part
Number
Size
AWG
or MCM
Ampacity*
(30 C
Ambient)
90CWet/Dry
T
H
R
E
E

C
O
N
D
U
C
T
O
R
F
O
U
R

C
O
N
D
U
C
T
O
R
14 7 30 1-#14 45 .482 140 25
12 7 30 1-#12 60 .552 197 30
10 7 30 1-#10 60 .605 230 40
8 7 45 1-#10 60 .735 361 55
6 7 45 1- #8 80 .856 552 75
4 7 45 1- #8 80 .96 746 95
2 7 45 1- #6 80 1.089 1,063 130
1 19 55 1- #6 80 1.195 1,286 150

14 7 30 1-#14 60 .546 180 20
12 7 30 1-#12 60 .592 230 24
10 7 30 1-#10 60 .651 267 32
8 7 45 1-#10 60 .796 436 44
6 7 45 1- #8 80 .928 671 60
4 7 45 1- #8 80 1.043 917 76
2 7 45 1- #6 80 1.188 1,320 104

* PER NEC TABLE 310-16 ** ER Rated all sizes with green ground or with no ground.
The overcurrent protection for items marked with an obelisk () shall not exceed 15 amps for 14 AWG, 20 amps for 12 AWG and
30 amps for 10 AWG per NEC 310-16 footnote.
NOTE: The data shown is approximate and subject to standard industry tolerances.
NOTE: 4-Conductor ampacity assumes all four conductors are hot. If three are hot and one is a neutral, use the three conductor ampacity. 2011
TCNHSHC14/3G
TCNHSHC12/3G
TCNHSHC10/3G
TCNHSHC8/3G
TCNHSHC6/3G
TCNHSHC4/3G
TCNHSHC2/3G
TCNHSHC1/3G
TCNHSHC14/4G
TCNHSHC12/4G
TCNHSHC10/4G
TCNHSHC8/4G
TCNHSHC6/4G
TCNHSHC4/4G
TCNHSHC2/4G
EnviroPlusTM Tray Cable
Factory Mutual Group 1 listed
UL Type TC
600 Volt Tray Cable
Zero Halogen, Limited Smoke
Standards:
UL1277, IMSA 19-1
Flame rated IEEE 1202/CSA FT-4, IEEE 383, UL1685, UL 1581
Factory Mutual Group 1 listed
Two-hour Firewall rated
Sunlight resistant for CT use; Direct Burial
Conductors Rated 90 C Wet/Dry
ICEA S-95-658/NEMA WC-70
Color Code: Black and numbered (#14 - #8 K-2)
Zero Halogen, Limited Smoke
Exposed Runs rated #6 AWG and larger (TC-ER)**
Description:
3 or 4 conductors, stranded copper, insulated with heat and mois-
ture resistant cross-linked polyethylene (Type XHHW-2), phase
identied. Cabled together with llers and bare copper ground
conductor. Cable core is covered with binder tape longitudinally
applied corrugated copper tape shield, and overall ame and
sunlight resistant black Zero Halogen, Limited Smoke, Zero Lead
Jacket.
Features:
Suitable for use in NEC Hazardous locations:
Class I, Div. 2; Class II, Div. 2, RoHS Compliant
Available with tinned conductors.
T
r
a
y

a
n
d

P
o
w
e
r

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
46
Made in the USA
Part
Number
Number
of Cond
Overall Jacket
(mils)
Nominal Diameter
(inches)
Approx. Net Weight
(lb/1000)
Ampacity* (30C Ambient
Wet/Dray) 90C
TCCPESHC14/2 2 45 .461 108 25
TCCPESHC14/3 3 45 .482 128 25
TCCPESHC14/4 4 60 .546 167 20
TCCPESHC14/5 5 60 .584 192 20
TCCPESHC14/7 7 60 .624 234 17
TCCPESHC14/9 9 60 .706 285 17
TCCPESHC14/12 12 60 .777 351 12
TCCPESHC14/19 19 80 .929 533 12
TCCPESHC12/2 2 45 .499 132 30
TCCPESHC12/3 3 60 .552 176 30
TCCPESHC12/4 4 60 .592 210 24
TCCPESHC12/5 5 60 .635 243 24
TCCPESHC12/7 7 60 .681 306 21
TCCPESHC12/9 9 60 .774 375 21
TCCPESHC12/12 12 80 .896 501 15
TCCPESHC12/19 19 80 1.024 718 15
TCCPESHC10/2 2 60 .578 162 40
TCCPESHC10/3 3 60 .605 197 40
TCCPESHC10/4 4 60 .651 235 32
TCCPESHC10/5 5 60 .701 272 32
TCCPESHC10/7 7 60 .754 339 28
TCCPESHC10/9 9 80 .903 459 28
TCCPESHC10/12 12 80 .997 565 20
TCCPESHC10/19 19 80 1.146 803 20
#
1
4

A
W
G
#
1
2

A
W
G
#
1
0

A
W
G
*Per NEC Table 310-16 (Ampacity derated in accordance with note 8a)
*The overcurrent protection for items marked with an () shall not exceed 15 amps for 14 AWG, 20 amps for 12 AWG and
30 amps for 10 AWG per NEC 310-16 footnote.
NOTE: The data shown is approximate and subject to standard industry tolerances. 2011
CPE Control Cable Shielded
FR-XLP/CPE
UL Type TC
600 Volt Control Cable
Standards:
UL1277, IMSA 19-1
Flame rated IEEE 1202/CSA FT-4, IEEE 383, UL 1581
Two-hour Firewall rated
Sunlight resistant for CT use; Direct Burial
Conductors rated 90 C Wet/Dry
ICEA S-95-658/NEMA WC-70
Color Code K-2 (Optional color codes available)
Exposed runs rated (TC-ER)
Description:
Conductors are stranded, annealed copper, insulated with 30 mils
heat and moisture resistant cross-linked polyethylene (type
XHHW-2), phase identied. Cabled together with llers (where
necessary). Cable core is covered with binder tape, longitudinally
applied corrugated copper tape shield, and an overall ame and
sunlight resistant black, CPE Jacket.
Features:
Suitable for use in NEC Hazardous locations:
Class I, Div. 2; Class II, Div. 2; RoHS Compliant
Available with tinned conductors.
T
r
a
y

a
n
d

P
o
w
e
r

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
47
Made in the USA
Approx.
Diameter
Overall (inch)
Approx. Net
Wt. per
1000 ft. (lbs.)
Jacket
Thickness
(mils)
Grounding
Conductor
(AWG)
Insulation
Thickness
(mils)
Strand
(no.)
Part
Number
Size
AWG
or MCM
Ampacity*
(30 C
Ambient)
90CWet/Dry
T
H
R
E
E

C
O
N
D
U
C
T
O
R
F
O
U
R

C
O
N
D
U
C
T
O
R
14 7 30 1-#14 45 .482 140 25
12 7 30 1-#12 60 .552 197 30
10 7 30 1-#10 60 .605 230 40
8 7 45 1-#10 60 .735 361 55
6 7 45 1- #8 80 .856 552 75
4 7 45 1- #8 80 .96 746 95
2 7 45 1- #6 80 1.089 1,063 130
1 19 55 1- #6 80 1.195 1,286 150

14 7 30 1-#14 60 .546 180 20
12 7 30 1-#12 60 .592 230 24
10 7 30 1-#10 60 .651 267 32
8 7 45 1-#10 60 .796 436 44
6 7 45 1- #8 80 .928 671 60
4 7 45 1- #8 80 1.043 917 76
2 7 45 1- #6 80 1.188 1,320 104

* PER NEC TABLE 310-16 ** ER Rated all sizes with green ground or with no ground.
The overcurrent protection for items marked with an obelisk () shall not exceed 15 amps for 14 AWG, 20 amps for 12 AWG and
30 amps for 10 AWG per NEC 310-16 footnote.
NOTE: The data shown is approximate and subject to standard industry tolerances.
NOTE: 4-Conductor ampacity assumes all four conductors are hot. If three are hot and one is a neutral, use the three conductor ampacity. 2011
TCCPESHC14/3G
TCCPESHC12/3G
TCCPESHC10/3G
TCCPESHC8/3G
TCCPESHC6/3G
TCCPESHC4/3G
TCCPESHC2/3G
TCCPESHC1/3G
TCCPESHC14/4G
TCCPESHC12/4G
TCCPESHC10/4G
TCCPESHC8/4G
TCCPESHC6/4G
TCCPESHC4/4G
TCCPESHC2/4G
CPE Tray Cable Shielded
FR-XLP/CPE
UL Type TC
600 Volt Tray Cable
Standards:
UL1277, IMSA 19-1
Flame rated I IEEE 1202/CSA FT-4, IEEE 383, UL1685, UL 1581
Two-hour Firewall rated
Sunlight resistant for CT use; Direct Burial
Conductors rated 90 C Wet/Dry
ICEA S-95-658/NEMA WC-70
Color Code: Black and numbered (#14 - #8 K-2)
Exposed Runs rated #6 AWG and larger (TC-ER)**
Description:
3 or 4 conductors, stranded copper, insulated with heat and mois-
ture resistant cross-linked polyethylene (Type XHHW-2), phase
identied. Cabled together with llers and bare copper ground
conductor. Cable core is covered with binder tape longitudinally
applied corrugated copper tape shield, and overall ame and
sunlight resistant black, CPE Jacket.
Features:
Suitable for use in NEC Hazardous locations:
Class I, Div. 2; Class II, Div. 2; RoHS Compliant
Available with tinned conductors.
T
r
a
y

a
n
d

P
o
w
e
r

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
48
Made in the USA
Description:
3 or 4 conductors, stranded, insulated with heat and moisture
resistant cross-linked polyethylene (type XHHW-2), phase identi-
ed. Cabled together with llers (where necessary) and bare copper
ground conductor. Cable core covered with mylar binder tape, lon-
gitudinally applied corrugated copper tape shield, and overall ame
and sunlight resistant black PVC jacket. Surface printed. Jacket
available in colors.
Features:
Suitable for use in NEC Hazardous locations:
Class I, Div. 2; Class II, Div. 2; RoHS Compliant
Standards:
UL1277, IMSA 19-1
Flame Rated: IEEE-383 (70,000 BTU)
IEEE 1202/CSA FT-4: Available upon request
Sunlight Resistant for CT Use; Direct Burial,
Two-hour Firewall rated
Oil Resistant II Jacket
Color Code: Black and numbered (#14 - #8 K-2)
Conductors rated 90 C Wet/Dry
ICEA S-95-658/NEMA WC-70
Exposed runs rated #4 and larger (TC-ER)**
Tray Cable Shielded
XHHW-2/PVC
UL Type TC
600 Volt Copper XHHW-2
Approx.
Diameter
Overall (inch)
Approx. Net
Wt. per
1000 ft. (lbs.)
PVC Jacket
Thickness
(mils)
Grounding
Conductor
(AWG)
Insulation
Thickness
(mils)
Strand
(no.)
Part
Number
Size
AWG
or MCM
Ampacity*
(30 C
Ambient)
90CWet/Dry
T
H
R
E
E

C
O
N
D
U
C
T
O
R
F
O
U
R

C
O
N
D
U
C
T
O
R
14 7 30 1-#14 45 .482 138 25
12 7 30 1-#12 60 .552 192 30
10 7 30 1-#10 60 .605 225 40
8 7 45 1-#10 60 .735 355 55
6 7 45 1- #8 80 .856 542 75
4 7 45 1- #8 80 .96 735 95
2 7 45 1- #6 80 1.089 1,051 130
1 19 55 1- #6 80 1.195 1,272 150

14 7 30 1-#14 60 .546 176 20
12 7 30 1-#12 60 .592 225 24
10 7 30 1-#10 60 .651 262 32
8 7 45 1-#10 60 .796 429 44
6 7 45 1- #8 80 .928 661 60
4 7 45 1- #8 80 1.043 906 76
2 7 45 1- #6 80 1.188 1,306 104

* PER NEC TABLE 310-16 ** ER Rated all sizes with green ground or with no ground.
The overcurrent protection for items marked with an obelisk () shall not exceed 15 amps for 14 AWG, 20 amps for 12 AWG and
30 amps for 10 AWG per NEC 310-16 footnote.
NOTE: The data shown is approximate and subject to standard industry tolerances.
NOTE: 4-Conductor ampacity assumes all four conductors are hot. If three are hot and one is a neutral, use the three conductor ampacity. 2011
TCXHSHC14/3G
TCXHSHC12/3G
TCXHSHC10/3G
TCXHSHC8/3G
TCXHSHC6/3G
TCXHSHC4/3G
TCXHSHC2/3G
TCXHSHC1/3G
TCXHSHC14/4G
TCXHSHC12/4G
TCXHSHC10/4G
TCXHSHC8/4G
TCXHSHC6/4G
TCXHSHC4/4G
TCXHSHC2/4G
T
r
a
y

a
n
d

P
o
w
e
r

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
49
Made in the USA
ServiceDrive ASD/VFD
Shielded Tray Drive Cable
PVC Jacket Overall
Patented
Description:
3 conductors, stranded, insulated with heat and moisture resistant
cross-linked polyethylene, phase identied, cabled together with suit-
able llers and 3 symmetrical bare copper ground conductors. Cable
core covered with 5-mil helical copper tape shield, and overall ame
and sunlight resistant black PVC jacket. Surface printed. Jacket avail-
able in colors.
Features:
Suitable for use in NEC Hazardous Locations:
Class I - Div 2, Class II - Div 2, and Class III, Div 1 and 2
For use in ASD / VFD applications; RoHS Compliant
Standards:
UL 1277
Flame Rated: IEEE 383 (70,000 BTU),
ICEA T-29-520 (210,000 BTU) on 1/0 and larger
IEEE 1202 / CSA FT-4
Two-hour Firewall rated, (2/0 AWG and smaller)
Sunlight Resistant, for CT Use; Direct Burial
Oil Resistant II Jacket
Code: Black and Numbered
Conductors rated 90 C Wet/Dry
ICEA S-95-658 / NEMA WC-70
Exposed runs rated #4 and larger (TC-ER)



T
H
R
E
E

C
O
N
D
U
C
T
O
R
Size
AWG
or
MCM
Part
Number
Strand
(no.)
Insulation
Thickness
(mils)
Approx. Net
Wt.
per 1000 ft.
(lbs.)
Copper
Grounding
Conductor(s)
(AWG)
PVC Jacket
Thickness
(mils)
Ampacity*
(30C Ambient
Wet/Dry)
14 7 45 3-#10 45 .470 239 25
12 7 45 3-#10 45 .520 270 30
10 7 45 3-#10 60 .600 338 40
8 7 45 3-#10 60 .644 415 55
6 7 45 3-#10 60 .725 538 75
4 7 45 3-#10 80 .869 757 95
3 7 45 3-#10 80 .929 886 110
2 7 45 3-#8 80 .998 1,100 130
1 19 55 3-#8 80 1.104 1,326 150
1/0 19 55 3-#6 80 1.188 1,658 170
2/0 19 55 3-#6 80 1.289 1,970 195
3/0 19 55 3-#4 80 1.390 2,486 225
4/0 19 55 3-#4 80 1.511 2,965 260
250 37 65 3-#4 110 1.754 3,554 290
350 37 65 3-#2 110 1.983 4,867 350
500 37 65 3-#1 110 2.271 6,641 430
600 61 80 3-1/0 110 2.504 8,009 475
750 61 80 3-2/0 140 2.790 10,007 535
Approx.
Diameter
Overall
(inch)
*Per NEC Table 310-16. The overcurrent protection for items marked with an obelisk (+) shall not exceed
15 amps for 14 AWG , 20 amps for 12 AWG, and 30 amps for 10 AWG per NEC 310-16 footnote.
Note: The data shown is approximate and subject to standard industry tolerances. 2011
ASDPTC14/3
ASDPTC12/3
ASDPTC10/3
ASDPTC8/3
ASDPTC6/3
ASDPTC4/3
ASDPTC3/3
ASDPTC2/3
ASDPTC1/3
ASDPTC1/03
ASDPTC2/03
ASDPTC3/03
ASDPTC4/03
ASDPTC250/3
ASDPTC350/3
ASDPTC500/3
ASDPTC600/3
ASDPTC750/3
Available with tinned conductors.
T
r
a
y

a
n
d

P
o
w
e
r

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
50
Made in the USA
Description:
3 conductors, stranded, insulated with heat and moisture resistant
cross-linked polyethylene, phase identied, cabled together with
suitable llers and 3 symmetrical bare copper ground conductors.
Cable core covered with 5-mil helical copper tape shield, and overall
ame and sunlight resistant black zero-halogen, limited smoke, zero
lead jacket.
Features:
Suitable for use in NEC Hazardous Locations:
Class I - Div 2, Class II - Div 2, and Class III, Div 1 and 2
For use in ASD / VFD applications; RoHS Compliant
Standards:
UL 1277
Flame Rated: IEEE 383 (70,000 BTU),
IEEE 1202 / CSA FT-4, UL 1685 LS
Factory Mutual Group 1 Listed
Two-hour Firewall rated, (2/0 AWG and smaller)
Sunlight Resistant, for CT Use; Direct Burial
Color Code: Black and Numbered
Conductors rated 90 C Wet/Dry
ICEA S-95-658 / NEMA WC-70
Zero Halogen, Limited Smoke
Exposed Runs rated 6 AWG and larger (TC-ER)


*Per NEC Table 310-16.
+ The overcurrent protection for items marked with an obelisk () shall not exceed 15 amps for 14 AWG , 20 amps for 12 AWG, and 30 amps for
10 AWG per NEC 310-16 footnote.
Note: The data shown is approximate and subject to standard industry tolerances. 2011
T
H
R
E
E

C
O
N
D
U
C
T
O
R
14 7 45 3-#10 45 .470 239 25
12 7 45 3-#10 45 .520 273 30
10 7 45 3-#10 60 .600 343 40
8 7 45 3-#10 60 .644 420 55
6 7 45 3-#10 60 .725 544 75
4 7 45 3-#10 80 .869 766 95
3 7 45 3-#10 80 .929 896 110
2 7 45 3-#8 80 .998 1,111 130
1 19 55 3-#8 80 1.104 1,339 150
1/0 19 55 3-#6 80 1.188 1,672 170
2/0 19 55 3-#6 80 1.289 1,984 195
3/0 19 55 3-#4 80 1.390 2,501 225
4/0 19 55 3-#4 80 1.511 2,982 260
250 37 65 3-#4 110 1.754 3,581 290
350 37 65 3-#2 110 1.983 4,898 350
500 37 65 3-#1 110 2.271 6,677 430
600 61 80 3-1/0 110 2.504 8,049 475
750 61 80 3-2/0 140 2.790 10,062 535
ServiceDrive Plus

ASD/VFD
Shielded Tray Drive Cable
Factory Mutual Group 1 Listed,
Zero Halogen, Limited Smoke,
Lead Free, Patented
Size
AWG
or
MCM
Part
Number
Strand
(no.)
Insulation
Thickness
(mils)
Approx. Net
Wt.
per 1000 ft.
(lbs.)
Copper
Grounding
Conductor(s)
(AWG)
Jacket
Thickness
(mils)
Ampacity*
(30C Ambient
Wet/Dry)
Approx.
Diameter
Overall
(inch)
ASDETC14/3
ASDETC12/3
ASDETC10/3
ASDETC8/3
ASDETC6/3
ASDETC4/3
ASDETC3/3
ASDETC2/3
ASDETC1/3
ASDETC1/03
ASDETC2/03
ASDETC3/03
ASDETC4/03
ASDETC250/3
ASDETC350/3
ASDETC500/3
ASDETC600/3
ASDETC750/3
Available with tinned conductors.
Manufacturing quality. Delivering service.
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
51
Made in the USA
ServiceDrive and ServiceDrive Plus
ASD/VFD Tray Cable Connectors, Termination Kit
Corresponding Part Numbers
SIZE CABLE CONNECTOR TERMINATION KIT
AWG OR MCM PART NUMBER PART NUMBER PART NUMBER
14 ASDPTC14/3 CONASDTC14/3 TERASD14-1/3
12 ASDPTC12/3 CONASDTC12/3 TERASD14-1/3
10 ASDPTC10/3 CONASDTC10/3 TERASD14-1/3
8 ASDPTC8/3 CONASDTC8/3 TERASD14-1/3
6 ASDPTC6/3 CONASDTC6/3 TERASD14-1/3
4 ASDPTC4/3 CONASDTC4/3 TERASD14-1/3
3 ASDPTC3/3 CONASTCD3/3 TERASD14-1/3
2 ASDPTC2/3 CONASDTC2/3 TERASD14-1/3
1 ASDPTC1/3 CONASDTC1/3 TERASD14-1/3
1/0 ASDPTC1/03 CONASDTC1/03 TERASD1/0-3/03
2/0 ASDPTC2/03 CONASDTC2/03 TERASD1/0-3/03
3/0 ASDPTC3/03 CONASDTC3/03 TERASD1/0-3/03
4/0 ASDPTC4/03 CONASDTC4/03 TERASD4/0-400/3
250 ASDPTC250/3 CONASDTC250/3 TERASD4/0-400/3
350 ASDPTC350/3 CONASDTC350/3 TERASD4/0-400/3
500 ASDPTC500/3 CONASDTC500/3 TERASD500-750/3
600 ASDPTC600/3 CONASDTC600/3 TERASD500-750/3
750 ASDPTC750/3 CONASDTC750/3 TERASD500-750/3

2011
A
S
D
/
V
F
D

C
o
n
n
e
c
t
o
r
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
52
Made in the USA
DESCRIPTION & FEATURES:
These patented connectors are designed exclusively to terminate
ASD/VFD cables in control centers, panel boards, junction boxes
and motor control enclosures.
ServiceDrive ASD/VFD
Tray Cable Connectors
Patented for use with ServiceDrive
and ServiceDrive Plus Cable Systems
PART NUMBER WIRE SIZE HUB SIZE SET SCREW SIZE
CONASDTC14/3 14 AWG 3 COND 3/4 10/32 X 1/4
CONASDTC12/3 12 AWG 3 COND 3/4 10/32 X 1/4
CONASDTC10/3 10 AWG 3 COND 3/4 10/32 X 1/4
CONASDTC8/3 8 AWG 3 COND 3/4 10/32 X 1/4
CONASDTC6/3 6 AWG 3 COND 3/4 10/32 X 1/4
CONASDTC4/3 4 AWG 3 COND 1 1/4-20 X 1/4
CONASDTC3/3 3 AWG 3 COND 1 10/32 X 1/4
CONASDTC2/3 2 AWG 3 COND 1-1/4 1/4-20 X 1/4
CONASDTC1/3 1 AWG 3 COND 1-1/4 1/4-20 X 1/4
CONASDTC1/03 1/0 AWG 3 COND 1-1/2 1/4-20 X 1/4
CONASDTC2/03 2/0 AWG 3 COND 1-1/2 1/4-20 X 1/4
CONASDTC3/03 3/0 AWG 3 COND 1-1/2 1/4-20 X 1/4
CONASDTC4/03 4/0 AWG 3 COND 1-1/2 1/4-20 X 5/16
CONASDTC250/3 250 MCM 3 COND 2" 1/4-20 X 5/16
CONASDTC300/3 300 MCM 3 COND 2 5/16-18 X 3/8
CONASDTC350/3 350 MCM 3 COND 2 5/16-18 X 3/8
CONASDTC400/3 400 MCM 3 COND 2 5/16-18 X 3/8
CONASDTC500/3 500 MCM 3 COND 2-1/2 5/16-18 X 3/8
CONASDTC600/3 600 MCM 3 COND 2-1/2 5/16-18 X 3/8
CONASDTC750/3 750 MCM 3 COND 3" 5/16-18 X 3/8

Listings:
Class 1, Div. 2 and Class 2, Div. 1 & 2
CSA Standard: C22.2 #18.98
NEMA 4
IP65
2011
A
S
D
/
V
F
D

T
e
r
m
i
n
a
t
i
o
n

K
i
t
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
53
Made in the USA
FEATURES:
1. Flat tinned Copper braid Woven tinned copper construction
2. Stainless steel spring clamp
3. Adhesive-backed copper foil tape Shields against EMI/RFI
radiation. Conductive through the adhesive.
ASD/VFD Termination Kit
For use with ServiceDrive
and ServiceDrive Plus
Armor and Tray Cable
Applications:
Used to properly terminate the helically applied copper
tape shield of ASD/VFD cable constructions.
Listings:
Braid QC-W-343 Type S and ASTM B-33
Copper Foil Tape UL 510 for ame retardancy
PART NUMBER DESCRIPTION
TERASD14-1/3 For use with 14 awg - 1 awg shielded armor and tray cable
TERASD1/0-3/03 For use with 1/0 awg - 3/0 awg shielded armor and tray cable
TERASD4/0-400/3 For use with 4/0 awg - 400 mcm shielded armor and tray cable
TERASD500-750/3 For use with 500 mcm - 750 mcm shielded armor and tray cable
2011
T
r
a
y

a
n
d

P
o
w
e
r

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
54
Made in the USA
Strand
(no.)
Conductor
Size
AWG
or
MCM
Approx.
Net Weight
per 1000ft.
(lbs.)
Approx.
Diameter
Overall
(inch)
PVC
Jacket
Thickness
(mils)
Copper
Grounding
Conductor(s)
(AWG)
Approx.
Diameter over
Single Cond.
(inch)
Insulation
Thickness
(mils)
Jacket
Thickness
(mils)
Power Cable
5kV/2.4 kV MV-105/MV-90
Nonshielded/Shielded
100% and 133%
UL Listed
5000/2400 Volt Copper EPR
* Per NEC Table 310-75. Based on one three-conductor cable.
NOTE: The data shown is approximate and subject to standard industry tolerances. 2011
S
H
I
E
L
D
E
D
N
O
N
-
S
H
I
E
L
D
E
D
Description:
Nonshielded: Class B stranded copper, extruded conductor shield,
insulated with heat and moisture resistant EPR (2,400 Volt rated).
Shielded: Class B stranded copper, extruded conductor shield,
heat and moisture resistant EPR (100% and 133% insulation
level), semi-conducting insulation shield, copper shield, overall
PVC jacket.
3 conductors, phase identied and cabled together with llers and
bare copper ground conductor(s). Cable core covered with binder
tape and overall ame and sunlight resistant black PVC jacket.
Surface printed. Jacket available in colors.
Standards:
UL 1072
UL CT Rated
Sunlight Resistant
Direct Burial, For CT use
Color Code K-2/other color codes available.
Conductors rated at 105 C (5kV) / 90 C (2.4kV)
Oil Resistant II Jacket
Non-shielded: ICEA S-96-659/NEMA WC-71
Shielded: ICEA S-93-639/NEMA WC-74
RoHS Compliant
8 7 125 80 .58 8 80 1.45 944 58
6 7 125 80 .62 6 80 1.54 1,125 77
4 7 125 80 .67 6 80 1.64 1,363 100
2 7 125 80 .73 6 110 1.83 1,805 135
1/0 19 125 80 .80 4 110 1.98 2,379 155
2/0 19 125 80 .85 4 110 2.09 2,737 260
4/0 19 125 95 1.01 3 110 2.44 4,063 285
250 37 140 110 1.09 3 110 2.61 4,572 315
350 37 140 110 1.19 2 140 2.88 5,970 390
500 37 140 110 1.32 1 140 3.16 7,785 475
750 61 155 125 1.56 1/0 140 3.68 11,106 585
6 7 115 60 .67 6 80 1.64 1,378 77
4 7 115 60 .73 6 110 1.83 1,775 100
2 7 115 60 .78 6 110 1.94 2,115 135
1 19 115 60 .82 4 110 2.03 2,491 155
1/0 19 115 80 .91 4 110 2.22 2,908 185
2/0 19 115 80 .96 4 110 2.33 3,301 210
4/0 19 115 80 1.05 3 110 2.52 4,324 285
250 37 115 80 1.11 3 110 2.65 4,872 315
350 37 115 80 1.21 2 140 2.93 6,289 390
500 37 115 80 1.36 1 140 3.25 8,244 475
750 61 115 80 1.55 1/0 140 3.66 11,350 585
Ampacity*
(40 C
Ambient)
Part
Number
P2.4K8/3EG
P2.4K6/3EG
P2.4K4/3EG
P2.4K2/3EG
P2.4K1/03EG
P2.4K2/03EG
P2.4K4/03EG
P2.4K250/3EG
P2.4K350/3EG
P2.4K500/3EG
P2.4K750/3EG
P5KS6/3EG
P5KS4/3EG
P5KS2/3EG
P5KS1/3EG
P5KS1/03EG
P5KS2/03EG
P5KS4/03EG
P5KS250/3EG
P5KS350/3EG
P5KS500/3EG
P5KS750/3EG
T
r
a
y

a
n
d

P
o
w
e
r

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
55
Made in the USA
2 7 220 80 1.04 6 110 2.50 3,058 165
1 19 220 80 1.08 4 110 2.59 3,381 185
1/0 19 220 80 1.13 4 110 2.70 3,779 215
2/0 19 220 80 1.18 4 140 2.86 4,385 245
4/0 19 220 80 1.26 3 140 3.04 5,389 320
250 37 220 80 1.34 3 140 3.21 6,090 350
350 37 220 80 1.44 2 140 3.42 7,433 430
500 37 220 80 1.57 1 140 3.70 9,393 525
750 61 220 110 1.82 1/0 140 4.24 13,020 635
Power Cable
15kV MV-105
133%
UL Listed
15000 Volt Copper EPR
Standards:
UL 1072
Sunlight Resistant
Direct Burial, For CT use
Color Code K-2
Conductors rated at 105 C
ICEA S-93-639/NEMA WC-74
Oil Resistant II Jacket
RoHS Compliant
Description:
3 conductors, Class B stranded copper, extruded conductor
shield, heat and moisture resistant EPR (133% insulation level),
semi-conducting insulation shield, copper wire shield, overall
PVC jacket. Phase identied and cabled together with llers and
bare copper ground conductor. Cable core covered with binder
tape and overall ame and sunlight resistant black PVC jacket.
Jacket available in colors.
Ampacity*
(40 C
Ambient)
Size
AWG
or
MCM
Approx.
Diameter
Overall
(inch)
PVC
Jacket
Thickness
(mils)
Jacket
Thickness
(mils)
* Per NEC Table 310-75. Based on one three-conductor cable.
NOTE: The data shown is approximate and subject to standard industry tolerances. 2011
Approx.
Net Weight
per 1000ft.
(lbs.)
Copper
Grounding
Conductor(s)
(AWG)
Approx.
Diameter over
Single Cond.
(inch)
Insulation
Thickness
(mils)
Conductor
Strand
(no.)
Part
Number
P15K2/3EG
P15K1/3EG
P15K1/03EG
P15K2/03EG
P15K4/03EG
P15K250/3EG
P15K350/3EG
P15K500/3EG
P15K750/3EG
A
r
m
o
r

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
56
Made in the USA
Feeder Size MC Cable
600V / UL Type MC
Galvanized Steel or Aluminum
Copper XHHW-2
Applications
Service Wires Feeder Size MC cable is designed to be a cost ef-
fective replacement for conduit & wire. Suitable for service, branch
& feeder circuits. Ideal for use in commercial, industrial & utility
applications. This exible cable assembly offers: labor/time savings,
an increased resistance to mechanical damage, system design ex-
ibility & the reliability of a factory assembled & tested cable system.
Features
Suitable for use in NEC hazardous locations:
Class I, Div. 2 Class II, Div. 2
Two-hour Firewall rated, (2/0 AWG and smaller)
For use in Theatres (Article 520), Motion Picture & TV Studios
(Article 530) & Places of Assembly with more than 100 people
Can be messenger supported (Article 330)
Description:
3 or 4 conductors, stranded, insulated with heat & moisture
resistant cross-linked polyethylene (type XHHW-2), phase identi-
ed, cabled together with suitable llers** & green or bare ground
conductor. Cable core covered with binder tape, aluminum or
galvanized steel interlocked armor. Jacket upon request.
Standards:
UL 1569, ICEA S-95-658/NEMA WC-70
NEC Article 330 Cable Tray Rated RoHS Compliant
600 Volt, 90 C rated
Color coding: Black and Numbered. Green ground on #1 and
smaller. Bare ground on 1/0 and larger.

F
O
U
R

C
O
N
D
U
C
T
O
R
T
H
R
E
E

C
O
N
D
U
C
T
O
R
90 C
Size
AWG
or
MCM
Strand
(no.)
Insulation
Thickness
(mils)
Approx. Net Wt.
per 1000 ft. (lbs.)
Alum.
Armor
Galv.
Armor
Insulated/Bare
Copper
Grounding
Conductor(s)
(AWG)
Diameter
over Armor
(inch)
Ampacity*
(30 C
Ambient
Wet/Dry)
T
W
O8 7 45 10 .71 259 337 55
6 7 45 8 .81 366 465 75
8 7 45 10 .81 339 434 55
6 7 45 8 .95 480 607 75
4 7 45 8 1.01 659 786 95
3 7 45 6 1.09 808 960 110
2 7 45 6 1.15 960 1,109 130
1 19 55 6 1.27 1,190 1,423 150
1/0 19 55 6 1.31 1,398 1,624 170
2/0 19 55 6 1.41 1,689 1,937 195
3/0 19 55 4 1.51 2,098 2,376 225
4/0 19 55 4 1.63 2,586 2,853 260
250 37 65 4 1.81 3,123 3,462 290
300 37 65 3 1.93 3,654 4,043 320
350 37 65 3 2.05 4,224 4,602 350
400 37 65 3 2.17 4,712 5,148 380
500 37 65 2 2.33 5,842 6,281 430
600 61 80 2 2.57 6,948 7,462 475
750 61 80 1 2.85 8,618 9,117 535
8 7 45 10 .89 416 517 44
6 7 45 8 1.03 591 730 60
4 7 45 8 1.11 823 968 76
3 7 45 6 1.23 1,010 1,172 88
2 7 45 6 1.33 1,237 1,491 104
1 19 55 6 1.43 1,507 1,783 120
1/0 19 55 6 1.43 1,789 2,047 136
2/0 19 55 6 1.55 2,174 2,450 156
3/0 19 55 4 1.65 2,700 3,011 180
4/0 19 55 4 1.79 3,295 3,639 208
250 37 65 4 1.99 4,027 4,397 232
300 37 65 3 2.13 4,717 5,160 256
350 37 65 3 2.25 5,465 5,884 280
400 37 65 3 2.37 6,104 6,594 304
500 37 65 2 2.57 7,585 8,063 344
600 61 80 2 2.85 9,040 9,619 380
750 61 80 1 3.09 11,212 11,774 428
*Per NEC Table 310-16. **Fillers used when required.
NOTE: The data shown is approximate and subject to standard industry tolerances.
NOTE: 4-Conductor ampacity assumes all four conductors are hot. If three are hot and one is a neutral, use the three conductor ampacity. 2011
Part
Number
MC8/2
MC6/2
MC8/3
MC6/3
MC4/3
MC3/3
MC2/3
MC1/3
MC1/03
MC2/03
MC3/03
MC4/03
MC250/3
MC300/3
MC350/3
MC400/3
MC500/3
MC600/3
MC750/3
MC8/4
MC6/4
MC4/4
MC3/4
MC2/4
MC1/4
MC1/04
MC2/04
MC3/04
MC4/04
MC250/4
MC300/4
MC350/4
MC400/4
MC500/4
MC600/4
MC750/4
A
r
m
o
r

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
57
Made in the USA
UL Listed Connectors
For Feeder MC
Listings:
UL: Class I* Group A, B, C and D
Class II* Group E, F and G
Class III
* Includes Division 1 and Division 2

DESCRIPTION & FEATURES:
These U.L. listed connectors are a one-piece body construction
with a unique scroll design that can provide a 360 degree ground to
armor.

This connector provides a fast and easy installation, eliminates in-
ternal components, prevents cable pullout and saves time and labor.
CONSTRUCTION
Suitable for industrial and commercial use.
Manufactured from 6061 copper-free aluminum.
A complete range of NPT (National Pipe Thread) sizes are available
from 1/2" through 4". This accommodates armored cable type MC
O.D. sizes.
Part
Number
Copper
MC
O.D.
Range
Part
Number
Copper
MC
O.D.
Range
Part
Number
Copper
MC
O.D.
Range
2/4 MC CON139 1.320-1.390
1/3 MC CON132 1.250-1.320
1/4 MC CON148 1.390-1.480
1/03 MC CON132 1.250-1.320
1/04 MC CON148 1.390-1.480
2/03 MC CON148 1.390-1.480
2/04 MC CON157 1.480-1.570
3/03 MC CON157 1.480-1.570
3/04 MC CON175 1.660-1.750
4/03 MC CON166 1.570-1.660
4/04 MC CON184 1.750-1.840
250/3 MC CON184 1.750-1.840
8/3 MC CON83 .760-.830
8/4 MC CON90 .830-.900
6/2 MC CON83 .760-.830
6/3 MC CON97 .900-.970
6/4 MC CON104 .970-1.040
4/2 MC CON90 .830-.900
4/3 MC CON104 .970-1.040
4/4 MC CON111 1.040-1.110
3/3 MC CON111 1.040-1.110
3/4 MC CON125 1.180-1.250
2/3 MC CON118 1.110-1.180
250/4 MC CON202 1.930-2.020
350/3 MC CON213 2.020-2.130
350/4 MC CON235 2.240-2.350
400/3 MC CON213 2.020-2.130
400/4 MC CON235 2.240-2.350
500/3 MC CON235 2.240-2.350
500/4 MC CON257 2.460-2.570
600/3 MC CON257 2.460-2.570
600/4 MC CON285 2.710-2.850
750/3 MC CON285 2.710-2.85
750/4 MC CON313 2.990-3.130
`
2011
A
r
m
o
r

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
58
Made in the USA
Interlocked Armor
600V / UL Type MC
Galvanized Steel or Aluminum
Multi-Conductor Copper XHHW-2
Description:
Conductors are Class B stranded copper, 30 mils, Type XHHW-2,
phase identied, and cabled together with a **bare copper ground
conductor. Cable Core covered with binder tape, Aluminum or Gal-
vanized steel interlocked Armor, with an overall ame and sunlight
resistant PVC Jacket. Jacket available under armor & in colors.
Features:
Suitable for use in NEC Hazardous locations:
Class I, Div. 2 Class II, Div. 2
Standards:
UL 1569
Flame Rated: IEEE-383 (70,000 BTU),
ICEA T-29-520 (210,000 BTU),
IEEE 1202/CSA FT-4
Two-hour Firewall rated
Sunlight Resistant for CT Use; Direct Burial
1
, Oil Resistant II
Jacket
Color Code K-2 / other color codes available
Temperature Rating: 90 C Wet/Dry
ICEA S-95-658/NEMA WC-70
RoHS Compliant
#
1
4

A
W
G


#
1
2

A
W
G
#
1
0

A
W
G
Number
of
Conductors
2 14 .55 50 .65 169 233 25
3 14 .55 50 .65 187 250 25
4 14 .57 50 .67 209 268 20
5 14 .59 50 .69 237 302 20
7 14 .67 50 .77 296 374 17
9 14 .75 50 .85 351 442 17
12 14 .81 50 .91 413 510 12
19 14 .91 50 1.01 565 681 12
25 14 1.04 50 1.14 694 853 11
37 14 1.23 50 1.33 977 1,157 10
2 12 .55 50 .65 194 258 30
3 12 .57 50 .67 225 284 30
4 12 .61 50 .71 261 326 24
5 12 .65 50 .75 297 368 24
7 12 .75 50 .85 380 466 21
9 12 .83 50 .93 456 559 21
12 12 .89 50 .99 544 653 15
19 12 1.00 50 1.10 759 891 15
25 12 1.16 50 1.26 939 1,128 13
37 12 1.37 50 1.47 1,336 1,545 12
2 10 .59 50 .69 243 312 40
3 10 .61 50 .71 287 360 40
4 10 .67 50 .77 341 415 32
5 10 .71 50 .81 390 479 32
7 10 .83 50 .93 505 605 28
9 10 .93 50 1.03 609 724 28
12 10 .99 50 1.09 741 874 20
19 10 1.13 50 1.23 1,049 1,204 20
25 10 1.31 50 1.41 1,348 1,607 18
37 10 1.55 60 1.67 1,907 2,217 16
*Per NEC Table 310-16 (Ampacity derated in accordance with note 8a)
1
Includes encasement in concrete.
The overcurrent protection for items marked with an obelisk () shall not exceed 15 amps for 14 AWG, 20 amps for 12 AWG, and 30 amps for 10
AWG per NEC 310-16 footnote.
** Cable with 7 conductors or more shall have a green insulated ground.
NOTE: The data shown is approximate and subject to standard industry tolerances 2011
Approx. Net Wt.
per 1000 ft. (lbs.)
Alum.
Armor
Galv.
Armor
Ampacity*
30 Ambient
Wet / Dry
Approximate
Overall
Diameter
(inch)
PVC
Jacket
Thickness
(mils)
Diameter
over
Armor (inch)
Grounding
Conductors
(AWG)
Part
Number
AAP14/2
AAP14/3
AAP14/4
AAP14/5
AAP14/7
AAP14/9
AAP14/12
AAP14/19
AAP14/25
AAP14/37
AAP12/2
AAP12/3
AAP12/4
AAP12/5
AAP12/7
AAP12/9
AAP12/12
AAP12/19
AAP12/25
AAP12/37
AAP10/2
AAP10/3
AAP10/4
AAP10/5
AAP10/7
AAP10/9
AAP10/12
AAP10/19
AAP10/25
AAP10/37
A
r
m
o
r

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
59
Made in the USA
*Per NEC Table 310-16.
1
Includes encasement in concrete.
**Fillers used when required.
NOTE: The data shown is approximate and subject to standard industry tolerances.
NOTE: 4-Conductor ampacity assumes all four conductors are hot. If three are hot and one is a neutral, use the three conductor ampacity. 2011
Interlocked Armor
600 Volt
UL Type MC
Galvanized Steel or Aluminum
Copper XHHW-2
Standards:
UL 1569
Flame Rated: IEEE-383 (70,000 BTU),
ICEA T-29-520 (210,000 BTU),
IEEE 1202/CSA FT-4
Two-hour Firewall rated, (2/0 AWG and smaller)
Sunlight Resistant for CT Use; Direct Burial
1
,
Oil Resistant II Jacket
Color Code Black and Numbered / other color codes available
Temperature rating at 90 C Wet/Dry
ICEA S-95-658/NEMA WC-70
RoHS Compliant
Description:
3 or 4 conductors, stranded, insulated with heat and moisture
resistant cross-linked polyethylene (type XHHW-2), phase identi-
ed, cabled together with suitable llers** and bare copper ground
conductor(s). Cable core covered with binder tape, aluminum or
galvanized steel interlocked armor, with ame and sunlight resis-
tant black PVC jacket. Jacket available under armor and in other
colors.
Features:
Suitable for use in NEC Hazardous locations:
Class I, Div. 2 Class II, Div. 2


T
H
R
E
E

C
O
N
D
U
C
T
O
R
Strand
(no.)
Approx.
Diameter
Overall
(inch)
Approx. Net Wt.
per 1000 ft. (lbs.)
Copper
Grounding
Conductor(s)
(AWG)
Diameter
over
Armor
(inch)
PVC
Jacket
Thickness
(mils)
Alum.
Armor
Galv.
Armor 90 C
Ampacity*
(30 C
Ambient
Wet/Dry)
Size
AWG
or
MCM
Insulation
Thickness
(mils)
8 7 45 1-#10 .750 50 .850 399 486 55
6 7 45 1- #8 .830 50 .930 538 646 75
4 7 45 1- #8 .910 50 1.010 718 839 95
3 7 45 1 - #6 .970 50 1.070 873 1,003 110
2 7 45 1- #6 1.050 50 1.150 1,030 1,164 130
1 19 55 1- #6 1.150 50 1.250 1,243 1,402 150
1/0 19 55 1- #6 1.310 50 1.410 1,515 1,749 170
2/0 19 55 1- #6 1.410 50 1.510 1,814 2,071 195
3/0 19 55 1- #4 1.510 60 1.630 2,262 2,521 225
4/0 19 55 1- #4 1.630 60 1.750 2,725 3,043 260
250 37 65 1- #4 1.810 60 1.930 3,305 3,674 290
300 37 65 1- #3 1.930 60 2.050 3,881 4,267 320
350 37 65 1- #3 2.050 60 2.170 4,425 4,839 350
400 37 65 1- #3 2.170 60 2.290 4,966 5,397 380
500 37 65 1- #2 2.330 75 2.480 6,134 6,623 430
600 61 80 1- #2 2.570 75 2.720 7,301 7,835 475
750 61 80 1- #1 2.850 75 3.000 8,955 9,520 535
8 7 45 1-#10 .810 50 .910 478 575 44
6 7 45 1- #8 .910 50 1.010 656 768 60
4 7 45 1- #8 1.010 50 1.110 894 1,022 76
3 7 45 1- #6 1.070 50 1.170 1,084 1,222 88
2 7 45 1- #6 1.150 50 1.250 1,287 1,437 104
1 19 55 1- #6 1.330 50 1.430 1,598 1,857 120
1/0 19 55 1- #6 1.430 50 1.530 1,914 2,185 136
2/0 19 55 1- #6 1.550 60 1.670 2,340 2,629 156
3/0 19 55 1- #4 1.650 60 1.770 2,873 3,205 180
4/0 19 55 1- #4 1.790 60 1.910 3,484 3,849 208
250 37 65 1- #4 1.990 60 2.110 4,219 4,630 232
300 37 65 1- #3 2.130 60 2.250 4,866 5,409 256
350 37 65 1- #3 2.250 75 2.400 5,744 6,214 280
400 37 65 1- #3 2.160 75 2.520 6,451 6,938 304
500 37 65 1- #2 2.570 75 2.720 7,894 8,439 344
600 61 80 1- #2 2.850 75 3.000 9,425 10,035 380
750 61 80 1- #1 3.090 85 3.260 11,619 12,284 428
F
O
U
R

C
O
N
D
U
C
T
O
R
Part
Number
AAP8/3
AAP6/3
AAP4/3
AAP3/3
AAP2/3
AAP1/3
AAP1/03
AAP2/03
AAP3/03
AAP4/03
AAP250/3
AAP300/3
AAP350/3
AAP400/3
AAP500/3
AAP600/3
AAP750/3
AAP8/4
AAP6/4
AAP4/4
AAP3/4
AAP2/4
AAP1/4
AAP1/04
AAP2/04
AAP3/04
AAP4/04
AAP250/4
AAP300/4
AAP350/4
AAP400/4
AAP500/4
AAP600/4
AAP750/4
A
r
m
o
r

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
60
Made in the USA
*Per NEC Table 310-16.
1
Includes encasement in concrete.
**Fillers used when required.
NOTE: The data shown is approximate and subject to standard industry tolerances.
NOTE: 4-Conductor ampacity assumes all four conductors are hot. If three are hot and one is a neutral, use the three conductor ampacity. 2011
Interlocked Armor
600 Volt / UL Type MC
50% Ground
Galvanized Steel or Aluminum
Copper XHHW-2
Standards:
UL 1569
Flame Rated: IEEE-383 (70,000 BTU),
ICEA T-29-520 (210,000 BTU),
IEEE 1202/CSA FT-4
Two-hour Firewall rated, (2/0 AWG and smaller)
Sunlight Resistant for CT Use; Direct Burial
1
,
Oil Resistant II Jacket
Color Code Black and Numbered / other color codes available
Temperature rating at 90 C Wet/Dry
ICEA S-95-658/NEMA WC-70
RoHS Compliant
Description:
3 or 4 conductors, stranded, insulated with heat and moisture
resistant cross-linked polyethylene (type XHHW-2), phase identi-
ed, cabled together with suitable llers** and bare copper ground
conductor (3 segmented grounds). Cable core covered with binder
tape, aluminum or galvanized steel interlocked armor, with ame
and sunlight resistant black PVC jacket. Jacket available under
armor and in other colors.
Features:
Suitable for use in NEC Hazardous locations:
Class I, Div. 2 Class II, Div. 2



T
H
R
E
E

C
O
N
D
U
C
T
O
R
Strand
(no.)
Approx.
Diameter
Overall
(inch)
Approx. Net Wt.
per 1000 ft. (lbs.)
Copper
Grounding
Conductor(s)
(AWG)
Diameter
over
Armor
(inch)
PVC
Jacket
Thickness
(mils)
Alum.
Armor
Galv.
Armor 90 C
Ampacity*
(30 C
Ambient
Wet/Dry)
Size
AWG
or
MCM
Insulation
Thickness
(mils)
8 7 45 3-#14 .75 50 0.85 405 492 55
6 7 45 3-#12 .83 50 0.93 548 656 75
4 7 45 3-#10 .91 50 1.01 765 885 95
3 7 45 3-#10 .97 50 1.07 889 1,018 110
2 7 45 3-#8 1.05 50 1.15 1,103 1,238 130
1 19 55 3-#8 1.15 50 1.25 1,317 1,475 150
1/0 19 55 3-#6 1.31 50 1.41 1,680 1,914 170
2/0 19 55 3-#6 1.41 50 1.51 1,980 2,236 195
3/0 19 55 3-#4 1.51 60 1.63 2,525 2,784 225
4/0 19 55 3-#4 1.63 60 1.75 2,988 3,306 260
250 37 65 3-#4 1.81 60 1.93 3,551 3,920 290
300 37 65 3-#3 1.93 60 2.05 4,191 4,578 320
350 37 65 3-#2 2.05 60 2.17 4,855 5,272 350
400 37 65 3-#2 2.17 60 2.29 5,398 5,829 380
500 37 65 3-#1 2.33 75 2.48 6,681 7,170 430
600 61 80 3-1/0 2.57 75 2.72 8,042 8,576 475
750 61 80 3-2/0 2.85 75 3.00 9,891 10,456 535
8 7 45 3-#14 .81 50 .91 485 581 44
6 7 45 3-#12 .91 50 1.01 666 778 60
4 7 45 3-#10 1.01 50 1.11 940 1,068 76
3 7 45 3-#10 1.07 50 1.17 1,100 1,237 88
2 7 45 3-#8 1.15 50 1.25 1,360 1,510 104
1 19 55 3-#8 1.33 50 1.43 1,672 1,930 120
1/0 19 55 3-#6 1.43 50 1.53 2,079 2,351 136
2/0 19 55 3-#6 1.55 60 1.67 2,506 2,794 156
3/0 19 55 3-#4 1.65 60 1.77 3,136 3,468 180
4/0 19 55 3-#4 1.79 60 1.91 3,747 4,112 208
250 37 65 3-#4 1.99 60 2.11 4,466 4,877 232
300 37 65 3-#3 2.13 60 2.25 5,277 5,720 256
350 37 65 3-#2 2.25 75 2.40 6,176 6,647 280
400 37 65 3-#2 2.16 75 2.52 6,883 7,371 304
500 37 65 3-#1 2.57 75 2.72 8,442 8,986 344
600 61 80 3-1/0 2.85 75 3.00 10,167 10,776 380
750 61 80 3-2/0 3.09 85 3.26 12,555 13,219 428
F
O
U
R

C
O
N
D
U
C
T
O
R
Part
Number
AAP8/3G3#14
AAP6/3G3#12
AAP4/3G3#10
AAP3/3G3#10
AAP2/3G3#8
AAP1/3G3#8
AAP1/03G3#6
AAP2/03G3#6
AAP3/03G3#4
AAP4/03G3#4
AAP250/3G3#4
AAP300/3G3#3
AAP350/3G3#2
AAP400/3G3#2
AAP500/3G3#1
AAP600/3G3-1/0
AAP750/3G3-2/0
AAP8/4G3#14
AAP6/4G3#12
AAP4/4G3#10
AAP3/4G3#10
AAP2/4G3#8
AAP1/4G3#8
AAP1/04G3#6
AAP2/04G3#6
AAP3/04G3#4
AAP4/04G3#4
AAP250/4G3#4
AAP300/4G3#3
AAP350/4G3#2
AAP400/4G3#2
AAP500/4G3#1
AAP600/4G3-1/0
AAP750/4G3-2/0
A
r
m
o
r

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
61
Made in the USA
EnviroPlusTM Armor
Factory Mutual Group 1 listed
UL TYPE MC
600 Volt Interlocked Armor
Zero Halogen, Limited Smoke
Description:
Conductors are stranded annealed copper, insulated with 30 mils,
with heat and moisture resistant cross-linked polyethylene (Type
XHHW-2), phase identied, and cabled together with a **bare copper
ground conductor. Cable core is covered with binder tape, aluminum or
galvanized steel interlocked armor, with an overall ame and sunlight
resistant, Zero Halogen, Limited Smoke, Zero Lead jacket.
Standards:
UL1569
Cable passes IEEE 1202/CSA FT-4, IEEE 383,
UL 1685, UL 1581 Flame Tests
Factory Mutual Group 1 listed
Sunlight Resistant for CT use; Direct Burial
1
Two-hour Firewall rated, (2/0 AWG and smaller)
Temperature Rating: 90 C Wet/Dry
ICEA S-95-658/NEMA WC-70
Color Code: K-2 (Other colors available upon request)
Inner Conductors rated VW-1
Zero Halogen, Limited Smoke Jacket
RoHS Compliant
Available with tinned conductors.
#
1
4

A
W
G


#
1
2

A
W
G
#
1
0

A
W
G
Number
of
Conductors
2 14 .55 50 .65 174 25+
3 14 .55 50 .65 192 25+
4 14 .57 50 .67 214 20+
5 14 .59 50 .69 237 20+
7 14 .67 50 .77 297 17+
9 14 .75 50 .85 353 17+
12 14 .81 50 .91 420 12
19 14 .91 50 1.01 568 12
37 14 1.39 50 1.49 1,211 10
2 12 .55 50 .65 199 30+
3 12 .57 50 .67 230 30+
4 12 .61 50 .71 266 24+
5 12 .65 50 .75 303 24+
7 12 .75 50 .85 386 21+
9 12 .83 50 .93 458 21+
12 12 .89 50 .99 551 15
19 12 1.01 50 1.11 763 15
37 12 1.53 60 1.65 1,618 12
2 10 .59 50 .69 228 40+
3 10 .61 50 .71 262 40+
4 10 .67 50 .77 306 32+
5 10 .71 50 .81 346 32+
7 10 .83 50 .93 431 28
9 10 .93 50 1.03 515 28
12 10 .99 50 1.09 617 20
19 10 1.13 50 1.23 854 20
37 10 1.71 60 1.83 2,239 16
*Per NEC Table 310-16 (Ampacity derated in accordance with note 8a)
1
Includes encasement in concrete.
+The overcurrent protection shall not exceed 15 amps for 14 AWG, 20 amps for 12 AWG, and 30 amps for 10 AWG per NEC 310-16 footnote.
** Cable with 7 conductors or more shall have a green insulated ground.
NOTE: Drawing is for illustration purposes only. The data shown is approximate and subject to standard industry tolerances. 2011
Features:
Suitable for use in NEC Hazardous locations:
Class I, Div. 2; Class II, Div. 2
Ampacity*
30C Ambient
90C Wet / Dry
Net Weight
Per 1000'
(lbs)
Approximate
Overall
Diameter (inch)
Jacket
Thickness
(mils)
Diameter
over
Armor (inch)
Grounding
Conductors
(AWG)
Part
Number
AIANH14/2
AIANH14/3
AIANH14/4
AIANH14/5
AIANH14/7
AIANH14/9
AIANH14/12
AIANH14/19
AIANH14/37
AIANH12/2
AIANH12/3
AIANH12/4
AIANH12/5
AIANH12/7
AIANH12/9
AIANH12/12
AIANH12/19
AIANH12/37
AIANH10/2
AIANH10/3
AIANH10/4
AIANH10/5
AIANH10/7
AIANH10/9
AIANH10/12
AIANH10/19
AIANH10/37
A
r
m
o
r

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
62
Made in the USA
EnviroPlusTM Armor
Factory Mutual Group 1 listed
UL Type MC
600 Volt Interlocked Armor
Zero Halogen, Limited Smoke
Standards:
UL1569
Cable passes IEEE 1202/CSA FT-4, IEEE 383,
UL 1685, UL 1581 Flame Tests
Factory Mutual Group 1 listed
Sunlight resistant for CT use; Direct Burial
1
Two-hour Firewall rated, (2/0 AWG and smaller)
Temperature Rating: 90 C Wet/Dry
ICEA S-95-658/NEMA WC-70
Color Code K-2 (Other colors available upon request)
Zero Halogen, Limited Smoke Jacket
RoHS Compliant
Description:
3 or 4 conductors, stranded copper, insulated with heat and moisture
resistant cross-linked polyethylene (Type XHHW-2), phase identi-
ed, cabled together with suitable llers and bare copper ground
conductor(s). (2 grounds/4 conductors) Cable core is covered with
binder tape, aluminum or galvanized steel interlocked armor, with
ame and sunlight resistant, Zero Halogen, Limited Smoke, Zero
Lead Jacket.
Features:
Suitable for use in NEC Hazardous locations: Class I, Div. 2; Class II, Div. 2
Available with tinned conductors.



T
H
R
E
E

C
O
N
D
U
C
T
O
R
Strand
(no.)
Approx.
Diameter
Overall
(inch)
Approx. Net Wt.
per 1000 ft. (lbs.)
Copper
Grounding
Conductor(s)
(AWG)
Diameter
over Armor
(inch)
Jacket
Thickness
(mils)
Alum.
Armor
Galv.
Armor
Ampacity*
(30 C
Ambient
90 C
Wet/Dry)
Size
AWG
or
MCM
Insulation
Thickness
(mils)
8 7 45 1-#10 .750 50 .850 405 492 55
6 7 45 1- #8 .830 50 .930 545 653 75
4 7 45 1- #8 .910 50 1.010 726 846 95
3 7 45 1- #6 .970 50 1.07 881 1,011 110
2 7 45 1- #6 1.050 50 1.150 1,035 1,172 130
1 19 55 1- #6 1.150 50 1.250 1,252 1,411 150
1/0 19 55 1- #6 1.310 50 1.410 1,525 1,759 170
2/0 19 55 1- #6 1.410 50 1.510 1,825 2,082 195
3/0 19 55 1- #4 1.510 60 1.630 2,771 2,533 225
4/0 19 55 1- #4 1.630 60 1.750 2,741 3,058 260
250 37 65 1- #4 1.810 60 1.930 3,321 3,691 290
350 37 65 1- #3 2.050 60 2.170 4,444 4,858 350
500 37 65 1- #2 2.330 75 2.480 6,161 6,650 430
600 61 80 1- #2 2.570 75 2.720 7,331 7,864 475
750 61 80 1- #1 2.850 75 3.000 8,988 9,552 535
8 7 45 1-#10 .810 50 .910 485 581 44
6 7 45 1- #8 .910 50 1.010 663 775 60
4 7 45 1- #8 1.010 50 1.110 902 1,029 76
3 7 45 1- #6 1.070 50 1.170 1,093 1,230 88
2 7 45 1- #6 1.150 50 1.250 1,296 1,446 104
1 19 55 1- #6 1.330 50 1.430 1,609 1,867 120
1/0 19 55 1- #6 1.430 50 1.530 1,925 2,196 136
2/0 19 55 1- #6 1.550 60 1.670 2,355 2,643 156
3/0 19 55 1- #4 1.650 60 1.770 2,888 3,220 180
4/0 19 55 1- #4 1.790 60 1.910 3,501 3,866 208
250 37 65 1- #4 1.990 60 2.110 4,238 4,649 232
350 37 65 1- #3 2.250 75 2.400 5,770 6,241 280
500 37 65 1- #2 2.590 75 2.740 7,924 8,469 344
600 61 80 1- #2 2.850 75 3.000 9,458 10,067 380
750 61 80 1- #1 2.090 85 3.260 11,659 12,324 428
F
O
U
R

C
O
N
D
U
C
T
O
R
*Per NEC Table 310-16.
1
Includes encasement in concrete.
NOTE: Drawing is for illustration purposes only. The data shown is approximate and subject to standard industry tolerances.
NOTE: 4-Conductor ampacity assumes all four conductors are hot. If three are hot and one is a neutral, use the three conductor ampacity. 2011

Part
Number
AIANH8/3
AIANH6/3
AIANH4/3
AIANH3/3
AIANH2/3
AIANH1/3
AIANH1/03
AIANH2/03
AIANH3/03
AIANH4/03
AIANH250/3
AIANH350/3
AIANH500/3
AIANH600/3
AIANH750/3
AIANH8/4
AIANH6/4
AIANH4/4
AIANH3/4
AIANH2/4
AIANH1/4
AIANH1/04
AIANH2/04
AIANH3/04
AIANH4/04
AIANH250/4
AIANH350/4
AIANH500/4
AIANH600/4
AIANH750/4
A
r
m
o
r

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
63
Made in the USA Made in the USA
DESCRIPTION & FEATURES:
These U.L. listed connectors are a one-piece body construction
with a unique scroll design that can provide a 360 degree ground to
armor.
This connector provides a fast and easy installation, eliminates in-
ternal components, prevents cable pullout and saves time and labor.
CONSTRUCTION
Suitable for industrial and commercial use.
Manufactured from 6061 copper-free aluminum.
A complete range of NPT (National Pipe Thread) sizes are available
from 1/2" through 4". This accommodates armored cable type MC
O.D. sizes from 0.38 - 4.33".
UL Listed Connectors
Water Tight
For Interlocked Armor Cable
with Jacket
Listings:
UL: Class I* Group A, B, C and D
Class II* Group E, F and G
Class III
* Includes Division 1 and Division 2
Part
Number
Copper
AIA-PVC
O.D.
Range
Part
Number
Copper
AIA-PVC
O.D.
Range
Part
Number
Copper
AIA-PVC
O.D.
Range
8/22/2011
14/2 AAP CONW56 .500 - .560 10/3 AAP CONW62 .560 - .620 1/04 AAP CONW148 1.390 - 1.480
14/3 AAP CONW56 .500 - .560 10/4 AAP CONW69 .620 - .690 2/03 AAP CONW148 1.390 - 1.480
14/4 AAP CONW56 .500 - .560 10/5 AAP CONW76 .690 - .760 2/04 AAP CONW157 1.480 - 1.570
14/5 AAP CONW62 .560 - .620 10/7 AAP CONW83 .760 - .830 3/03 AAP CONW157 1.480 - 1.570
14/7 AAP CONW69 .620 - .690 10/9 AAP CONW97 .900 - .970 3/04 AAP CONW175 1.660 - 1.750
14/9 AAP CONW76 .690 - .760 10/19 AAP CONW118 1.110 - 1.180 4/03 AAP CONW166 1.570 - 1.660
14/12 AAP CONW83 .760 - .830 10/25 AAP CONW139 1.320 - 1.390 4/04 AAP CONW184 1.750 - 1.840
14/19 AAP CONW104 .970 - 1.040 10/37 AAP CONW157 1.480 - 1.570 250/3 AAP CONW184 1.750 - 1.840
14/25 AAP CONW104 .970 - 1.040 8/3 AAP CONW76 .690 - .760 250/4 AAP CONW202 1.930 - 2.020
14/37 AAP CONW125 1.180 - 1.250 8/4 AAP CONW83 .760 - .830 300/3 AAP CONW202 1.930 - 2.020
12/2 AAP CONW56 .500 - .560 6/3 AAP CONW83 .760 - .830 300/4 AAP CONW224 2.130 - 2.240
12/3 AAP CONW56 .500 - .560 6/4 AAP CONW97 .900 - .970 350/3 AAP CONW213 2.020 - 2.130
12/4 AAP CONW62 .560 - .620 4/3 AAP CONW97 .900 - .970 350/4 AAP CONW235 2.240 - 2.350
12/5 AAP CONW69 .620 - .690 4/4 AAP CONW104 .970 - 1.040 400/3 AAP CONW224 2.130 - 2.240
12/7 AAP CONW76 .690 - .760 3/3 AAP CONW104 .970 - 1.040 400/4 AAP CONW246 2.350 - 2.460
12/9 AAP CONW83 .760 - .830 3/4 AAP CONW111 1.040 - 1.110 500/3 AAP CONW235 2.240 - 2.350
12/12 AAP CONW90 .830 - .900 2/3 AAP CONW111 1.040 - 1.110 500/4 AAP CONW257 2.460 - 2.570
12/19 AAP CONW104 .970 - 1.040 2/4 AAP CONW125 1.180 - 1.250 600/3 AAP CONW257 2.460 - 2.570
12/25 AAP CONW111 1.040 - 1.110 1/3 AAP CONW125 1.180 - 1.250 600/4 AAP CONW285 2.710 - 2.850
12/37 AAP CONW139 1.320 - 1.390 1/4 AAP CONW139 1.320 - 1.390 750/3 AAP CONW285 2.710 - 2.850
10/2 AAP CONW62 .560 - .620 1/03 AAP CONW139 1.320 - 1.390 750/4 AAP CONW313 2.990 - 3.130
A
r
m
o
r

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
64
Made in the USA
Teck Armor
600 Volt/C(UL) Type MC
Inner/Outer Jacket
Copper XHHW-2
Standards:
UL 1569
C(UL) Teck 90:CSA/UL Listed
Flame Rated: IEEE-383 (70,000 BTU),
ICEA T-29-520 (210,000 BTU), / FT4 Flame Test
IEEE 1202/CSA FT-4
Two-hour Firewall rated
Sunlight Resistant for CT Use; Direct Burial
1
,
Oil Resistant II Jacket
Color Code K-2/other color codes available
Temperature rating at 90 C Wet/Dry
ICEA S-95-658/NEMA WC-70
RoHS Compliant
Description:
Class B stranded copper, insulated with heat and moisture resistant
cross-linked polyethylene (type XHHW-2), phase identied, cabled
with **bare copper ground conductor. Cable core covered with
binder tape, an inner PVC jacket, aluminum interlocked armor and
an outer PVC jacket.
Features:
Teck cable is suitable for use in exposed or concealed wiring in dry
or wet locations, in ventilated or ladder type cable trays in dry or wet
conditions, on walls or beams, or directly buried. Suitable for use in
NEC Hazardous locations: Class I Groups A, B, C and D; Class II
Groups E, F and G; Class III All Groups
#
1
4

A
W
G


#
1
2

A
W
G
#
1
0

A
W
G
Number
of
Conductors
2 14 50 50 .401 .610 .710 218 25+
3 14 50 50 .422 .630 .730 243 25+
4 14 50 50 .456 .670 .770 274 20+
5 14 50 50 .494 .690 .790 300 20+
7 14 50 50 .575 .770 .870 367 17+
9 14 50 50 .653 .850 .950 429 17+
12 14 50 50 .704 .910 1.010 501 12
19 14 50 50 .812 1.010 1.110 658 12
2 12 50 50 .439 .650 .750 257 30+
3 12 50 50 .462 .670 .770 290 30+
4 12 50 50 .502 .710 .810 330 24+
5 12 50 50 .545 .750 .850 370 24+
7 12 50 50 .638 .850 .950 461 21+
9 12 50 50 .727 .930 1.030 541 21+
12 12 50 50 .784 .990 1.090 639 15
19 12 50 50 .909 1.110 1.210 862 15
2 10 50 50 .488 .690 .790 290 40+
3 10 50 50 .515 .710 .810 326 40+
4 10 50 50 .561 .770 .870 375 32+
5 10 50 50 .611 .810 .910 418 32+
7 10 50 50 .719 .930 1.030 513 28
9 10 50 50 .822 1.030 1.130 606 28
12 10 50 50 .889 1.090 1.190 714 20
19 10 50 50 1.034 1.270 1.370 965 20
*Per NEC - Table 310-16
1
Includes encasement in concrete.
** Cable with 7 conductors or more shall have a green insulated ground.
Fillers used when required.
NOTE: The data shown is approximate and subject to standard industry tolerances 2011
Diameter PVC Jacket Thickness Ampacity*
90
Ambient
Approximate
Net Weight
Per 1000' (lbs)
Overall Armor Inner
Jacket
Outer
(mils)
Inner
(mils)
Grounding
Conductors
(AWG)
Part
Number
TECK14/2
TECK14/3
TECK14/4
TECK14/5
TECK14/7
TECK14/9
TECK14/12
TECK14/19
TECK12/2
TECK12/3
TECK12/4
TECK12/5
TECK12/7
TECK12/9
TECK12/12
TECK12/19
TECK10/2
TECK10/3
TECK10/4
TECK10/5
TECK10/7
TECK10/9
TECK10/12
TECK10/19
A
r
m
o
r

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
65
Made in the USA
Teck Armor
600 Volt/C(UL) Type MC
Inner/Outer Jacket
Copper XHHW-2
Standards:
UL 1569
C(UL) Teck 90:CSA/UL Listed
Flame Rated: IEEE-383 (70,000 BTU),
ICEA T-29-520 (210,000 BTU),
IEEE 1202/CSA FT-4
Two-hour Firewall rated, (2/0 AWG and smaller)
Sunlight Resistant for CT Use; Direct Burial
1
,
Oil Resistant II Jacket
Color Code Black and Numbered / other color codes available
Temperature rating at 90 C Wet/Dry
ICEA S-95-658/NEMA WC-70
RoHS Compliant
Description:
Stranded copper, insulated with heat and moisture resistant cross-
linked polyethylene (type XHHW-2), phase identied, cabled with
bare copper ground conductor(s). Cable core covered with binder
tape, an inner PVC jacket, aluminum interlocked armor and an
outer PVC jacket.
Features:
Teck cable is suitable for use in exposed or concealed wiring in dry
or wet locations, in ventilated or ladder type cable trays in dry or
wet conditions, on walls or beams, directly buried. Suitable for use
in NEC Hazardous locations: Class I Groups A, B, C and D; Class
II Groups E, F and G; Class III All Groups



T
H
R
E
E

C
O
N
D
U
C
T
O
R
Strand
(no.)
Overall
Approx.
Net Wt.
per
1000 ft. (lbs.)
Copper
Grounding
Conductor(s)
(AWG)
Inner
Jacket
Armor
Ampacity*
90 C
Size
AWG
or
MCM
Insulation
Thickness
(mils)
8 7 45 1-#10 50 50 .645 .850 .950 481 55
6 7 45 1- #8 50 50 .726 .930 1.030 650 75
4 7 45 1- #8 50 50 .830 1.030 1.130 851 95
3 7 45 1- #6 50 50 .890 1.090 1.190 1,015 110
2 7 45 1- #6 50 50 .959 1.230 1.330 1,192 130
1 19 55 1- #6 50 50 1.065 1.330 1.430 1,454 150
1/0 19 55 1- #6 50 50 1.149 1.430 1.530 1,717 170
2/0 19 55 1- #6 50 60 1.250 1.510 1.630 2,067 195
3/0 19 55 1- #4 50 60 1.351 1.630 1.750 2,515 225
4/0 19 55 1- #4 50 60 1.472 1.750 1.870 3,012 260
250 37 65 1- #4 60 60 1.675 1.950 2.070 3,568 290
350 37 65 1- #3 60 60 1.904 2.170 2.290 4,722 350
500 37 65 1- #2 60 75 2.192 2.470 2.620 6,494 430
600 61 80 1- #2 75 75 2.455 2.730 2.880 7,784 475
750 61 80 1- #1 75 75 2.681 2.970 3.120 9,480 535
8 7 45 1-#10 50 50 .706 .910 1.010 566 44
6 7 45 1- #8 50 50 .798 1.010 1.110 777 60
4 7 45 1- #8 50 50 .913 1.110 1.210 1,032 76
3 7 45 1- #6 50 50 .981 1.230 1.330 1,240 88
2 7 45 1- #6 50 50 1.058 1.330 1.430 1,488 104
1 19 55 1- #6 50 50 1.177 1.430 1.530 1,792 120
1/0 19 55 1- #6 50 60 1.271 1.550 1.670 2,167 136
2/0 19 55 1- #6 50 60 1.384 1.650 1.770 2,587 156
3/0 19 55 1- #4 50 60 1.498 1.790 1.910 3,157 180
4/0 19 55 1- #4 60 60 1.653 1.930 2.090 3,837 208
250 37 65 1- #4 60 60 1.858 2.130 2.250 4,508 232
350 37 65 1- #3 60 75 2.114 2.390 2.540 6,081 280
500 37 65 1- #2 60 75 2.467 2.710 2.860 8,291 344
600 61 80 1- #2 75 85 2.728 3.010 3.180 10,018 380
750 61 80 1- #1 75 85 2.982 3.250 3.420 12,215 428
* Per NEC 310-16
1
Includes encasement in concrete. ** Fillers used when required.
NOTE: The data shown is approximate and subject to standard industry tolerances
NOTE: 4-Conductor ampacity assumes all four conductors are hot. If three are hot and one is a neutral, use the three conductor ampacity. 2011
Diameter
F
O
U
R

C
O
N
D
U
C
T
O
R
PVC Jacket
Thickness (mils)
Inner Outer
Part
Number
TECK8/3
TECK6/3
TECK4/3
TECK3/3
TECK2/3
TECK1/3
TECK1/03
TECK2/03
TECK3/03
TECK4/03
TECK250/3
TECK350/3
TECK500/3
TECK600/3
TECK750/3
TECK8/4
TECK6/4
TECK4/4
TECK3/4
TECK2/4
TECK1/4
TECK1/04
TECK2/04
TECK3/04
TECK4/04
TECK250/4
TECK350/4
TECK500/4
TECK600/4
TECK750/4
A
r
m
o
r

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
66
Made in the USA
ServiceDrive ASD/VFD
Shielded Interlocked
Armor Drive Cable
600 Volt / UL Type MC Shielded
Patented or Galvanized Steel,
Copper XHHW-2
Description:
3 conductors, stranded, insulated with heat and moisture resistant
cross-linked polyethylene, phase identied, cabled together with suit-
able llers** and 3 symmetrical copper ground conductors. Cable core
covered with binder tape, 5-mil helical copper tape shield, galvanized
steel interlocked armor, with ame and sunlight resistant PVC jacket
overall. Jacket available in colors.
Features:
Suitable for use in NEC Hazardous Locations:
Class I - Div 2, Class II - Div 2, and Class III, Div 1 and 2
For use in ASD / VFD applications
Standards:
UL 1569
Flame Rated: IEEE 383 (70,000 BTU),
ICEA T-29-520 (210,000 BTU),
IEEE 1202 / CSA FT-4
Two-hour Firewall rated, (2/0 AWG and smaller)
Sunlight Resistant, for CT Use; Direct Burial
1
Oil Resistant II Jacket
Color Code: Black and Numbered
Temperature Rating: 90 C Wet / Dry
ICEA S-95-658 / NEMA WC-70
RoHS Compliant
T
H
R
E
E

C
O
N
D
U
C
T
O
R
Strand
(no.)
Approx.
Diameter
Overall
(inch)
Approx.
Net Wt.
per 1000 ft.
(lbs.)
Copper
Grounding
Conductor(s)
(AWG)
Diameter
over Armor
(inch)
PVC
Jacket
Thickness
(mils)
90 C
Ampacity*
(30 C
Ambient
Wet/Dry)
Size
AWG
or
MCM
Insulation
Thickness
(mils)
14 7 45 3-#14 .61 50 0.71 359 25+
12 7 45 3-#14 .65 50 0.75 407 30+
10 7 45 3-#14 .71 50 0.81 482 40+
8 7 45 3-#14 .73 50 0.83 555 55
6 7 45 3-#12 .81 50 0.91 722 75
4 7 45 3-#10 .93 50 1.03 979 95
3 7 45 3-#10 .99 50 1.09 1,122 110
2 7 45 3-#8 1.05 50 1.15 1,350 130
1 19 55 3-#8 1.15 50 1.25 1,599 150
1/0 19 55 3-#6 1.31 50 1.41 2,069 170
2/0 19 55 3-#6 1.41 50 1.51 2,413 195
3/0 19 55 3-#4 1.51 60 1.63 2,994 225
4/0 19 55 3-#4 1.63 60 1.75 3,513 260
250 37 65 3-#4 1.81 60 1.93 4,062 290
350 37 65 3-#2 2.05 60 2.17 5,445 350
500 37 65 3-#1 2.33 75 2.48 7,359 430
600 61 80 3-1/0 2.57 75 2.72 8,797 475
750 61 80 3-2/0 2.85 75 3.00 10,731 535
*Per NEC Table 310-16.
1
Includes encasement in concrete. **Fillers used when required.
+ The overcurrent protection for items marked with an obelisk (+) shall not exceed 15 amps for 14 AWG, 20 amps for 12 AWG, and 30 amps for 10
AWG per NEC 310-16 footnote.
Note: The data shown is approximate and subject to standard industry tolerances. 2011
Part
Number
ASDP14/3
ASDP12/3
ASDP10/3
ASDP8/3
ASDP6/3
ASDP4/3
ASDP3/3
ASDP2/3
ASDP1/3
ASDP1/03
ASDP2/03
ASDP3/03
ASDP4/03
ASDP250/3
ASDP350/3
ASDP500/3
ASDP600/3
ASDP750/3
Available with tinned conductors.
A
r
m
o
r

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
67
Made in the USA
Description:
3 conductors, stranded, insulated with heat and moisture resistant
cross-linked polyethylene, phase identied, cabled together with suit-
able llers and 3 symmetrical copper ground conductors. Cable core
covered with binder tape, 5-mil helical copper tape shield, aluminum
or galvanized steel interlocked armor, with ame and sunlight resistant
zero halogen, limited smoke, zero lead jacket overall.
Features:
Suitable for use in NEC Hazardous Locations:
Class I - Div 2, Class II - Div 2, and Class III, Div 1 and 2
For use in ASD / VFD applications.
Standards:
UL 1569
Flame Rated: IEEE 383 (70,000 BTU),
IEEE 1202 / CSA FT-4, UL 1685 LS
Factory Mutual Group 1 listed
Two-hour Firewall rated, (2/0 AWG and smaller)
Sunlight Resistant, for CT Use; Direct Burial
1
Color Code: Black and Numbered
Temperature Rating: 90 C Wet / Dry
ICEA S-95-658 / NEMA WC-70
Zero Halogen, Limited Smoke Jacket
RoHS Compliant
ServiceDrive Plus ASD/VFD
Shielded Interlocked Armor
Drive Cable
600 Volt / UL Type MC Shielded
Patented, Factory Mutual Group
1 Listed, Galvanized Steel, Copper
XHHW-2, Zero Halogen, Limited Smoke
T
H
R
E
E

C
O
N
D
U
C
T
O
R
Strand
(no.)
Approx.
Diameter
Overall
(inch)
Approx.
Net Wt.
per 1000 ft.
(lbs.)
Copper
Grounding
Conductor(s)
(AWG)
Diameter
over Armor
(inch)
Jacket
Thickness
(mils)
90 C
Ampacity*
(30 C
Ambient
Wet/Dry)
Size
AWG
or
MCM
Insulation
Thickness
(mils)
14 7 45 3-#14 .61 50 0.71 364 25+
12 7 45 3-#14 .65 50 0.75 412 30+
10 7 45 3-#14 .71 50 0.81 487 40+
8 7 45 3-#14 .73 50 0.83 561 55
6 7 45 3-#12 .81 50 0.91 728 75
4 7 45 3-#10 .93 50 1.03 986 95
3 7 45 3-#10 .99 50 1.09 1,130 110
2 7 45 3-#8 1.05 50 1.15 1,358 130
1 19 55 3-#8 1.15 50 1.25 1,608 150
1/0 19 55 3-#6 1.31 50 1.41 2,079 170
2/0 19 55 3-#6 1.41 50 1.51 2,423 195
3/0 19 55 3-#4 1.51 60 1.63 3,008 225
4/0 19 55 3-#4 1.63 60 1.75 3,528 260
250 37 65 3-#4 1.81 60 1.93 4,078 290
350 37 65 3-#2 2.05 60 2.17 5,464 350
500 37 65 3-#1 2.33 75 2.48 7,386 430
600 61 80 3-1/0 2.57 75 2.72 8,827 475
750 61 80 3-2/0 2.85 75 3.00 10,764 535
*Per NEC Table 310-16.
1
Includes encasement in concrete. **Fillers used when required.
+ The overcurrent protection for items marked with an obelisk (+) shall not exceed 15 amps for 14 AWG, 20 amps for 12 AWG, and 30 amps for 10 AWG
per NEC 310-16 footnote.
Note: The data shown is approximate and subject to standard industry tolerances. 2011
Part
Number
ASDE14/3
ASDE12/3
ASDE10/3
ASDE8/3
ASDE6/3
ASDE4/3
ASDE3/3
ASDE2/3
ASDE1/3
ASDE1/03
ASDE2/03
ASDE3/03
ASDE4/03
ASDE250/3
ASDE350/3
ASDE500/3
ASDE600/3
ASDE750/3
Available with tinned conductors.
Manufacturing quality. Delivering service.
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
68
Made in the USA
ServiceDrive and ServiceDrive Plus
ASD/VFD Armor Connectors, Termination Kit
Corresponding Part Numbers
SIZE CABLE CONNECTOR TERMINATION KIT
AWG OR MCM PART NUMBER PART NUMBER PART NUMBER
14 ASDE14/3 CONASD14/3 TERASD14-1/3
12 ASDE12/3 CONASD12/3 TERASD14-1/3
10 ASDE10/3 CONASD10/3 TERASD14-1/3
8 ASDE8/3 CONASD8/3 TERASD14-1/3
6 ASDE6/3 CONASD6/3 TERASD14-1/3
4 ASDE4/3 CONASD4/3 TERASD14-1/3
3 ASDE3/3 CONASD3/3 TERASD14-1/3
2 ASDE2/3 CONASD2/3 TERASD14-1/3
1 ASDE1/3 CONASD1/3 TERASD14-1/3
1/0 ASDE1/03 CONASD1/03 TERASD1/0-3/03
2/0 ASDE2/03 CONASD2/03 TERASD1/0-3/03
3/0 ASDE3/03 CONASD3/03 TERASD1/0-3/03
4/0 ASDE4/03 CONASD4/03 TERASD4/0-400/3
250 ASDE250/3 CONASD250/3 TERASD4/0-400/3
350 ASDE350/3 CONASD350/3 TERASD4/0-400/3
500 ASDE500/3 CONASD500/3 TERASD500-750/3
600 ASDE600/3 CONASD600/3 TERASD500-750/3
750 ASDE750/3 CONASD750/3 TERASD500-750/3
2011
A
S
D
/
V
F
D

C
o
n
n
e
c
t
o
r
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
69
Made in the USA
DESCRIPTION & FEATURES:
These patented connectors are designed exclusively to terminate
ASD/VFD cables in control centers, panel boards, junction boxes
and motor control enclosures.
ServiceDrive ASD/VFD
Armor Cable Connectors
Patented for use with ServiceDrive
and ServiceDrive Plus Cable System
PART NUMBER WIRE SIZE HUB SIZE SET SCREW SIZE
CONASD14/3 14 AWG 3 COND 3/4 10/32 X 1/4
CONASD12/3 12 AWG 3 COND 3/4 10/32 X 1/4
CONASD10/3 10 AWG 3 COND 3/4 10/32 X 1/4
CONASD8/3 8 AWG 3 COND 3/4 10/32 X 1/4
CONASD6/3 6 AWG 3 COND 1-1/4 1/4-20 X 1/4
CONASD4/3 4 AWG 3 COND 1-1/4 1/4-20 X 1/4
CONASD3/3 3 AWG 3 COND 1-1/4 1/4-20 X 1/4
CONASD2/3 2 AWG 3 COND 1-1/4 1/4-20 X 1/4
CONASD1/3 1 AWG 3 COND 1-1/4 1/4-20 X 1/4
CONASD1/03 1/0 AWG 3 COND 1-1/2 1/4-20 X 1/4
CONASD2/03 2/0 AWG 3 COND 1-1/2 1/4-20 X 1/4
CONASD3/03 3/0 AWG 3 COND 1-1/2 1/4-20 X 1/4
CONASD4/03 4/0 AWG 3 COND 2 1/4-20 X 5/16
CONASD250/3 250 MCM 3 COND 2 1/4-20 X 5/16
CONASD300/3 300 MCM 3 COND 2 1/4-20 X 5/16
CONASD350/3 350 MCM 3 COND 2-1/2 5/16-18 X 3/8
CONASD400/3 400 MCM 3 COND 2-1/2 5/16-18 X 3/8
CONASD500/3 500 MCM 3 COND 2-1/2 5/16-18 X 3/8
CONASD600/3 600 MCM 3 COND 3 5/16-18 X 3/8
CONASD750/3 750 MCM 3 COND 3 5/16-18 X 3/8

Listings:
Class 1, Div. 2 and Class 2, Div. 1 & 2
CSA Standard: C22.2 #18.98
NEMA 4
IP65
2011
A
S
D
/
V
F
D

T
e
r
m
i
n
a
t
i
o
n

K
i
t
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
70
Made in the USA
FEATURES:
1. Flat tinned Copper braid Woven tinned copper construction
2. Stainless steel spring clamp
3. Adhesive-backed copper foil tape Shields against EMI/RFI
radiation. Conductive through the adhesive.
ASD/VFD Termination Kit
For use with ServiceDrive
and ServiceDrive Plus
Armor and Tray Cable
Applications:
Used to properly terminate the helically applied copper
tape shield of ASD/VFD cable constructions.
Listings:
Braid QC-W-343 Type S and ASTM B-33
Copper Foil Tape UL 510 for ame retardancy
PART NUMBER DESCRIPTION
TERASD14-1/3 For use with 14 awg - 1 awg shielded armor and tray cable
TERASD1/0-3/03 For use with 1/0 awg - 3/0 awg shielded armor and tray cable
TERASD4/0-400/3 For use with 4/0 awg - 400 mcm shielded armor and tray cable
TERASD500-750/3 For use with 500 mcm - 750 mcm shielded armor and tray cable
2011
A
r
m
o
r

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
71
Made in the USA
Interlocked Armor
2000 Volt Type MC
Galvanized Steel or Aluminum
Copper RHH or RHW-2
Description:
3 Conductors, stranded, insulated with heat and moisture resistant
cross-linked polyethylene, phase identied, cabled together with
suitable llers and bare copper grounding conductor. Cable core
covered with binder tape, aluminum or galvanized steel interlocked
armor, with ame, oil and sunlight resistant black PVC jacket.
Jacket available under armor and in other colors. Available with
EnviroPlus

jacket.
Application:
Service Wires 2000 Volt Interlocked Armor Cables are designed
for use in industrial power distribution systems where continuity of
service is the prime consideration. These cables may be installed
in wet or dry locations, directly buried or embedded in concrete.
Cables are also suitable for use in cable tray.
Standards:
ICEA S-95-658 / NEMA WC-70
UL 44
UL 854
UL 1569
Features:
Temperature rating 90 C Wet /Dry
Flame Rated: IEEE-383 (70,000 BTU),
ICEA T-29-520 (210,000 BTU),
IEEE 1202/CSA FT-4
Two-hour Firewall rated, (2/0 AWG and smaller)
Sunlight Resistant for CT Use; Direct Burial
1
,
Oil Resistant II Jacket
Excellent mechanical protection
Suitable for use in NEC Hazardous locations:
Class I, Div. 2; Class II, Div. 2
Factory Mutual Group 1 upon request.
RoHS Compliant
Size
AWG
or
MCM
Strand
(no.)
Insulation
Thickness
(mils)
Copper
Grounding
Conductor(s)
(AWG)
Diameter
over
Armor
(inch)
PVC
Jacket
Thickness
(mils)
Approx.
Diameter
Overall
(inch) Alum.
Armor
Galv.
Armor
Approx. Net Wt.
per 1000 ft. (lbs.)
Ampacity*
(30 C
Ambient)
6 7 70 8 .93 50 1.03 657 715 75
4 7 70 6 1.03 50 1.13 848 948 95
2 7 70 6 1.27 50 1.37 1,224 1,258 130
1 7 90 6 1.37 50 1.47 1,399 1,653 150
1/0 19 90 6 1.47 50 1.57 1,649 1,906 170
2/0 19 90 6 1.55 60 1.67 2,031 2,276 195
3/0 19 90 4 1.67 60 1.79 2,416 2,726 225
4/0 19 90 4 1.79 60 1.91 2,890 3,235 260
250 37 105 4 1.99 60 2.11 3,693 3,915 290
350 37 105 3 2.25 75 2.40 4,926 5,180 350
500 37 105 2 2.53 75 2.68 6,621 6,918 430
750 61 120 1 2.97 75 3.12 9,543 9,884 535
T
H
R
E
E

C
O
N
D
U
C
T
O
R
*Per NEC Table 310-16.
1
Includes encasement in concrete.
NOTE: The data shown is approximate and subject to standard industry tolerances. 2011
Part
Number
AAP2K6/3
AAP2K4/3
AAP2K2/3
AAP2K1/3
AAP2K1/03
AAP2K2/03
AAP2K3/03
AAP2K4/03
AAP2K250/3
AAP2K350/3
AAP2K500/3
AAP2K750/3
A
r
m
o
r

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
72
Made in the USA
Interlocked Armor
2000 Volt Type MC
Galvanized Steel or Aluminum
Copper RHH or RHW-2
Standards:
ICEA S-95-658 / NEMA WC-70
UL 44
UL 854
UL 1569
Features:
Temperature rating 90 C Wet /Dry
Flame Rated: IEEE-383 (70,000 BTU),
ICEA T-29-520 (210,000 BTU),
IEEE 1202/CSA FT-4
Two-hour Firewall rated, (2/0 AWG and smaller)
Sunlight Resistant for CT Use; Direct Burial
1
,
Oil Resistant II Jacket
Excellent mechanical protection
Suitable for use in NEC Hazardous locations:
Class I, Div. 2; Class II, Div. 2
Factory Mutual Group 1 upon request.
RoHS Compliant
Description:
4 Conductors, stranded, insulated with heat and moisture resis-
tant cross-linked polyethylene, phase identied, cabled together
with suitable llers and bare copper grounding conductor(s).
Cable core covered with binder tape, aluminum or galvanized
steel interlocked armor, with ame, oil and sunlight resistant black
PVC jacket. Jacket available under armor and in other colors.
Available with EnviroPlus

jacket.
Application:
Service Wires 2000 Volt Interlocked Armor Cables are designed
for use in industrial power distribution systems where continuity of
service is the prime consideration. These cables may be installed
in wet or dry locations, directly buried or embedded in concrete.
Cables are also suitable for use in cable tray.
Size
AWG
or
MCM
Strand
(no.)
Insulation
Thickness
(mils)
Copper
Grounding
Conductor(s)
(AWG)
Diameter
over
Armor
(inch)
PVC
Jacket
Thickness
(mils)
Approx.
Diameter
Overall
(inch) Alum.
Armor
Galv.
Armor
Approx. Net Wt.
per 1000 ft. (lbs.)
Ampacity*
(30 C
Ambient)
6 7 70 8 1.01 50 1.11 804 856 60
4 7 70 8 1.13 50 1.23 1,057 1,152 76
2 7 70 6 1.41 50 1.51 1,535 1,550 104
1 7 90 6 1.51 60 1.63 1,789 2,061 120
1/0 19 90 6 1.61 60 1.73 2,116 2,410 136
2/0 19 90 4 1.71 60 1.83 2,567 2,833 156
3/0 19 90 4 1.83 60 1.95 3,068 3,409 180
4/0 19 90 4 1.97 60 2.09 3,693 4,063 208
250 37 105 4 2.21 60 2.33 4,724 4,928 232
350 37 105 3 2.45 75 2.60 6,300 6,545 280
500 37 105 2 2.77 75 2.92 8,514 8,815 344
750 61 120 1 3.29 85 3.46 12,408 12,713 428
F
O
U
R

C
O
N
D
U
C
T
O
R
*Per NEC Table 310-16.
1
Includes encasement in concrete.
NOTE: The data shown is approximate and subject to standard industry tolerances.
NOTE: 4-Conductor ampacity assumes all four conductors are hot. If three are hot and one is a neutral, use the three conductor ampacity. 2011
Part
Number
AAP2K6/4
AAP2K4/4
AAP2K2/4
AAP2K1/4
AAP2K1/04
AAP2K2/04
AAP2K3/04
AAP2K4/04
AAP2K250/4
AAP2K350/4
AAP2K500/4
AAP2K750/4
A
r
m
o
r

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
73
Made in the USA
Standards:
UL 1072
Flame Rated: IEEE-383 (70,000 BTU),
ICEA T-29-520 (210,000 BTU),
IEEE 1202/CSA FT-4
Class 1 Div II
Sunlight Resistant for CT Use; Direct Burial
1
,
Two-hour Firewall rated, (2/0 AWG and smaller)
Oil Resistant II Jacket
Color Code K-2/other color codes available
Conductors rated at 105 C (5kV) / 90 C (2.4kV)
Non-shielded: ICEA S-96-659/NEMA WC-71
Shielded: ICEA S-93-639/NEMA WC-74
RoHS Compliant
Interlocked Armor
5kV/2.4kV MV-105/MV-90
Nonshielded/Shielded
UL Type MC
Galvanized Steel or Aluminum
5000/2400 Volt Copper EPR
Description:
Nonshielded: Class B stranded copper, extruded conductor shield,
insulated with heat and moisture resistant ethylene propylene rubber
(2,400 Volt rated).
Shielded: Class B stranded copper, extruded conductor shield, heat
and moisture resistant ethylene propylene rubber (100% and 133%
insulation level), semi-conducting insulation shield, copper shield,
and overall PVC jacket. 3 conductors cabled together with suitable
llers** and bare copper ground conductor. Cable core covered with
binder tape, aluminum or galvanized interlocked armor, with ame
and sunlight resistant yellow PVC jacket. Jacket available under
armor and in other colors.
6 7 125 80 6 1.65 60 1.77 1,234 1,555 69
4 7 125 80 6 1.75 60 1.87 1,463 1,818 91
2 7 125 80 6 1.89 60 2.01 1,795 2,172 125
1 19 125 80 4 1.95 60 2.07 2,076 2,467 140
1/0 19 125 80 4 2.03 60 2.15 2,345 2,765 165
2/0 19 125 80 4 2.17 60 2.29 2,693 3,124 190
4/0 19 125 95 3 2.49 75 2.64 4,015 4,530 255
250 37 140 110 3 2.65 75 2.80 4,769 5,332 280
350 37 140 110 2 2.89 75 3.04 6,017 6,635 350
500 37 140 110 1 3.17 85 3.34 7,881 8,564 425
750 61 155 125 1/0 3.69 85 3.86 11,594 12,397 525
6 7 115 60 6 1.75 60 1.87 1,478 1,833 69
4 7 115 60 6 1.89 60 2.01 1,765 2,142 91
2 7 115 60 6 1.99 60 2.11 2,085 2,496 125
1 19 115 60 4 2.09 60 2.21 2,889 2,889 140
1/0 19 115 80 4 2.27 75 2.42 2,898 3,374 165
2/0 19 115 80 4 2.37 75 2.52 3,268 3,766 190
4/0 19 115 80 3 2.57 75 2.72 4,255 4,800 255
250 37 115 80 3 2.71 75 2.86 5,075 5,641 280
350 37 115 80 2 2.91 75 3.06 6,326 6,950 350
500 37 115 80 1 3.25 85 3.42 8,650 9,352 425
750 61 115 80 1/0 3.65 85 3.65 11,827 12,621 525
Size
AWG
or
MCM
Jacket
Thickness
(mils)
Insulation
Thickness
(mils)
Diameter
over
Armor
(inch)
Copper
Grounding
Conductor(s)
(AWG)
PVC
Jacket
Thickness
(mils)
Approx.
Diameter
Overall
(inch)
Alum.
Armor
Galv.
Armor
Ampacity*
(40 C
Ambient)
Conductor
Strand
(no.)
S
H
I
E
L
D
E
D
N
O
N
-
S
H
I
E
L
D
E
D
Approx. Net Wt.
per 1000 ft. (lbs.)
*Per NEC Table 310-75. Based on one three-conductor cable.
1
Includes encasement in concrete.
**Fillers used when required.
NOTE: The data shown is approximate and subject to standard industry tolerances. 2011
Part
Number
AP2.4K6/3E
AP2.4K4/3E
AP2.4K2/3E
AP2.4K1/3E
AP2.4K1/03E
AP2.4K2/03E
AP2.4K4/03E
AP2.4K250/3E
AP2.4K350/3E
AP2.4K500/3E
AP2.4K750/3E
AP5KS6/3E
AP5KS4/3E
AP5KS2/3E
AP5KS1/3E
AP5KS1/03E
AP5KS2/03E
AP5KS4/03E
AP5KS250/3E
AP5KS350/3E
AP5KS500/3E
AP5KS750/3E
A
r
m
o
r

C
a
b
l
e
s
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
74
Made in the USA
Description:
3 conductors, Class B stranded annealed copper, extruded semi-
conducting shield, heat and moisture resistant ethylene propylene
rubber type EPR, 133% insulation level, semi-conducting insula-
tion shield, copper shield, overall PVC jacket. Cabled together with
suitable llers** and bare copper ground conductor. Cable core
covered with binder tape, aluminum or galvanized steel interlocked
armor, with ame and sunlight resistant red PVC jacket. Jacket
available under armor and in other colors.
Standards:
UL 1072
Flame Rated: IEEE-383 (70,000 BTU),
ICEA T-29-520 (210,000 BTU),
IEEE 1202/CSA FT-4
Class 1 Div II
Sunlight Resistant for CT Use; Direct Burial
1
,
Two-hour Firewall rated, (2/0 AWG and smaller)
Oil Resistant II Jacket
Color Code K-2/other color codes available
Conductors rated at 105 C
ICEA S-93-639/NEMA WC-74
RoHS Compliant
Interlocked Armor
15kV MV - 105
133% Insulation Level
UL Type MC
Galvanized Steel or Aluminum
15,000 Volt Copper EPR
2 7 220 80 6 2.57 75 2.72 2,987 3,527 145
1 19 220 80 4 2.65 75 2.80 3,298 3,861 165
1/0 19 220 80 4 2.77 75 2.92 3,674 4,243 195
2/0 19 220 80 4 2.85 75 3.00 4,083 4,692 220
4/0 19 220 80 3 3.09 85 3.26 5,100 5,733 290
250 37 220 80 3 3.21 85 3.38 6,180 6,872 315
350 37 220 80 2 3.41 85 3.58 7,507 8,246 385
500 37 220 80 1 3.69 85 3.86 9,878 10,682 470
750 61 220 110 1/0 4.21 85 4.38 13,610 14,537 570
Size
AWG
or
MCM
Jacket
Thickness
(mils)
Insulation
Thickness
(mils)
Diameter
over
Armor
(inch)
Copper
Grounding
Conductor(s)
(AWG)
PVC
Jacket
Thickness
(mils)
Approx.
Diameter
Overall
(inch)
Alum.
Armor
Galv.
Armor
Ampacity*
(40 C
Ambient)
Conductor
Strand
(no.)
1
3
3
%

E
P
R

I
N
S
U
L
A
T
I
O
N
Approx. Net Wt.
per 1000 ft. (lbs.)
*Per NEC Table 310-75. Based on one three-conductor cable.
1
Includes encasement in concrete.
**Fillers used when required.
NOTE: The data shown is approximate and subject to standard industry tolerances. 2011
Part
Number
AP15K2/3E
AP15K1/3E
AP15K1/03E
AP15K2/03E
AP15K4/03E
AP15K250/3E
AP15K350/3E
AP15K500/3E
AP15K750/3E
P
u
m
p

a
n
d

I
r
r
i
g
a
t
i
o
n
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
75
Made in the USA
Submersible Pump Cable
TYPE THW-TWISTED
with Ground 75C/600V
Description & Features:
General purpose UL listed Type THW Twisted, unjacketed,
submersible pump cable features solid or stranded copper con-
ductors individually insulated with a tough Type THW polyvinyl
chloride (PVC) compound.
UL/CSA listed as Type THW-Twisted Submersible Pump cable
Rated 75C
Oil and grease resistant conductors
Applications:
For use within the well casing to supply power to the sub-
mersible pump
Construction:
Conductors: Solid or stranded soft annealed copper
Insulation: Thermoplastic polyvinyl chloride (PVC)
Color coding: black, red, yellow, green (ground)
Assembly: The individually insulated conductors are twisted with
a green insulated grounding conductor (sized in accordance with
Table 250-122 of the NEC)
Temperature: 75C Voltage: 600
Specications & Standards:
UL 83; UL1581; RoHS Compliant
CSA Listed
Per Table 310-16 of the NEC
#2 AWG through 4/0 AWG Twisted Unjacketed available upon request.
All values are nominal; all weights are exclusive of packaging. All diameters and weights are subject to normal manufacturing tolerances.
All sales are subject to Standard Terms & Conditions of Sale.
2011
Standard Ampacity Weight
Item Code Power Ground Insulation O.D. Packaging NEC (Lbs./Mft.)
PT14/2GG 14/2 (solid) 14 (solid) .045 .34 500 & 1000 15 67
PT12/2GG 12/2 (solid) 12 (solid) .045 .38 500 & 1000 20 94
PT10/2GG 10/2 (solid) 10 (solid) .045 .43 500 & 1000 30 135
PT14/3GG 14/3 (solid) 14 (solid) .045 .38 500 & 1000 15 89
PT12/3GG 12/3 (solid) 12 (solid) .045 .42 500 & 1000 20 125
PT10/3GG 10/3 (solid) 10 (solid) .045 .48 500 & 1000 30 180
PT8/3GG 8/3 (7 str) 10 (7 str) .060 .64 500 & 1000 50 275
PT6/3GG 6/3 (19 str) 8 (19 str) .060 .74 500 & 1000 65 409
PT4/3GG 4/3 (19 str) 8 (19 str) .060 .87 500 & 1000 85 572

TWO OR THREE CONDUCTORS WITH GREEN INSULATED GROUNDING CONDUCTOR
Conductor Size, AWG Dimensions (inches)
P
u
m
p

a
n
d

I
r
r
i
g
a
t
i
o
n
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
76
Made in the USA
Submersible Pump Cable
TYPE THW ROUND JACKETED
75C/600V
Description & Features:
UL listed Type THW twisted submersible pump cable is a multi-
purpose cable with individually insulated color coded conductors,
green insulated ground (optional) and an overall jacket.
Construction provides copper stranding insulated with a polyvinyl
chloride (PVC) compound. A tough PVC jacket is easily stripped
to facilitate installation yet provide optimum exibility, mechanical
protection and crush resistance.
UL/CSA listed as Type THW Submersible Pump cable
Oil and grease resistant conductors
Acid, alkali, oil and grease resistant jacket
Weather, ozone and sunlight resistant jacket
Abrasion and crush resistant
Sequential Footage Marks
Applications:
For use within the well casing to supply power to the submersible
pump
Designed for use where extra mechanical protection during
installation and operation are required
Construction:
Conductors: Stranded soft annealed copper
Insulation: Thermoplastic polyvinyl chloride (PVC)
Color coding: black, red, yellow, green (ground)
Assembly: The insulated conductors, including the green ground-
ing conductor, are cabled.
Jacket: Black thermoplastic polyvinyl chloride (PVC)
Temperature: 75C Voltage: 600
Specications & Standards:
UL 83; UL1581; RoHS Compliant
CSA Listed
Conductor Size, AWG
PTJ12/3 12 (19str) .045 .045 .481 500' & 1,000' 20 135
PTJJ10/3 10 (19str) .045 .045 .534 500' & 1,000' 30 182
PTJ8/3 8 (19str) .060 .045 .663 500' & 1,000' 50 281
PTJ6/3 6 (19str) .060 .045 .745 500' & 1,000' 65 393
PTJ4/3 4 (19str) .060 .060 .879 500' & 1,000' 85 589
PTJ12/3GG 12 (19str) 12 (19str) .045 .045 .528 500' & 1,000' 20 171
PTJ10/3GG 10 (19str) 10 (19str) .045 .045 .623 500' & 1,000' 30 233
PTJ8/3GG 8 (19str) 10 (19str) .060 .045 .732 500' & 1,000' 50 333
PTJ6/3GG 6 (19str) 8 (19str) .060 .045 .824 500' & 1,000' 65 499
PTJ4/3GG 4 (19str) 8 (19str) .060 .060 .924 500' & 1,000' 85 675
PTJ2/3GG 2 (19str) 6 (19str) .060 .060 1.098 500' & 1,000' 115 980

Standard Ampacity Weight
Part Number Power Ground Insulation Jacket O.D. Packaging NEC (Lbs./Mft.)
THREE CONDUCTORS WITH NO GROUND
Dimensions (inches)
THREE CONDUCTORS WITH GROUND
Per Table 310-16 of the NEC
#1 AWG through 4/0 AWG round jacketed pump available upon request.
NOTE: Direct burial rated upon request.
All values are nominal; all weights are exclusive of packaging. All diameters and weights are subject to normal manufacturing tolerances.
All sales are subject to Standard Terms & Conditions of Sale.
2011
P
u
m
p

a
n
d

I
r
r
i
g
a
t
i
o
n
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
77
Made in the USA
Rainbow Wire
TM
Submersible Pump Cable
TYPE THW-FLAT with Ground
75C/600V
Description & Features:
UL listed Type THW general purpose at rainbow submersible
pump cable. Copper stranding covered with a tough PVC insula-
tion applied directly over the conductors. Conductors are bonded
together to assure easy separation, which facilitates installation,
yet provides exibility and mechanical protection.
UL/CSA listed as Type THW Submersible Pump cable
Oil and grease resistant
Abrasion resistant
Sequential footage marks
Applications:
For use within the well casing to supply power to the submersible
pump
Designed for use where fexibility during installation and opera-
tion are required
Construction:
Conductors: Stranded soft annealed copper
Insulation/Assembly: Insulated conductors, including the ground-
ing conductor, are congured at and parallel. Conductors are
bonded together with no overall jacket.
Conductors are solid colors of Black, Red, Yellow, and Green
Temperature: 75C Voltage: 600
Specications & Standards:
UL 83; UL1581; RoHS Compliant
CSA Listed
Per Table 310-16 of the NEC
All values are nominal; all weights are exclusive of packaging. All diameters and weights are subject to normal manufacturing tolerances.
All sales are subject to Standard Terms & Conditions of Sale.
2011
Standard Ampacity Weight
Item Code Size AWG/No. Ground Wire Insulation O.D. Packaging NEC (Lbs./Mft.)
PRB12/2GG 12/2 (19 str) 12(19 str) .045 .190 x .570 500 & 1000 20 95
PRB10/2GG 10/2 (19 str) 10 (19 str) .045 .211 x .663 500 & 1000 30 138
PRB8/2GG 8/2 (19 str) 10 (19 str) .045 .268 x .747 500 & 1000 50 199
PRB12/3GG 12/3 (19 str) 12 (19 str) .045 .190 x .752 500 & 1000 20 126
PRB10/3GG 10/3 (19 str) 10 (19 str) .045 .211 x .836 500 & 1000 30 182
PRB8/3GG 8/3 (19 str) 10 (19 str) .060 .268 x 1.056 500 & 1000 50 269
PRB6/3GG 6/3 (19 str) 8 (19 str) .060 .306 x 1.230 500 & 1000 65 401

Conductor
TWO OR THREE CONDUCTORS WITH GROUND
Dimensions (inches)
P
u
m
p

a
n
d

I
r
r
i
g
a
t
i
o
n
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
78
Made in the USA
Submersible Pump Cable
TYPE THW-Heavy Duty FLAT
BLACK JACKETED with Ground
75C/600V
Description & Features:
UL listed Type THW heavy duty at submersible pump cable is
a multi-purpose cable with parallel, individually insulated, color
coded conductors, green ground insulated conductor and an
overall jacket. Construction provides exible copper stranding
insulated with Type THW (PVC) compound. A tough PVC jacket,
with a non-penetrating web, is easily stripped to facilitate instal-
lation yet provide optimum exibility, mechanical protection and
crush resistance.
UL/CSA listed as Type THW Submersible Pump Cable
Acid, alkali, oil and grease resistant
Weather, ozone and sunlight resistant jacket
Abrasion and crush resistant
Sequential footage marks
Applications:
For use within the well casing to supply power to the submersible
pump
Designed for use where extra mechanical protection and fex-
ibility during installation and operation are required
Construction:
Conductors: Flexible stranded soft annealed copper
Insulation: Thermoplastic polyvinyl chloride (PVC)
Color coding: black, red, yellow, green (ground)
Assembly: The insulated conductors, including the grounding
conductor, are congured at and parallel without llers
Jacket: Black thermoplastic polyvinyl chloride (PVC) applied
directly over the conductors with a non-penetrating web
Temperature: 75C Voltage: 600
Specications & Standards:
UL Standard 83; RoHS Compliant
CSA Listed
Per Table 310-16 of the NEC
All values are nominal; all weights are exclusive of packaging. All diameters and weights are subject to normal manufacturing tolerances.
* Direct Burial rated in sizes 12 through 500 KCMIL, upon request
All sales are subject to Standard Terms & Conditions of Sale.
2011
Standard Ampacity Weight
Part Number Power Ground Insulation Jacket O.D. Packaging NEC (Lbs./Mft.)
Conductor Size, AWG
THREE CONDUCTORS WITH GREEN INSULATED GROUNDING CONDUCTORS
Dimensions (Inches)

TWO CONDUCTORS WITH GREEN INSULATED GROUNDING CONDUCTORS

PFB14/3GG 14/3 (7 str) 14 (7 str) .045 .045 .261 x .763 500 & 1000 15 145
PFB12/3GG 12/3 (19 str) 12 (19 str) .045 .045 .280 x .840 500 & 1000 20 189
PFB10/3GG 10/3 (19 str) 10 (19 str) .045 .045 .305 x .940 500 & 1000 30 255
PFB8/3GG 8/3 (19 str) 10 (19 str) .060 .045 .364 x 1.120 500 & 1000 50 374
PFB6/3GG 6/3 (19 str) 8 (19 str) .060 .045 .414 x 1.336 500 & 1000 65 522
PFB4/3GG 4/3 (19 str) 8 (19 str) .060 .045 .465 x 1.489 500 & 1000 85 714
PFB2/3GG 2/3 (19 str) 6 (19 str) .060 .045 .535 x 1.749 500 & 1000 115 1,036
PFB1/03GG 1/03 (19 str) 6 (7 str) .080 .060 .660 x 1.990 Bulk 150 1,613
PFB2/03GG 2/03 (19 str) 6 (7 str) .080 .060 .700 x 2.120 Bulk 175 1,932
PFB3/03GG 3/03 (19 str) 4 (7 str) .080 .060 734 x 2.314 Bulk 200 2,135
PFB4/03GG 4/03 (19 str) 4 (7 str) .080 .060 .800 x 2.490 Bulk 230 2,871
PFB250/3GG 250/3 (37 str) 4 (7 str) .095 .080 .925 x 2.807 Bulk 235 3,518
PFB350/3GG 350/3 (37 str) 3 (7 str) .095 .080 1.031 x 3.153 Bulk 310 4,689
PFB500/3GG 500/3 (37 str) 2 (7 str) .095 .080 1.163 x 3.590 Bulk 380 6,410
PFB14/2GG 14/2 (7 str) 14 (7 str) .045 .045 .261 x .592 500 & 1000 15 112
PFB12/2GG 12/2 (19 str) 12 (19 str) .045 .045 .280 x .654 500 & 1000 20 152
PFB10/2GG 10/2 (19 str) 10 (19 str) .045 .045 .305 x .729 500 & 1000 30 210
PFB8/2GG 8/2 (19 str) 10 (19 str) .060 .045 .364 x .828 500 & 1000 50 276
P
u
m
p

a
n
d

I
r
r
i
g
a
t
i
o
n
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
79
Made in the USA
Type UF / Type TWU
SINGLE CONDUCTOR
60C/600V

Description & Features:
C(UL) listed Single Conductor Type UF/Type TWU is suitable
for use as Sprinkler Irrigation Control Wire for general purpose
lighting and power. Construction provides solid or stranded soft
annealed copper conductor insulated with polyvinyl chloride
(PVC) compound that provides excellent abrasion, acid, chemical,
oil and moisture resistance.
UL listed Type UF 600 Volt (#14 thru 4/0 AWG)
C(UL) Listed Type TWU 600 Volt (#14 thru 4/0 AWG)
Direct burial rated
Resistant to acids, alkali, grease and chemicals
Abrasion, crush and moisture resistant
Applications:
Suitable for use as power and control conductors for irrigation
systems
For use in accordance per NEC Article 339
Construction:
Conductors: Soft annealed copper
Solid (18 AWG to 8 AWG)
Stranded (6AWG to 4/0 AWG)
Insulation: Polyvinyl chloride (PVC) compound
Temperature: 60C Voltage: 600 Volts
Specications & Standards:
UL 493; UL1581; RoHS Compliant
Federal Spec AA-59544, CSA C22.2 No. 75
ULE18SOL 18 (solid) .045 .130 X X 13
ULE16SOL 16 (solid) .045 .141 X X 15
UF14SOL 14 (solid) .060 .184 X X 27
UF12SOL 12 (solid) .060 .201 X X 36
UF10SOL 10 (solid) .060 .272 X 50
UF8SOL 8 (solid) .060 .303 X 81
UF6 6 (7 str) .060 .342 X 121
UF4 4 (7 str) .080 .389 X 176
UF2 2 (7 str) .080 .450 X 261
UF1/0 1/0 (19 str) .095 .557 Bulk 408
UF2/0 2/0 (19 str) .095 .602 Bulk 502
UF4/0 4/0 (19 str) .095 .715 Bulk 763
*
UL Listed - UNDERGROUND LOW ENERGY 150 VOLT CIRCUIT CABLE SUNLIGHT RESISTANT.
All values are nominal; all weights are exclusive of packaging. All diameters and weights are subject to normal manufacturing tolerances.
Type UF SINGLE CONDUCTOR 60C/600V
Part Number AWG Insulation O.D. (Lbs./Mft.)
Dimensions (inches)
Weight
Standard Packaging
500' 1000' 2500'
*
*
Conductor
STANDARD COLORS
NOTE: S = Stock, A = Available
All sales are subject to Standard Terms & Conditions of Sale. 2011
RD WE BE GN YW OE BN BK PE GY PK TN
Single cond. size 18 and 16 S S A A A A A S A A A A
Single cond. size 14 S S S S S S S S S S S S
Single cond. size 12 and 10 S S A S A A A S A A A A
Single cond. size 8 and larger A A A A A A A A A A A A
P
u
m
p

a
n
d

I
r
r
i
g
a
t
i
o
n
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
80
Made in the USA
All values are nominal; all weights are exclusive of packaging. All diameters and weights are subject to normal manufacturing tolerances.
All sales are subject to Standard Terms & Conditions of Sale. 2011
Sprinkler Control Cable
MULTI-CONDUCTOR
60C / 30V
Description & Features:
Multi-conductor sprinkler control cable is a general purpose ir-
rigation system control cable. Polyethylene (PE) jacket provides
excellent abrasion, acid, chemical, oil and moisture resistance.
Moisture resistant insulation
Suitable for Direct Burial use
Resistant to acids, alkali, grease and chemicals
Impact, abrasion, and crush resistant
Applications:
Suitable for use as control cable for commercial and residential
irrigation systems
Construction:
Conductors: Soft annealed solid copper
Insulation: Colored polyvinyl chloride (PVC) compound
Assembly: Conductors are cabled and jacketed with black PE
(nylon rip cord under jacket).
Temperature: 60C
Specications & Standards:
UL Listed; RoHS Compliant
SPR18/2 18 2 .015 .025 .121 x .191 X X 18
SPR18/3 18 3 .015 .025 .202 X X X X 24
SPR18/4 18 4 .015 .025 .220 X X X X 31
SPR18/5 18 5 .015 .025 .240 X X X X X 38
SPR18/6 18 6 .015 .025 .267 X X X X 44
SPR18/7 18 7 .015 .025 .267 X X X X X 51
SPR18/8 18 8 .015 .025 .283 X X X X 57
SPR18/9 18 9 .015 .025 .304 X X X X 64
SPR18/10 18 10 .015 .025 .332 X X X X X 71
SPR18/12 18 12 .015 .025 .343 X X X X 84
SPR18/13 18 13 .015 .025 .346 X X X X 90
MULTI-CONDUCTOR SPRINKLER CONTROL CABLE/60C
Item Code AWG No. Insulation Jacket O.D. (Lbs./Mft.)
Conductor (solid) Dimensions (inches)
Weight
Standard Packaging
100 250 500 1000 2500
RD WE BE GN YW OE BN BK PE GY PK TN DK BE
Color Sequence 1 2 3 4 5 6 7 8 9 10 11 12 13

P
u
m
p

a
n
d

I
r
r
i
g
a
t
i
o
n
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
81
Made in the USA
Grounding Wire
Type THW Single Conductor
75C/600V
Type TW Single Conductor
60C/600V
Description & Features:
Single conductor ground wires suitable for non-grounded multi-
conductor cables. Compatible with twisted, heavy-duty, jacketed,
or parallel cables. These wires are made to UL standard Type
THW and TW. The solid bare copper conductor is insulated with a
green moisture-resistant, polyvinyl chloride (PVC) insulation.
Rated 75C for THW, 60C for TW
Oil and grease resistant insulation
Abrasion and crush resistant
Available in stranded
Application:
Suitable for providing grounding of submersible pump motors
Construction:
Conductor: Soft annealed copper
Insulation: Green polyvinyl chloride (PVC)
Temperature: 75 C for THW, 60C for TW
Voltage: 600 volts
Specications & Standards:
UL 83; UL 1581; ASTM B3; RoHS Compliant
GROUNDING INFORMATION FOR SUBMERSIBLE
PUMP MOTORS
The National Electric Code requires all motor-operated water
pumps, including submersibles to be grounded. These grounds
may be separate from the power feed cable. Per UL, the
grounding conductor must be insulated and must be color-cod-
ed or identied for use only as a grounding conductor. Sizing of
the ground wire is per UL 83. Check with your local inspector
for proper installation procedure in your area.
All values are nominal; all weights are exclusive of packaging. All diameters and weights are subject to normal manufacturing tolerances.
All sales are subject to Standard Terms & Conditions of Sale.
2011
THW14SOL 14 .045 .124 2,500' 22
THW12SOL 12 .045 .171 2,500' 30
THW10SOL 10 .045 .192 2,500' 39
TW8SOL 8 .045 .219 2,500 68

TYPE THW or TW/PVC GROUNDING WIRE 75C or 60C/600V
Weight
Part Number AWG Insulation O.D. Standard Packaging Lbs./Mft.
Conductor (solid)
Dimensions (inches)
P
u
m
p

a
n
d

I
r
r
i
g
a
t
i
o
n
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
82
Made in the USA
Low Energy Circuit Cable
UNDERGROUND LANDSCAPE
LIGHTING WIRE 60C/150V
Description & Features:
Underground Low Energy circuit Cable (Landscape Lighting Wire)
is a superior multi-purpose product. A tough integral insulation
and jacket of polyvinyl chloride (PVC) compound covers the con-
ductors and provides excellent abrasion, crush, chemical, oil and
moisture resistance. A Mid rip between conductors provides for
easy splitting and stripping.
UL listed Underground Low Energy Circuit Cable 150 Volts
Direct Burial rated
Extra fexible stranding
Resistant to acids, alkalis, grease and chemicals
Sunlight and Abrasion Resistant
Application:
Suitable for use in direct burial landscaping and lighting applica-
tions
Construction:
Conductor: Soft annealed extra exible stranded copper per
ASTM B-174 (#16, 12 and 10 AWG) and ASTM B-172 (#8 AWG)
Assembly: Two conductors are congured at and parallel.
Black polyvinyl chloride (PVC) is applied directly over the conduc-
tors. Conductors are identied with ridges on the surface of the
insulation.
Temperature: 60 C Voltage: 150
Specications & Standards:
UL 1493; RoHS Compliant
ULE16/2 16/2 26 .045 .310 x .150 100', 250', 500', 1,000' 34
ULE12/2 12/2 65 .045 .382 x .186 100', 250', 500', 1,000' 64
ULE10/2 10/2 104 .045 .426 x .208 100', 250', 500', 1,000' 92
ULE8/2 8/2 168 .060 .558 x .274 100', 250', 500', 1,000' 149

All values are nominal; all weights are exclusive of packaging. All diameters and weights are subject to normal manufacturing tolerances.
All sales are subject to Standard Terms & Conditions of Sale. 2011
LOW ENERGY CIRCUIT CABLE; UNDERGROUND LANDSCAPE LIGHTING WIRE 75C/150V
Part Number Size AWG No. of Strands Insulation O.D. Standard Packaging (Lbs./Mft.)
Conductor Dimensions (inches)
Weight
P
u
m
p

a
n
d

I
r
r
i
g
a
t
i
o
n
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
83
Made in the USA
Golf Course Sprinkler
Wire Polyethylene
60C/600V
GOLF14SOL 14 0.45 .154 2,500' 19
GOLF12SOL 12 0.45 .171 2,500' 27
GOLF10SOL 10 0.45 .192 2,500' 39
All values are nominal; all weights are exclusive of packaging. All diameters and weights are subject to normal manufacturing tolerances.
All sales are subject to Standard Terms & Conditions of Sale. 2011
Contact your sales representative for available colors.
Golf Course Sprinkler Wire 60C/600V
Part Number AWG Insulation O.D. (Lbs./Mft.)
Conductor (sol) Weight
Dimensions (inches)
Packaging
Description & Features:
UL listed Golf Course Sprinkler Wire is a solid copper conductor
insulated with a polyethylene compound that provides excellent
abrasion, crush, chemical, oil and moisture resistance.
UL listed for Direct Burial
Moisture resistant
Chemical, oil resistant
Impact, crush and abrasion resistant
Suitable for use as Pipeline Tracer Wire (PTW)
Application:
Suitable for use as power and control conductors for golf course
irrigation systems.
Construction:
Conductor: Soft annealed solid copper per ASTM B-3
Insulation: Polyethylene
Temperature: 60C dry and wet Voltage: 600 volts
Specications & Standards:
UL listed
RoHS Compliant
P
u
m
p

a
n
d

I
r
r
i
g
a
t
i
o
n
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
84
Made in the USA
Description & Features:
Solid bare copper, soft, medium hard, or hard drawn. Packaged
on convenient spools.
Per ASTM B49
Highest Conductivity per unit area of all commercially available
metals used to conduct electricity.
Soft Drawn: Flexible; easily formed into place
Medium Hard and Hard Drawn; higher tensile strengths, respec-
tively; more difcult to form
Easily welded and soldered
Plater Wire
Bare Copper
Application:
Used as a hanger in the electro-plating industry
Construction:
Bare Copper
Specications & Standards:
Soft Drawn: Per ASTM B3
Medium Drawn: Per ASTM B2
Hard Drawn Per ASTM B1
RoHS Compliant
All diameters are nominal values; all weights are product weights exclusive of packaging. All diameters and weights are subject to normal
manufacturing tolerances.
All sales are subject to Standard Terms & Conditions of Sale. 2011
PLATER WIRE/BARE COPPER
PLATER24 24 Solid 818 6 x 10 lb. Spools 60 1.2
PLATER22 22 Solid 514 6 x 10 lb. Spools 60 1.9
PLATER20 20 Solid 323 6 x 10 lb. Spools 60 3.1
PLATER16 16 Solid 128 6 x 10 lb. Spools 60 7.8
PLATER14 14 Solid 81 2 x 25 lb. Spools 50 12.4
PLATER12 12 Solid 51 2 x 25 lb. Spools 50 19.8
PLATER10 10 Solid 32 2 x 25 lb. Spools 50 31.4
PLATER8 8 Solid 20 2 x 25 lb. Spools 50 50.0
PLATER6 6 Solid 13 2 x 25 lb. Spools 50 79.4
PLATER4 4 Solid 8 2 x 25 lb. Spools 50 126.3
PLATER2 2 Solid 5 2 x 25 lb. Spools 50 200.9
Part Conductor Approximate Standard Put-up Standard Product Wgt.
Number AWG Ft./lb. Per Carton Pack lbs./Mft.
P
u
m
p

a
n
d

I
r
r
i
g
a
t
i
o
n
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
85
Made in the USA
UFB14/2G 14 (sol) .015 .004 .185 x .385 250 Ctn, 500 Reel 1000 Reel 20 53
UFB12/2G 12 (sol) .015 .004 .195 x .415 250 Ctn, 500 Reel 1000 Reel 20 75
UFB10/2G 10 (sol) .020 .004 .230 x .460 250 Ctn, 500 Reel 1000 Reel 30 140
UFB8/2G 8 (7 str) .030 .005 .320 x .620 1000 Reel 40 213
UFB6/2G 6 (7 str) .030 .005 .385 x .800 1000 Reel 55 305

Type UF-B
UNDERGROUND FEEDER
CABLE/600V
Applications:
Permitted for use underground including direct burial in earth as
Feeder or Branch Circuit Cable where provided with overcurrent
protection
For use in interior wiring in wet, dry or corrosive locations under
recognized wiring methods of the National Electrical Code (NEC)
Acceptable to be installed as a Non-Metallic Sheathed Cable in
accordance with NEC Article 339-3 (4)
Acceptable for use in accordance with NEC Articles 300-4(b)
and 339
Temperature: 75C Voltage: 600
Specications & Standards:
UL Standard 493 - Thermoplastic-Insulated Underground Feeder
and Branch Circuit Cables
Description & Features:
Type UF-B Underground Feeder Cables construction provides
solid or stranded Type THHN/THWN conductors laid parallel with
an uninsulated grounding conductor. An outer jacket of tough
polyvinyl chloride (PVC), provides protection against mechanical
damage, moisture, chemicals and corrosion.
Grease and chemical resistant conductors
Moisture, chemical and sunlight resistant jacket
All values are nominal; all weights are exclusive of packaging. All diameters and weights are subject to normal manufacturing tolerances.
Per Table 310-16 of the NEC.
* Reduced ground wire.
All sales are subject to Standard Terms & Conditions of Sale.
2011
Ampacity Weight
Item Code AWG PVC Nylon O.D. Standard Packaging NEC Lbs./Mft.
TWO CONDUCTORS WITH GROUND
Dimensions (inches)
THREE CONDUCTORS WITH GROUND
*
*
UFB14/3G 14 (sol) .015 .004 .185 x .575 250 Ctn, 500 Reel 1000 Reel 20 93
UFB12/3G 12 (sol) .015 .004 .195 x .620 250 Ctn, 500 Reel 1000 Reel 20 134
UFB10/3G 10 (sol) .020 .004 .230 x .690 250 Ctn, 500 Reel 1000 Reel 30 194
UFB8/3G 8 8 (7 str) .030 .005 .320 x .990 500 Reel 1000 Reel 40 330
UFB6/3G 6 6 (7 str) .030 .005 .385 x 1.20 1000 Reel 55 449
Manufacturing quality. Delivering service.
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
86
STAINLESS STEEL - TYPE 302
MES1/4SS 1/4" .242 7 # 12 8,500 lbs. 135
MES3/8SS 3/8" .385 7 # 8 18,000 lbs. 282
MES1/2SS 1/2" .486 7 # 6 33,700 lbs. 535
MES(size)SS Size O.D. Stranding Breaking Strength Wgt./Mft.
NOTE: The data shown is approximate and subject to standard industry tolerances. 2011
COPPERWELD - EHS, 30% CONDUCTIVITY
MESSENGERS FOR AERIAL CABLE
MES1/4CUWELD 1/4" .242 7 #12 5,783 lbs. 128
MES5/16CUWELD 5/16" .306 7 # 10 9,196 lbs. 204
MES3/8CUWELD 3/8" .385 7 # 8 13,890 lbs. 324
MES1/2CUWELD 1/2" .486 7 # 6 20,460 lbs. 515
MES9/16CUWELD 9/16" .546 7 # 5 24,650 lbs. 650
Made in the USA
MES(size)CUWELD Size O.D. Stranding Breaking Strength Wgt./Mft.
MES1/4EHSGAL 1/4" .242 7 # 12 6,650 lbs. 121
MES5/16EHSGAL 5/16" .306 7 # 10 11,200 lbs. 205
MES3/8EHSGAL 3/8" .385 7 # 8 15,400 lbs. 273
MES1/2EHSGAL 1/2" .486 7 # 6 26,900 lbs. 517
GALVANIZED - EHS
MES(size)EHSGAL Size O.D. Stranding Breaking Strength Wgt./Mft.
Service Wire Company believes the information presented herein is, to the best of our knowledge, true and accurate based on currently
available industry data. However no warranties, either expressed or implied, are made as to the accuracy or completeness of any
information contained herein. Consequently, Service Wire Company makes no guarantee of the results and assumes no obligation or
liability whatsoever in connection with this information.
Manufacturing quality. Delivering service.
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
87
COLOR CODES
2011
Made in the USA
Conductor
Number
Conductor
Color
Stripe Color
1 Black -
2 White -
3 Red -
4 Green -
5 Orange -
6 Blue -
7 White Black
8 Red Black
9 Green Black
10 Orange Black
11 Blue Black
12 Black White
13 Red White
14 Green White
15 Blue White
16 Black Red
17 White Red
18 Orange Red
19 Blue Red
20 Red Green
21 Orange Green
ICEA Method 1 (K-1)
(Colored Compounds with Stripes)
Conductor
Number
Conductor
Color
Stripe Color
1 Black -
2 Red -
3 Blue -
4 Orange -
5 Yellow -
6 Brown -
7 Red Black
8 Blue Black
9 Orange Black
10 Yellow Black
11 Brown Black
12 Black Red
13 Blue Red
14 Orange Red
15 Yellow Red
16 Brown Red
17 Black Blue
18 Red Blue
19 Orange Blue
20 Yellow Blue
21 Brown Blue
ICEA Method 2 (K-2)
(Colored Compounds with Stripes)
ICEA Method 4
(Black Compound with Numbers)
Conductor Number Printing Conductor Number Printing
1 1-One 12 12-Twelve
2 2-Two 13 13-Thirteen
3 3-Three 14 14-Fourteen
4 4-Four 15 15-Fifteen
5 5-Five 16 16-Sixteen
6 6-Six 17 17-Seventeen
7 7-Seven 18 18-Eighteen
8 8-Eight 19 19-Nineteen
9 9-Nine 20 20-Twenty
10 10-Ten 21 21-Twenty-One
11 11-Eleven
Service Wire Company believes the information presented herein is, to the best of our knowledge, true and accurate based on currently
available industry data. However no warranties, either expressed or implied, are made as to the accuracy or completeness of any
information contained herein. Consequently, Service Wire Company makes no guarantee of the results and assumes no obligation or
liability whatsoever in connection with this information.
Manufacturing quality. Delivering service.
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
88
Made in the USA
MINIMUM BENDING RADII FOR CABLES
This section contains the minimum values for the radii to which cables may be bent for permanent train-
ing during installation. These limits do not apply to conduit bends, sheaves, or other curved surfaces around
which the cable may be pulled under tension while being installed. Larger radii bends are required for such
conditions. The minimum radii specied refers to the inner surface of the cable and not to the axis of the con-
ductor.
POWER & CONTROL CABLES WITHOUT METALLIC SHIELDING OR ARMOR
Insulation
Thickness
(Inches)
Overall Diameter of Cable (Inches)
4 5 6 .169" & less

2.001" & over 1.001" - 2.000" 1.000" & less
POWER & CONTROL CABLES WITH METALLIC SHIELDING &/OR ARMOR
7
12/7
(1)
Minimum Bending
Radius as a Multiple of
Cable Diameter
Cable Description
(1) 12 x individual shielded conductor diameter, or 7 x overall cable diameter, whichever is greater
Above tables per ICEA S-95-658/NEMA WC70, Appendix F
MINIMUM BENDING RADIUS AS A MULTIPLE OF CABLE DIAMETER
Interlocked Armor (with non-shielded cond.)
Metallic Tape Shielded (conductors or cable)

Service Wire Company believes the information presented herein is, to the best of our knowledge, true and accurate based on currently
available industry data. However no warranties, either expressed or implied, are made as to the accuracy or completeness of any
information contained herein. Consequently, Service Wire Company makes no guarantee of the results and assumes no obligation or
liability whatsoever in connection with this information.
Manufacturing quality. Delivering service.
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
89
Made in the USA
MAXIMUM PULLING TENSIONS
1. Pulling Eye
Maximum pulling tension for use with a pulling eye can be determined from the following
formula:
Tmax = k x n x CA Where: k = .008 for copper
.006 for aluminum
n = number of conductors
CA = conductor area of one conductor,
in circular mils
Tmax should not exceed 6,000 lb. for a single conductor cable.
Tmax should not exceed 10,000 lb. for 2 or more conductors.
2. Pulling Grip
Maximum pulling tension when using a basket type grip should not exceed 1,000 lb. or the
value determined in the above formula, whichever is smaller.
NOTE 1: Do not exceed the load stated by the manufacturer of the pulling device.
NOTE 2: Do not consider the area of neutral or grounding conductors in cable(s) when
calculating maximum pulling tensions.
NOTE 3: Pulling tensions should be reduced by 20% to 40% when several conductors are
being pulled simultaneously (in parallel) since the tension will not be distributed
evenly among conductors.
NOTE 4: The above procedure pertains to straight pulls, and does not consider side wall
loading.
See pages 81-84 for additional details.
Service Wire Company believes the information presented herein is, to the best of our knowledge, true and accurate based on currently
available industry data. However no warranties, either expressed or implied, are made as to the accuracy or completeness of any
information contained herein. Consequently, Service Wire Company makes no guarantee of the results and assumes no obligation or
liability whatsoever in connection with this information.
Manufacturing quality. Delivering service.
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
90
Sheave Selection Chart
Sheave
diameter
(inches)
Maximum Cable Diameter per Sheave
Single/multi
Conductor power
(inches)
Control
Cable
(inches)
Shielded 600 V
Power
(inches)
MV Power
Shielded
(inches)
6 0.375 0.214 0.150 0.107 0.125
12 0.984 0.563 0.940 0.281 0.328
18 1.750 1.000 0.700 0.500 0.583
24 2.453 1.402 0.981 0.701 0.818
Armor
(inches)
Pull considerations:
1. Plan direction of cable pulls to minimize tension by putting as many bends as possible early in the pull.
2. Proper setups cost initially, but will save by creating safer and easier pulls.
3. Published allowable conductor tensions are for STRAIGHT PULLS ONLY.
4. Published allowable equipment loading does not apply to the SWP of the cable pull.
Notes: 1.) You must select the sheave by radius NOT diameter. 2.) Sidewall limits for most cables are 500 lbs.
per foot radius maximum. 3.) All tensions on a cable pull are additive.
600 V
Cable
Examples of Minimum Bend Radii
Multiply
Sample
diameter Calcuation
Resulting
Minimum
Bend Radii
Less than 1 inch 4 .75 in. OD 4 x .75= 3 in. radius
1 to 2 inches 5 1.5 in. OD 5 x 1.5= 7.5 in. radius
2 in. or larger 6 3.0 in. OD 6 x 3= 18 in. radius
Interlock Armor 7 3.0 in. OD 7 x 3= 21 in. radius
Made in the USA
Service Wire Company believes the information presented herein is, to the best of our knowledge, true and accurate based on currently
available industry data. However no warranties, either expressed or implied, are made as to the accuracy or completeness of any
information contained herein. Consequently, Service Wire Company makes no guarantee of the results and assumes no obligation or
liability whatsoever in connection with this information.
Manufacturing quality. Delivering service.
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
91
Cable Installation Tips
Sheave strength ratings are for straight pulls only. Always refer to allowable tensions for each radius.
Most single and conveyor sheaves are rated at 4000 lbs or more, but these ratings can only be used for the
pulling rope, not the cable. Single sheaves are best for guiding and supporting cable. For cable bends use
conveyor sheave assemblies to control sidewall pressure.
Cable damage can occur when too small of a radius wheel is used.
NOTE: When using conveyor sheave equipment, it is critical for set up that the lead and exit sheaves not
have a bending radius smaller than the center wheels. (see below left)
Danger
Too small!
Don't confuse the diameter of the
sheave with the radius.
The radius MUST match the
cable's bending radius
12"
24"
18"
6"
Made in the USA
Service Wire Company believes the information presented herein is, to the best of our knowledge, true and accurate based on currently
available industry data. However no warranties, either expressed or implied, are made as to the accuracy or completeness of any
information contained herein. Consequently, Service Wire Company makes no guarantee of the results and assumes no obligation or
liability whatsoever in connection with this information.
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
92
This method can cause sidewall pressure and crush the cable.
Right:
This method will support and distribute all bearing loads for successful cable installation.
Create a smooth radius with sheaves using temporary
messengers and proper spacing.
Cable Installation Tips
Stringing Aerial cables on poles (this applies to pulling in or out)
Loading cable into tray
Wrong:
This method can cause sidewall pressure and crush the cable at the leading point. Lack of rollers will increase
drag creating more tension.
Right:
Use a large multi-wheel conveyor to distribute sidewall pressure. Lead and exit wheels must meet
minimum cable bend. Use tray rollers to eliminate cable drag.
Made in the USA
Wrong: Wrong:
Rollers
Anchor spud
or Line truck
Service Wire Company believes the information presented herein is, to the best of our knowledge, true and accurate based on currently
available industry data. However no warranties, either expressed or implied, are made as to the accuracy or completeness of any
information contained herein. Consequently, Service Wire Company makes no guarantee of the results and assumes no obligation or
liability whatsoever in connection with this information.
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
93
Tray Roller Assembly
It is important that these assemblies be aligned and secure.
Shifting of roller assemblies can cause the cable to climb over sheave edge and cut the cable.
All rollers to be free rolling to eliminate friction.
Space tray rollers to minimize cable drag.
Use greater bending radii than allowed.
Good
but cable
can drag
Good
for tray
defection
Better
reduces
cable drag
Best
with more
elevation
For cable
loading and
corners
Made in the USA
Service Wire Company believes the information presented herein is, to the best of our knowledge, true and accurate based on currently
available industry data. However no warranties, either expressed or implied, are made as to the accuracy or completeness of any
information contained herein. Consequently, Service Wire Company makes no guarantee of the results and assumes no obligation or
liability whatsoever in connection with this information.
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
USEFUL CONVERSION FACTORS
AWG to METRIC
DIAMETER
22 0.32 640 0.029
20 0.52 1020 0.036
18 0.82 1620 0.046
16 1.31 2580 0.058
14 2.08 4110 0.073
12 3.31 6530 0.092
10 5.26 10380 0.116
9 6.63 13090 0.130
8 8.37 16510 0.146
6 13.20 26240 0.184
4 21.2 41740 0.232
3 26.7 52620 0.260
2 33.6 66360 0.292
1 42.4 83690 0.332
1/0 53.5 105600 0.373
2/0 67.4 133100 0.419
3/0 85.0 167800 0.470
4/0 107.0 211600 0.528
DIAMETER
350 177 350000 0.681
400 202 400000 0.728
500 253 500000 0.813
550 278 550000 0.855
600 304 600000 0.893
700 354 700000 0.964
750 380 750000 0.998
900 456 900000 1.094
1000 506 1000000 1.152

AWG MM
2
CMIL INCHES
MISCELLANEOUS CONVERSIONS
UNIT MULTIPLY BY TO GET
Centimeters 0.3937 Inches
Circular Mils 0.7854 Square Mils
5.0671x10
-4
Square Millimeters
Cubic Centimeters 0.0610 Cubic Inches
Cubic Inches 16.386 Cubic Centimeters
Inches 2.54 Centimeters
Kilograms 2.2046 Pounds
Kilograms/Kilometers 0.6720 Pounds/1000ft.
Kilometers 0.6214 Miles
3280.8 Feet
Meters 3.2808 Feet
Mils 0.001 Inches
0.0254 Millimeters
Miles 1.6093 Kilometers
Millimeters 0.03037 Inches
Ohms/Kilometer 0.3048 Ohms/1000ft.
Ohms/1000ft. 3.2808 Ohms/Kilometer
Pounds 0.4536 Kilograms
Pounds/1000ft. 1.4881 Kilograms/Kilometer
Square Centimeters 1.55x10
5
Square Mils
1.97x10
5
Circular Mils
Square Inches 1.2732x10
6
Circular Mils
645.16 Square Millimeter
Square Millimeter 1973.5 Circular Mils

KCMIL MM
2
CMIL INCHES
250 126 250000 0.575
300 152 300000 0.630
2011
Service Wire Company believes the information presented herein is, to the best of our knowledge, true and accurate based on currently
available industry data. However no warranties, either expressed or implied, are made as to the accuracy or completeness of any
information contained herein. Consequently, Service Wire Company makes no guarantee of the results and assumes no obligation or
liability whatsoever in connection with this information.
94
Made in the USA
0.03937
13.2
DIAMETER
Phoenix, AZ Culloden, WV Houston, TX Pittsburgh, PA
877-623-9473 800-624-3572 800-231-9473 800-624-3572
www.servicewire.com
Manufacturing quality. Delivering service.
PAYMENT
For purposes of payment, each shipment and invoice therefore shall be a separate sale. Payment is due and payable thirty (30) days after
invoice date unless otherwise specied herein. A FINANCE CHARGE OF 1 1/2% PER MONTH WILL BE ADDED TO THE UNPAID BALANCE
ON ALL ACCOUNTS NOT PAID IN FULL ON OR BEFORE THE DUE DATE. THE FINANCE CHARGE IS EQUIVALENT TO AN ANNUAL
PERCENTAGE RATE OF 18%. Time is of the essence and, in addition to any other rights, Service Wire shall further have the right, at its
option, to terminate this agreement without notice to Buyer if payment is not made on or before the due date, or if Buyer becomes insolvent,
or if Buyer's ability to pay debts in the normal course of business otherwise becomes impaired.
QUANTITY VARIATION
On all orders, quantities are subject to a quantity variation of plus or minus ten percent (10%) unless otherwise specied or agreed upon.
RETURNED GOODS
No credit will be allowed for goods returned without Service Wire's prior authorization, nor will Service Wire accept responsibility for return
shipping costs. All returned goods will be subject to a restocking charge. All claims for credit must be made within 7 days of receipt of goods.
Merchandise cut to Buyer's measurements, or manufactured to Buyer's specications, cannot be returned.
DELIVERY
Delivery or shipment dates specied are Service Wire's best estimates and will not bind Service Wire to ship or make deliveries on the date
specied. Service Wire shall have no liability whatsoever for failure to meet delivery or shipment schedules.
Service Wire reserves the right to invoice buyer after having held nished manufacture product at our facility fteen (15) days after scheduled
shipping date. In addition after 15 days, storage charges will be charged to buyer.
Buyer's order is accepted subject to Service Wire being able to obtain the necessary raw materials and subject to government priorities and
other government regulations that may be issued from time to time.
ACCEPTANCE
Buyer's assent to the terms and conditions hereof may be expressed either by written acceptance or by failure to object to the terms and
conditions hereof within 10 days of its receipt by Buyer.
PRICE
Unless otherwise specied, prices are subject to change without notice. All shipments will be billed at prices in effect at date of shipment
unless otherwise stated in writing.
TAXES
Any applicable Federal, State, and/or local taxes imposed by reason of this sale shall be for the account of the Buyer.
LIMITED WARRANTY
All Service Wire's products are carefully inspected, tested, and packaged before shipment, and are receipted for by carrier in rst class
condition. Should any goods or materials prove defective due to defects in manufacture within one year from invoice date, upon written
notice to Service Wire, such material shall be replaced F.O.B. original destination point. This guarantee covers the cost of replacement of the
product only and does not include the cost for installation, shipping, and handling. In no event will Service Wire be liable to the purchaser
or the ultimate user of its product or any other party, for any damages, including but not limited to, loss of prots, loss of use, cost to repair,
replacement of damaged goods or property; or any other incidental or consequential damages arising out of the use of the product, even
if Service Wire, its agents or representatives, has been advised of the possibility of such damages.
THIS WARRANTY IS EXPRESSLY IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR IMPLIED INCLUDING THE WARRANTIES
FOR LABOR CHARGES, OR MERCHANTABILITY, AND OF FITNESS FOR A PARTICULAR PURPOSE, AND SHALL BE VOIDED IF ANY
WORK OR MODIFICATION IS PERFORMED ON THE CABLE WITHOUT FACTORY AUTHORIZATION.
This limited warranty represents the complete and exclusive agreement between Service Wire and Buyer concerning warranties of the
product and supersedes any proposal or prior agreement, oral or written, and any communications between Service Wire and Buyer con-
cerning the product.
95

Das könnte Ihnen auch gefallen