The purpose of this application note is to describe the options for using DeltaV M Series Virtual IO Modules with

S Series
Controllers.
The DeltaV Virtual IO Module (VIM), VIM-4201, will not only work with DeltaV M Series carriers but also with DeltaV S Series
carriers. Please follow the guidelines below for successful carrier selection and installation.
General Guidelines
The Virtual IO Module(s) will need to be installed in a controller slot(s) of the Vertical Plus 4-wide carrier
Each Virtual IO Module will require a DeltaV System Power Supply mounted in the power supply slot to the left of the
controller slot.
The total DeltaV Railbus distance of 6 meters cannot be exceeded. This is the distance that includes all carriers, carrier
extenders, and carrier extender cables.
Horizontal S Series Carrier Configuration
The S-series interfaces provide improved ease of installation with the same proven proven features of M-series I/O interfaces.
Simplex or redundant controllers can be configured to ocmmunicate with simplex/redundant Virtual I/O Module. If redundant
Controllers are required, two 2-wide s series carriers will need to be added. The S Series I/O carriers should be installed first
prior to bus extender installation for Virtual I/O Module installation.
The S Series controllers will requre a right bus extender to connect to the left bus extender on the m series vertical plus 4-wide.
Vertical Plus M Series Carrier Configuration
The vertical 4-wide carrier only has slots for two Virtual I/O Modules. If the vertical carrier is not a VerticalPlus carrier the
following configuration will not work.
1
One of the enhancements with the DeltaV VerticalPlus Carriers is the ability to connect two Virtual I/O Modules, allowing the use
of redundant Virtual I/O Modules. A sample configuration is shown below. Please refer to the DeltaV Installation and Planning
guide and the Virtual I/O Manual for more information. For more information on Virtual I/O Module configuration please reference
the following documents:
IOD-4101 Modbus TCP Master/Slave Driver for DeltaV Virtual I/O Module
IOD-4102 Ethernet/IP Master Driver for DeltaV Virtual I/O Module
IOD-4104 Generic Ethernet/IP Master Driver for DeltaV Virtual I/O Module
VerticalPlus Carrier and Extender Bill of Materials
Qty Model Description
1-2 KJ4005X1-BA1 2-Wide Horizontal-Mount Power/Controller Carrier
1 KJ4005X1-BC1 Extender Card for S Series Horizontal Carrier
1 VE3056 4-Wide Vertical-Mount Power/Controller Carrier; SIS
Compatible
1 KJ4003X1-BF1 Extender Card for VerticalPLUS Carrier;
bottom right or top left
1 KJ4003X1-BH2 Extender Cable, 0.4 meter (17 inches), for VerticalPLUS
Carriers

Source URL: http://www.mynah.com/knowledge-base/using-deltav-m-series-virtual-io-modules-s-series-controllers
MYNAH Technologies LLC
390 South Woods Mill Road, Suite 100
Chesterfield, MO 63017 USA
+1.636.728.2000 (International)
+1.636.728.2001 (Fax)
Email: support@mynah.com
Web: www.mynah.com
2
Copyright 2014 MYNAH Technologies LLC. All rights reserved.
MiMiC and the MiMiC design are marks of MYNAH Technologies. All other marks are the property of their respective owners. The contents of this publication are presented for informational purposes
only, and while every effort has been made to ensure their accuracy, they are not to be construed as warrantees or guarantees, express or implied, regarding the products or services described
herein or their use or applicability. All sales are governed by our terms and conditions, which are available on request. We reserve the right to modify or improve the design or specification of such
products at any time without notice.
3

Das könnte Ihnen auch gefallen