AND CHILLED WATER SYSTEMS DADE COUNTY AVIATION DEPARTMENT DESIGN GUIDELINES MANUAL DIVISION 15 - MECHANICAL DATE: 01/97 SECTION 15182 - HVAC-WATER TREATMENT OF CONDENSER AND CHILLED WATER SYSTEMS 1. CONDENSER WATER SYSTEMS a. Specify equipment, pipe connections, piping, chemicals and Contractor service to treat condenser water to minimize corrosion, scale, and biological growth in all parts of the system for one year. b. Corrosion control shall be maintained and documented by tests every 30 days while the Condenser Water System is in operation. These Corrosion monitoring tests shall utilize a preweighted mild steel test coupon immersed in the recirculating Condenser Water. The Coupon shall be installed in a one (1) inch PVC test coupon manifold having a 5-10 gpm flow rate. Each test period shall be for a 30 day duration. Twelve (12) test studies shall thus be done each year, each for a 30 day period. The Contractor shall perform the required Test Coupon studies and report the corrosion rates found. It is required that corrosion shall be maintained at below 2.0 mpy (mils per year) on each 30 day test. Corrosion shall not be in the form of pitting attack. Since biological growths impact upon the corrosion rates of mild steel test coupons, especially in the form of pitting attack, the test coupon monitoring program will also serve to corroborate control of biological growths are within acceptable limits. Additional field test measurements by means of Easicult test kit should be performed periodically as an aid to maintain continuously acceptable biological counts. Contractor shall document that the biological count the recirculating condenser water is maintained below 200,000 colonial per millimeter. Tests shall be made every 45 days by Field Easicult test procedure. c. The following equipment shall be furnished and installed by the Contractor under this section: (1) The control system shall be housed in a corrosion resistant NEMA 12X fiberglass enclosure with a viewing window in the door and a padlocking hasp. (2) The unit shall provide an analog display of the cooling water conductivity and shall have a front panel selectable 0-2000 and 0-5000 umho/cm dual scale. (3) A flow switch shall be mounted on the enclosure along with the sensor housing. The sensor shall be pre-wired and shall include automatic temperature compensation and shall be readily removable for cleaning by a quick disconnect that requires no tools. The flow switch shall provide a visual indication of loss of water flow to the sensor and shall prevent chemical feeding upon loss of water flow to sensor. (4) A water meter of appropriate size shall be specified for installation in the cooling tower makeup line. The water meter shall be field programmable to provide a pulse to the inhibitor pump that is proportional to the makeup water flow rate. The water meter shall also totalize the flow. The controller shall have a selector switch on the front panel that permits control of the inhibitor pump by either pulsing from the water meter, ON-OFF control from the conductivity controller or control by a repeat cycle 30 minute percentage timer. (5) The controller shall have front panel calibration adjustment and shall have adjustable high and low conductivity alarms in addition to the front panel set point adjustment. 01/97 DGM SECTION 15182 2 OF 4 HVAC - WATER TREATMENT OF CONDENSER AND CHILLED WATER SYSTEMS (6) A 7-Day biocide timer shall be housed in the controller and shall be programmable to turn the biocide pump ON and OFF at an adjustable feed frequency and duration. Inhibitor feed and bleed-off is automatically stopped during the biocide feeding and for all adjustable length of time after biocide feeding. (7) An electrically operated solenoid valve of appropriate size shall be supplied for installation in the bleed-off line and shall be wired to the controller by the installing Contractor. (8) A pre-wired, pre-plumbed panel shall be specified onto which the controllers shall be mounted along with the inhibitor and biocide pump monitors. The biocide pump discharge line shall be a line strainer and sampling valve pre-plumbed into the monitoring line. (9) The Piping Contractor shall provide 3/4" connection in the recirculating line for the controller monitoring line and for the inhibitor pump chemical feed line. A bleed-off line shall also be installed at the location and size specified by the water treatment service company. d. Inhibitor Feed Pump: One (1) positive displacement chemical feed pump shall be specified for the inhibitor feed. Both stroke length and stroke frequency shall be adjustable. The pump shall be capable of selectively being externally pulsed by the water meter. The pump shall have the appropriate output capacity, pressure rating and materials of construction for the application. The pump shall feed directly from the storage tank of inhibitor and discharge into the cooling water recirculation line ahead of the condenser with a corporation stop and injection assembly at the injection point. Specify polyprel pump seal rings. e. Inhibitor Storage Tank(s): 50 gallon polyethylene storage tank with cover and with a low level alarm shall be specified. The number of tanks shall be as required for the particular application. f. Biocide Feed Pumps: One (1) positive displacement biocide feed pump of appropriate size shall be specified to slug feed the required dosage to the cooling water system within one (1) hour or less. The pump shall have both stroke length and stroke frequency adjustment. Pump shall be specified with polyprel seal rings. g. Biocide Storage Tank: Polyethylene biocide tank shall be specified. The tank shall be specified with a low level alarm and a cover for mounting the alarm on the tank. The number of tanks shall be as required for the particular application. 2. CONDENSER WATER SYSTEM - WATER TREATMENT CHEMICALS a. The cooling water inhibitor and scale prevention agent shall be a phosphorate-based treatment. Copper corrosion inhibitor components and deposit controlling polymers shall be included in the formulation. The chemical treatment shall be supplied in liquid form. b. Algae and slime controlling agent shall be specified for the control of algae and slime accumulations in the cooling tower system. The microbicide shall be supplied in liquid form. c. All empty shipping containers shall be immediately removed from the job site by the Water Treatment Contractor at his own expense. d. The use of chemicals containing chromates is not permitted. 01/97 DGM SECTION 15182 3 OF 4 HVAC - WATER TREATMENT OF CONDENSER AND CHILLED WATER SYSTEMS 3. CLOSED CHILLED WATER SYSTEM - CHEMICAL FEEDING AND CONTROL EQUIPMENT a. Control Systems: One (1) control system shall be specified for the chilled water closed system. The controller shall continuously monitor the conductivity of the closed system water and shall automatically add additional protective treatment as needed to maintain the desired treatment level. The system shall include the following features: (1) The system shall be housed in NEMA 1 enclosure with viewing window in the door. (2) The monitor/controller shall provide an analog display of the conductivity level and shall have a 0-5000 umho/cm scale. (3) A 3/4" monitoring line shall be installed around the recirculating pump by the piping contractor. (4) The controller for the chilled water system shall include an alarm to indicate excessive water loss. b. Inhibitor Feed Pumps: A positive displacement chemical feed pump shall be specified for each closed system. Both the stroke length and stroke frequency shall be adjustable. The pumps shall be of appropriate output capacity, pressure rating and materials of construction for adding to the chemical treatment. 4. WATER TREATMENT SERVICES REQUIRED a. Contractor shall begin water treatment program when system first begins to operate on a regular basis. b. Make weekly chemical analysis of water at the beginning until water stabilizes. Bi-monthly analysis required thereafter. Submit a copy of each chemical analysis and a report of every service call and chemical adjustment made to the Chief of Maintenance, Dade County Aviation Department. Results shall be in the mail within five business days from date of sampling. c. Adjust chemicals as required to control scale, corrosion and biological growth. Removing scale by quick clean acid will not be allowed. d. Provide additional corrosion test coupons plus costs of analysis should original coupon indicate corrosion. e. Other services to be included in basic construction contract for first year: (1) Provide space to store chemicals (DCAD to provide). (2) Remove heads of condensers for inspection and flush-out or brush-out sedimentation. (3) Hire independent testing laboratory to analyze the corrosion test coupons on a quarterly basis. (4) Clean cooling tower, minimum of 2 times per year. f. The field service representative shall be supervised by a graduate chemist or chemical 01/97 DGM SECTION 15182 4 OF 4 HVAC - WATER TREATMENT OF CONDENSER AND CHILLED WATER SYSTEMS engineer of a University whose chemistry department is accredited by the American Chemical Society. g. The chemical company must maintain a fully equipped water analysis laboratory in either Dade, Broward or Palm Beach county. h. The laboratory must be staffed by a full-time qualified water treatment chemist. i. Delivery of chemicals must be completed within four (4) days of the order. j. Additional testing by laboratory personnel will provide results within seventy-two (72) hours for samples requiring more than ordinary field testing. k. Emergency repair capability of chemical feed and control equipment shall be locally available by the chemical supplier. 5. APPROVED MANUFACTURERS a. Betz b. Ecolochem c. Mitco d. Mogul e. Olin 6. CHILLED WATER SYSTEMS a. New systems not connected to central chiller plants shall be equipped with pot feeders. The Contractor shall maintain anti-scale and corrosion chemical content in system of specified concentration for one year. b. New systems being connected to an existing central chiller plant will not require pot feeders. A compatible chemical to that being currently used (equal to Ecolochem No. 670, a Borate- nitrite corrosion inhibitor), shall be delivered to the central chiller plant in the amount of one gallon of chemical for each 100 gallons of water in the system. The feeding of the chemical to the system will be performed under a separate contract. Include the following statement in the specifications: "The new piping on this project will have a volume of _______ gallons of chilled water." c. Chemicals shall not destroy pump seals or damage any part of the system and shall be acceptable by controlling authorities. d. Secure chemicals analysis of the treated chilled water within two (2) weeks of the initial charge and in the 12th month to prove that the water is free of all damaging contaminants. e. Written reports of all tests and services shall be submitted to the DCAD Maintenance and Engineering Division. f. Quarterly chemical analysis by independent test laboratory shall be made to provide system is being properly maintained. END OF SECTION