Name: Ubayeda Shaqer Student number: 15975669 Title of the experiment: Restricted Earth Fault Protection For A ____________________Three Phase transformer Laboratory group: Monday (1400-1600)(Even) Laboratory supervisor: Hadi Laboratory partners: Scott Date performed the experiment: -09-2014 Due date: 06-09-2014 Date submitted: 06-09-2014
I hereby declare that the report presents entirely my own work and have not copied from any other student or past student. Student signature: ________________________________________
Page 2 of 20
Table of Contents
Introduction: ........................................................................................................................................... 3 Aim: ......................................................................................................................................................... 3 Summary of report: ................................................................................................................................. 3 Theory ..................................................................................................................................................... 3 Procedure ................................................................................................................................................ 5 Equipment ........................................................................................................................................... 6 Results ..................................................................................................................................................... 7 Test 1:No Load Tests ........................................................................................................................... 7 Test 2:Balanced Load Test .................................................................................................................. 7 Test 3:Unbalanced Load Tests ............................................................................................................ 8 Discussion................................................................................................................................................ 9 Answers to the questions ..................................................................................................................... 11 No Load Tests .................................................................................................................................... 11 Balanced Load Test ........................................................................................................................... 13 Unbalanced Load Tests ..................................................................................................................... 16 Conclusion ............................................................................................................................................. 20
Page 3 of 20
Restricted Earth Fault Protection of a Three-Phase Power Transformer (Using Current Sensitivity Relay) Introduction:
This lab tests the restricted earth fault protection for a three-phase power transformer. The sensitivity is adjusted and the current is measured across various points. Aim:
This lab has been designed to test the restricted in the fault which is used to protect earthed and wye-connected three phase machines but cant be used delta connected setting due to the fact this type of protection works on the neutral phase of the three phase setting. The protection scheme was tested on three different circuits one with no load in the system, balanced load and unbalanced load. Summary of report:
The experiment was successfully completed. Faults that occurred in the protection zone was identified and cleared- but any external faults (i.e. outside the reach of the relays) did not trip the circuit. Theory
An earth fault relay generally provides protection against faults by measuring the neutral or the residual current or both. Ideally the neutral and residual currents of a system are zero. Under normal conditions and by application of Kirchhoffs laws the sum of currents in both current transformers (CTs) equals zero. The REF under external faults, the current in the line CTs are balanced with the neutral CTs; however this is not the case under internal faults the current is not balanced and current flows in the neutral circuit therefore this is an indication of an fault and the REF operates. The REF is a combination of residual current relay which detects the current differential of the three phases (in a three phase system) and a second relay thats operates on the neutral line of the wye connected scheme. The currents in both the lines are observed and this is how faults are detected and then cleared; this is very accurate approach for protection. Page 4 of 20
Figure 1: Protection Scheme Three current transformers for each phase and current transformer for the neutral line is used to measure current in this protection scheme. As seen in the figure above the secondary windings of the line current transformers are connected in parallel to obtain the vector sum of the three line currents. These secondary windings are also connected in parallel with a protective relay and the secondary winding of the neutral current transformer. This is similar to a differential protection however a REF protection scheme is comparatively cheaper than differential protection scheme.
Any unbalance between the two current initiates the protection system causes the protective scheme to trip and isolated the transformer. However this is true only for the secondary side of the transformer. According to requirements and budget a REF can be placed in the primary side of the transformer too. This would provide a complete protection for the entire system against both external and internal faults in the system. REF protection is fast and can isolate winding faults extremely quickly, thereby limiting damage and consequent repair costs.
Figure 2: Protection Scheme and Single Line Diagram for REF Page 5 of 20
Procedure
The EMS Workstation and the Protective Relaying Control Station was set up according to the schematic provided.
Figure 3: Schematic For REF protection
The circuit was connected according to each connection i.e. for the red wire phase A of the 3 phase circuit was selected and connected from the input to its end at RL (1). Following colour one by one starting and ending its connection was procedure used to begin and complete the circuit. Faults were then manually initiated for different 3 different setting of the circuit under no load, a balanced load and unbalanced. The time and current in the ammeter were observed and recorded. The sensitivity settings were set according to the instruction (Sensitive Relay to 20 % and 50%). In this protection scheme the time setting were already placed internally with in the relay. Page 6 of 20
In Restricted Earth Fault scheme the common terminals of phase CTs are connected to the secondary of Neutral CT in such a manner that secondary unbalance electric current of phase CTs and the secondary electric current of Neutral CT will oppose each other. If these both electric currents are equal in amplitude there will not be any resultant electric current circulate through the said close path. Ammeters were used to measure this current.
Equipment
Current sensitive relay Relay test set
Figure 4: Completed Connected Schematic This figure displays the complete connected circuit.
Page 7 of 20
Results
Test 1:No Load Tests
7.1 The primary line current (indicated by ammeter I1), the secondary line current (indicated by ammeter I2), the neutral current (indicated by ammeter I3), and the current flowing in the AC/DC Current Sensitive Relay (indicated by ammeter 14)
Table 1: Ammeter Currents (No Load)
7.2 An earth fault near the neutral end of the secondary winding of transformer T1. Table 2: Ammeter Currents (Internal Fault at T1) I1= 40mA I2=4,0mA I3= 600mA I4 = 600mA
7.3 A phase-to-earth fault beyond the line current transformers. Table 3: Ammeter Currents (External Fault) I1= 650mA I2= 650mA I3= 800mA I4 = 0mA
Test 2:Balanced Load Test
8.1 An earth fault near the middle of the secondary winding of transformer T1. Table 4: Ammeter Currents (Internal Fault at T1) 11= 200mA 12= 200mA 13= 600mA I4 =420 mA why zero?? balanced
I1= 0 A I2= 0 A I3= 0 A I4=0 A Page 8 of 20
8.2 An earth fault near the middle of the secondary winding of transformer T3. Table 5: Ammeter Currents (Internal Fault at T3) I1= 350mA I2= 350mA I3= 600mA I4 = 550mA
8.3 A phase-to-earth fault beyond the line current transformers. Table 6: Ammeter Currents (External Fault) I1= 1.05A I2= 1.05A I3= 600mA I4 = 0mA
Test 3:Unbalanced Load Tests
9.1 This unbalances the three-phase load currents. Table 7: Ammeter Currents (Unbalanced Load)
I1= 200mA I2= 200mA I3= 200mA I4 = 0mA
9.2 An earth fault near the middle of the secondary winding of transformer T1. Table 8: Ammeter Currents (Internal Fault at T1) I1= 200mA I2= 200mA I3= 150mA I4 = 180mA
9.3 An earth fault near the middle of the secondary winding of transformer T3. Table 9: Ammeter Currents (Internal Fault at T1) I1= 0A .8 I2= 0A.8 I3= 0A .8 I4 = 600mA ,4ma
9.4 A phase-to-earth fault beyond the line current transformers. Table 10: Ammeter Currents (External Fault) I1= 750mA I2=750mA I3= 800mA I4 = 0mA Page 9 of 20
Discussion
This laboratory investigates the function and limits of the Restricted Earth Fault. The REF requires 4 CTs to be connected in parallel. The CTs compare the difference in the neutral and residual current in order to detect a fault. As seen in the schematics (figure 1) the protection system has been designed where under normal conditions the neutral current and the CT currents should cancel out (Ammeter 4 should always be zero). This lab primarily deals with two different faults internal and external faults. The faults test is conducted under three different configurations No load, Balanced load and Unbalanced load. In all three cases the internal faults are detected and cleared by the REF protection system. However in all three cases the external faults could not be detected nor cleared by the REF. This was simply because the faults were outside the scope and reach of the CTs therefore they completely avoid detection. This suggest the REF system is highly stable and reliable as it operates when required and within its zone. The internal faults that were investigated were located in two different locations in T1 or T3 and in the middle of the winding or the neutral. Faults in the secondary winding cause an imbalance between the neutral and residual current; this is detected by Ammeter 4 which then triggers the relay according to the current setting of the relay (sensitivity). 0% means the relay is most sensitive and will trip the circuit when any amount of current is detected under any conditions (not necessary a fault present in the circuit). The current setting is setting up a standard or reference fault current which will allow the relay to distinguish between fault current and normal current; when to or not to trip the circuit. Therefore the relay must be adjusted according to the rated power and current setting taking into consideration the maximum fault current that can be expected. Most of the ammeter reading are in Millie-Ampere which is very difficult to decipher between whether the detections actually error or saturation or mismatch but however since the relay operated during faults and cleared the internal faults; it can safely be assumed the currents during the fault are the actual fault current, where a percentage of the current has been contributed by the various error issues of the circuit. CT mismatch, CT saturation, tolerance of the equipment and spill currents are sources of error that affect the recorded current values.
Ammeter 1 and Ammeter 2 display the phase currents on the primary and secondary winding of the transformer. Since there is no protection on the primary side faults on the primary cant be detected or cleared. Ammeter 3 displays neutral current which is essential in detection of the faults or unbalances in the system. As the winding fault position moves towards the neutral, the magnitude of the current seen on the primary rapidly decreases and could potentially not be detected (limiting the amount of winding which can be protected).
Page 10 of 20
A restricted earth fault system supplied by a three phase transformers must include a time delay in order to avoid dubious and nuisance triggering resulting from transients. Generally it recommended that current setting must not be lower than 15% of the transformer rating at best, or 20 % of the transformer ratings in the most unfavourable cases. Moreover, if an earth fault occurs in a star winding near a neutral point, the maximum fault current is only a small part of the maximum fault current which is limited by the neutral earth impedance. For this reason, the current setting is usually 20% of the maximum current limited by the neutral earth in order to protect 80% of the windings.
Earth fault protection applied to a delta-connected or unearthed star winding is inherently restricted, since no zero sequence components can be transmitted through the transformer to the other windings. If a fault occurs on the delta side it cannot be detected or cleared. Build of fault current can lead to catastrophic failure in the system.
It can be observed that fault currents recorded near the neutral for the primary side have smaller amplitude comparatively. Hence, although the prospective current level decreases as fault positions progressively nearer the neutral end of the winding ;a large percentage of the winding can be covered if the protection system is placed on the secondary side (as seen in the schematics figure 2). Both windings of a transformer can be protected separately with restricted earth fault protection, thereby providing high-speed protection against earth faults Because the fault detection is limited between the lines of CT it is restricted in this zone which why the protection scheme is called the Restricted earth fault system. REF are comparatively cheaper than the differential protection scheme therefore it is better option due to the fact it is reliable, fast and stable protection system .
Page 11 of 20
Answers to the questions No Load Tests
7. 1 Record the primary line current (indicated by ammeter I1), the secondary line current (indicated by ammeter I2), the neutral current (indicated by ammeter I3), and the current flowing in the AC/DC Current Sensitive Relay (indicated by ammeter 14) in the following blank spaces. The circuit currents are:
Is the REF protection system almost perfectly balanced? Briefly explain. Yes, the REF protection system was balanced. Under normal conditions the system was balanced because there was no fault in the system and by application of Kirchhoffs laws the sum of currents in both current transformers (CTs) equals zero. This has been observed and recorded above, all ammeter values equal to zero.
7. 2 On the Fault able Transformers, set fault switch FS3 of transformer T1 to the I position to insert an earth fault near the neutral end of the secondary winding of transformer T1. While doing this, observe the circuit currents and the tripping indicator (red LED) on the AC/DC Current Sensitive Relay. Adjust the current set point of the AC/DC Current Sensitive Relay to 20 % and 50%, respectively and observe the operation of relay. The circuit currents are: I1= 40mA I2=4,0mA I3= 600mA I4 = 600mA
Describe what happens when an earth fault occurs near the neutral end of one of the power transformer secondary windings. Due to an earth faults and imbalance in current is seen through the circuit. The ammeter placed in the circuits detects currents due to the imbalance and the presence of a fault. Current through Ammeter 1 and 2 are the same because they are placed across two different phases of the three phase system and Ammeter 3 and 4 detects the difference in current therefore subtraction of the phase current and neutral current results in the same value. I1= 0 A I2= 0 A I3= 0 A I4=0 A Page 12 of 20
The circuit trips when the difference in current reaches a certain value (level). This tripping characteristic is set for a certain reference in order to take into account error of the CT and prevent any false trips. 7. 3 On the Universal Fault Module, depress the INITIATE FAULT button to produce a phase-to-earth fault beyond the line current transformers. The circuit currents are: I1= 650mA I2= 650mA I3= 800mA I4 = 0mA
Set the current setting of relay on 20% and observe the operation of relay. After that change the current setting of relay to 0% (minimum) and apply same fault again. While doing this, observe the circuit currents and the tripping indicator on the AC/DC Current Sensitive Relay. Describe what has happened. 0% means the relay is the most sensitive any differential current in I4 would cause the protection scheme to operate and the circuit to trip. However the with the manual initiation of the UFM the circuit did not trip nor was a differential current detected in I4. This is because from the schematic we can see the fault is outside the protection zone and scope of the REF therefore even the most sensitive relay settings will not pick up the fault. Is the REF protection system stable for faults outside the protection zone defined by the four current transformers? Briefly explain. Yes the system is stable. The protection system only operates when it is required that is the fault is within its protection zone. The UFM is outside the protection zone of the CTs so the fault is not detected and no difference in current detected by Ammeter 4. Therefore in case of an external fault the relay is not activated, the CTs dont pick up any fault and REF is stable. An external fault in the star side will result in current flowing in the line current transformer of the affected phase and at the same time a balancing current flows in the neutral current transformer; hence the resultant electric current in the relay is therefore zero. So this REF relay will not be operating for external earth fault. Has the fault been cleared by the REF protection system? Why? Yes No The REF does not clear the fault because it does not see the fault; it is outside the protection zone and scope of the CTs; the fault must be cleared by another protection scheme. The system is operative for faults within the region between current transformers that is, for faults on the star winding in question. The system will remain stable for all faults outside this zone. Page 13 of 20
Balanced Load Test
8. 1 On the Fault able Transformers, set fault switch FS3 of transformer T1 to the I position to insert an earth fault near the middle of the secondary winding of transformer T1. Set the current setting of relay on 20% and observe the operation of relay. After that change the current setting of relay to 50% and apply same fault again. While doing this, observe the circuit currents and the tripping indicator on the AC/DC Current Sensitive Relay. The circuit currents are: 11= 200mA 12= 200mA 13= 600mA I4 =420 mA why zero?? balanced
Describe what happens when an earth fault occurs on one of the power transformer secondary windings and describe the difference of relay operation for mentioned two settings. At 20% a lower current initiates the protection scheme as the relay is more sensitive (the reference current is lower) than it is at 50%. But the measurement obtained is degraded by the inaccuracies of all three current transformers, in particular in the event of transient over-currents when the transformers become saturated. This means the fault current is detected earlier when the relay is at 20% but protection scheme takes the same amount of time to clear the fault. When an earth fault occurs at the secondary winding the neutral current transformer carries the unbalanced fault current and this initiates Restricted Earth Fault Relay to isolate the transformer against the internal fault. For which current setting of relay, the fault has been cleared by the REF protection system? By both the current setting the fault was cleared by the relay. The setting just adjusted at what fault current the REF tripped the circuit but it cleared both the faults. The sensitivity setting must be adjusted in order to in to consideration mismatch, error, and saturation; make sure there are no nuisance trips.
Page 14 of 20
8. 2 On the Fault able Transformers, set fault switch FS3 of transformer T3 to the I position to insert an earth fault near the middle of the secondary winding of transformer T3. Set the current setting of relay on 50% and observe the operation of relay. After that change the current setting of relay to 70% and apply same fault again. While doing this, observe the circuit currents and the tripping indicator on the AC/DC Current Sensitive Relay.
Describe what happens when an earth fault occurs on one of the power transformer secondary windings. At 50% current setting the relay (protection and trip) is initiated for smaller current as it is more sensitive (the reference current is lower) than it is at 70%. But the measurement obtained is degraded by the inaccuracies of all three current transformers, in particular in the event of transient over-currents when the transformers become saturated. Most of the current setting recorded is in milliamps. This means the fault current is detected earlier when the relay is at 50% but protection scheme takes the same amount of time to clear the fault. When an earth fault occurs at the secondary winding the neutral current transformer carries the unbalanced fault current and this initiates Restricted Earth Fault Relay to isolate the transformer against the internal fault.
For which current setting of relay, the fault has been cleared by the REF protection system? The relay functioned for both the current settings. It is usually recommended to keep the current setting at 20% to 80% is an optimum standard depending on fault levels this range ignores nuisance trips at the same time functions for high fault levels (high powered transformers).
Page 15 of 20
8. 3 On the Universal Fault Module, depress the INITIATE FAULT button to produce a phase-to-earth fault beyond the line current transformers. The circuit currents are: I1= 1.05A I2= 1.05A I3= 600mA I4 = 0mA
Set the current setting of relay on 20% and observe the operation of relay. After that change the current setting of relay to 0% (minimum) and apply same fault again. While doing this, observe the circuit currents and the tripping indicator on the AC/DC Current Sensitive Relay. Describe what has happened. The manual initiation of the UFM the circuit did not trip nor was a differential current detected in I4. This is because from the schematic we can see the fault is outside the protection zone and scope of the REF therefore even the most sensitive relay settings (i.e. 0%) will not pick up the fault.
Is the REF protection system stable for faults outside the protection zone defined by the four current transformers? Briefly explain. Yes the system is stable. The protection system only operates when it is required that is the fault is within its protection zone. The UFM is outside the protection zone of the CTs so the fault is not detected and no difference in current detected by Ammeter 4. Therefore in case of an external fault the relay is not activated, the CTs dont pick up any fault and REF is stable. An external fault in the star side will result in current flowing in the line current transformer of the affected phase and at the same time a balancing current flows in the neutral current transformer; hence the resultant electric current in the relay is therefore zero. So this REF relay will not be operate for external earth fault On the Universal Fault Module, place the INITIATE FAULT button in the released position. Has the fault been cleared by the REF protection system? Yes No
Page 16 of 20
Unbalanced Load Tests
9. 1 Set the resistance of resistor R1 to the value given in the following table. (Make all the 3 existing 4800 (ohm) resistors parallel) This unbalances the three-phase load. The circuit currents are: I1= 200mA I2= 200mA I3= 200mA I4 = 0mA
9.2 On the Fault able Transformers, set fault switch FS3 of transformer T1 to the I position to insert an earth fault near the middle of the secondary winding of transformer T1. Set the current setting of relay on 10% and observe the operation of relay. After that change the current setting of relay to 30% and apply same fault again. While doing this, observe the circuit currents and the tripping indicator on the AC/DC Current Sensitive Relay. The circuit currents are: I1= 200mA I2= 200mA I3= 150mA I4 = 180mA
Describe what happens when an earth fault occurs on one of the power transformer primary windings. When a fault occurs on the primary winding it is less likely the fault is going to be detected by the REF protection scheme. This is because the CTs are all connected on the secondary side of the transformer not the primary. There no protection placed on the primary or any neutral current present in the primary winding. If a fault occurs in the primary then the fault current will circulate in the circuit will build until it leads to a catastrophic failure in the transformer and circuit. According to the test 9.2 when a fault occurs in the secondary winding the following results were observed and recorded. At 10% current setting the relay is initiated without a fault in the circuit. This is because the relay is very sensitive therefore it trips (nuisance trip) due to any difference in current that is present due errors that have not been take into consideration (i.e. CT mismatch saturation etc.). The current measurement obtained is degraded by the inaccuracies of all three current transformers, in particular in the event of transient over-currents when the transformers become saturated. Most of the current setting recorded is in milliamps. This means the fault current is detected earlier when the relay is at 30% but protection scheme takes the same amount of time to clear the fault as the time setting are fixed and we are only changing the current setting. Page 17 of 20
When an earth fault occurs at the secondary winding the neutral current transformer carries the unbalanced fault current and this initiates Restricted Earth Fault Relay to isolate the transformer against the internal fault. For which current setting of relay, the fault has been cleared by the REF protection system? For both the current setting the faults were cleared by the protection scheme. This is because the faults are internal but 10% the relay is too sensitive which lead nuisance trips small difference in currents is considered to be a fault current which is the not case. Even without manually introducing the fault in the system the protection scheme operates. Are the values of I4 same for both faults in steps 8-2 and 9-2? Why? No they are not the same. This due to the fact the load requirements in the circuit are different in between 8.2 and 9.2 and due CT mismatch, saturation and presence of spill current directly effects the current values that have been recorded. The current measurement obtained is degraded by the inaccuracies of all four current transformers. 9. 3 On the Fault able Transformers, set fault switch FS3 of transformer T3 to the I position to insert an earth fault near the middle of the secondary winding of transformer T3. Set the current setting of relay on 30% and observe the operation of relay. After that change the current setting of relay to 60% and apply same fault again. While doing this, observe the circuit currents and the tripping indicator on the AC/DC Current Sensitive Relay. The circuit currents are: I1= 0A .8 I2= 0A.8 I3= 0A .8 I4 = 600mA ,4ma
Describe what happens when an earth fault occurs on one of the power transformer secondary windings. At 30% current setting the relay is activated and protection scheme is initiated for a smaller fault current as it is more sensitive (the reference current is lower) than it is at 70%. 70% current setting is generally considered as the optimum sensitivity setting where high fault current can detected and cleared by the transformer. Due to the fault in the phase T3 there is an imbalance in the phase currents which is carried by the neutral compared with the CT current; the difference of the two is a sign a fault has occurred and the I4 activates the relay which causes the circuit to trip. But the measurement obtained is degraded by the inaccuracies of all three current transformers, in particular in the event of transient over-currents when the transformers become saturated. Most of the current setting recorded is in milliamps.
Page 18 of 20
This means the fault current is detected earlier when the relay is at 70% but protection scheme takes the same amount of time to clear the fault. When an earth fault occurs at the secondary winding the neutral current transformer carries the unbalanced fault current and this initiates Restricted Earth Fault Relay to isolate the transformer against the internal fault. For which current setting of relay, the fault has been cleared by the REF protection system? For both the current setting the faults were cleared by the REF protection system as they are internal faults and in accurate range of the relay sensitivity. Are the values of I4 same for both faults in steps 8-3 and 9-3? Why? No they are not the same. This due to the fact the load requirements in the circuit are different in between 8.3 and 9.3 and due CT mismatch, saturation and presence of spill current directly effects the current values that have been recorded. The current measurement obtained is degraded by the inaccuracies of all four current transformers.
9. 4 On the Universal Fault Module, depress the INITIATE FAULT button to produce a phase-to-earth fault beyond the line current transformers. The circuit currents are: I1= 750mA I2=750mA I3= 800mA I4 = 0mA
Set the current setting of relay on 20% and observe the operation of relay. After that change the current setting of relay to 0% (minimum) and apply same fault again. While doing this, observe the circuit currents and the tripping indicator on the AC/DC Current Sensitive Relay. Describe what has happened. 0% means the relay is the most sensitive any differential current in I4 would cause the protection scheme to operate and the circuit to trip. However the with the manual initiation of the UFM the circuit did not trip nor was a differential current detected in I4. This is because from the schematic we can see the fault is outside the protection zone and scope of the REF therefore even the most sensitive relay settings will not pick up the fault.
Page 19 of 20
Is the REF protection system stable for faults outside the protection zone defined by the four current transformers? Briefly explain. Yes the system is stable. The protection system only operates when it is required (stable) that is the fault is within its protection zone. The UFM is outside the protection zone of the CTs so the fault is not detected and no difference in current detected by Ammeter 4. Therefore in case of an external fault the relay is not activated, the CTs dont pick up any fault and REF is stable. An external fault in the star side will result in current flowing in the line current transformer of the affected phase and at the same time a balancing current flows in the neutral current transformer; hence the resultant electric current in the relay is therefore zero. So this REF relay will not be operating for external earth fault. Has the fault been cleared by the REF protection system? Yes No
Page 20 of 20
Conclusion
The REF is a combination of residual current relay which detects the current differential of the three phases (in a three phase system) and a second relay thats operates on the neutral line of the wye connected scheme. The currents in both the lines are observed and this is how faults are detected and then cleared; this is very accurate approach for protection. It is far cheaper method of protection when compared to the differential protection. Unlike this lab investigation if REF is used on both sides of the transformer this will ensure fault protection throughout the transformer.