AIR CONDITIONING AND MECHANICAL VENTILATION DESIGN
GENERAL AND TECHNICAL SPECIFICATIONS
VERSION 1.0 Since: 27/ 02 / 2014 DEVELOPED: Eng. Jose J. Bendeck V. REVIEWED: Eng. Juan G. Mahecha B. APPOINTMENT: Project Engineer ARCH. SIGNING: SINGING:
GENERAL DESCRIPTION OF THE PROJECT The general specifications and techniques are listed below and the accompanying drawings are part of the design for the supply, installation and commissioning of air conditioning systems and mechanical ventilation for Wineries Navy , whose construction lead after the Guaimaral city Department of Cundinamarca.
In an overview of the project, a mechanical ventilation system shall be determined in areas of the first floor (warehouse) to maintain indoor air quality in the cellars. Warm room for a ventilation unit is installed with electrical resistance in the duct, controlled by a room thermostat. In the fourth case of hazardous waste shall be installed according to plans , axial exhaust fans located in the walls , which discharge air volume extracted to the outside of the building.
For department office type two independent mini split systems will be installed in the office area, with evaporator type and cassette type wall accordingly. In the bathrooms two separate false ceiling fans shall be provided, which will activate the lights on and have a running time of 5 minutes delay.
For the project has established the following operating conditions:
Exterior Conditions:
Dry bulb temperature : 72.0 F. Wet bulb temperatura : 61.0 F. Height above sea level : 8.600 ft. North Latitude : 4 .10 Long : 74.20
Indoor Conditions:
Ambientes generales
Temperatura de bulbo seco : 72.0 F. 22.2 C Humedad relativa : 50 %
TECHNICAL SPECIFICATIONS
NOTE
The proponent shall clearly specify each of the items in its proposal. You must complete each and every one of the pictures of air conditioning units in accordance with the equipment offered. In the items on which options are set you should indicate what type of equipment, component or part is to be used . No keywords allowed " ... or approved equivalent."
1. CONDITIONING SYSTEM TYPE MINI-SPLIT (U-MINI SPLIT-01)
To put the office # 2, will supply and install air conditioning units of MINI-SPLIT type outdoor, placement on the wall. Each unit will consist of the following: conditioning unit and condensing unit type Mini Split Wall
Condenser Unit
Each condensing unit to install in the right place, it will be the type of horizontal discharge, with capacity for 12,000 BTUH (AHRI STD conditions.), Completely factory assembled, designed to operate with refrigerant R-410 A. The condensing unit shall consist of the following elements: Compressor A hermetic rotary compressor, preferably SCROLL TYPE INVERTER, with service valves on the suction and discharge; forced lubrication system and engine cooling the coolant passage. Includes oil filter, oil heater, internal relief valve, electric motor with thermal protection and top speed of 1750 rpm The compressor is mounted on vibration eliminators. Includes boot system with thermal magnetic protection, pressure switch for high and low pressure coolant, fuses, relays interconnect, time relays and directional signs. Condenser Condenser made of copper tubing and aluminum fins mechanically expanded, enough to dissipate the heat absorbed during the cycle capacity. The condenser fan is the axial type, taking the air and discharging laterally upward. Cover Protective cover in bonderizada sheet specially designed for outdoor work unit. Conditioning unit Mini Split conditioning unit type for installation on wall, includes cooling coil, expansion device, decorative finish on galvanized sheet with electrostatic paint and air supply rack with deflector blades (directional). Operating Characteristics: Thermostat control. Quiet operation. Three-speed fan. Grids double row of fins for air distribution.
System Components conditioning Mini-Split type 2. BLOWER AIR SUPPLY ONLINE
Be supplied and installed where indicated levels, or the site agreed with the Management of Projects, ventilation units with filter section and fan section, as indicated in the case.
SECTION OF FANS The fan section is equal to that described for the previous sections. They include centrifugal fans type, the type of multiple fins tilted forward or backward, double width, double inlet, statically and dynamically balanced. Fans shall have AMCA certified for the specified capacity.
The panels, which are easily removable, they are made of smooth sheet of minimum 16 gauge galvanized steel, painted inside and out with acrylic or electrostatic paint for installation outdoors additionally be insulated on the inside with glass wool 1 "(25.4 mm ) thick and a pound per cubic foot (16 kg/m3) density, protected inside face against the erosion caused by the flow of air, equal to AEROCOR produced by Fiberglass Colombia SA.
MOTOR The motor is supplied with each unit together will be single or three phase, 110 to 208/230 volts, with a maximum speed of 1750 rpm. The unit will have rail clamps for the engine, transmission belts and pulleys in "V". The BIDDER to whom the contract is awarded shall verify system pressure drop and adjust engine power to suit your requirements. TECHNICAL EXHAUST FAN UNITS BIDDER MUST COMPLETE SPECIFICATIONS UNIT UBS-01 COMPANY MODEL LOCATE UBS 01 : HOT ROOM
AREA SERVIDA UBS 01 : HOT ROOM
TYPE HORIZONTAL FLOW CFM 1300 STATIC PRESSURE 0.5 C. A. POWER HP VOLTAGE 110 PHASES 1 CYCLES 60 DIMENSIONS (mts) (L X A X H)
914x813x480 WEIGHT 58 kg
UNIT UBS-02/03 COMPANY MODEL LOCATE UBS 02 : FIRST FLOOR UBS 03 : FIRST FLOOR
AREA SERVIDA FIRST FLOOR
TYPE HORIZONTAL FLOW CFM 2600 STATIC PRESSURE 0.3 C. A. POWER 1/3 HP VOLTAGE 110 PHASES 1 CYCLES 60 DIMENSIONS (mts) (L X A X H)
1473x1067x584 WEIGHT 290 kg
UNIT OF MEASURE UNIT
BENCHMARKS GREENHECK LOREN COOK SOLER & PALAU
3. INDEPENDENT EXTRACTION FAN Be supplied and installed at the locations indicated Broan fans centrifugal extraction or equivalent type, direct drive, horizontal discharge, equipped with extraction grid for ceiling location. The kit includes mounting elements, circular damper duct connector. The characteristics of the equipment listed below.
UNIT IEF 01/02 LOCATE Bathroom Second Floor
COMPANY MODEL FLOW CFM 100 CFM STATIC PRESSURE 0.3 in c.a. GRID 10 5/8 X 11 1/8 DIMENSION (L X W X H) 8 X 8 X 5 3/4
POWER 32 W AMPERAGE 1.3 A NOISE LEVEL 41 dbA SPEED 2500 RPM VOLTAJE 110 1 60 WEIGHT APPROX. 2.1 kg
The fan drive shall comprise the light switch in each of the bathrooms. Additionally take a timer so that the fan will continue in operation until three to five minutes after turning off the light.
INDEPENDENT EXTRACTION FAN UNIT OF MEASURE UNIT Includes: Timer 0-5 min Installation BENCHMARKS GREENHECK BROAN LOREN COOK 4. CONDUITS IN GALVANIZED SHEET For supply and return ducts for air conditioning and ventilation, we supply and install all ductwork in accordance with the project plans with the following specifications: Galvanized steel smooth ACESCO quality, according to the unions gauges and reinforcements specified below shall be used: Gauge Fitting more less than 760 mm: Gauge 24 Long side between 780 and 1380 mm: Gauge 22 Long side between 1400 and 2140 mm: Gauge 20 Above 2160 mm long side: 18 Gauge Transverse Joints: Fitting more less than 460 mm: S - SLIP Long side between 480 and 1020 mm: TDC or TDF with two clips Long side between 1040 and 1380 mm: TDC or TDF with three clips Long side between 1400 and 2140 mm: TDC or TDF with four clips Greater than 2160 mm Fitting: TDC or TDF with clips every 220mm Reinforcements: Fitting more less than 380 mm: No reinforcement Long side between 400 and 900: Vena 300 mm Long side between 920 and 1380 mm: Vena and reinforcement with Gauge 22 Z Long side between 1400 and 2140 mm: Vena and reinforcement with 20 Gauge Z Side greater than 2160 mm: with double Z "Tie Roads" Inner radius elbows have equal or higher side of the duct, if used right elbow deflector guides according to ASHRAE standards are installed. For sites that require volume dampers will be installed to facilitate system balancing. Ducts shall be supported with: Fitting more less than 900 mm: Platen 1 " x 1/ 8" Long side between 920 and 1520 mm, rods Bridge 3/8 ", 1" Angle Long side between 1540 and 3000 mm rod Bridge 3/8 " angle of 1 1 /2" Side greater than 3000 mm: Bridge rod 1/2 " , 2" angle For horizontal sections Ramset fixing bolts or similar is used, vertical ducts shall be fixed to the plates of each floor. Profiles should be placed in iron T or U, between the joists to secure the brackets. Fixing all ducts , rectangular, triangular or circular shall be executed in accordance with the Law on Earthquake resistant buildings , and taking into account the rules of " SEISMIC RESTRAIN MANUAL - GUIDELINES FOR MECHANICAL SISTEMS " SMACNA . The Contractor shall submit for approval detailed drawings supports auditing of proposed use. All angle profiles, rods and plates to be used as carriers for both connections and reinforcements, should be covered with a layer of approved anticorrosive paint before installation.
This item includes dampers and splitter dampers required for correct balancing system, which will be installed at the locations indicated on the drawings of the project and those which are essential to achieve your goal.
MATERIAL Quality galvanized steel sheet ACESCO Payment Unit Square meter m2 Includes - Unions - Reinforcements - Support - Gates of regulation - Waste - Installation - Evidence of leaks 5. DIFFUSER, GRILLES AND BLINDS DESCRIPTION Be supplied and installed rectangular diffusers to be built, extruded, aluminum same or similar 3D series, frame hook, manufactured by LAMINAIRE models. S. A. Diffusers to be installed in areas where modular false ceiling supported on aluminum profiles modulated in 2 'x 2' installed (61 x 61 cm) will be the perforated type, made of aluminum, the same or similar models series 7500-6 produced by "METAL - AIR" metal plenum and directional flaps including BDS operated circular pattern from the bottom of the diffuser, finished in white electrostatic paint throttle damper volume type.
CONSIDERATIONS Return vents and / extraction Grids extraction or return to be installed in areas where it is intended to ceiling modular type 2 ' x 2' ( 0.61 x 0.61 m) will be built in aluminum perforated same or similar kind to those produced by " mETAL- AIR " model 7500R -6 Plenum and metal circular flow regulating gate BDS model operated from the bottom of the grid , finished in white electrostatic paint. Extraction grilles type cubes Grids extraction will be made of aluminum cubes type with damper , similar to the CC- 5DA models manufactured by " METAL- AIR " (USA ) or model RRTC (L- RAG x OB) of LAMINAIRE ; THE PLOT OF CUBES TO BE MADE IN FULL BY ALUMINIUM . Louvered grilles extraction Extraction grids will be made of aluminum , with louvered damper , similar to the L -RA- OB -TB models manufactured by Laminaire . The racks will be equipped with a volume control on the type of multiple opposing fins, operated pinion system to regulate airflow . Blinds Blinds discharge and air intake to be installed will be built in extruded aluminum profiles , identical or similar to the model OAL -4 -F with protective mesh manufactured by METALAIRE . Louvers The louvers will be manufactured with extruded aluminum profiles , forming a fixed louver fin . Each element air distribution will be equipped with a volume control on the type of multiple opposing fins, operated pinion system to regulate airflow . Dampers manuals Be supplied and installed at the locations indicated in the project drawings , manual dampers , made of smooth galvanized steel sheet , the type of opposite leaves , with bushings made of brass, with outer drive and position indicator. 6. AXIAL WALL FAN For the area of hazardous waste shall be supplied and installed axial fans for installation on the wall, swing type, low noise level operation. Which have in their composition the explosion proof motor. Las caractersticas principales sern: Flow 800 cfm Number of fins cinco (5) Fin Material Steel, Aluminum Speed range 1550 rpm Voltage 120 V Power 1/20 hp Weight 3.7 kg Control Wired remote - Included in the price Installation In Wall Noise Criterial Low
BENCHMARKS Soler y palau AIR KING AIR MASTER DAYTON UNIT OF MEASURE Payment will be made for each unit to the manufacturer, this includes equipment and accessories mounting the officer and his assistants must use tool. Further control of the team included. Will be included installation and commissioning of ventilation equipment. 7. ELECTRICAL AND CONTROL BOARD DESCRIPTION Be supplied and installed electrical panels for operation and protection of each set of equipment installed. Each board will be for three-phase system, manufactured in accordance with NEMA standards, Type 1, commonly used. Each board their bus bar protection shall include electro less copper terminals, automatic protection switch distributions, magnetic starters for each motor thermal bimetallic overload protection relays, push button, signal lamps, power strips and control signs and indicators . CONSIDERATIONS The electrical panel TEAA -01 include comprehensive measurement center or multi meter , digital type , compatible with BACnet communication protocol , in which the line currents , phase and line voltage , active power and power factor is verified Boards including starts air conditioning units of the operating room will speed drives including frequency variation in cost flow sensor to maintain this constant. All items to be used are of top quality, Siemens, Schneider (Telemecanique) or LG , which meet the standards set by NEMA for this type of facility. The board should include provisions for its management interface with a digital direct control. Also you must include transformers for operating controls, either 115V or 24 VAC . All boards should be made taking into account the rules of RETIE and must have their certificate of conformity. REGULATIONS - NEC - RETIE MEASUREMENT AND PAYMENT Complete unit based on the final installation site.