Sie sind auf Seite 1von 138

Motorpact Medium Voltage Motor Controllers

Controladores de motores de media tensin


Motorpact
Commandes de moteurs moyenne tension Motorpact
MC
Instruction Bulletin
Boletn de instrucciones
Directives d'utilisation
46032-700-06E
Retain for Future Use. /
Conservar para uso futuro. /
conserver pour usage ultrieur.
Motorpact Medium Voltage Motor Controllers
Class 8198
Instruction Bulletin
46032-700-06E
Retain for future use.
E
N
G
L
I
S
H
HAZARD CATEGORIES AND
SPECIAL SYMBOLS
Read these instructions carefully and look at the equipment to become
familiar with the device before trying to install, operate, service or maintain it.
The following special messages may appear throughout this bulletin or on
the equipment to warn of potential hazards or to call attention to information
that clarifies or simplifies a procedure.
The addition of either symbol to a Danger or Warning safety label
indicates that an electrical hazard exists which will result in personal injury if
the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal
injury hazards. Obey all safety messages that follow this symbol to avoid
possible injury or death.
PLEASE NOTE Electrical equipment should be installed, operated, serviced, and maintained
only by qualified personnel. No responsibility is assumed by Schneider
Electric for any consequences arising out of the use of this material.
DANGER
DANGER indicates an imminently hazardous situation which, if not
avoided, will result in death or serious injury.
WARNING
WARNING indicates a potentially hazardous situation which, if not
avoided, can result in death or serious injury.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided,
can result in minor or moderate injury.
CAUTION
CAUTION, used without the safety alert symbol, indicates a potentially
hazardous situation which, if not avoided, can result in property damage.
Signals a reference to another document.
Provides additional information to clarify or simplify a procedure.
Lists the tools needed for procedure.
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Table of Contents
20032009 Schneider Electric All Rights Reserved 3
E
N
G
L
I
S
H
Table of Contents
SECTION 1: INTRODUCTION .................................................................................................................... 10
Application ................................................................................................ 11
Full Voltage Non-Reversing Controller ................................................ 11
Full Voltage Reversing Controller ........................................................ 12
Dual Voltage Transfer Starter .............................................................. 13
2-Speed, 1-Winding Controller ............................................................ 14
2-Speed, 2-Winding Controller ............................................................ 15
Reduced Voltage Autotransformer ...................................................... 16
Application Notes........................................................................... 17
Reduced Voltage Soft Start Controllers .............................................. 17
Incoming Section ................................................................................. 19
Mechanically Latched Controllers ....................................................... 19
Voltage Transformer ............................................................................ 19
Transformer Disconnects .................................................................... 19
Feeder Disconnects ............................................................................ 19
Capacitor Bank Disconnects ............................................................... 19
Prepared Spaces ................................................................................. 19
SECTION 2: SAFETY PRECAUTIONS .................................................................................................................... 20
SECTION 3: RATINGS .................................................................................................................... 21
Enclosure and Bus .............................................................................. 21
Contactor ............................................................................................. 21
Latched Contactor ............................................................................... 22
Load Discharge Assembly ................................................................... 22
Incoming Section ................................................................................. 22
Voltage Transformer Section ............................................................... 22
SECTION 4: RECEIVING, HANDLING, AND STORAGE ....................................................................................................... 23
Receiving .................................................................................................. 23
Identification .............................................................................................. 23
Handling .................................................................................................... 23
Lifting Provisions ................................................................................. 24
Using a Forklift .................................................................................... 24
Storage ..................................................................................................... 24
Typical Dimensions and Weights .............................................................. 25
Indoor (NEMA 1 Construction) ............................................................ 25
Approximate Weights .......................................................................... 29
SECTION 5: TOP AND FLOOR PLAN DRAWINGS .............................................................................................................. 30
FVNR, FVR, FVS, 2S1W, 2S2W, RVAT/RVSS Controllers or RVSS
Standalone Section (29.50 in.) ............................................................ 30
RVAT ................................................................................................... 32
RVSS ................................................................................................... 33
Incoming Section ................................................................................. 34
SECTION 6: INSTALLATION .................................................................................................................... 35
Preparing the Site ..................................................................................... 35
Seismic Certification of Motorpact Medium Voltage (MV) Motor
Controllers ........................................................................................... 36
Responsibility for Mitigation of Seismic Damage........................... 36
Maintaining Seismic Certification................................................... 36
Field Installation ........................................................................................ 37
Accessing the Medium Voltage Compartments (Prior to Installation) . 37
Opening FVNR/Controller MV Door .............................................. 37
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Table of Contents 07/2009
20032009 Schneider Electric All Rights Reserved 4
Opening RVAT or RVSS MV Door................................................. 37
Anchoring Equipment .......................................................................... 38
Anchoring and J oining the Shipping Splits..................................... 38
Anchoring the Autotransformer...................................................... 40
Accessing the Bus Compartment ........................................................ 44
FVNR/FVR/Controller Section....................................................... 45
RVAT/RVSS Enclosure.................................................................. 46
Through Bus Splice Connections ........................................................ 47
Connecting the Through Bus Bars................................................. 47
Ground Bus Splice Connections .......................................................... 49
Cable Terminations ............................................................................. 49
Shielded Cable............................................................................... 49
Cable Installation........................................................................... 50
Loadbox Barrier ............................................................................. 52
RVAT Cable Connections (44.25 and 59.00 Sections).................. 52
RVSS Cable Connections.............................................................. 53
RVSS Standalone Section Cable Connections.............................. 54
Control Wiring Terminations and Routing ............................................ 56
FVNR/FVR/Controller Section LV Wiring....................................... 56
RVSS Section LV Wiring................................................................ 57
Hi-pot (Dielectric) Testing .......................................................................... 57
Phase-to-Phase Hi-pot Testing ........................................................... 58
Phase-to-Ground Hi-pot Testing .......................................................... 59
Performing a Final Inspection ................................................................... 60
SECTION 7: FEATURES AND OPERATION .................................................................................................................... 61
In This Section .......................................................................................... 61
Arc Resistant Features .............................................................................. 61
Clearances .......................................................................................... 62
Back Light Assembly ................................................................................. 62
Blown Fuse Indicator ................................................................................. 63
Contactors ................................................................................................. 64
Electrically Maintained Contactors ...................................................... 64
Latched Contactor ............................................................................... 65
Inserting/Withdrawing Contactors ........................................................ 65
FVNR/FVR/Controller Contactors.................................................. 65
RVAT/RVSS Contactors................................................................ 66
Door and Mechanical Interlock Features .................................................. 67
Mechanical Interlocks .......................................................................... 67
Unlocking/Locking FVNR/FVR/Controller Doors ................................. 68
Unlocking/Locking RVAT/RVSS Doors ............................................... 68
Key Interlocks ...................................................................................... 69
Defeating Controller Interlocks....................................................... 70
MDT107 Thermal Diagnostic System ....................................................... 70
Description ........................................................................................... 70
Functions ............................................................................................. 71
Monitoring of Temperature Buildup in Two Zones......................... 71
Triggering of a Pre-alarm............................................................... 71
Triggering of an Alarm................................................................... 71
Self-monitoring of the Module........................................................ 72
Self-monitoring of Sensors............................................................. 72
Ratings ................................................................................................ 73
MDT107 Module Location ................................................................... 74
MDT107 Sensors Location .................................................................. 75
Setting the Temperature Rise Thresholds ........................................... 75
Setting the Ambient Temperature Correction ...................................... 76
Troubleshooting ................................................................................... 76
Isolation Means (IM) .................................................................................. 77
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Table of Contents
20032009 Schneider Electric All Rights Reserved 5
E
N
G
L
I
S
H
Description .......................................................................................... 77
IM View Port ........................................................................................ 77
Operating Instruction Label ................................................................. 78
Operating the IM .................................................................................. 78
Live-Line Indicators (LLI) and Capacitive Dividers .................................... 83
Live-Line Indicators ............................................................................. 83
Replace LLIs ....................................................................................... 83
Capacitive Divider ............................................................................... 84
Load Discharge Assembly ........................................................................ 84
Interlock Shuttle ................................................................................... 86
LDA Interlock System Operation................................................... 86
Charging and Latching the LDA Back to the Ungrounded Position 86
Low Voltage Compartment Features ........................................................ 87
Accessing the LV Compartment .......................................................... 87
Test Power Plug .................................................................................. 87
Current Transformer (CT) Shorting ..................................................... 88
Padlock Features ...................................................................................... 89
Number of Possible Padlocks ............................................................. 89
Padlocking the Isolation Means ........................................................... 89
Padlocking the Load Discharge Assembly (Optional) ......................... 89
Padlocking the Incoming Cable Section Doors ................................... 90
Voltage Transformer (VT) Section ............................................................ 90
Cold Sequence VT .............................................................................. 90
Hot Sequence VT ................................................................................ 90
SECTION 8: ENERGIZING THE CONTROLLER ................................................................................................................... 91
Preliminary Operating Check .................................................................... 91
RVSS Standalone Section .................................................................. 91
Starting the Controller ............................................................................... 92
Stopping the Controller ............................................................................. 93
SECTION 9: MAINTENANCE .................................................................................................................... 94
Preventive Maintenance ........................................................................... 94
Recommended Inspection Guidelines ................................................. 94
Environmental Conditions ................................................................... 94
Ideal Conditions............................................................................. 94
Standard Conditions...................................................................... 95
Aggressive Conditions................................................................... 95
Inspecting the Equipment .................................................................... 95
Corrective Maintenance .......................................................................... 106
Medium Voltage Fuses ...................................................................... 106
Removing Fuses.......................................................................... 107
Installing Fuses ................................................................................. 108
Optional Fuse Tool ............................................................................ 109
Installing Rear and Middle Fuses ................................................ 110
Installing Front Fuses .................................................................. 114
Removing Fuses.......................................................................... 116
Removing and Installing Voltage Transformer (VT) Primary and
Current Power Transformer (CPT) Fuses ......................................... 117
To Disassemble Fuse Tube......................................................... 117
To Assemble Fuse Tube ............................................................. 117
SECTION 10: TROUBLESHOOTING .................................................................................................................. 118
SECTION 11: REPLACEMENT PARTS .................................................................................................................. 119
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Table of Contents 07/2009
20032009 Schneider Electric All Rights Reserved 6
SECTION 12: TYPE 3R NON-WALK-IN SWITCHGEAR ........................................................................................................120
Introduction ............................................................................................. 120
Safety Precautions .................................................................................. 121
Receiving, Handling, and Storage ........................................................... 122
Receiving ........................................................................................... 122
Identification ...................................................................................... 122
Handling ............................................................................................ 122
Lifting Provisions.......................................................................... 122
Using a Forklift............................................................................. 123
Storage .............................................................................................. 124
Installation ............................................................................................... 124
Preparing the Site .............................................................................. 124
Foundation Requirements............................................................ 124
Conduit Locations........................................................................ 124
Equipment Ground....................................................................... 124
J oining and Anchoring Shipping Sections ......................................... 127
Connecting a Transition Throat ......................................................... 130
Operation, Inspection, and Maintenance ................................................131
Operation ........................................................................................... 131
Inspection and Maintenance ..............................................................131
Outlines ................................................................................................... 132
SECTION 13: GLOSSARY .................................................................................................................. 133
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 List of Figures and Tables
20032009 Schneider Electric All Rights Reserved 7
E
N
G
L
I
S
H
List of Figures Figure 1: Full Voltage Non-Reversing Controller ................................ 11
Figure 2: Full Voltage Reversing Controller ........................................ 12
Figure 3: Dual Votage Transfer Starter .............................................. 13
Figure 4: 2-Speed, 1-Winding Controller ............................................ 14
Figure 5: 2-Speed, 2-Winding Controller ............................................ 15
Figure 6: Reduced Voltage Autotransformer ...................................... 16
Figure 7: Reduced Voltage Soft Start Enclosure ................................ 18
Figure 8: Motorpact Identification .................................................... 23
Figure 9: Lifting Provisions ................................................................. 24
Figure 10: Handling Using a Forklift ..................................................... 24
Figure 11: Typical 450 A FVNR Side, Front, and Plan Drawing
Indoor .................................................................................. 25
Figure 12: Typical 720 A FVNR Side, Front, and Plan Drawing
Indoor .................................................................................. 26
Figure 13: Side, Front, and Plan DrawingTypical 450 A FVR, FVS,
2S1W, and 2S2W Motor ControllersIndoor ..................... 27
Figure 14: Reduced Voltage Soft Start (RVSS) .................................... 28
Figure 15: Reduced Voltage Autotransformer (RVAT) ......................... 28
Figure 16: Incoming Sections ............................................................... 29
Figure 17: FVNR, FVR, FVS, 2S1W, 2S2W, or RVAT/RVSS
Controllers, 450 A ................................................................ 30
Figure 18: Full Voltage Non-Reversing Controller, 720 A (Top Exiting
Load Cables) ....................................................................... 31
Figure 19: Full Voltage Non-Reversing Controller, 720 A (Bottom
Exiting Load Cables) ........................................................... 31
Figure 20: RVAT Enclosure Dimensions .............................................. 32
Figure 21: RVSS Roof and Floor Plan Views ....................................... 33
Figure 22: Incoming Section 20.00 in. (508 mm) Roof and Floor Plan
Views ................................................................................... 34
Figure 23: Incoming Section 29.50 in. (749 mm) .................................. 34
Figure 24: Door Swing Allowances ....................................................... 35
Figure 25: Opening the Medium Voltage Door ..................................... 37
Figure 26: Typical Door Release .......................................................... 38
Figure 27: Bolt Hole Locations for Indoor Enclosures .......................... 39
Figure 28: J oining the Shipping Splits .................................................. 39
Figure 29: Anchoring Subsequent Shipping Sections .......................... 39
Figure 30: Removing the Latch Center Post, Gussets, and the Lower
Closing Channel .................................................................. 41
Figure 31: Anchoring the Autotransformer ........................................... 42
Figure 32: Accessing the Bus Compartment in Rear-Accessible
Enclosures ........................................................................... 45
Figure 33: Removing the Main Bus Access Panel in the Low Voltage
Compartment ....................................................................... 46
Figure 34: Pass Through Bus Access .................................................. 47
Figure 35: Bus Bar Connections ........................................................... 48
Figure 36: Ground Bus Splice .............................................................. 49
Figure 37: Cable Routing for a Single Section Controller
(Rear View)450 A or Below ............................................... 50
Figure 38: Typical 450 A Cable Connections ....................................... 51
Figure 39: Typical 720 A Cable Connections ....................................... 51
Figure 40: Loadbox Flexible Barrier ..................................................... 52
Figure 41: Autotransformer Cables ...................................................... 53
Figure 42: RVSS Standalone Section Cable Connections ................... 54
Figure 43: Accessing Cable Connections ............................................. 55
Figure 44: Securing MV Cables in RVSS Standalone Section ............. 55
Figure 45: LV Cable Routing and Connection ...................................... 56
Figure 46: Wire Routing ........................................................................ 57
Figure 47: Motorpact Motor Controller with Arc-Resistant Optional
Features .............................................................................. 61
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
List of Figures and Tables 07/2009
20032009 Schneider Electric All Rights Reserved 8
Figure 48: Back Light Assembly ........................................................... 63
Figure 49: Blown Fuse Indicator ........................................................... 64
Figure 50: Motorpact Contactors ....................................................... 65
Figure 51: Withdrawing the Contactor .................................................. 66
Figure 52: Removing the Contactors .................................................... 67
Figure 53: Unlocking/Locking RVAT and RVSS Doors ......................... 69
Figure 54: Key Interlocks ...................................................................... 69
Figure 55: Defeating Interlock Functions .............................................. 70
Figure 56: Wiring and Operation for MDT107 ....................................... 73
Figure 57: MDT107 Module Location .................................................... 74
Figure 58: MDT107 Sensors Location .................................................. 75
Figure 59: Selector Switches for Temperature Rise Threshold
(250 A contactor settings shown) ........................................ 75
Figure 60: Selector Switch for Ambient Temperature Correction ......... 76
Figure 61: Isolation Means .................................................................... 77
Figure 62: Viewing Port ......................................................................... 77
Figure 63: Operating Instructions on Escutcheon ................................. 78
Figure 64: Moving the Isolation Means to the Grounded Position ........ 79
Figure 65: Closing the Isolation Means ................................................. 80
Figure 66: Moving the LDA to the CLOSED/Grounded Position ........... 81
Figure 67: Moving the LDA to the Open Position and Closing the IM ... 82
Figure 68: Live Line Indicator Location (450 A and Below) Main
Controller ............................................................................. 83
Figure 69: LLI Tag (located on the wiring harness) .............................. 83
Figure 70: LLI Box ................................................................................. 84
Figure 71: LDA ...................................................................................... 85
Figure 72: Interlock Shuttle ................................................................... 86
Figure 73: Opening the Low Voltage Door and Accessing the Low
Voltage Panel ...................................................................... 87
Figure 74: Latch Locking Screw ............................................................ 87
Figure 75: Low Voltage Compartment Details ...................................... 88
Figure 76: Padlocking the Isolation Means ........................................... 89
Figure 77: Padlocking the Load Discharge Assembly .......................... 89
Figure 78: Padlocking the Incoming Cable Section Doors .................... 90
Figure 79: Typical Schematic for Full Voltage Non-Reversing
(FVNR) Controllers .............................................................. 97
Figure 80: Typical Schematic for Full Voltage Non-Reversing
(FVNR), Latched Controllers ............................................... 98
Figure 81: Typical Schematic for Full Voltage Reversing (FVR) Motor
Controllers ........................................................................... 99
Figure 82: Typical Schematic for 2-Speed, 1-Winding (2S1W)
Controller ........................................................................... 100
Figure 83: Typical Schematic for 2-Speed, 1-Winding (2S2W)
Controller ........................................................................... 101
Figure 84: Typical Schematic for Non-Reversing Reduced Voltage
Autotransformer Starter ..................................................... 102
Figure 85: Typical Schematic for Reduced Voltage Soft Start ............ 104
Figure 86: Striker Pin .......................................................................... 107
Figure 87: Removing Fuses ................................................................ 108
Figure 88: Fuse Characteristics and Striker Pin Directions ................ 109
Figure 89: Installing Fuses .................................................................. 109
Figure 90: Optional Fuse Tool ............................................................ 110
Figure 91: Aligning Fuse Tool ............................................................. 110
Figure 92: Inserting Fuse Tool ............................................................ 111
Figure 93: Bringing Fuse Into Enclosure ............................................. 111
Figure 94: Inserting Fuse Into Upper Clip ........................................... 112
Figure 95: Swinging Lower End of Fuse Into Place ............................ 112
Figure 96: Rotating Pusher ................................................................. 113
Figure 97: Pushing Fuse Into Lower Clip ............................................ 113
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 List of Figures and Tables
20032009 Schneider Electric All Rights Reserved 9
E
N
G
L
I
S
H
Figure 98: Inserting Fuse Tool ............................................................ 114
Figure 99: Bringing Fuse Into Enclosure ............................................ 114
Figure 100: Swinging Lower End of Fuse Into Place ............................ 115
Figure 101: Pushing Fuse Into Lower Clip ........................................... 115
Figure 102: Removing Fuses with the Fuse Tool ................................. 116
Figure 103: Replacing VT and CPT Fuses ........................................... 117
Figure 79: Type 3R Non-Walk-in Enclosure ....................................... 120
Figure 80: Lifting Provisions ............................................................... 123
Figure 81: Handling Using a Forklift ................................................... 123
Figure 82: 29.5-inch Floor PlanControllers ..................................... 125
Figure 83: 29.5-inch Floor PlanIncoming and Auxiliary .................. 125
Figure 84: 73.75-inch/88.5-inch Floor PlanRVSS/RVAT ................ 126
Figure 85: Conduit Plates Location .................................................... 127
Figure 86: Factory-Installed Gasket ................................................... 127
Figure 87: FVNR/FVR Cubicle Anchoring Dimensions ...................... 128
Figure 88: RVAT/RVSS Cubicle Anchoring Dimensions .................... 128
Figure 89: Lineup Alignment ............................................................... 129
Figure 90: Attaching Roof Caps ......................................................... 129
Figure 91: Transition Throat ............................................................... 130
Figure 92: 29.5-inch FVNR Sections .................................................. 132
Figure 93: 59-inch RVSS and RVAT; 73.75-inch and 88.5-inch
RVAT ................................................................................. 132
List of Tables Table 1: Medium Duty Cycle Motor Ratings (201 to 3000
Horsepower, Inclusive)........................................................ 17
Table 2: Enclosure and Bus Ratings................................................. 21
Table 3: Motorpact Vacuum Contactor Ratings............................. 21
Table 4: Motorpact (Latched Type Only) Vacuum Contactor
Ratings .................................................................................... 22
Table 5: Approximate Dimensions and Weights 450 A
2.47.2 kVIndoor ............................................................. 25
Table 6: Approximate Dimensions and Weights 720 A
2.47.2 kVIndoor ............................................................. 26
Table 7: Approximate Dimensions and Weights450 A FVR, FVS,
2S1W, and 2S2W Motor Controllers, 2.47.2 kVIndoor .. 27
Table 8: Autotransformer Approximate Weight................................. 42
Table 9: Torque Values..................................................................... 48
Table 10: Hi-pot Field Test Values...................................................... 58
Table 11: Mechanical Interlock Dependencies.................................... 67
Table 12: Optical Fiber Probes CFO733............................................. 73
Table 13: MDT107 module.................................................................. 73
Table 14: Factory Settings .................................................................. 75
Table 15: Recommended Inspection/Maintenance Guidelines........... 94
Table 15: General Troubleshooting................................................... 118
Table 16: Mechanism Troubleshooting............................................. 118
Table 17: Replacement Parts............................................................ 119
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 1Introduction 07/2009
20032009 Schneider Electric All Rights Reserved 10
Section 1Introduction
Square D

Motorpact medium voltage (MV) motor controllers feature a


one-high design, with drawout contactors and a completely isolated low
voltage (LV) control compartment. When combined with other electrical
distribution and control products from Schneider Electric, the Motorpact
motor controller provides a system-wide solution you can trust.
This instruction bulletin contains installation, operation, maintenance, and
troubleshooting procedures for Motorpact MV motor controllers. It also
contains ratings, a list of replacement parts, and information about optional
features.
Motorpact is the latest innovation in Square D MV motor control equipment.
The 450 A base unit is compact, measuring 14.75 in. (375 mm) wide and
37.25 in. (946 mm) deep. It is available only in a one-high design with a
drawout contactor. However, the drawout design features make it as reliable
as any other bolt-in contactor equipment. Its compact size allows two
one-high units to occupy the same or less floor space than typical two-high
equipment. The equipment is front and rear accessible.
Motorpact meets the following standards: UL 347, NEMA ICS 3, and
IEC 60470.
All Motorpact starters are available in either a lineup or stand-alone
configuration.
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 1Introduction
20032009 Schneider Electric All Rights Reserved 11
E
N
G
L
I
S
H
Application
Full Voltage Non-Reversing Controller The full voltage non-reversing (FVNR) controller provides full voltage to the
motor terminals during starting. Full voltage starting allows the motor to
generate the maximum starting torque available (up to 150%). FVNR
controllers are the most economical type for the control and protection of
medium voltage motors.
Figure 1: Full Voltage Non-Reversing Controller
A. Low voltage compartment and door
B. Operator panel
C. Medium voltage compartment door
D. Contactor
E. Rear access cover
F. Low voltage components and wiring
G. Main bus
H. Isolation means (IM)
I. Medium voltage fuses
J . Current transformers (CTs)/Low power
current transformer (LPCT)
K. Control power transformer (CPT)
L. Voltage transformer (VT)
M. CPT/VT fuse tray
A
B
C
D
E
F
G
H
I
J
K
L
M
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 1Introduction 07/2009
20032009 Schneider Electric All Rights Reserved 12
Full Voltage Reversing Controller The full voltage reversing (FVR) controller is a full voltage, bi-directional
motor starter with an operating range of 23007200 V. This product will
deliver the highest starting torque (about 150% of full load torque) to the
motor terminals in either direction (forward or reverse). This starter bases
interrupting ratings on fused applications.
Figure 2: Full Voltage Reversing Controller
A. Low voltage compartment and door
B. Low voltage components and wiring
C. Operator panel
D. Medium voltage compartment door
E. Forward contactor
F. Isolation means (IM)
G. Main bus
H. Medium voltage fuses
I. Load box
J . Reverse contactor
K. CPT/VT fuse tray
A
B
E
K
J
I
H
G
F
C
D
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 1Introduction
20032009 Schneider Electric All Rights Reserved 13
E
N
G
L
I
S
H
Dual Voltage Transfer Starter The dual voltage transfer starter (FVS) is designed to operate as part of a
smart sequence starter application or multiple motors soft starting application.
A smart sequence starter system starts multiple motors, one at a time, with a
predetermined minimum start time between each motor start.
The FVS is part of a lineup that also includes a full voltage non-reversing
starter (FVNR) and a soft start module (RVSS). One FVS is required
per motor.
Figure 3: Dual Votage Transfer Starter
A. Low voltage compartment and door
B. Low voltage components and wiring
C. Operator panel
D. Medium voltage compartment door
E. Main contactor
F. Isolation means (IM)
G. Main bus
H. Medium voltage fuses
I. Load box
J . Soft start contactor
K. CPT / VT fuse tray
A
B
E
K
J
I
H
G
F
C
D
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 1Introduction 07/2009
20032009 Schneider Electric All Rights Reserved 14
2-Speed, 1-Winding Controller The 2-speed, 1-winding controller (2S1W) is designed for the control of
2-speed AC motors with a single winding. Since the motor has a single
winding, the speed change is accomplished by reconfiguring the winding
outside of the motor using a third contactor.
The 2S1W starter has two sections. Only the second section is shown
below. The first section is a full voltage non-reversing starter (FVNR) that
has the load box for fast speed windings.
Figure 4: 2-Speed, 1-Winding Controller
A. Low voltage compartment and door
B. Low voltage components and wiring
C. Operator panel
D. Medium voltage compartment door
E. Slow-speed contactor
F. Isolation means (IM)
G. Main bus
H. Medium voltage fuses
I. Load box (cables for slow-speed windings)
J . Shorting contactor
K. CPT/VT fuse tray
A
B
E
K
J
I
H
G
F
C
D
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 1Introduction
20032009 Schneider Electric All Rights Reserved 15
E
N
G
L
I
S
H
2-Speed, 2-Winding Controller The 2-speed, 2-winding controller (2S2W) is designed for the control of AC
motors with separate windings for high- and low-speed operation. Two
interlocked contactors are used with overload protection. The contactors are
included for each motor winding.
Figure 5: 2-Speed, 2-Winding Controller
A. Low voltage compartment and door
B. Low voltage components and wiring
C. Operator panel
D. Medium voltage compartment door
E. Slow-speed contactor
F. Isolation means (IM)
G. Main bus
H. Load box (cables for slow-speed winding)
I. Medium voltage fuses
J . Load box (cables for fast-speed winding)
K. Fast-speed contactor
L. CPT/VT fuse tray
A
B
C
D
E
F
G
I
H
K
L
J
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 1Introduction 07/2009
20032009 Schneider Electric All Rights Reserved 16
Reduced Voltage Autotransformer The reduced voltage autotransformer (RVAT) controller provides reduced
voltage to the motor terminals during starting through the use of a tapped,
three-winding, three-phase, autotransformer. The standard taps on the
autotransformer provide selection of 50%, 65%, or 80% line voltage applied
to the motor during starting. However, because of the transformer action,
the line current during starting will be less than the motor current, being
25%, 42%, or 64% of full voltage values. Starting torque will be 25%, 42%,
or 64%, respectively, of full voltage values. Therefore current at motor
terminals will be 50%, 65%, or 80% of full voltage starting current. Reduced
voltage autotransformer starting allows maximum starting torque with
minimum line current. In contrast, reduced voltage reactor starting draws
twice as much line current for the same amount of motor torque.
Square D

reduced voltage controllers utilize autotransformers that are


NEMA/EEMAC medium duty rated.
The RVAT starter includes the following components:
A main controller, which includes the starter isolation means, main power
fuses, main contactor, and an optional load discharge assembly (LDA)
switch. The main controller is located to the left of the RVAT enclosure.
A separate RVAT enclosure, which includes a medium-voltage
autotransformer with multiple voltage taps.
Start and run contactors (see Figure 6). The two contactors are
mechanically interlocked so that only one can be closed at a time.
Figure 6: Reduced Voltage Autotransformer
A. Internal arc vent cover (optional)
B. Low voltage (LV) control cable entry plate
C. Contactor door
D. Run contactor
E. Start contactor
F. LV door
G. Autotransformer door
H. Surge arresters
I. Main bus bar access cover
J . Door interlock
K. Main bus bar compartment
L. Ground bus bar
M. Autotransformer
A B
C
D
E
F
G
J
I
K
L
M
H
NOTE: The main controller is not shown.
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 1Introduction
20032009 Schneider Electric All Rights Reserved 17
E
N
G
L
I
S
H
Application Notes
1. Standard autotransformers are medium duty as defined by NEMA
ICS 9-1993. Medium duty autotransformers are designed to perform the
duty cycle per Table 1. These ratings must not be exceeded.
2. The transition from reduced voltage to full voltage is based upon current
and not time. A current transition relay (CTR) governs the current level at
which transfer is allowed. Configure the CTR so as not to allow current
transitions above 120% motor full load current (FLA). This current
transition level is the maximum transition level and must not be exceeded.
The current transition relay settings are based on percentage of CT
secondary current. To convert the percentage of FLA to a relay setting,
perform the following calculation:
CTR setting percentage =CT pri./CTsec. x FLA x multiplier
The multiplier is based on the desired % of FLA for transition. Normally,
115% of FLA is the desired transition current level, which means the
multiplier would be 1.15.
3. An incomplete sequence relay (ISR) monitors the time needed to
transfer from reduced voltage to full voltage. The ISR should be set to
acceleration time (per motor manufacturers data curves) plus two
seconds. If the transfer is not performed within the allotted time, the ISR
will stop the motor acceleration by opening the main contactor. Do not
exceed a 30 second ISR setting for medium duty autotransformers.
Reduced Voltage Soft Start Controllers Motorpact Reduced Voltage Soft Start (RVSS) Motor Control units
provide a pre-engineered, integrated motor control package for reduced
voltage starting and soft stopping of three-phase medium voltage induction
(squirrel cage) motors. The Motorpact RVSS is a NEMA class E-2,
three-phase, microprocessor-based, digitally controlled reduced voltage soft
starter for medium voltage AC motor applications. The unit controls the
motor start-up by delivering an adjustable amount of initial voltage and
current to the motor, then slowly increases the voltage and current to 100
percent. The Motorpact RVSS has a linear voltage versus time ramp, unless
setup for current limit or ramp configuration. This adjustable acceleration
ramp allows a smooth transition from the point where the motor shaft begins
to turn, to full motor speed, regardless of the type of load. The Motorpact
RVSS also features a selectable dual adjustment mode that can be
programmed for a second load type. The Motorpact RVSS is offered in
voltages from 2.3 kV to 7.2 kV, and current ratings from 100 A to 400 A.
The RVSS starter includes a main controller that has the starter isolation
means, main power fuses, main contactor, and an optional LDA switch. The
main controller is located to the left of the RVSS enclosure.
CAUTION
HAZARD OF EQUIPMENT DAMAGE
The duty cycle ratings shown in Table 1 must not be exceeded.
The current at time of transition must not exceed 120% motor full
load current.
Failure to follow these instructions can result in equipment damage.
Table 1: Medium Duty Cycle Motor
Ratings (201 to 3000
Horsepower, Inclusive)
On 30 seconds
Off 30 seconds
Repeat 2 times (for a total of 3 cycles)
Rest 1 hour
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 1Introduction 07/2009
20032009 Schneider Electric All Rights Reserved 18
In addition to a main controller, the following is included in a separate 29.5
in. (750 mm) wide RVSS enclosure:
Silicon controlled rectifier (SCR) stack assemblies
By-pass contactor
Microprocessor-based protection and control system
Digital display
The acceleration ramp time for a typical start-up is thirty (30) seconds or
less, and is adjustable (0-120 s) to allow the motor to smoothly accelerate
the load. The current limit is adjustable from 100% to 600% of programmed
motor full load amperage (FLA). This adjustment is separate from the
acceleration time, to allow greater control of peak power usage. At the end
of the start cycle, the unit will switch in a bypass contactor, placing the unit
across the line with overload protection still present.
For details on RVSS ratings, start-up procedures, programming
information, troubleshooting procedures, and additional wiring
diagrams, see Schneider Electric bulletin no. 46032-700-04.
Figure 7: Reduced Voltage Soft Start Enclosure
A. Internal arc vent cover (optional)
B. Low voltage (LV) control cable entry plate
C. Contactor door
D. LV door
E. Human machine interface (HMI) soft start
control interface module
F. Soft Start power compartment door
G. Heater (optional)
H. LV control cable entry plate
I. Customer conduit wireway
J . Bypass contactor
K. Ground fault board (optional)
L. Terminal control board
M. Main bus bar compartment
N. Ground bus bar
O. Control power, CPU boards, RTD board
(optional)
P. Main bus bar access cover
Q. LV compartment
R. Door interlock
S. Ring transformers
T. Silicon control rectifier stacks
U. Line and load connections - RVSS
Standalone section only (rear access required
for standalone configuration)
A
B
C
D
E
F
G
I
J
K
L
M
N
O
P
Q
R
S
T
S
H
U
NOTE: The main controller is not shown.
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 1Introduction
20032009 Schneider Electric All Rights Reserved 19
E
N
G
L
I
S
H
Incoming Section Sections are available to bring in line connections via cable or bus duct.
When required, an incoming cable auxiliary section is provided for up to
3000 A. Units are offered for installation at the ends of a lineup with bottom
entry measuring 20.00 in. (508 mm). Should installation at the middle of a
lineup or top entry be required, the unit width will be 29.50 in. (750 mm).
Sections are also available for utility metering transformers.
Mechanically Latched Controllers Mechanically latched controllers can be used in place of load interrupter
switches or metal-clad circuit breakers in applications where the load
remains connected to the power source, even during severe undervoltage
or power loss conditions, or for long periods of time. The controller uses a
mechanical latching mechanism that holds the contactor closed. Therefore,
the load remains connected unless the release is activated either electrically
or manually.
Voltage Transformer An auxiliary section is provided to house voltage transformers (VTs) larger
than those available in the controller compartment or special metering
devices that are required. Sections are available to mount voltage
transformers with primary fuses and an IM.
Two types of units are available:
Cold sequence (with a IM ahead of the transformers). The VT unit is
offered in a 20.00-in. wide unit.
Hot sequence (transformers connected directly to the main bus). These
units are always 20.00 in. (508 mm) wide.
The cold sequence units use the Motorpact IM to disconnect the power
circuit from these transformers. The units also include the Motorpact
instrument compartment as standard.
The hot sequence units allow the transformers to be connected directly to
the main bus. Key interlocking should be coordinated with the factory to
ensure proper operation of these units.
Transformer Disconnects Transformer disconnects provide a means to control and protect
transformers. Mechanically latched controllers are typically used for this
purpose and are supplied with E-rated fuses. Additional protection is
available using voltage, current, or multi-function protective relays.
Feeder Disconnects Feeder disconnects usually involve mechanically latched controllers to switch
power in a medium voltage circuit. E-rated fuses are used to provide
overcurrent protection for the conductors and connected load. Additional
protection is available using voltage, current, or multi-function
protective relays.
Capacitor Bank Disconnects Motorpact controllers may be used for capacitor bank switching
applications. Mechanically latched controllers are typically used for this
purpose and are supplied with E-rated fuses, which are sized for the kVA
rating and system voltage. Additional protection is available using voltage,
current, or multi-function protective relays.
Prepared Spaces Prepared spaces are available for blank compartments to allow future
installation of a complete full voltage non-reversing controller. Both
mechanical and electrical packages are available.
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 2Safety Precautions 07/2009
20032009 Schneider Electric All Rights Reserved 20
Section 2Safety Precautions
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Only qualified personnel familiar with medium voltage equipment are to
perform work described in this set of instructions. Workers must
understand the hazards involved in working with or near medium
voltage circuits.
Perform such work only after reading and understanding all of the
instructions contained in this bulletin.
Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See NFPA 70E.
Turn off all power before working on or inside equipment.
Use a properly rated voltage sensing device to confirm that the power
is off.
Before performing visual inspections, tests, or maintenance on the
equipment, disconnect all sources of electric power. Assume that all
circuits are live until they have been completely de-energized, tested,
grounded, and tagged. Pay particular attention to the design of the
power system. Consider all sources of power, including the possibility
of backfeeding.
Handle this equipment carefully and install, operate, and maintain it
correctly in order for it to function properly. Neglecting fundamental
installation and maintenance requirements may lead to personal injury,
as well as damage to electrical equipment or other property.
Do not make any modifications to the equipment or operate the system
with the interlocks removed. Contact your local field sales
representative for additional instruction if the equipment does not
function as described in this manual.
Carefully inspect your work area and remove any tools and objects left
inside the equipment.
Replace all devices, doors, and covers before turning on power to
this equipment.
All instructions in this manual are written with the assumption that the
customer has taken these measures before performing maintenance
or testing.
Failure to follow these instructions will result in death or serious injury.
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 3Ratings
20032009 Schneider Electric All Rights Reserved 21
E
N
G
L
I
S
H
Section 3Ratings
Enclosure and Bus

Contactor
Table 2: Enclosure and Bus Ratings
450 A Max. Controller 720 A Max. Controller
Minimum line-to-line voltage (kV) 1.0 1.0
Maximum line-to-line voltage (kV) 7.2 7.2
BIL (kV) up to 3300 ft. (1000 m) 60 60
Frequency (Hz) 50/60 50/60
Main bus continuous amps 600/1200/2000/3000 600/1200/2000/3000
Short circuit withstand at rated voltage(kA peak) main
bus to fuse line-side terminal
130 130
Short time rating (kA) symmetrical:
Main bus (2 seconds) 50 50
(0.25 second through IM to main power fuse) 50 50
Controller (from load) (1 second) 6.75 10.8
Controller (from load) (30 seconds) 2.7 4.3
Dielectric withstand (kV) (1 minute) 20 20
Standard maximum altitude rating 1000 m (3300 ft.) 1000 m (3300 ft.)
The mechanical life of the isolation means is 5000 operations.
Table 3: Motorpact Vacuum Contactor Ratings
450 A Max. Contactor 720 A Max. Contactor
Rated voltage 7200 V 7200 V
Rated operational current 200/400/450 A 720 A
Class E1 kA 5.0 7.2
Class E2 kA 50 50
Overcurrent strength (peak value) 85 kA 85 kA
Interrupting capacity 5000 A 7200 A
Permissible switching frequency 1200/hour 600/hour
Mechanical life 2,500,000 operations 1,000,000 operations
Electrical life 250,000 operations 200,000 operations
Impulse withstand 60 kV 60 kV
Dielectric strength 22 kV1 minute 22 kV1 minute
Closing time 80 ms or less 80100 ms
Opening time 25 ms or less 4060 ms
Opening time (delayed) Approximately 300 ms
1
To be field configured in protective relay.
Arcing time 10 ms or less 10 ms or less
Pick-up voltage AC or DC 85% rated (hot)70% rated (cold) 85% rated (hot)70% rated (cold)
Drop-out voltage AC or DC 50% rated (hot)40% rated (cold) 50% rated (hot)40% rated (cold)
Rated control voltage AC 115/120 or 230/240 V 115/120 or 230/240 V
Rated control voltage DC 120/125 or 240/250 V 120/125 or 240/250 V
Coil circuit inrush 670 VA AC 840 VA AC
Coil circuit holding 85 VA AC 120 VA AC
Auxiliary contact arrangement 3 (N.O./N.C.) 3 (N.O./N.C.)
Auxiliary contact current 10 A continuous (NEMA Class A600) 10 A continuous (NEMA Class A600)
1
Terminals 3 and 4 jumpered.
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 3Ratings 07/2009
20032009 Schneider Electric All Rights Reserved 22
Latched Contactor Ratings for the latched vacuum contactor are the same as in Table 3,
except as listed in the table below.
Load Discharge Assembly The LDA is a spring operated quick making device, capable of making 5kA
symmetrical current with 14kA peaks at 7.2kV up to 5 times. It has no
interrupting capability. It has been designed to require several complete
rotations of the handle to allow time for the system to dissipate the energy in
the cables, motor, or transformer before it will close. Grounding is
accomplished by a single ground bar located behind the face of the load
box. This bar is forced by springs to simultaneously engage all three phases
at the load terminal pad assembly. See Figure 71 on page 85. The device is
designed for 1000 no-load operations.
Incoming Section Incoming cable sections are rated up to 3000 A. The 3000 A units require a
10.00 in. high plenum on top of all compartments for cooling.
Voltage Transformer Section The size and rating of voltage transformers are specified by the customer.
Please refer to the customer order drawing package for more information.
Auxiliary contact voltage 48 V (min.)600 V (max.) 48 V (min.)600 V (max.)
Auxiliary contact AC 720 VA (P.F.0.35) 720 VA (P.F.0.35)
Auxiliary contact DC 60 W (L/R 150 ms) 60 W (L/R 150 ms)
Table 3: Motorpact Vacuum Contactor Ratings
1
Terminals 3 and 4 jumpered.
Table 4: Motorpact (Latched Type Only) Vacuum Contactor
Ratings
450 A Max. Contactor 720 A Max. Contactor
Permissible switching
frequency
300/hour 300/hour
Mechanical life 250,000 operations 200,000 operations
Minimum tripping voltage 4060% of coil rating DC (cold) 4060% of coil rating DC (cold)
Tripping current 4.8 DC max. 4.8 DC max.
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 4Receiving, Handling, and Storage
20032009 Schneider Electric All Rights Reserved 23
E
N
G
L
I
S
H
Section 4Receiving, Handling, and Storage
Receiving Check the packing list against the equipment received to ensure the order
and shipments are complete. Make claims for shortages or other errors in
writing within 30 days after receipt of shipment. Failure to do so constitutes
unqualified acceptance and a waiver of all such claims to the purchaser.
Inspect the equipment for damage. If you find or suspect damage,
immediately file a claim with the carrier and notify Schneider Electric.
Identification
Handling Equipment is normally shipped in an upright position on a pallet and
wrapped in plastic.
Figure 8: Motorpact Identification
Controller nameplate
factory order number
manufacture date
ratings
CAUTION
HAZARD OF PERSONAL INJURY OR EQUIPMENT DAMAGE
Do not remove the skids until the shipping sections are at the final
location.
Always use the skids to move shipping sections to prevent equipment
distortion.
Failure to follow these instructions can result in injury or equipment
damage.
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 4Receiving, Handling, and Storage 07/2009
20032009 Schneider Electric All Rights Reserved 24
Lifting Provisions
Using a Forklift Review the shipping documentation to verify the actual weight of the
Motorpact medium voltage motor controller to ensure that the lifting
equipment is sufficient. When an overhead crane is not available, rollers,
pipes, or a forklift may be used.
This equipment is shipped up to a maximum of five vertical sections73.75
in. (1875 mm) wide, with the exception of the RVAT controller combination,
which is 88.00 in. (2235 mm) wide.
Storage Keep this equipment in a clean, dry place that is free from corrosive
elements and mechanical abuse. Energize the heaters inside the controller,
or add heat from a separate source, such as a light bulb or blower. Use a
minimum of 125 watts of heat per vertical section to keep the equipment dry
during storage.
Figure 9: Lifting Provisions
Indoor lifting provisions
WARNING
UNSTABLE LOAD
If lifting the motor controller by forklift, stabilize the shipping section with a
safety strap to reduce the possibility of tipping.
Failure to follow this instruction can result in death or serious injury.
Figure 10: Handling Using a Forklift
Safety strap
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 4Receiving, Handling, and Storage
20032009 Schneider Electric All Rights Reserved 25
E
N
G
L
I
S
H
Cover the equipment with a tarpaulin when necessary to protect it from
contaminants and moisture. Do not store indoor units outdoors.
Monitor the equipment closely in areas with high humidity. If necessary, use
additional heat to keep the equipment dry. Contact the factory if the internal
heaters do not adequately prevent condensation for your location or
environmental condition.
Typical Dimensions and Weights Below are examples of typical motor controllers. Refer to the customer
drawings for actual weights, dimensions, and conduit entry locations. The
weights given below are approximate.
Indoor (NEMA 1 Construction)
Figure 11: Typical 450 A FVNR Side, Front, and Plan DrawingIndoor
90.60 (2300)
39.30 (998,2)
37.30 (947,4)
6.50 (165)
76.50 (1943)
59.00 (1498,6)
51.80 (1314,5)
39.80 (1011)
37.40 (948,8)
34.00 (863,6)
11.70 (298)
14.75 (375)
NOTE: All dimensions are in inches (millimeters).
Table 5: Approximate Dimensions and Weights 450 A
2.47.2 kVIndoor
Frame Width (X)
14.75 in. (375 mm) 20.00 in. (508 mm) 29.50 in. (750 mm)
Base unit weight
1
1
Includes: isolation means, fuse, contactor, bus, and enclosure.
1090 lb (494.4 kg) 1210 lb (548.8 kg) 1440 lb (653.2 kg)
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 4Receiving, Handling, and Storage 07/2009
20032009 Schneider Electric All Rights Reserved 26
Figure 12: Typical 720 A FVNR Side, Front, and Plan DrawingIndoor

90.60 (2300)
39.30 (998,2)
37.30 (947,4)
6.50 (165)
76.50 (1943)
59.00 (1498,6)
51.80 (1314,5)
39.80 (1011)
34.00 [863,6]
29.50 (749)
29.00 (737)
9.60 (243,5)
NOTE: All dimensions are in inches (millimeters).
Table 6: Approximate Dimensions and Weights 720 A
2.47.2 kVIndoor
29.50 in. (750 mm) Frame Width
Base unit weight
1
1
Includes: isolation means, fuse, contactor, bus, and enclosure.
1440 lb (653.2 kg)
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 4Receiving, Handling, and Storage
20032009 Schneider Electric All Rights Reserved 27
E
N
G
L
I
S
H
Figure 13: Side, Front, and Plan DrawingTypical 450 A FVR, FVS, 2S1W, and 2S2W Motor ControllersIndoor
76.50 (1943)
6.50 (165) 37.30 (947)
90.60 (2300)
39.30 (998)
39.80 (1011)
11.70 (298)
37.40 (950)
34.00 (864)
59.00 (1499)
51.80 (1316)
29.50 (749)
NOTE: All dimensions are in inches (millimeters).
Table 7: Approximate Dimensions and Weights450 A FVR, FVS,
2S1W, and 2S2W Motor Controllers, 2.47.2 kVIndoor
29.50 in. (750 mm) Frame Width
Base unit weight 1480 lb (673.2 kg)
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 4Receiving, Handling, and Storage 07/2009
20032009 Schneider Electric All Rights Reserved 28
Figure 14: Reduced Voltage Soft Start (RVSS)
Figure 15: Reduced Voltage Autotransformer (RVAT)
(946) (750)
3.11 (79)
90.6 (2300)
29.5 37.24
(1125)
(1500)
(946) (79)
(2300)
90.6
37.24 3.11
(946) (79)
2300
(90.6)
37.24 3.11
44.25
59.00
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 4Receiving, Handling, and Storage
20032009 Schneider Electric All Rights Reserved 29
E
N
G
L
I
S
H
Approximate Weights
Figure 16: Incoming Sections
(946)
3.11 (79)
(2300)
(508)
20 37.24
90.60
(946)
90.6 (2300)
16.37 (416)
(749)
(554)
37.24
21.81
3.11 (79)
29.5
Enclosure Type
Enclosure Width
in (mm)
Approximate Weight
lb (kg)
RVSS 29.5 (750) 622 (1370)
RVAT*
44.25 (1125) 728 (1605)
59.00 (1500) 885 (1950)
Incoming section
20.00 (500) 350 (770)
29.5 (750) 900 (1985)
*Autotransformer weight to be added
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 5Top and Floor Plan Drawings 07/2009
20032009 Schneider Electric All Rights Reserved 30
Section 5Top and Floor Plan Drawings
FVNR, FVR, FVS, 2S1W, 2S2W, RVAT/RVSS Controllers or RVSS Standalone Section (29.50 in.)
Figure 17: FVNR, FVR, FVS, 2S1W, 2S2W, or RVAT/RVSS Controllers, 450 A
Medium voltage
cable conduit area
when both outgoing
and incoming
20.00 in. (508 mm) and
29.50 in. (749 mm)
width only
2.56
(65)
1.34
(34)
2.00
(51)
2.00
(51)
1.38
(35)
1.00
(25)
39.28
(998)
8.00
(203)
6.38
(162)
A
Door edge
(front)
6.00
(152)
33.00
(838)
3.56
(90)
6.00
(152)
37.37
(949)
2.00
(51)
7.00
(178)
11.37
(289)
.75
(19)
C
B
3.75
(95)
3.63
(92)
Customer control conduit area
Customer control
conduit area
Medium voltage
cable conduit area
(4) .56 (14)
Floor Plan Roof Plan
F
1.38
(35)
2.38
(60)
D
E
Medium voltage
cable conduit area
(2) 0.87 (22 mm) x 1.42 (36 mm)
OUT IN
G
1.38
(35)
A
Cabinet Width
In. (mm)
B
IEC
In. (mm)
C
NEMA
In. (mm)
D
In. (mm)
E
In. (mm)
F
In. (mm)
G
In. (mm)
14.75/375 7.25/184 7.50/191 12.00/305 10.00/254
20.00/500 12.50/318 12.75/324 17.25/438 15.25/387 17.25/438 1.25/32
29.50/749
1
1
RVSS standalone section only available in 29.50 inch width
22.00/559 22.25/565 26.75/679 24.75/629 26.75/679 2.75/70
NOTE: All dimensions are
given in inches (millimeters).
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 5Top and Floor Plan Drawings
20032009 Schneider Electric All Rights Reserved 31
E
N
G
L
I
S
H
Figure 18: Full Voltage Non-Reversing Controller, 720 A (Top Exiting Load Cables)
2.56
(65)
1.34
(34)
2.00
(51)
2.00
(51)
1.38
(35)
1.00
(25)
39.28
(998)
8.00
(203)
6.38
(162)
Door edge
(front)
6.00
(152)
33.00
(838)
3.56
(90)
37.37
(949)
2.00
(51)
7.00
(178)
11.37
(289)
.75
(19)
3.75
(95)
3.63
(92)
Customer control conduit area
Customer control
conduit area
Medium voltage
cable conduit area
Floor Plan Roof Plan
2.38
(60)
(2) 0.87 (22 mm) x 1.42 (36 mm)
1.38
(35)
29.50 (749)
22.25
(565)
22.00
(559)
12.00
(305) (4) .56 (14)
NOTE: All dimensions are given
in inches (millimeters).
Figure 19: Full Voltage Non-Reversing Controller, 720 A (Bottom Exiting Load Cables)
2.56
(65)
1.34
(34)
2.00
(51)
2.00
(51)
1.38
(35)
1.00
(25)
39.28
(998)
8.00
(203)
6.38
(162)
29.50 (749)
Door edge
(front)
6.00
(152)
33.00
(838)
3.56
(90)
6.00
(152)
37.37
(949)
2.00
(51)
7.00
(178)
11.37
(289)
.75
(19)
22.25
(565)
22.00
(559)
3.75
(95)
3.63
(92)
Customer control conduit area
Customer control
conduit area
Medium voltage
cable conduit area
Floor Plan Roof Plan
2.38
(60)
12.00
(305)
Medium voltage cable conduit area
(2) 0.87 (22 mm) x 1.42 (36 mm)
4.20
(107)
12.00
(304.8)
1.38
(35)
(4) .56 (14)
NOTE: All dimensions are given
in inches (millimeters).
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 5Top and Floor Plan Drawings 07/2009
20032009 Schneider Electric All Rights Reserved 32
RVAT
Figure 20: RVAT Enclosure Dimensions
C

(6
Roof Plan Floor Plan
39.28
(998)
Door edge
(front)
A
8.00
(203)
2.00
(51)
6.38
(162)
2.00
(51)
Customer
control
conduit
area
3.56
(90)
37.37
(949)
33.00
(838)
3.63
(92)
3.75
(95)
.56
(14)
2.38
0)
G
1.00
(25)
TYP 0.51 (13) X .79 (20)
(4) .75 / (19) Autotransfomer
mounting locations use 1/2-13 (M12)
bolts and washers
0.866 (22) X 1.42 (36)

E F
B
D
2.56
(65)

7.71
(196)
NOTES: The main controller is not
shown. All dimensions are given in
inches (millimeters).
Cabinet WidthsInches (mm)
A B C D E F G
29.50 (750) 22.25 (565) 24.75 (629) 22.00 (559) 10.21 (259) 13.00 (330) 27.50 (698)
44.25 (1125) 37.00 (940) 39.50 (1003) 36.75 (933) 12.08 (307) 21.00 (533) 22.00 (559)
59.00 (1500) 51.75 (1315) 54.25 (1378) 51.50 (1308) 18.96 (481) 21.00 (533) 22.00 (559)
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 5Top and Floor Plan Drawings
20032009 Schneider Electric All Rights Reserved 33
E
N
G
L
I
S
H
RVSS
Figure 21: RVSS Roof and Floor Plan Views
Floor Plan View Roof Plan View
0.866 (22 mm) x 1.42 (36 mm)
RECT. (2 PLCS)
Customer Control
Conduit Area
Customer Control
Conduit Area
7
.
0
0

(
1
7
7
,
8
)
4
.
3
8

(
1
1
1
)
2.00 (50,8)
.75 (19)
3.75 (95,2)
3.63 (92)
22.00 (558,8)
22.25 (565,2)
3
3
.
0
0

(
8
3
8
,
2
)
2
.
5
6

(
6
5
)
3
.
5
6

(
9
0
,
4
)

24.75 (628,7) 2.38 (60,3)
.56 (14,3) 4x
29.50 (749,3)
8.00 (203,2) 2.00 (50,8)
2
.
0
0

(
5
0
,
8
)
6
.
3
8

(
1
6
2
)
2
.
1
3

(
5
4
)
3
7
.
3
0

(
9
4
7
,
4
)


3
9
.
2
8

(
9
9
8
)
NOTES: The main controller is not shown. All
dimensions are given in inches (millimeters).
Front
For RVSS standalone section, refer to Figure 17 for 29.50 inch wide section.
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 5Top and Floor Plan Drawings 07/2009
20032009 Schneider Electric All Rights Reserved 34
Incoming Section
Figure 22: Incoming Section 20.00 in. (508 mm) Roof and Floor Plan Views
Roof Plan View Floor Plan View
2x 22x36 mm
Rect
Customer
Control
Conduit
Area
7.38 (187,3)
2.00 (50,8)
7
.
0
0

(
1
7
7
,
8
)

26.00 (660,4)
4.37 (111)
.56 (14,3) 4x
3.63 (92)
3.75 (95,3)
12.75 (324)
39.28 (998)
6.38 (162)
2.00 (50,8)
15.25 (387,4)
3.88 (98,4) 11.00 (279,4)
2.38 (60,3)
37.30 (947,4)
Medium
Voltage
Cable
Conduit
Area
20.00 (508)
8.00 (203,2)
33.00 (838,2)
(NEMA)
2
.
5
6

(
6
5
)
3
.
5
6

(
9
0
.
4
)
.75 (19)
Customer Control Conduit Area
2.00 (50,8)
NOTE: All dimensions are given in inches (millimeters).
Front
Figure 23: Incoming Section 29.50 in. (749 mm)
Roof Plan View Floor Plan View
Customer Control
Conduit Area
0.87 (22 mm) x 36 (20 mm)
RECT. (2 PLCS.)
5.00 (127)
14.00 (355,6)
24.00 (609,6) 2.74 (69,6)
8.00
(203,2)
2
.
0
0

(
5
0
,
8
)
6.38 (162)
2.00 (50,8)
29.50 (749,3)
4.38 (111)
.75 (19)
3.63 (92)
3
.
5
6

(
9
0
,
4
)
22.25 (565,2)
3.75 (95,3)
2
.
5
6

(
6
5
)
7.37
(187,2)
2
6
.
0
0

(
6
6
0
,
4
) 2.00 (50,8)
7.00 (177,8)
.56 (14,3) 4x
3
3
.
0
0

(
8
3
8
,
2
)
3
7
.
3
0

(
9
4
7
,
4
)
39.28 (998)
2.38 (60,3) 24.75 (628,7)
9.70 (246,4) 11.00 (279,4)
Customer
Control
Conduit
Area
Medium Voltage
Cable Conduit Area
Medium Voltage
Cable Conduit Area
NOTE: All dimensions are given in inches (millimeters).
Front
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 6Installation
20032009 Schneider Electric All Rights Reserved 35
E
N
G
L
I
S
H
Section 6Installation
Preparing the Site Compare the site plans and specifications with the motor controller
drawings to be sure there are no discrepancies. Check the site to verify that
the equipment will fit properly.
Ensure that the floor is level within 1/16 inch per foot (2 mm per 305 mm), or
a maximum of 1/4 inch (6 mm) within the area of the controller lineup. If the
floor is not within the tolerances, use shims or other means to ensure
equipment is installed on level.
Unless otherwise specified, the equipment is front accessible for
non-seismic hazard designated locations.
Allow working space clearance per National Electrical Code (NEC) Article
110.34, Work Space and Guarding. Minimum clearances must meet all
local and national requirements. Door swing allowances are shown in
Figure 24.
Check customer drawings to see if front-only accessibility and shielded
cable are required. The cables may need to be prepared before the
equipment is placed in position.
Provide area ventilation, heating, and air conditioning to maintain the
ambient temperature around the equipment between 0 C (32 F) and
40 C (104 F).
Adequate lighting and convenience outlets should be available near the
equipment. Route sewer, water, and steam lines away from the equipment.
Provide floor drains to prevent water buildup.
Seismic hazard for site specific locations as defined by the current
edition of the International Building Code or NFPA 5000 or relevant
local building code or consulting engineer of record.
Figure 24: Door Swing Allowances
20.00 (508)
18.20 (462,7)
29.50 (749,3)
27.70 (703,7)
14.75 (374,7)
13.00 (329,8)
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 6Installation 07/2009
20032009 Schneider Electric All Rights Reserved 36
Seismic Certification of Motorpact
Medium Voltage (MV) Motor Controllers
Motorpact MV motor controllers that are seismically certified have been
qualified for the sitespecific seismic requirements of the listed model
building codes and/or standards. Optional construction features may be
required, depending on the location of the installation and the particular
code and/or standard of interest. Seismic certificates of compliance and
equipment labels are provided with all seismicallycertified equipment. To
maintain the validity of this certification, the installation instructions provided
in this bulletin must be followed.
Responsibility for Mitigation of Seismic Damage For the purposes of the model building codes, Motorpact MV motor
controllers are considered nonstructural building components. Equipment
capacity was determined from tri-axial seismic shake table test results as
defined in the International Code Counsel Evaluation Service (ICC ES)
Acceptance Criteria for Seismic Qualification Testing of Nonstructural
Components (AC156). Unless otherwise indicated, an equipment
importance factor of 1.5 (IP =1.5) was used, indicating that equipment
functionality was verified before and after shaker table seismic simulation
testing. This importance factor is indicative of critical facilities where
maximizing the probability of post event functionality is a priority. AC156 is
published by the ICC ES and has been recognized by the Building Seismic
Safety Council (BSSC) as an appropriate methodology in the 2003 National
Earthquake Hazard Reduction Program (NEHRP) Commentary (FEMA 450
Part 2). The National Institute of Building Sciences established the BSSC in
1979 to develop and promote regulatory provisions for earthquake risk
mitigation at the national level.
Incoming and outgoing cable and conduit must also be considered as
related but independent systems. They must be designed and restrained to
withstand the forces generated by the seismic event without increasing the
load transferred to the equipment. For applications where seismic hazard
exists, bottom entry and/or exit of cable and conduit is preferred. If the
spectral acceleration value (Ss as defined by the International Building Code
or NFPA 5000) is in excess of 2.67g (such as the New Madrid seismic
area), then the equipment must also be braced at the top using a lateral
restraint system. A lateral restraint system is required in situations where
horizontal motion at the top of the equipment is not desirable (such as
applications where top entry and/or exit of conduit are used). This system
must be capable of transferring the loads created to the load-bearing path of
the building structural system.
Maintaining Seismic Certification Schneider Electrics seismic qualification of nonstructural components is
just one link in the chain of responsibility required to maximize the
probability that the equipment will be intact and functional after a seismic
event. During a seismic event, the equipment must be able to transfer the
loads that are created through the mounting pad and anchorage to the
loadbearing path of the building structural system.
The structural civil engineer or design engineer of record is responsible for
detailing the equipment connection and anchorage requirements (including
the lateral restraint system, if appropriate) for the given installation. The
installer and manufacturers of the anchorage and lateral restraint system
are responsible for assuring that the mounting requirements are met.
Schneider Electric is not responsible for the specification and performance
of these systems.
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 6Installation
20032009 Schneider Electric All Rights Reserved 37
E
N
G
L
I
S
H
Field Installation After properly preparing the site, field assemble the shipping splits.
Field assembly includes:
Accessing the Medium Voltage Compartments (Prior to Installation) on
page 37
Anchoring Equipment on page 38
Accessing the Bus Compartment on page 44
Through Bus Splice Connections on page 47
Ground Bus Splice Connections on page 49
Cable Terminations on page 49
Control Wiring Terminations and Routing on page 56
Accessing the Medium Voltage
Compartments (Prior to Installation)
The isolation means (IM) is shipped in the grounded position. If the
controller doors are locked, refer to Figure 61 on page 77 and Figure 67 on
page 82.
Opening FVNR/Controller MV Door
Opening RVAT or RVSS MV Door Follow the steps below to access the contactor and autotransformer in the
RVAT and RVSS enclosures.
1. Turn and remove the key from the key interlock on the operator panel
(located on the controller to the left of the RVAT or RVSS enclosure).
2. Open the middle door(s) on the RVAT or RVSS enclosure.
Figure 25: Opening the Medium Voltage Door
1
2 3 Step
Step Step
Door Closed
Rotate Handle 90
Handle
Rotated
Door
Open
It is important that the RVSS standalone section interlock key
be coordinated with the main controller key interlock (key
removable when disconnector is open). This guarantees that
the RVSS standalone section MV doors cannot be opened
unless the disconnected in the main controller is open. If the
main controller is a Square D

brand controller, then a key


locking scheme should be ordered so the RVSS standalone
section interlock uses the main controller key. If the main
controller is not a Square D controller, it is highly
recommended that the RVSS key be permanently attached
(welded or solid riveted) to the main controller key.
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 6Installation 07/2009
20032009 Schneider Electric All Rights Reserved 38
3. Insert and turn the interlock key to release door-latching mechanism.
4. Insert the operating handle as shown in Figure 26 page 38. Rotate
counterclockwise to release the doors.
Anchoring Equipment
Anchoring and J oining the Shipping Splits Follow the steps below and instructions in Figures 27, 28, and 29 for
anchoring units.
1. Review the assembly drawings to ensure that the equipment shipping
splits will be assembled in the correct order.
2. Locate and anchor the first shipping split.
For seismic hazard designated locations, each section must be
anchored per details supplied by engineer of record to the loadbearing
path of the building structural system. Use 1/2-in. or 12-mm grade 5 or
higher bolts and hardened flat and lock washers.
For non-seismic hazard locations, 3/8-in. or 10-mm grade 5 bolts are
permissible. For either application, torque bolts to the value specified by
the anchor manufacturer.
Figure 26: Typical Door Release


Door latch keylock
Operating handle
CAUTION
HAZARD OF EQUIPMENT DAMAGE
Install the shipping split bus connectors only
after the shipping sections are securely
anchored in place.
Failure to follow this instruction can result
in equipment damage.
If the equipment will connect to an existing lineup, mount the
connecting section or shipping split first.
Be sure to mount all shipping splits on the same plane and
level them to verify that they are properly connected.
For 14.75-in. (375 mm) units that do not have rear access,
anchor to the front bolt holes only (non-seismic hazard
locations).
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 6Installation
20032009 Schneider Electric All Rights Reserved 39
E
N
G
L
I
S
H
3. Pull the control wire and make cable connections as required before
joining the next shipping split.
4. Locate the next shipping split according to the assembly drawing.
5. Level the shipping split and join it to the previously installed shipping
split. Use factory supplied M10 (10 mm) Grade 8.8 hardware to join
shipping splits. See Figure 28. Torque to 20 lb-ft (27.1 Nm).
6. Anchor the shipping split per instructions in step 2.
7. Repeat steps 4 through 6 for each additional shipping split.
Figure 27: Bolt Hole Locations for Indoor Enclosures
Depth
Holes for customer-supplied hardware
A (Width) B C
14.75 (375) 7.50 (191) 10.00 (254)
20.00 (508) 12.75 (324) 15.25 (387)
29.50 (749) 22.25 (565) 24.75 (629)
44.25 (1125) 37.00 (940) 39.50 (1003)
59.00 (1500) 51.75 (1314) 54.25 (1378)
Dimensions given in inches (millimeters).
F
r
o
n
t
3.56 (90) 33 (838)
B
A C
3.75 (95)
2.38
(60)
Lifting eyes must be removed between shipping splits prior to
final placement.
Figure 28: Joining the Shipping Splits
11 screw locations
Figure 29: Anchoring Subsequent Shipping Sections
Section
1
Section
2
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 6Installation 07/2009
20032009 Schneider Electric All Rights Reserved 40
Anchoring the Autotransformer Installing 29.5 Inch (750 mm) Autotransformer Enclosures
Follow the steps below to install 29.50 in. (750 mm) wide autotransformer
enclosures. Autotransformers in 29.50 in. wide enclosures are mounted and
shipped in the enclosure.
1. Locate and level the RVAT enclosure.
For seismic hazard designated locations, each section must be
anchored per details supplied by engineer of record to the loadbearing
path of the building structural system. Use 1/2-in. or 12mm grade 5 or
higher bolts and hardened flat and lock washers.
For non-seismic hazard locations, 3/8-in. or 10mm grade 5 bolts are
permissible. For either application, torque bolts to the value specified by
the anchor manufacturer.
For bolt hole locations, see Figure 27 on page 39.
2. Secure the autotransformer using four 3/8 in. bolts (Grade 5) with
expansion anchors.
Installing Autotransformers in 44.25 Inch (1125 mm) and 59 Inch
(1500 mm) Wide Enclosures
An autotransformer that requires installation in a 44.25 in. (1125 mm) or
59.00 in. (1500 mm) wide enclosure will be crated and shipped separately
from the lineup. The contractor is responsible for installing the
autotransformer using the following procedure.
Follow the steps below to install the RVAT enclosure.
1. Place the enclosure in its final position.
2. Gain access to the lower compartment using the procedure described in
Opening RVAT or RVSS MV Door on page 37.
3. Anchor the rear of the enclosure with 1/2-in. or 12mm grade 5 or higher
bolts and hardened flat and lock washers.
For non-seismic hazard locations, 3/8-in. or 10mm grade 5 bolts are
permissible. For either application, torque bolts to the value specified by
the anchor manufacturer.
For bolt hole locations, see Figure 27 on page 39.
NOTE: Wait before installing the front anchors.
Because of limited access, the four holes that are required to
anchor the autotransformer must be drilled prior to setting the
enclosure. Installation of the expansion anchors may also be
required before the enclosure is set. The customer is responsible
for providing the necessary hardware to secure both the
autotransformer and the enclosure.
WARNING
HAZARD OF PERSONAL INJURY OR EQUIPMENT DAMAGE
The 44.25 in. (1125 mm) or 59.00 in. (1500 mm) sections are not
designed to be moved with autotransformer installed. Do not install
autotransformer before enclosure is placed in its final position.
Autotransformers are top heavy; exercise caution when moving them.
Failure to follow these instructions can result in personal injury or
equipment damage.
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 6Installation
20032009 Schneider Electric All Rights Reserved 41
E
N
G
L
I
S
H
4. Remove and retain the door latch center-post by removing the four
upper screws and two lower screws as indicated in Figure 30.
5. Remove and retain the lower gussets and lower closing channel as
indicated in Figure 30. This will provide adequate clearance for installing
the autotransformer.
6. Uncrate the autotransformer and inspect it prior to installation. Next,
locate and install the casters in accordance with Schneider Electric
bulletin no. 46035-799-01.
Figure 30: Removing the Latch Center Post, Gussets, and the Lower Closing Channel




Door latch
center-post
Top of post
Lower latch
Remove two screws
Remove two screws
Bottom of post
Lower closing
channel
Door latch
center-
post
Remove two screws
Remove screw
Remove screw
Remove screw
Lower closing channel
Gussets
Gussets
Door latch
center-post
The casters may not be necessary if they are not beneficial to
the installation of the autotransformer.
CAUTION
HAZARD OF EQUIPMENT DAMAGE
Autotransformer should be handled with care. Do not apply force to
autotransformer insulation.
Failure to follow this instruction can result in equipment damage.
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 6Installation 07/2009
20032009 Schneider Electric All Rights Reserved 42
7. Roll the autotransformer into the enclosure or use a forklift (or other
similar means). Align the mounting holes in the autotransformer base
over the four holes in the floor pan. Autotransformer taps should face the
front of the enclosure.
8. Secure the autotransformer to concrete using 1/2 in. bolts (Grade 5) with
tapered washers, hardened flat washers, and expansion anchors (not
furnished). For applications with seismic ratings, casters must
be removed.
Table 8: Autotransformer Approximate Weight
Horsepower
Approximate Wt.
(kg/lbs.)
Horsepower
Approximate Wt.
(kg/lbs.)
300 386/850 1250 816/1800
400 408/900 1500 862/1900
450 431/950 1700 885/1950
500 454/1000 1750 907/2000
550 499/1100 2000 952/2100
600 544/1200 2250 998/2200
650 590/1300 2500 1020/2250
700 635/1400 2700 1043/2300
800 680/1500 3000 1066/2350
900 726/1600 3100 1088/2400
1000 771/1700 3500 1134/2500
Figure 31: Anchoring the Autotransformer
Anchor autotransformer,
4 places
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 6Installation
20032009 Schneider Electric All Rights Reserved 43
E
N
G
L
I
S
H
9. Reinstall the door latch center-post, gussets, and lower closing channel
using the hardware removed in steps 4 and 5. Next, validate that the
lower door interlocks are operating properly. To do this, follow steps
below (and see Figure 26 on page 38):
a. Close both the upper doors and tighten the thumb screw to prevent
them from reopening. Next, close the two lower doors.
b. Push the door release button, located next to the handle insert.
c. Rotate the handle clockwise.
If the lower interlocks are reinstalled correctly, the lower doors should be
locked closed. If the lower doors are not locked, check to see if all the
hardware has been reinstalled.
10. Install the two front anchoring bolts for the RVAT enclosure.
WARNING
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
To maintain electrical clearances, make sure autotransformer is properly
aligned over mounting holes provided in floor pan. A minimum clearance of
3.5 in. (89 mm) is required from the autotransformer to any grounded sheet
metal.
Failure to follow this instruction can result in death, serious injury,
or equipment damage.
WARNING
PROPER DOOR AND INTERLOCK OPERATION
Failure to reinstall the door latch center-post and lower closing channel
will render the RVAT door interlocks inoperative.
Failure to follow this instruction can result in death, serious injury,
or equipment damage.
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 6Installation 07/2009
20032009 Schneider Electric All Rights Reserved 44
Accessing the Bus Compartment
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Only qualified personnel familiar with medium voltage equipment are to
perform work described in this set of instructions. Workers must
understand the hazards involved in working with or near medium
voltage circuits.
Perform such work only after reading and understanding all of the
instructions contained in this bulletin.
Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See NFPA 70E.
Turn off all power supplying this equipment before working on or inside
equipment.
Use a properly rated voltage sensing device to confirm that the power is off.
Before performing visual inspections, tests, or maintenance on the
equipment, disconnect all sources of electric power. Assume that all
circuits are live until they have been completely de-energized, tested,
grounded, and tagged. Pay particular attention to the design of the
power system. Consider all sources of power, including the possibility of
backfeeding.
Handle this equipment carefully and install, operate, and maintain it
correctly in order for it to function properly. Neglecting fundamental
installation and maintenance requirements may lead to personal injury,
as well as damage to electrical equipment or other property.
Do not make any modifications to the equipment or operate the system
with the interlocks removed. Contact your local field sales
representative for additional instruction if the equipment does not
function as described in this manual.
Carefully inspect your work area and remove any tools and objects left
inside the equipment.
Replace all devices, doors, and covers before turning on power to
this equipment.
All instructions in this manual are written with the assumption that the
customer has taken these measures before performing maintenance or
testing.
Failure to follow these instructions will result in death or serious injury.
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 6Installation
20032009 Schneider Electric All Rights Reserved 45
E
N
G
L
I
S
H
FVNR/FVR/Controller Section
To access the bus compartment in rear-accessible enclosures, remove the
rear barrier (see Figure 32, step 1). To access the bus compartment in
front-accessible enclosures, you must first open the low voltage
compartment (see Figure 33, step 1 on page 46). Then, remove the access
panel (see Figure 33, step 2 on page 46).
CAUTION
HAZARD OF EQUIPMENT DAMAGE
Avoid disconnecting any wire connections before
removing the bus compartment access panel.
Failure to follow this instruction can result in
equipment damage.
If a component is mounted to the bus compartment access panel,
remove and restrain the component before removing the access
panel. If wires are removed, refer to factory order drawings for
reconnection.
Figure 32: Accessing the Bus Compartment in Rear-Accessible
Enclosures
Step 1
Step 2 Step 3
Remove outer panel
by removing bolts
Remove inner panels
by removing bolts
Bus compartment
accessed
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 6Installation 07/2009
20032009 Schneider Electric All Rights Reserved 46
* Access panel may not be removable on some models.
RVAT/RVSS Enclosure Pass through bus bars joining each section of a lineup may be installed in
the RVAT or RVSS enclosure. Access to the bus bars can be made through
bolt-on panels located behind the middle door.
Figure 33: Removing the Main Bus Access Panel in the Low Voltage Compartment
Step Step
Access panel*
1 2
Access panel
removed
Component Mounted
Component Not Mounted
Step 1
Step 2
Arc terminator
junction box
Access panel*
Arc terminator
junction box
removed from
access panel
Access panel*
Access panel
removed
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 6Installation
20032009 Schneider Electric All Rights Reserved 47
E
N
G
L
I
S
H
Through Bus Splice Connections
Connecting the Through Bus Bars 1. Make sure the isolation means is in the closed position. See Figure 62
on page 77.
2. Make sure the bus bar connector contact surfaces are clean. When
necessary, clean the bus bars with a mild cleaning agent such as
denatured alcohol, or a suitable cleaning solution, and a soft cloth. Be
careful not to remove the bus bars plating during cleaning.
3. Connect the bus bar connectors one phase at a time. Attach, but do not
tighten, the bus hardware.The bus hardware is provided and can be
found in the carton packing. The hardware inserts in the isolation means
and all main bus hardware are M10 (10 mm).
4. After bus bars are in place and properly aligned, tighten the bolt using a
torque wrench. See Table 9 on page 48 for torque values. If optional
insulated boots are provided, install them at this time.
Figure 34: Pass Through Bus Access
Access panels
removed
Pass through bus bars
Access panel
removed
RVAT Enclosure RVSS Enclosure
WARNING
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
The disconnector must be in the CLOSED position when the busbar
hardware is torqued.
Failure to follow this instruction can result in death or serious injury.
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 6Installation 07/2009
20032009 Schneider Electric All Rights Reserved 48
Figure 35: Bus Bar Connections
6.50
(165)
(a)
(b)
C
B
A A
B
C
15.46
(393)
6.50 (165)
4.78 (122)



Enclosure a b
375 14.75 (375) 10.20 (259)
500 20.00 (508) 15.45 (392)
750 29.75 (749) 24.95 (634)
Dimensions given in inches (millimeters).
Transition
bus bar
Left Hand Transition
Top View
Right Hand Transition
Top View
1.00 (25.4) typ.
Transition bus bar
.375 x 3 Copper bar typ.
3000 A
Existing main bus bar C,
B
D
C, D
A
2000 A
1200 A
600 A
C B A
Screw C
3000 A: M10 x 100
2000 A: M10 x 80
1200 A: M10 x 60
600 A: M10 x 40

Passthrough Connection Splice Connection
A. Splice main bus bar; length
depends on section width
B. Bus bar shim
C. M10 screws; length depends on
bus bar quantity. See table.
D. Conical washer
Rear View
Front
Table 9: Torque Values
Bolt Size (mm)
Sheet Metal Joints
(Grade 8.8 Steel Bolts)
Electrical Connections
(Grade 8.8 Steel Bolts)
2.5 1.5 lb-ft (2 Nm) 2.2 lb-ft (3 Nm)
3 2.6 lb-ft (3.5 Nm) 3.7 lb-ft (5 Nm)
5 4.4 lb-ft (6 Nm) 6.6 lb-ft (9 Nm)
6 7.4 lb-ft (10 Nm) 10.3 lb-ft (14 Nm)
8 14.7 lb-ft (20 Nm) 22.1 lb-ft (30 Nm)
10 22.1 lb-ft (30 Nm) 36.9 lb-ft (50 Nm)
12 36.9 lb-ft (50 Nm) 51.6 lb-ft (70 Nm)
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 6Installation
20032009 Schneider Electric All Rights Reserved 49
E
N
G
L
I
S
H
Ground Bus Splice Connections To connect the ground bus at each shipping split, remove and retain the
existing hardware. Position the unit and then reinstall and tighten the
hardware per Table 9 on page 48.
Cable Terminations Before making cable connections, check to see if special site preparation
requirements are needed. Determine the phase identity of each cable. Viewing
the controller from the front, standard bus sequence is normally phased ABC
front to rear, left to right, or top to bottom, unless labeled otherwise.
Shielded Cable Install the appropriate stress cone in accordance with the stress cone
manufacturers instructions. Space is provided for prefabricated stress cones
only; Schneider Electric does not supply stress cones. Because of some
limited space applications, Schneider Electric recommends Quick Term II
stress cones by 3M.
For all Motorpact controllers using shielded cable, with or without stress
cones, the cable is limited to 1-500 MCM or 2-250 MCM for 450 A and
1-1000 MCM or 2-750 MCM for 720 A for both top and bottom entry.
Follow the lug manufacturers instructions to attach the cable lug on the cable.
Figure 36: Ground Bus Splice
Connect
ground bus
splice to the
next enclosure
RVSS Standalone Section


Ground bar
Incoming Section
Ground bar
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 6Installation 07/2009
20032009 Schneider Electric All Rights Reserved 50
Cable Installation Avoid sharp turns, corners, and edges that could damage or weaken the
cable insulation. Follow the cable manufacturers instructions to determine
the minimum bending radius of cables.
Maximum length of unsupported cable is 18.00 in. (457 mm) for
line side cable, and 42.00 in. (1100 mm) for load side cable.
WARNING
HAZARD OF ELECTRICAL SHOCK OR BURN
Make sure the insulated cable does not contact any grounded metal
parts or other phases.
If insulating boots are supplied for cable connections, install them prior
to energizing equipment.
Failure to follow these instructions can result in death or serious injury.
Figure 37: Cable Routing for a Single Section Controller
(Rear View)450 A or Below
Bottom Cable Routing
Top Cable Routing
Line cable
Load
cable
Line cable
Load
cable
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 6Installation
20032009 Schneider Electric All Rights Reserved 51
E
N
G
L
I
S
H
Figure 38: Typical 450 A Cable Connections
Figure 39: Typical 720 A Cable Connections
Line Connections Load Connections
Factory supplied
insulating boots required
at cable connection.
Line Connections Load Connections
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 6Installation 07/2009
20032009 Schneider Electric All Rights Reserved 52
Loadbox Barrier The load-side connections are protected by a flexible barrier as shown in
Figure 40. To attach the cable, the upper and lower barriers must be folded
out and the middle barrier must be removed.
To attach the cable,
1. remove fuses to provide working access,
2. remove the middle barrier,
3. fold back the upper and lower barriers,
4. attach the cable,
5. replace the upper and lower barriers,
6. replace the middle barrier, and
7. replace the fuses.
NOTE: All barriers must be reattached prior to operation.
RVAT Cable Connections (44.25 and 59.00
Sections)
1. Once the autotransformer is secured, connect the nine power cables to
it using the supplied 10 mm hardware. See Figure 41 on page 53.
2. Connect the three smaller surge arrester cables provided to the 0% taps
on the autotransformer. If the optional power factor correction capacitors
are included, connect these three wires to the 100% taps. Torque the
hardware to 36.9 lb-ft (50 Nm).
CAUTION
MINIMAL ELECTRICAL CLEARANCES IN
THIS AREA
Remove the barrier to install cables.
Replace the barrier before energizing
equipment.
Failure to follow these instructions can
result in equipment damage.
Figure 40: Loadbox Flexible Barrier
?
? ?
Loadbox flexible
barrier (removable)
Loadbox flexible barrier
(non-removable)
NOTE: The load-
side connections
shown are for
450 A and below.
The cables have been labeled for easy identification. Be sure
to remove the tags before energizing.
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 6Installation
20032009 Schneider Electric All Rights Reserved 53
E
N
G
L
I
S
H
RVSS Cable Connections Customer power cable connections are not required within the RVSS
enclosure. All power cable connections have been made at the factory
between the RVSS enclosure and adjacent main controller. Customer
power cable connections should be made at the load box in the controller.
WARNING
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Remove the tags from the power cables and surge arrester cables before
energizing equipment.
Failure to follow this instruction can result in death, serious injury,
or equipment damage.
Figure 41: Autotransformer Cables
Additional cabling notes: The line side connections (100%
taps) feeding the autotransformer originate from the load side
of the main contactor in the controller. The load side cables
originating from the 80/65/50% taps are routed back to the
main controller and terminate at the load box on the left side.
Customer connections are made inside the controller at the
load box.
C-phase 100% Cable
C-phase load connection shown at
80% tap (Select 50%, 65%, or 80%
depending upon customer
requirements).
C-phase Zero Tap Cable
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 6Installation 07/2009
20032009 Schneider Electric All Rights Reserved 54
RVSS Standalone Section Cable Connections
Figure 42: RVSS Standalone Section Cable Connections
Top entry Bottom entry
Line Load
Line
Load
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 6Installation
20032009 Schneider Electric All Rights Reserved 55
E
N
G
L
I
S
H
To attach the cable:
1. Remove the tie channel cover (10 screws).
2. Remove the upper and lower rear covers (4 screws). Use caution as
covers are heavy.
3. Remove the cable connection insulating barrier (14 nylon screws).
4. Attach the load (motor) cables to the connectors labeled load. Attach
the cables from the main starter contactor load side to the connectors
labeled line. Attach the cables per the cable manufacturers instruction.
Conical washers placed on external sides of the connectors and lugs
ensure better distribution of stress regarding bolts tightened to
recommended torques. Tightening torque: 36.9 lb-ft (50 Nm)
(10 mm bolt).
5. It is important to mount the cables vertically straight and not at an angle.
It is also important to make sure the bolts are inserted correctly so they
do not contact the insulating barrier.
6. Secure cables to cable support bar with cable ties or through plastic
clamps on cable support bracket (unit specific).
7. Replace the insulating barrier. Tighten plastic screws and nuts. Secure
nut to screw using Loctite 425 or equivalent adhesive.
8. Replace the upper and lower rear covers. Tightening torque: 22.1 lb-ft
(29.93 Nm).
9. Replace the tie channel cover. Tightening torque: 22.1 lb-ft (29.93 Nm).
10. If applicable, remove old caulk from tie channel cover and apply new
caulk to seal tie channel cover.
Figure 43: Accessing Cable Connections
Cable
connection
insulation
barrier
CAUTION
MINIMAL ELECTRICAL CLEARANCES IN
THIS AREA
Remove the barrier to install cables.
Replace the barrier before energizing
equipment.
Do NOT replace plastic hardware with metal
hardware.
Failure to follow these instructions can
result in equipment damage.
Figure 44: Securing MV Cables in RVSS
Standalone Section
MV cable secured to cable support bar
with cable ties
MV cable secured to cable support
bracket with plastic clamps
All barriers must be reattached prior to operation.
Upper MV cover
Tie Channel
cover
Lower MV cover
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 6Installation 07/2009
20032009 Schneider Electric All Rights Reserved 56
Control Wiring Terminations and Routing
FVNR/FVR/Controller Section LV Wiring 1. If necessary, plug the inter-shipping split control wiring back together.
2. Make all outgoing control connections according to the wiring diagrams.
After the wiring is complete, carefully check all connections to verify that
they are secure and in their proper location.
Figure 45: LV Cable Routing and Connection









Remove the roofing sheet on each section
(4 screws).
Place the strand and the feed wires. Route
the wiring section by section, by passing wires
through the cutout in cable troughs.
Carry out connections to the terminal
blocks.
Reassemble the roofing sheets (4 screws
per sheet). Torque 7.4 lb-ft (10 Nm).
Remove the cable lead-through sheet
located on the roofs of the sections
(2 screws), as well as the roofing sheets
(4 screws).
Cut the cable lead-through sheets
according to the wires to be installed.
Install the glands on these sheets and pass
the wires through.
Customer connection
Replace the sheet (2 screws).
Connect the wires to the terminal blocks and
replace the roofing sheet (4 screws). Torque
7.4 lb-ft (10 Nm).
Incoming Cables at the End of the Section
Incoming Cables through the Top,
Section by Section
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 6Installation
20032009 Schneider Electric All Rights Reserved 57
E
N
G
L
I
S
H
RVSS Section LV Wiring For bottom incoming control wiring a conduit has been provided for wire
routing to top located connections. See Figure 7 on page 18. In addition to
the bottom located conduit entry, a customer wireway extends across the
top front portion of the enclosure. Refer to Schneider Electric bulletin no.
46032-700-04 for wiring diagrams.
Hi-pot (Dielectric) Testing
Perform a hi-pot (dielectric) test to measure insulation integrity. See
Table 10 for hi-pot test values.
Take the following minimum actions to help promote the safety of personnel
and equipment:
Restrict entry into the area to prevent any unauthorized personnel from
approaching the gear during testing.
Notify all persons that the test is going to be conducted.
Follow all local lockout and tag-out procedures.
Remove all fuseslow voltage and medium voltage.
Disconnect surge arresters, surge capacitors, and power factor
correction capacitors (if supplied).
NOTE: Do not use the load discharge assembly (LDA), if supplied, to
discharge capacitors.
Figure 46: Wire Routing
Wire Entering from Bottom
Remove the operator
panel (4 screws)
Remove the floor trough
covers and floor plate
Customer wiring location
Route customer wiring from bottom entry through low
voltage compartment.
Remove 4 screws to
access wireway
Route wires through
wireway
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Only qualified electrical personnel should perform this testing.
During testing, maintain a minimum clearance of 6 feet (1829 mm) from
the equipment.
Failure to follow these instructions will result in death or serious
injury.
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 6Installation 07/2009
20032009 Schneider Electric All Rights Reserved 58
Disconnect or ground capacitive dividers, if supplied.
Unground the LDA, if supplied. For operation procedures, see Section
7Features and Operation, Load Discharge Assembly on page 84.
All ground connections must be properly made and tightened according
to Table 9 on page 48. Refer to Ground Bus Splice Connections
beginning on page 49 and Figure 36 on page 49.
Do not use unfiltered, half-wave rectified dc hi-pot test units. Use of such
devices greatly increases the chance of x-ray generation.
Phase-to-Phase Hi-pot Testing Follow these steps to perform a phase-to-phase hi-pot test:
1. Perform a phase-to-phase hi-pot test on the main bus.
a. Gradually increase the voltage to the levels shown in Table 10.
b. Verify that the equipment sustains the specified voltage without
flashover for one minute.
2. Turn off the test equipment. Discharge to ground the phase bus before
removing the test cables.
WARNING
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
If load is a capacitor bank, wait 5 minutes before servicing equipment.
Capacitors should have an internal resistor to dissipate voltage to 50 V
maximum after 5 minutes.
Failure to follow this instruction can result in death or serious injury.
Table 10: Hi-pot Field Test Values
Equipment Maximum
Rating (kV)
Field Test Values
AC (kV) DC (kV)
2.4 5.5 7.9
3.3 7.1 10.1
4.16 8.5 12.1
4.8 9.6 13.6
5 10.0 14.1
5.5 10.8 15.3
6 11.6 16.4
6.6 12.7 17.9
6.9 13.2 18.7
WARNING
HAZARD OF ELECTRIC SHOCK
After completing hi-pot testing, temporarily ground the bus bars to remove
any residual charges.
Failure to follow this instruction can result in injury.
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 6Installation
20032009 Schneider Electric All Rights Reserved 59
E
N
G
L
I
S
H
Phase-to-Ground Hi-pot Testing Follow these steps to perform a phase-to-ground hi-pot test:
1. Perform a phase-to-ground hi-pot test on the main bus.
a. Gradually increase the voltage to the levels shown in Table 10 on
page 58.
b. Verify that the equipment sustains the specified voltage without
flashover for one minute.
2. Turn off the test equipment. Discharge to ground the phase bus before
removing the test cables.
If the test is unsuccessful, inspect the insulators for leakage paths. If
necessary, clean the surface of the insulator(s) with denatured alcohol and
re-test. If problems persist, DO NOT ENERGIZE THE EQUIPMENT.
Contact your local field sales office or your distributor.
If the equipment has been stored for several months or has been exposed to
high humidity during the storage time period, PERFORM A HI-POT TEST.
First energize the heater circuits for a minimum of 24 hours. See Table 10 on
page 58 for test values and additional information. Follow other equipment
testing procedures as required by customer in-house standards.
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 6Installation 07/2009
20032009 Schneider Electric All Rights Reserved 60
Performing a Final Inspection
After installing the equipment and making all interconnections, follow the
steps below to test the equipment and perform a final inspection before
placing it in service.
1. Verify that a hi-pot test has been performed.
2. Check all control wiring with the wiring diagrams. Verify that all
connections are properly made and tightened, all fuses are installed,
current transformer circuits are complete, all fault detection devices
have been properly connected and set, and that loose connections are
tightened to the proper tightening torque (see Table 9 on page 48).
3. Verify that all protective relays have been configured with proper
settings per the outcome of the customers coordination study. The
contactor opening time must be coordinated with the supplied power
fuse's time-current characteristics. Power fuses must interrupt currents
which exceed contactor ratings. For contactor ratings, which include
interrupting capability and opening times, refer to Schneider Electric
bulletin no. 46032-700-02, Motorpact 200/400/450 A Vacuum
Contactors or bulletin no. 46032-700-03, Motorpact 720 A Vacuum
Contactors. In some cases, a contactor opening time delay will have to
be configured in the protective relay.
4. Ensure that all transition, control, and timing relays are configured per
customer requirements and these settings do not exceed the restrictions
identified in Application Notes on page 17.
5. Verify that all insulating surfaces, including the primary support
insulators and isolation barriers, are clean and dry.
6. Verify that all fuses are installed and orientated properly and do not
exceed the nameplate rating for their sections (see Table 10 on
page 58).
7. Before energizing any source of electric power, make a final check of the
equipment. Inspect every compartment for loose parts, tools, litter, and
miscellaneous construction items.
8. Review key interlock schemes carefully (if used). Insert only the proper
keys in the locks. Remove all extra keys and store them where only
authorized personnel can access them.
9. Verify that all barriers, covers, and doors are secured.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
ALWAYS assume that all circuits are live until they have been
completely de-energized, tested, grounded, and tagged.
Follow all lock-out/tag-out procedures. If disconnect switches cannot be
opened, disconnect the line leads.
Failure to follow these instructions will result in death or serious
injury.
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 7Features and Operation
20032009 Schneider Electric All Rights Reserved 61
E
N
G
L
I
S
H
Section 7Features and Operation
In This Section Arc Resistant Features on page 61
Back Light Assembly on page 62
Blown Fuse Indicator on page 63
Contactors on page 64
Door and Mechanical Interlock Features on page 67
MDT107 Thermal Diagnostic System on page 70
Isolation Means (IM) on page 77
Live-Line Indicators (LLI) and Capacitive Dividers on page 83
Load Discharge Assembly on page 84
Low Voltage Compartment Features on page 87
Padlock Features on page 89
Voltage Transformer (VT) Section on page 90
Arc Resistant Features Motorpact motor controllers can be provided with an arc-resistant Type 2
rating up to 50 kA on all four sides, as an option. If desired, a plenum for
exhausting the arc products can also be supplied.
Exhaust vents and optional arc plenums are located at the top of each
compartment to help retain the structural integrity of the enclosure in the
event of an electrical fault.
Figure 47: Motorpact Motor Controller with Arc-Resistant Optional
Features
Plenum
Vented Optional Plenum
Vent flap
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 7Features and Operation 07/2009
20032009 Schneider Electric All Rights Reserved 62
Arc resistance includes the following features:
Gasketing throughout the enclosure: roof, rear panels, end sheets,
medium voltage door, and between frames in a line-up
Caulking of seams throughout the enclosure
End sheets of 11 GA sheet metal
Either flaps or an optional plenum
Additional interlocking of medium voltage door
Full side latching engagement for the medium voltage door
Clearances For arc-resistant equipment, the minimum ceiling height above the
enclosure is 79 in. (2 m). If this clearance is not available, the optional arc
plenums must be used so that fumes can be vented outside the building
housing the motor controllers.
When a plenum is not installed, the fume vent on the roof of the enclosure is
covered by a set of trap doors to keep out debris. These doors open
outward and must not be blocked or restricted in any way.
Back Light Assembly The optional back light illuminates the interior of the IM to clearly show the
position of the main contact blades. If the optional LDA is installed, its
position indicator is also illuminated. The back light pushbutton switch is
above the IM viewing window. See Figure 48 on page 63.
The expected life of the back light batteries is approximately four years.
Replace with two size AA alkaline batteries.
To replace the batteries, follow steps 15 below and see Figure 48 on
page 63.
1. De-energize the equipment.
2. Open both the LV and the MV doors.
3. Remove the plastic cover (escutcheon) by removing the four screws
using a 10 mm wrench. Pull cover straight out.
NOTE: The batteries are visible just inside the viewing window, up and
to the left.
4. Remove the batteries by pulling them straight down from their spring
clips.
5. When inserting batteries, the leftmost battery () end should be nearest
to the operator and the other battery is installed opposite in polarity.
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 7Features and Operation
20032009 Schneider Electric All Rights Reserved 63
E
N
G
L
I
S
H
Blown Fuse Indicator Motorpact motor controllers can be provided with a blown fuse indicator
assembly located on the line side of the MV power fuses. It operates a flag
that is visible through a window in the MV door. Should a blown fuse occur,
the power fuse striker pin will pop up and activate the assembly. When
activated, a flag is operated that is visible through the upper window of the
MV door.
In addition to visual indication, the blown fuse indicator has two Form C
contactsone drives a direct acting contactor trip and the second is
available for remote indication.
Figure 48: Back Light Assembly
Back light
pushbutton
To replace the back
light batteries, first
remove the
escutcheon
(4 screws).
Access batteries through
viewing window after the
escutcheon has been removed.
Front of
Equipment
Viewed from Top
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 7Features and Operation 07/2009
20032009 Schneider Electric All Rights Reserved 64
Contactors
Electrically Maintained Contactors The Motorpact contactor is a three-pole device rated 7.2 kV maximum,
60 kV BIL, with an interrupting rating of 7200 A symmetrical for 720 ampere
and 5000 A symmetrical for 450 ampere contactors. This basic contactor
contains three vacuum interrupters, a DC operating coil with a rectifier
circuit, and auxiliary contacts. The contactor is used as the main (42M)
contactor on full voltage non-reversing (FVNR) controllers.
Figure 49: Blown Fuse Indicator
Flag indicator
Blown fuse (red) Good fuse (white)
Flag indicator
Striker pin, top
of fuse
For more information on the latched contactor, see Schneider
Electric bulletin no. 46032-700-02, Motorpact 200/400/450A
Vacuum Contactors or bulletin no. 46032-700-03, Motorpact
720A Vacuum Contactors.
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 7Features and Operation
20032009 Schneider Electric All Rights Reserved 65
E
N
G
L
I
S
H
Latched Contactor Contactors are available with an optional mechanical latch. The
mechanically-latched contactor is used primarily for transformer feeder
circuits, transfer schemes, and applications where it is desirable for the
contactor to remain closed during a voltage dip or loss.
Latched contactors are closed electrically and are held closed mechanically.
They are opened by a separate electrical release coil. As a backup, there is
a mechanical release button marked RESET near the bottom of the MV
door. A mechanically latched contactor may only be installed in an
enclosure equipped with these release devices.
Inserting/Withdrawing Contactors
FVNR/FVR/Controller Contactors Follow steps 16 and refer to Figure 51 on page 66 to remove the contactor.
1. Review the safety precautions on page 20.
2. If the equipment has been energized, press the STOP/OFF or OPEN (if
latched) button located on the operator panel.
3. Move the isolation means to the OPEN/Grounded position. If an optional
LDA is installed, it must also be CLOSED/Grounded. See Isolation
Means (IM) on page 77 for operational procedures.
4. Open the MV door.
5. Pull the contactor rail down. This will disengage the contactor from the
line and load bus bar connections.
6. Roll the contactor out and remove from the rail.
Figure 50: Motorpact Contactors
Load
connections
Control terminal
blocks with
drive unit
Closing
coils
Auxiliary
switch
Closing coils
Load
connections
200/400/450 A
720 A
For more information on the latched contactor, see
Schneider Electric bulletin no. 46032-700-02, Motorpact
200/400/450A Vacuum Contactors or bulletin no. 46032-700-03,
Motorpact 720 A Vacuum Contactors.
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 7Features and Operation 07/2009
20032009 Schneider Electric All Rights Reserved 66
Follow steps 16 to install the contactor. For steps 46, see Figure 51.
1. Carefully inspect the work area and ensure that no tools or objects are
left inside the equipment.
2. If more than one contactor is present, before inserting the contactor,
verify that it is rated for the controller.
3. Lower the contactor rail.
4. Lift the contactor and carefully align the wheels on the rail.
5. Gently push the contactor into the cradle until it stops.
6. Slowly raise the contactor rail. This will engage the contactor to the line
and load bus bars.
7. Close the MV door.
RVAT/RVSS Contactors Removing the Contactors
Follow steps 16 and refer to Figure 52 to remove an RVAT or RVSS
contactor.
1. Review the safety precautions on page 20.
2. If the equipment has been energized, open the contactors by pressing
the STOP/OFF button on the main controller to the left of the
RVAT/RVSS enclosure. If the unit is an RVSS standalone section, make
sure the main contactor in the separate main controller is open and no
power is coming to the RVSS section.
3. Gain access to the upper compartment. See Unlocking/Locking
RVAT/RVSS Doors on page 68.
Figure 51: Withdrawing the Contactor

Medium Voltage Door Open Contactor Rail Assembly Pulled Down Contactor Withdrawn
CAUTION
HAZARD OF PERSONAL INJURY OR EQUIPMENT DAMAGE
Handle the contactors carefully. Contactors weigh approximately
61 lbs. (27.7 kg).
Failure to follow this instruction can result in personal injury and
equipment damage.
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 7Features and Operation
20032009 Schneider Electric All Rights Reserved 67
E
N
G
L
I
S
H
4. Lower the contactor rail. This will disengage the contactor from the line
and load bus bars.
5. Gently pull the contactor forward until the front wheels are positioned in
safety wheel slot, as shown in Figure 52.
6. To remove the contactor from the rail assembly, manually lift the front of
the contactor up. Pull forward, allowing the rear wheels to clear the
safety guide (located on the rail). The contactor can then be removed
from the rail assembly manually or with the optional lift truck.
Door and Mechanical Interlock
Features
Mechanical Interlocks Motorpact controllers are equipped with mechanical systems built into
each unit to promote safe operation and maintenance. The mechanical
interlocks provide coordinated control between the contactor, IM, medium
voltage door, and the optional LDA. Table 11 demonstrates the interlock
dependencies that are provided with each controller.
Figure 52: Removing the Contactors
Contactor
Rail assembly
Safety wheel slot
Safety guide
Table 11: Mechanical Interlock Dependencies
Device Dependency Dependency Dependency
CNT =I LDA =O IM =I MVD =I
CNT =O LDA =I/O IM =I/O MVD =I/O
LDA =I CNT =O and E/W, OT IM =O MVD =I/O
LDA =O CNT =I/O and E/W, OT IM =I/O MVD =I/O, OT
IM =I CNT =I/O and E/W LDA =O MVD =I
IM =O CNT =I/O and E/W, OT LDA =I/O, OT MVD =I/O, OT
MVD =I CNT =I/O and E/W LDA =I/O IM =I/O
MVD =O CNT =O and E/W LDA =I/OT IM =O
Key: CNTContactor; LDALoad discharge assembly (optional); IMIsolation means;
MVDMedium voltage door
I =Closed, O =Open, W =Withdrawn, E =Engaged, OT =Test
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 7Features and Operation 07/2009
20032009 Schneider Electric All Rights Reserved 68
Unlocking/Locking FVNR/FVR/Controller
Doors
The locking of the FVNR/FVR/Controller door is governed by the position of
the isolation means (IM) and/or the load discharge assembly (LDA),
commonly referred to as a cable grounding switch. The doors will be
unlocked when the IM is grounded. If an LDA is present, it must also be
grounded. The door will be locked when either the IM is closed or the LDA is
open. See the Isolation Means (IM) section on page 77 for further details.
Unlocking/Locking RVAT/RVSS Doors Door interlocks are provided to prevent inadvertent access to energized
components and to promote the proper operation of the isolation means and
the RVAT and RVSS enclosures. Close and lock all equipment doors before
energizing the equipment.
Follow steps 16 to unlock RVAT/RVSS doors. For steps 46, see Figure
53 on page 69.
1. Review the Safety Precautions on page 20.
2. If the equipment has been energized, open the contactors by pressing
the STOP/OFF button on the main controller to the left of the
RVAT/RVSS enclosure. If the unit is a RVSS standalone section, make
sure the main contactor in the separate main controller is open and
power is off in the RVSS section.
3. Turn and remove the key from the key interlock (located on the operator
panel of the controller to the left of the RVAT or RVSS enclosure).
4. Open the middle door(s) on the RVAT or RVSS enclosure.
5. Insert and turn the interlock key to release the door-latching mechanism.
6. Insert the operating handle. Rotate counterclockwise to release the
doors.
Follow the steps below to secure all the compartment doors before
energizing the equipment.
1. Close all doors except middle door(s) on the RVAT or RVSS enclosure.
If the enclosure contains rightside hinged doors, they must be closed
before the leftside doors. To ensure the upper door remains closed in
the RVSS enclosure, tighten the thumb screw located on the lower
flange.
2. Push the release button (located next to the handle insert) and rotate the
handle clockwise to lock doors. See Figure 53.
RVSS Standalone Section:
It is important that the RVSS standalone
section interlock key be coordinated with
the main controller key interlock (key
removable when disconnector is open).
This guarantees that the RVSS
standalone section MV doors cannot be
opened unless the disconnector in the
main controller is open.
If the main controller is a Square D

brand controller, then a key locking


scheme should be ordered so the RVSS
standalone section interlock uses the
main controller key. If the main
controller is not a Square D brand
controller, it is highly recommended the
RVSS key be permanently attached
(welded or solid riveted) to the main
controller key.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not make any modifications to the equipment or operate the system
with the interlocks removed. Contact your local Schneider Electric
representative for additional instructions if the equipment does not
function as described in this manual.
Carefully inspect your work area and remove any tools and objects left
inside the equipment.
Replace all devices, doors, and covers before turning on the power to
this equipment.
Failure to follow these instructions will result in death or serious injury.
All doors must be fully closed prior to handle rotation.
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 7Features and Operation
20032009 Schneider Electric All Rights Reserved 69
E
N
G
L
I
S
H
3. Once the doors are locked and before closing the IM, remove the key
from the RVAT and RVSS enclosures. Insert the key into the lock
located on the operator panel of the main controller (to the left of the
RVAT and RVSS enclosures).
Key Interlocks Motorpact controllers can be provided with up to two key interlocks for the
IM and one key interlock for the LDA. Refer to the package of drawings
accompanying the controller line-up.
Figure 53: Unlocking/Locking RVAT and RVSS Doors




Door latch keylock
Operating handle
Release
button
Locking
Unlocking
For the RVSS standalone section, return the RVSS key to main
controller, if it is permanently attached, or to its secure location.
Figure 54: Key Interlocks

Key
interlock
Locking the IM open or
closed with key interlock
2 key
interlocks
Locking the IM open or
closed with 2 key interlocks
Locking the LDA open or
closed with key interlock
Key
interlocks
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 7Features and Operation 07/2009
20032009 Schneider Electric All Rights Reserved 70
Defeating Controller Interlocks
When testing cables, the LDA must be ungrounded. This procedure
requires defeating two separate interlock functions (see Figure 55).
MDT107 Thermal Diagnostic
System
The MDT107 Thermal Diagnostic system is mounted in the equipment at
the factory for shipping. Wiring connections must be completed and tested
on site before putting the equipment into service.
Description The MDT107 Thermal Diagnostic system is used to measure the
temperature of medium voltage circuits. Using Schneider Electric patented
technology, the MDT107 system provides:
continuous monitoring of the temperature rise of power circuits at upper
fuse holders and customer cable connections
triggering of a pre-alarm, then an alarm by activation of outputs on dry
contacts
visual indication of the zone and phase in which a temperature rise
exceeds a set threshold
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
This equipment must be installed and serviced only by qualified
personnel.
Qualified persons performing diagnostics or troubleshooting that require
electrical conductors to be energized must comply with NFPA 70 E
Standard for Electrical Safety Requirements for Employee Workplace
and OSHA Standards 29 CFR Part 1910 Subpart S Electrical.
Failure to follow these instructions will result in death or serious injury.
Figure 55: Defeating Interlock Functions
Slide the access door to the right
Press the medium voltage door
interlock toward the equipment
Press down on the medium
voltage door interlock
NOTE: Perform all three
actions simultaneously in
order to defeat the interlocks.
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 7Features and Operation
20032009 Schneider Electric All Rights Reserved 71
E
N
G
L
I
S
H
The MDT107 system includes:
An MDT107 electronic module mounted on a DIN rail in the LV
compartment of the Motorpact unit. The module transmits calibrated
impulses to one or more circuits via optical fibers. The calculation of a
circuits temperature is based on the impulses the circuit sends back to
the module.
Two CFO733 temperature sensors. Each of these factory-built
assemblies includes three sensor heads, three optical fibers, and the
connector for connecting to the readout module. The sensor heads are
made from a light-sensitive material whose fluorescence time depends
on temperature. The connector incorporates an opticalelectric
conversion circuit, eliminating the need for optical connections during
installation.
Accessories for factory installation of the sensors in the MV panel.
Functions The MDT107 module performs the following functions:
Monitoring of Temperature Buildup in Two Zones Each CFO733 sensor corresponds to a three-point zone to be monitored in
the panel, monitoring being based on temperature rise. The module
measures the temperature at three points per zone, as well as the ambient
temperature in order to calculate the temperature rise for each point.
Given the temperature differences between the inside of the LV
compartment and the outside of the enclosure, correction of the ambient
temperature measured by the module is configured by means of an
additional setting.
Monitoring is done by comparison with a maximum temperature rise
threshold, which can be adjusted separately for each zone and is common
to the three measurement points. This form of monitoring is completed by a
fixed maximum absolute sensor temperature threshold.
Therefore, the module includes three settings, access to which is sealed
after the ambient temperature settings are made on site.
Triggering of a Pre-alarm When the temperature rise at one of the three points reaches a first set point
equal to 85%
1
of the preset threshold for the zone, or when one of the three
points reaches the maximum absolute temperature of 239 F (115 C), a
pre-alarm is generated and results in:
activation of the pre-alarm indication relay common to the two zones
activation in flashing mode of one of the six front panel indicators which
identify the zone and related point
Triggering of an Alarm When the temperature rise at one of the three points reaches the preset
maximum threshold
2
for the zone, or when one of the three points reaches
the maximum absolute temperature of 248 F (120 C), an alarm is
generated and results in:
activation of the alarm power relay common to the two zones
activation in constant mode of one of the six front panel indicators which
identify the zone and related point
1
This is a fixed value; it cannot be modified.
2
These seven setting values are defined at the factory. They are identified as A to G in Figure 56
on page 73.
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 7Features and Operation 07/2009
20032009 Schneider Electric All Rights Reserved 72
Self-monitoring of the Module The MDT107 module has internal self-tests and is equipped with an
indicator that indicates availability:
In both cases, the pre-alarm output contact is also activated when the
indicator is steadily on.
Self-monitoring of Sensors The module provides continuous monitoring of the connected sensor(s). An
Off position is included in the settings for each zone for the various
situations that can occur:
If no sensors are connected to the module
the indicator is on and flashes
the pre-alarm output contact is activated
the six sensor identification indicators are off
If one of the three points of each sensor is detected as being faulty (cut
or damaged fibers, malfunction of sensor-embedded electronics)
the indicator is on and flashes
the pre-alarm output contact is activated
the indicator linked to the faulty measurement point flashes
When only one zone is connected, the unused zone should be set to
Off. If this is not done, the three points of the related zone are detected
as being faulty.
Availability
Indicator
Each time the module is initialized. The indicator
turns on in constant mode when the module is
switched on and then turns off after the module
initialization phase is successfully completed, unless
the required sensors are missing (see
Self-monitoring of Sensors below).
In steady-state operation. If a fault is detected, the
indicator turns on in constant mode.
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 7Features and Operation
20032009 Schneider Electric All Rights Reserved 73
E
N
G
L
I
S
H
Ratings
Figure 56: Wiring and Operation for MDT107
7
off
G
F
E
C
B
A
D
off
G
F
E
C
B
A
D
Zone B
Zone A
DT build-up
setting
-18
-16
-14
-12
-8
-6
-4
-10
Ambient T
correction
(C)
Zone B Zone A
L3
L1
L2
on
A B
Temperature
rise threshold
setting switches
Terminals 25 and
26 not used
Five relay output, dry contact,
connection terminals:
Pre-alarm (1NO, 20-21)
Alarm (1NCNO; 22-23-24)
Module grounding terminal
via green/yellow wire
(PE, safety of personnel)
24-250 Vdc and 110-240 Vac
power supply correction
terminals
Six red indicators identifying the
sensor (zone A or B) and the
circuit/sensor at the origin of the alarm
Ambient temperature
correction setting switch
Green power onindicator and
red availabilityindicator
NOTE: The modules screw type connectors can receive two wires with
a maximum size of AWG 24-12 (0.2 to 2.5 mm
2
), with or without fittings.
Alarm
Pre-
alarm
Table 12: Optical Fiber Probes CFO733
Highest voltage for the equipment 17.5 kV
Rated power frequency voltage 38 kV
Impulse voltage 95 kV
Maximum fiber/sensor temperature 248 F (120 C)
Table 13: MDT107 module
Temperature rise setting Factory set
Operating and storage temperature -13 F to +158 F (-25C to +70C)
Absolute maximum threshold values
pre-alarm =239 F (115 C)
alarm =248 F (120 C)
Multi9 profile width 4.13 in. (10.5 cm)
Module power supply 24/250 Vdc, 110/240 Vac
Dry contacts voltage: 24, 48, 127, 220 Vdc - 100 to 240 Vac
Continuous current:
5A permanent (pre-alarm)
8A permanent (trip)
Consumption (stand-by to maximum)
AC
DC
<1.2 W (stby) to <3.4 W (max.)
<4.4 W (stby) to <6.6 W (max.)
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 7Features and Operation 07/2009
20032009 Schneider Electric All Rights Reserved 74
MDT107 Module Location
CAUTION
HAZARD OF EQUIPMENT DAMAGE
Use caution when working in the enclosure near the MDT107 sensors.
The sensor heads can be damaged easily.
Failure to follow this instruction can result in equipment damage.
Figure 57: MDT107 Module Location
Field
shapers
Load
box
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 7Features and Operation
20032009 Schneider Electric All Rights Reserved 75
E
N
G
L
I
S
H
MDT107 Sensors Location
Setting the Temperature Rise Thresholds The module is equipped with two mechanical selector switches for setting
the temperature rise threshold for each zone. Each switch has eight
possible setting positions. The factory settings are shown in Table 14.
The selector switches are accessible from the front panel. They are
protected by a sealed cover. To change the setting for a zone:
1. Remove the protective cover.
2. Insert the tip of a screwdriver into one of the arrow-shaped slots.
NOTE: Use a flathead screwdriver with a tip width of 0.15 in. (4 mm).
3. Turn the switch to the desired setting.
4. Replace the protective cover.
Figure 58: MDT107 Sensors Location
Load Box
Field Shapers
Figure 59: Selector Switches for
Temperature Rise Threshold
(250 A contactor settings shown)
Zone B
Zone A
off
G
F
E
C
B
A
D
off
G
F
E
C
B
A
D
T build-up
setting
Table 14: Factory Settings
Contactor Rated
Current (A)
Zone A
Load Box Connection
Zone B
Field Shapers Connection
200 B C
400 D E
450 D F
720 C G
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 7Features and Operation 07/2009
20032009 Schneider Electric All Rights Reserved 76
Setting the Ambient Temperature
Correction
The module contains a mechanical selector switch for correcting the
ambient temperature measured on the MDT107 module. The switch has
eight possible setting positions. It is accessible from the front panel and is
protected by a sealed cover. To change a setting:
1. Measure the temperature in the LV compartment where the MDT107
module is located, then measure the ambient temperature outside the
switchgear. Note the difference in temperature between the two
locations.
2. Remove the protective cover.
3. Insert the tip of a screwdriver into the arrow-shaped slot.
NOTE: Use a flathead screwdriver with a blade width of 0.15 in. (4 mm).
4. Turn the switch to the setting closest to the temperature difference
measured in step 1.
5. Replace the protective cover.
Troubleshooting The following troubleshooting chart is provided to help minimize downtime.
If the proposed solutions do not correct the problem, please contact your
Schneider Electric sales representative.
Figure 60: Selector Switch for Ambient Temperature Correction
Ambient T
correction
(C)
-18 -4
-6
-8
-10 -12
-14
-16
Symptoms Faulty Devices Probable Causes/Solutions
The green indicator is off. External power supply
Ensure the power supply is present
and connected.
Insufficient voltage (out of range).
The MDT107 module is faulty and
must be replaced.
The red indicator
remains on after
energization.
Setting selector switches if
indicators L1L3 are flashing.
Incorrect positioning of selector
switches, for example, one or more
switches is between two positions.
Indicators L1L3 in Zones A
and B are off
The MDT107 module is faulty and
must be replaced.
The red indicator
is flashing.
Probe connection
The probe(s) are not connected, or
the associated selector switch is in
the Offposition.
Probes or sensors
The probe or sensor is faulty and
must be replaced.
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 7Features and Operation
20032009 Schneider Electric All Rights Reserved 77
E
N
G
L
I
S
H
Isolation Means (IM)
Description The isolation means (IM) is designed to disconnect a controller from the line
or source and is required to allow for maintenance of the units. Each
Motorpact controller is equipped with an isolation means like the one
shown below.
The isolation means is a medium voltage, three-pole, manually operated
device. The IM is encased in an arc resistant and flame-retardant housing.
In the open position, the IM is grounded.
Designed for use on systems up to 7.2 kV, the isolation means are rated
200, 400, 450, and 720 A. The IMs are non-load break devices, which
means the devices cannot interrupt a power load. Design of the IM allows
for interrupting CPT and/or VT loads only. Mechanical and electrical
interlocking prohibit opening or closing the IM with the contactor closed.
IM View Port
To determine position of the switch, use the viewing port to determine
whether it is OPEN/Grounded or closed.
Figure 61: Isolation Means
Figure 62: Viewing Port
IM Grounded IM Closed
Viewing port
IM blades
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 7Features and Operation 07/2009
20032009 Schneider Electric All Rights Reserved 78
Operating Instruction Label Operating instructions for the motor controller can be found on the
escutcheon (see Figure 63).
Operating the IM When the IM is moved to the grounded position, it grounds the IM blades
and load side power circuit down to the line side of the contactor.
To move the IM to the grounded position, see Figure 64 on page 79.
To close the IM, see Figure 65 on page 80.
To move the LDA to the CLOSED/Grounded position, see Figure 66 on
page 81.
To move the LDA to the open position and close the IM, see Figure 67
on page 82.
If an LDA is installed, the escutcheon label will be different from the
label shown in Figure 63. Refer to the section Load Discharge
Assembly on page 84.
Figure 63: Operating Instructions on Escutcheon
The contactor must be open and the medium voltage door must be
closed to operate the IM.
Moving the IM to the grounded position does not ground the load
side of the contactor, load cables, or any other components (such
as power factor correction capacitors) that are connected to the
load side of the controller.
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 7Features and Operation
20032009 Schneider Electric All Rights Reserved 79
E
N
G
L
I
S
H
Figure 64: Moving the Isolation Means to the Grounded Position

IM is CLOSED. Rotate handle counter-clockwise.
IM is in OPEN/Grounded Position. Access port
cannot be closed unless IM is in the fully connected
or grounded position.
1 Step
Handle Access Port is OPEN. Remove the handle and slide
the access door to the left to close the Handle Access Port.
Press the STOP/OFF button on the operator panel. Handle Access
Port is CLOSED. To open the port, slide the access door to the right.
Handle Access Port is OPEN. Insert the handle.
2 Step
3 Step
5 Step 6 Step
4 Step
Open the medium voltage door.
Access Door
Access Door
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 7Features and Operation 07/2009
20032009 Schneider Electric All Rights Reserved 80
Figure 65: Closing the Isolation Means

To operate the equipment, close
the door and fully engage the
handle. Access port must be
closed to close MV door.
1 Step 2 Step
3 Step
Handle Access Port is CLOSED. To open the port, slide the
access door to the right.
IM is grounded. To close, insert the
handle and rotate clockwise.
Access Door
IM is CLOSED. Remove handle and close access port.
4 Step
Access Door
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 7Features and Operation
20032009 Schneider Electric All Rights Reserved 81
E
N
G
L
I
S
H
Figure 66: Moving the LDA to the CLOSED/Grounded Position

IM will be OPEN/Grounded. IM access
port is CLOSED. Interlock shuttle handle
is on the left. LDA access port is closed.
1 Step
Move interlock shuttle to the right. Lower the LDA
access port. IM access port will not open when
interlock shuttle is on the right side.
2 Step
3 Step
4 Step
Open the medium voltage door.
LDA is CLOSED/Grounded. Remove the handle and close the
LDA access port.
LDA access port
IM access door
Follow steps
15 on Figure
64.
Interlock shuttle
Insert the handle and rotate counterclockwise
approximately ten times. Handle must be rotated until
resistance is encountered or the door interlock will not
be released.
LDA access port
5 Step
CAUTION
HAZARD OF EQUIPMENT DAMAGE
LDA will close at approximately eight rotations. Continue to turn
for an additional two rotations. Do not apply excessive force
when resistance is met.
Failure to follow this instruction can result in equipment
damage.
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 7Features and Operation 07/2009
20032009 Schneider Electric All Rights Reserved 82
Figure 67: Moving the LDA to the Open Position and Closing the IM
1 Step 2 Step
3 Step

Close the medium voltage door.
LDA is CLOSED/Grounded. Lower the LDA access port. Insert
the handle and rotate clockwise approximately ten times.
Interlock shuttle
LDA is OPEN. Remove handle and raise the
LDA access port. Move the interlock shuttle
to the left.
4 Step
IM is closed. Remove the handle and close
the IM access port.
IM access door
5 Step
LDA access port
OPEN IM access port. Insert handle and rotate clockwise to close the IM.
CAUTION
HAZARD OF EQUIPMENT DAMAGE
When resistance is met at the end of ten rotations, do not apply
excessive force to the handle.
Failure to follow this instruction can result in equipment
damage.
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 7Features and Operation
20032009 Schneider Electric All Rights Reserved 83
E
N
G
L
I
S
H
Live-Line Indicators (LLI) and
Capacitive Dividers
Live-Line Indicators Optional live line indicators (LLIs) may be installed to indicate the presence of
voltage. The LLI module is located on the front of the escutcheon of the main
controller or in the low voltage compartment door of the RVSS standalone
section. LLIs are wired to the capacitive dividers that are located at the load
connections. Optional capacitive dividers are installed near the main bus and
line side of the IM with the LLI mounted on the front of the low voltage
compartment door. For the RVSS standalone section, these optional
capacitive dividers are installed at the line or load side cable connectors.
Test ports on the LLIs, located below the neon lamps, are suitable for
testing voltage with a properly rated voltage-sensing device. They will be at
5070 V whenever the lamps are illuminated. LLIs are not a replacement for
voltage indication when accessing the MV compartment. Use a properly
rated voltage sensing device to ensure no voltage is present before
performing any maintenance procedures.
Replace LLIs Follow the steps outlined below to replace LLIs (450 A and below).
1. Turn off all power supplying the equipment. Use a properly rated voltage
sensing device to confirm that the power is off.
2. Remove the two mounting screws.
3. Pull the LLI outside of the cover.
4. Unplug the wiring harness.
5. Plug the wiring harness into the new LLI head. Secure wiring harness to
LLI head using a cable tie through hole in tag.
6. Push the LLI back into the cover opening.
7. Replace the two mounting screws.
Follow all of the safety precautions and procedures outlined in the
instruction bulletin supplied with your equipment to properly energize the
equipment.
Figure 68: Live Line Indicator Location (450 A and Below) Main
Controller
L3A
L2B
L1C
Rear view of
low voltage panel
Detail A
Detail B
Right side
view of
equipment
Figure 69: LLI Tag (located on the wiring
harness)
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 7Features and Operation 07/2009
20032009 Schneider Electric All Rights Reserved 84
If the lights on the LLI do not illuminate, repeat steps 17 above. If after
repeating the procedure results are not satisfactory, turn off all power to the
equipment and contact your Square D/Schneider Electric representative.
Capacitive Divider The capacitive divider is a cylindrical insulator mounted to the load
connection base or, for line-side sensing, a standoff support insulator. Both
have the capacitor permanently bonded inside. This capacitor powers the
neon lamps in the LLIs.
Load Discharge Assembly In addition to the standard controller, an optional LDA, or grounding
switch, is used to ground the load cables. The LDA is housed within the
insulating base (load box) where the load cable connections are bolted. The
LDA is mechanically interlocked with the IM and is actuated using the same
operating handle.
Figure 70: LLI Box
A. Voltage presence indicator light (one for each
phase)
B. Connection ports enabling voltage testing to
verify phasing between multiple sources
A
B
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 7Features and Operation
20032009 Schneider Electric All Rights Reserved 85
E
N
G
L
I
S
H
Figure 71: LDA
Open position
Label
Grounded
position
LDAenlarged view
Indicator pin
Grounding bar
LDA closed LDA open
CAUTION
IMPROPER LDA OPERATION
Do not use the LDA as a system grounding switch.
If the controller with LDA is used as a primary switching device for a
power transformer, key interlocking must be used between the primary
and secondary disconnecting devices.
If the controller with LDA is used as a tie, key interlocking must be used
between the LDA and all primary disconnecting devices.
Failure to follow these instructions can result in personal injury and
equipment damage.
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 7Features and Operation 07/2009
20032009 Schneider Electric All Rights Reserved 86
Interlock Shuttle An interlock shuttle is provided on all FVNR/FVR/controller sections with a
load discharge assembly. This shuttle must be in the left-hand position to
operate the isolation means and in the right-hand position to operate the LDA.
LDA Interlock System Operation The interlock system requires the following conditions to be met before the
LDA can be actuated:
Contactor must be in the OPEN position.
IM must be in the OPEN/Grounded position.
IM operating port access must be closed (see Figure 66 on page 81).
Charging and Latching the LDA Back to the
Ungrounded Position
To charge and latch the LDA back to the ungrounded position:
1. Close and latch the MV door.
2. Turn the LDA handle in the opposite direction (clockwise) approximately
10 turns or until solid resistance is felt and the indicator is in the charged
position.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The LDA has no interrupting capability. Several complete rotations of the
handle are required to allow time for the system to completely dissipate
electric power in the cables or transformer before the LDA will close.
Failure to follow this instruction will result in death or serious injury
See the section Isolation Means (IM) on page 77 for further
operating instructions.
Figure 72: Interlock Shuttle
D G
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 7Features and Operation
20032009 Schneider Electric All Rights Reserved 87
E
N
G
L
I
S
H
Low Voltage Compartment
Features
Accessing the LV Compartment
Test Power Plug To operate the contactor using an external test source:
1. Move the isolation means to the grounded position (see Figure 64 on
page 79).
2. Open the low voltage door and plug in 120 Vac test power using a
suitable extension cord. See Figure 75.
Figure 73: Opening the Low Voltage Door and Accessing the Low Voltage Panel
1
Step
Step
Lift latch and rotate counter-clockwise. Open the LV door.
2
Latch
Figure 74: Latch Locking Screw

Closed latch
Locking screw
NOTE: The latch locking screw is
provided as standard for arc-resistant
enclosures.
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 7Features and Operation 07/2009
20032009 Schneider Electric All Rights Reserved 88
Current Transformer (CT) Shorting To short the current transformers, use the short circuit terminal blocks
located in the low voltage compartment (if applicable). See job schematics
and wiring diagrams for quantity and locations.
Figure 75: Low Voltage Compartment Details
Terminal block
mounting bracket
Top wireway
Sepam relay
Low voltage door
(inside)
Customer TB
Operator panel harness
IM switch harness
FuseLogic harness
LDA harness
IM switch light harness
To
heater harness
CPT/VT wire harness
contactor harness
CT/LPCT wire harness
cradle ground wire
Low voltage mounting pan
Right Side View
Low Voltage Control Area
Detail
A
Detail
B
Detail C
Detail A
Detail C
Detail B
Low voltage compt ground
Ground bus
To low voltage mounting plan
To low voltage
door
Customer
connection
Customer TB (top entry)
CTs, VTs, CPTs,

3 (N.O./N.C.) contacts
(option)
3 (N.O./N.C.) contacts
(option)
3 (N.O./N.C.) contacts
(standard)
3 (N.O./N.C.) contacts
(standard)
4 form C contacts
(standard)
4 form C contacts
(option)
LDA 4 form C contacts
(option)
Control power and
IM switch light
Low voltage ground bar
Control power
FuseLogic 2 form C
contacts (option)
120 VAC test plug
Low voltage compartment ground
(to ground bus)
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 7Features and Operation
20032009 Schneider Electric All Rights Reserved 89
E
N
G
L
I
S
H
Padlock Features
Number of Possible Padlocks One padlock on each isolation means (for preventing operation)
One padlock on each load discharge assembly (for preventing
operation)
One padlock on each incoming cable section door (for preventing
access)
Padlocking the Isolation Means Place one padlock on the isolation means access door. See Figure 76.
This lock can be used to prevent operation of the isolation means in either
the CLOSED or OPEN/Grounded position.
Padlocking the Load Discharge
Assembly (Optional)
Place one padlock on the load discharge assembly operating access port.
This lock can be used to prevent operation of the load discharge assembly
in either the CLOSED/Grounded or OPEN position.
Figure 76: Padlocking the Isolation Means
Figure 77: Padlocking the Load Discharge Assembly
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 7Features and Operation 07/2009
20032009 Schneider Electric All Rights Reserved 90
Padlocking the Incoming Cable Section
Doors
Place one padlock on each padlockable incoming cable section door, upper
and lower.
This lock can be used to prevent medium voltage access whenever a key
lock is not requested.
Voltage Transformer (VT) Section
Cold Sequence VT The Cold Sequence units use the Motorpact IM to disconnect the power
circuit from these transformers. See Figure 64 on page 79 for description
and operation. The IM must be open and in the grounded position to access
the medium voltage fuses and transformers.
Hot Sequence VT The Hot Sequence units are supplied with two doors. The doors are
interlocked so that the upper door must be operated first. The end user must
install key interlocks with upstream disconnecting devices.
Figure 78: Padlocking the Incoming Cable Section Doors
WARNING
HAZARD OF IMPROPER OPERATION
The hot sequence units require proper coordination of key interlocks with
upstream disconnecting devices for proper operation.
Failure to follow this instruction can result in serious injury or death.
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 8Energizing the Controller
20032009 Schneider Electric All Rights Reserved 91
E
N
G
L
I
S
H
Section 8Energizing the Controller
Preliminary Operating Check Before energizing the equipment, perform the following operating tests.
1. Operate the load discharge assembly (LDA), if equipped, a minimum of
five times. Verify that the LDA is functioning properly.
2. Operate the isolation means (IM) a minimum of five times.
3. With the IM in the CLOSED (I) position (see Figure 65 on page 80),
verify that the medium voltage door cannot be opened.
4. If applicable, verify that the key interlocks function properly according to
the drawings.
5. Verify that all low voltage compartment plugs are connected.
6. Replace all devices, doors, and covers before turning on the power to
the equipment.
7. Verify that all protective relays have been configured with proper
settings per the outcome of customers coordination study. The
contactor opening time must be coordinated with the supplied power
fuse's time-current characteristics. Power fuses must interrupt currents
which exceed contactor ratings. For contactor ratings, which include
interrupting capability and opening times, refer to Schneider Electric
bulletin no. 46032-700-02, Motorpact 200/400/450 A Vacuum
Contactors or bulletin no. 46032-700-03, Motorpact 720A Vacuum
Contactors. In some cases, a contactor opening time delay will have to
be configured in the protective relay.
8. Ensure that all transition, control, and timing relays are configured per
customer requirements and these settings do not exceed the restrictions
identified in Application Notes on page 17.
RVSS Standalone Section Before energizing the RVSS standalone section perform the following
checks:
1. Verify phasing between the controller, RVSS section, and motor are
correct.
2. Control power from the main controller CPT is supplied to the RVSS
section before medium voltage power is applied. This will allow the
RVSS electronics protection to be functioning before MV power is
applied.
If any of the operating tests provide unacceptable results, DO NOT
ENERGIZE THE CONTROLLER. Contact your local field sales
office or distributor.
CAUTION
HAZARD OF EQUIPMENT DAMAGE
Before adjusting the Forward (FCR) or Reverse (RCR) timing relays,
determine the maximum time required for the motor to come to a complete
stop. The FCR and RCR settings should not be set below this value.
Failure to follow this instruction can result in equipment damage.
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 8Energizing the Controller 07/2009
20032009 Schneider Electric All Rights Reserved 92
Starting the Controller
1. Before starting, review the Preliminary Operating Check on page 91 to
ensure equipment is ready for operation.
2. Energize the equipment in sequence, starting with the main devices,
then the feeder devices, and then the motor starter devices.
3. If the controller is equipped with an LDA, move it to the
OPEN/Ungrounded position. See Figure 67 on page 82 for operating
procedure.
4. Close the IM. See Figure 65 on page 80.
5. Press the RUN/START button located on the operator panel. For an
FVR application, press the Forward or Reverse push button to energize
the motor.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Only qualified personnel familiar with medium voltage equipment should
perform work described in these instructions. Workers must understand
the hazards involved in working with or near medium voltage circuits.
Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See NFPA 70E.
Do not make any modifications to the equipment or operate the system
with the interlocks removed. Contact your local field sales representative
for additional instruction if the equipment does not function as described
in this manual.
Carefully inspect your work area and remove any tools and objects left
inside the equipment.
Replace all devices, doors, and covers before turning on power to this
equipment.
Failure to follow these instructions will result in death or serious injury.
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 8Energizing the Controller
20032009 Schneider Electric All Rights Reserved 93
E
N
G
L
I
S
H
Stopping the Controller
1. Press the STOP/OFF button located on the operator panel.
2. If the section is equipped with the contactor viewing window (located on
the lower left side of the MV door), look through the window to ensure
the contactor is open. The indicator arm will be positioned on the green
side of the label.
3. If access is required within the MV compartment or maintenance of
downstream devices is required, open/ground the IM. If an LDA is
present, it must be CLOSED/Grounded. Refer to Figure 64 on page 79
and Figure 66 on page 81.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Only qualified personnel familiar with medium voltage equipment should
perform work described in these instructions. Workers must understand
the hazards involved in working with or near medium voltage circuits.
Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See NFPA 70E.
Turn off all power before working on or inside equipment.
Use a properly rated voltage-sensing device to confirm that the power is off.
Before performing visual inspections, tests, or maintenance on the
equipment, disconnect all sources of electric power. Assume that all
circuits are live until they have been completely de-energized, tested,
grounded, and tagged. Pay particular attention to the design of the power
system. Consider all sources of power, including the possibility of
back feeding.
All instructions in this manual are written with the assumption that the
customer has taken these measures before performing maintenance
or testing.
Failure to follow these instructions will result in death or serious injury.
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 9Maintenance 07/2009
20032009 Schneider Electric All Rights Reserved 94
Section 9Maintenance
Preventive Maintenance
Recommended Inspection Guidelines Inspect the equipment periodically to determine the conditions to which the
units are subjected. After determining the environmental conditions
according to the guidelines in this section (see Environmental Conditions),
perform inspections and maintenance according to Table 15.
* See Environmental Conditionssection below for definitions.
Inspect the equipment immediately after abnormal or stressful operating
conditions occur, or after the equipment experiences a fault current.
These inspection/maintenance guidelines cover only the controller. If
conditions cannot be established and documented, assume the operating
conditions are aggressive.
These inspection/maintenance guidelines do not warrant any field
connections, field modifications, or supersede any maintenance procedures
or schedules recommended by component manufacturers.
Environmental Conditions
Ideal Conditions 1. Unit is installed and commissioned in accordance with the
manufacturers instructions.
2. Humidity is below 40%, and there is no dripping water.
3. Indoor, protected from the weather.
4. Minimum of dust and air circulation.
5. Ambient temperature is between 0 C and 40 C.
6. No contact with any chemical agents (salt, H2S, etc.).
7. No infestation of any animal life (rodents, insects, etc.).
8. No contact with any plant life (mold, etc.).
9. No earth movements.
10. No damage to the unit of any kind.
11. No operating problems of any kind.
12. No abnormally high number of operations.
13. No abnormally high number of faults.
14. No over-voltage or over-current (above ratings).
Table 15: Recommended Inspection/Maintenance Guidelines
Component
Ideal
Conditions*
Standard
Conditions*
Aggressive
Conditions*
Section interior (bus and mechanism)
Every 5 years Every 2 years Once per year Exterior of polyester isolation means housing
Instruments, relays, and other devices
For more information regarding the
warranty of this product, refer to
Square D Conditions of Sale,
document no. 0100PL0041.
For the optional MDT107, see MDT107 Thermal Diagnostic
System on page 70.
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 9Maintenance
20032009 Schneider Electric All Rights Reserved 95
E
N
G
L
I
S
H
Standard Conditions All the above conditions listed under Ideal Conditionsapply with the
exception of the following:
Number 2: Humidity below 60%.
Numbers 3 through 5: The unit must not be subjected to regular
extremes of temperatures greater than 40 C or less than minus 30 C.
No regular thick covering of leaves or other debris.
Aggressive Conditions Any environmental conditions that do not satisfy one of the two above
descriptions are aggressive.
This product is warranted per Square D Conditions of Sale, document
no. 0100PL0041, and has been tested under ideal laboratory conditions to
the values listed below:
1000 mechanical no load operations
3 fuse fault transfer current operations (see IEC 420 for application)
The device has been designed and tested to NEMA ICS-3 and UL 347
requirements. The mechanical life of the isolation means is 5000 operations.
Inspecting the Equipment
To verify the contact life of the contactor, see Schneider Electric
bulletin no. 46032-700-02, Motorpact 200/400/450 A Vacuum
Contactors or bulletin no. 46032-700-03, Motorpact 720 A
Vacuum Contactors.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
This equipment must be installed and serviced only by qualified
electrical personnel.
Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See NFPA 70E.
Turn off all power supplying this equipment before working on or inside.
Always use a properly rated voltage sensing device to confirm that
power is off.
Inspection and maintenance should only be performed with the primary
source(s) of power disconnected and locked open. Be absolutely sure
there is no back-feed through any feeder circuit.
Replace all devices, doors, and covers before turning on the power to
this equipment.
Failure to follow these instructions will result in death or serious
injury.
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 9Maintenance 07/2009
20032009 Schneider Electric All Rights Reserved 96
To ensure the controller is properly maintained, perform at least the
following inspection procedures.
1. Bus and Connections: Deenergize the primary and secondary circuits.
Perform a hi-pot test to measure bus insulation integrity. See Hi-pot
(Dielectric) Testing on page 57.
2. Inspect the connections for symptoms that indicate overheating or
weakened insulation. Remove dust from the surfaces of the bus bars,
connections, supports, and enclosures. Wipe clean with a solvent such
as denatured alcohol. Vacuum the equipment. Do not use compressed
air to blow dust from the surfaces inside the controller.
3. Maintain the instruments, relays, and other devices according to the
specific instructions supplied. Inspect the devices and their contacts for
dust or dirt; wipe clean as necessary. The maintenance schedule for
individual devices such as meters and relays should be based upon
recommendations contained in the individual instruction manual for each
device. Coordinate the various schedules with the overall maintenance
program.
4. Inspect control wiring connections for tightness and damage.
5. Manually operate mechanical moving parts such as switch assemblies,
interlocks, and doors.
6. Make sure all bus areas are well ventilated. Inspect grille work and air
passages on controllers to make sure they are free from obstruction and
dirt accumulation.
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 9Maintenance
20032009 Schneider Electric All Rights Reserved 97
E
N
G
L
I
S
H
Figure 79: Typical Schematic for Full Voltage Non-Reversing (FVNR) Controllers
LDA Interlock
(Delete if no LDA) 120V from
CPT
Remote Start
Remove jumper after remote
stop pushbutton is installed.
Load Discharge Assembly
(Contacts shown in grounded position)
Blown Fuse Indication
(Contacts shown when fuses are not blown)
Blown Fuse Indication
Power Supply
(Delete if
not required)
Programmed N.C. Programmed N.C.
Legend
__FU Fuse LWG 120 Vac test plug
1CR Control relay MFR Sepam Multi-Function Relay
42M Main contactor RUN Red pilot light
IMAS Isolation means auxiliary switch X__ __ Control plug/disconnect
__TA__ __ Terminal block START Start pushbutton
HTR Heater STOP Stop pushbutton
OFF Green pilot light
NOTE: This applies to 200, 400, and 450 A
contactors only. A contactor drop-out time of
30 ms is shown. A contactor drop-out time of
300 ms may be achieved by shorting contactor
terminals 3 and 4 and relocating the 1CR
contact in series with terminal 1 of the
contactor.
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 9Maintenance 07/2009
20032009 Schneider Electric All Rights Reserved 98
Figure 80: Typical Schematic for Full Voltage Non-Reversing (FVNR), Latched Controllers
Load Discharge Assembly
(Contacts shown in grounded position)
Blown Fuse Indication
(Contacts shown when fuses are not blown)
Blown Fuse Indication
(Contacts shown when fuses are not blown)
120V from CPT
LDA Interlock
(Delete if no LDA)
Remote
Open
Power Supply
Blown Fuse Indication
(Delete if not required)
Blown Fuse Indication
(Delete if not required)
Programmed
N.C.
Programmed N.O.
Trip On
Remote Close
Mechanically Latched
Legend
__FU Fuse MFR Sepam Multi-Function Relay
1CR Control relay RUN Red pilot light
42M Main contactor X__ __ Control plug/disconnect
IMAS Isolation means auxiliary switch START Start pushbutton
__TA__ __ Terminal block STOP Stop pushbutton
HTR Heater TC Contactor Trip Coil
OFF Green pilot light CTU Capacitor Trip Unit
LWG 120 Vac test plug
NOTE: The multifunction relay's
opening/tripping contact has an opening
delay programmed by customer (based on
coordination with power fuses).
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 9Maintenance
20032009 Schneider Electric All Rights Reserved 99
E
N
G
L
I
S
H
Figure 81: Typical Schematic for Full Voltage Reversing (FVR) Motor Controllers
LDA Interlock
(Delete if no LDA)
Remote Fwd
Remove jumper after remote
stop pushbutton is installed.
Load Discharge Assembly
(Contacts shown in grounded position)
Blown Fuse Indication
(Contacts shown when fuses are not blown)
Blown Fuse Indication
(Delete if not required)
Power Supply
Programmed N.C. Programmed
N.C.
Programmed
N.C.
Remote Rev
Heater
Inlet
Legend
__FU Fuse LWG 120 Vac test plug
__CR Control relay MFR Sepam multi-function relay
42F Forward contactor X____ Control plug
42R Reverse contactor FWD Red pilot light
IMAS Isolation means auxiliary switch FWD Forward pushbutton
__TA__ Terminal block STOP Stop pushbutton
HTR Heater REV Reverse pushbutton
OFF Green pilot light REV Red pilot light
NOTE: This applies to 200, 400, and 450 A
contactors only. A contactor drop-out time of
30 ms is shown. A contactor drop-out time of
300 ms may be achieved by shorting contactor
terminals 3 and 4 and relocating the FCR and
RCR contacts in series with terminal 1 of the
contactor.
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 9Maintenance 07/2009
20032009 Schneider Electric All Rights Reserved 100
Figure 82: Typical Schematic for 2-Speed, 1-Winding (2S1W) Controller
Legend
42SHT Short contactor OFF Green pilot light
42SLW Slow contactor LWG 120 Vac test plug
42FST Fast contactor MFR Sepam multi-function relay
11 Multifunction relay RUN SLOW Red pilot light
__FU Fuse FAST RUN Red pilot light
__CR Control relay SLOW Slow start pushbutton
IMAS Isolation means auxiliary switch FAST Fast start pushbutton
__TA__ Terminal block STOP Stop pushbutton
HTR Heater
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 9Maintenance
20032009 Schneider Electric All Rights Reserved 101
E
N
G
L
I
S
H
Figure 83: Typical Schematic for 2-Speed, 1-Winding (2S2W) Controller
Legend
42FST Fast contactor OFF Green pilot light
42SLW Slow contactor LWG 120 Vac test plug
11 Multifunction relay MFR Sepam multi-function relay
__FU Fuse RUN SLOW Red pilot light
__CR Control relay FAST RUN Red pilot light
IMAS Isolation means auxiliary switch SLOW Slow start pushbutton
__TA__ Terminal block FAST Fast start pushbutton
HTR Heater STOP Stop pushbutton
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 9Maintenance 07/2009
20032009 Schneider Electric All Rights Reserved 102
Figure 84: Typical Schematic for Non-Reversing Reduced Voltage Autotransformer Starter
A B
LDA Interlock
(Delete if no LDA)
R/S Section HTR-2
R/S Section HTR-1
Main Section HTR-1
120V from CPT
Continued on next page
Legend
CTR
Current Transition Relay energizes on overcurrent,
de-energizes on undercurrent. Factory set as follows:
Time Delay =0, Pickup/Dropout =100%
Customer set as follows: Pickup/Dropout per actual condition
__TA__ __ Terminal block
MR
Timing relay, set for 0.5 sec., allows starting with CTR
de-energized.
HTR Heater
ISR
Incomplete sequence timer, set for normal acceleration time
plus 2 seconds.
OFF Green pilot light
42R Run contactor LWG 120 Vac test plug
42M Main contactor MFR Sepam Multi-Function Relay
42S Start contactor RUN Red pilot light
__FU Fuse X__ __ Control plug/disconnect
1CR Control relay START Start pushbutton
42M Main contactor MI Mechanically interlocked
IMAS Isolation means auxiliary switch
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 9Maintenance
20032009 Schneider Electric All Rights Reserved 103
E
N
G
L
I
S
H
A B
Remote
Start
OPC Start
Programmed N.C.
Programmed N.C.
Blown Fuse Indication
(Delete if not required)
Power Supply
Load Discharge Assembly
(Contacts shown in grounded position)
Blown Fuse Indication
(Contacts shown when fuses are not blown)
Continued from previous page
Legend
CTR
Current Transition Relay energizes on overcurrent,
de-energizes on undercurrent. Factory set as follows:
Time Delay =0, Pickup/Dropout =100%
Customer set as follows: Pickup/Dropout per actual condition
__TA__ __ Terminal block
MR
Timing relay, set for 0.5 sec., allows starting with CTR
de-energized.
HTR Heater
ISR
Incomplete sequence timer, set for normal acceleration time
plus 2 seconds.
OFF Green pilot light
42R Run contactor LWG 120 Vac test plug
42M Main contactor MFR Sepam Multi-Function Relay
42S Start contactor RUN Red pilot light
__FU Fuse X__ __ Control plug/disconnect
1CR Control relay START Start pushbutton
42M Main contactor MI Mechanically interlocked
IMAS Isolation means auxiliary switch
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 9Maintenance 07/2009
20032009 Schneider Electric All Rights Reserved 104
Figure 85: Typical Schematic for Reduced Voltage Soft Start
LDA Interlock
(Delete if no LDA)
120V
from
CPT
Soft Start
Terminal Control Board
Soft Start
Ground Fault Board
Main Section HTR
only
Bypass Section HTR
Legend
__FU Fuse OFF Green pilot light
BX Bypass contactor control relay LWG 120 Vac test plug
42M Main contactor TCB Terminal control board
IMAS Isolation means auxiliary switch RUN Red pilot light
__TA__ __ Terminal block X__ __ Control plug/disconnect
MX Main contactor control relay START Start pushbutton
HTR Heater STOP Stop pushbutton
Continued on next page
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 9Maintenance
20032009 Schneider Electric All Rights Reserved 105
E
N
G
L
I
S
H
Shutdown for Blown
Fuse Indicators and/or
Disconnect Interlock Contacts
(N.C. Contacts)
When FU1 is not used Remove FU1
Contact and Add Jumper
Closed Auxiliary
Contact Bypass Contactor
Emergency Bypass
Load Discharge Assembly
(Contacts Shown in Grounded Position)
Continued from previous page
Legend
__FU Fuse OFF Green pilot light
BX Bypass contactor control relay LWG 120 Vac test plug
42M Main contactor TCB Terminal control board
IMAS Isolation means auxiliary switch RUN Red pilot light
__TA__ __ Terminal block X__ __ Control plug/disconnect
MX Main contactor control relay START Start pushbutton
HTR Heater STOP Stop pushbutton
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 9Maintenance 07/2009
20032009 Schneider Electric All Rights Reserved 106
Corrective Maintenance
Medium Voltage Fuses
Always follow the steps listed below before accessing the fuse compartment
to replace or perform maintenance on the fuses.
1. Turn off all power supplying this equipment before working on or inside.
Always use a properly rated voltage sensing device to confirm that
power is off. Wear appropriate personal protective equipment when
removing or installing fuses from the fuseholder assemblies.
2. To determine if a fuse has blown, check the optional blown fuse
indicator.
3. Move the IM to the grounded position. See Figure 64 on page 79. If
equipped with an LDA, it must also be grounded.
4. Follow the Lock OutTag Out procedures to all upstream or
downstream sources that could energize the primary fuses or control
power to prevent inadvertent closure or energization.
5. Open the medium voltage door.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See NFPA 70E.
Turn off all power before working on or inside equipment.
Use a properly rated voltage sensing device to confirm that the power is off.
Before performing visual inspections, tests, or maintenance on the
equipment, disconnect all sources of electric power. Assume that all
circuits are live until they have been completely de-energized, tested,
grounded, and tagged. Pay particular attention to the design of the power
system. Consider all sources of power, including the possibility of
backfeeding.
Handle this equipment carefully and install, operate, and maintain it
correctly in order for it to function properly. Neglecting fundamental
installation and maintenance requirements may lead to personal injury,
as well as damage to electrical equipment or other property.
Do not make any modifications to the equipment or operate the system
with the interlocks removed. Contact your local field sales representative
for additional instruction if the equipment does not function as described
in this manual.
Carefully inspect your work area and remove any tools and objects left
inside the equipment.
Replace all devices, doors, and covers before turning on power to this
equipment.
Failure to follow these instructions will result in death or serious
injury.
CAUTION
HAZARD OF EQUIPMENT DAMAGE
Do not substitute any other fuse.
Failure to follow this instruction can result in equipment damage.
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 9Maintenance
20032009 Schneider Electric All Rights Reserved 107
E
N
G
L
I
S
H
6. Use a properly rated voltage sensing device to test and verify that the
power is off.
7. Inspect the fuse trigger, a trigger button on top of the fuse that pops up
when the fuse blows.
The power fuses have a top-mounted trigger (striker pin) that pops up
when the fuse element melts (see Figure 86). This can activate an
optional contact for remote indication.
8. To remove or install fuses, follow the procedures as described in
Removing Fuses on page 107 and Installing Fuses on page 108.
9. Close the medium voltage door.
10. Open the LDA first (if so equipped). Close the isolation means to
re-energize the circuit. See Figure 65 on page 80.
Removing Fuses
Figure 86: Striker Pin
To avoid nuisance tripping, always replace all fuses, even if
only one has blown. When one fuse blows, the others have
been exposed to over-currents and are also damaged.
Striker pin
CAUTION
HAZARD OF PERSONAL INJURY OR EQUIPMENT DAMAGE
The body of a fuse that has blown or carried load current can be
EXTREMELY HOT and will burn unprotected hands.
Never try to insert or remove both ends of the fuse at once. The
fuse body can be made of FRAGILE PORCELAIN (glass-like) and can
shatter if handled incorrectly (see Figure 87 on page 108 and Figure 89
on page 109).
Always remove the lower end first.
Always install the upper end of the fuse first; then install the lower end.
Always push on the ferrule being inserted (see Figure 89 on page 109).
Failure to follow these instructions can result in personal injury and
equipment damage.
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 9Maintenance 07/2009
20032009 Schneider Electric All Rights Reserved 108
To ease fuse removal, rotate the fuse and lubricate the fuse clips with
Mobil

28 red grease.
1. Always use a properly rated voltage sensing device to confirm that
power is off. Always wear personal protective equipment appropriate for
the hazard when handling the fuses.
2. Grasp the fuse by the lower end. While gently pulling the fuse, rotate the
fuse body slightly to help ease the fuse ferrule out of the lower
fuseholder. See Figure 87.
3. After the lower end of the fuse is free of its fuseholder, pull the fuse
straight down to remove it from the upper fuseholder.
Installing Fuses To ease fuse installation, lubricate the fuse clips with Mobil 28 red grease.
1. Always use a properly rated voltage sensing device to confirm that
power is off. Always wear personal protective equipment appropriate for
the hazard when handling the fuses.
2. Grasp the fuse by the upper end.
3. Insert the fuse ferrule into the upper fuseholder.
Figure 87: Removing Fuses
To avoid nuisance tripping, always replace all fuses, even if only
one has blown.
The striker pin assembly must always point upward. The fuse
characteristics and striker pin directions are printed on the
fuse label. Always turn the fuse so that the label is in the front
and the arrow points upward.
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 9Maintenance
20032009 Schneider Electric All Rights Reserved 109
E
N
G
L
I
S
H
4. Insert the lower end of the fuse into the bottom fuseholder. Gently push
while rotating the fuse body to help ease the fuse ferrule into the
fuseholder. See Figure 89.
NOTE: Never insert both ends at once.
Optional Fuse Tool This fuse tool is an ergonomic aid for inserting and extracting fuses in
de-energized Motorpact motor controllers. The fuse tool does not protect
the operator in any way from contacting live parts.
Figure 88: Fuse Characteristics and Striker Pin Directions
Figure 89: Installing Fuses
Striker pin (used in indicating
option)
Ferrule
Fuse body
Fuse label
To ease installation,
lubricate fuse clips with
Mobil 28 red grease.
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 9Maintenance 07/2009
20032009 Schneider Electric All Rights Reserved 110
Installing Rear and Middle Fuses The process is the same for installing fuses in the rear and middle
fuseholders. Begin by installing the rear fuses.
1. Align the fuse tool so that the hook and the pusher are toward the handle
end of the tool.
Figure 90: Optional Fuse Tool
The fuse tool has limited application for 720 A controllers. It is
not designed to remove or install the rightmost fuse.
The photos on these pages are factory demonstrations.
WARNING
HAZARD OF PERSONAL INJURY
Always wear gloves when working with fuses. The fuses could be hot and
will burn unprotected hands.
Failure to follow this instruction can result in personal injury.
Hook
Handle
Pusher
Lifting rod
Hinge
Figure 91: Aligning Fuse Tool
Hook
Pusher
Handle
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 9Maintenance
20032009 Schneider Electric All Rights Reserved 111
E
N
G
L
I
S
H
2. Insert the hinge in the narrow vertical space in front of the fuseholder,
between the holder and the fuse tray. See Figure 92. In some cases, this
may be a tight fit. The handle should be horizontal and extend towards
the door.
3. Bring the fuse into the enclosure. With the upper end of the fuse behind the
upper fuse holder, bring the lower end of the fuse to rest on the lifting rod.
4. Visually align the upper end of the fuse with the upper clip and raise the
tool handle to push the fuse into the upper clip. Verify that the fuse is
fully inserted into the upper clip.
Figure 92: Inserting Fuse Tool
.
Figure 93: Bringing Fuse Into Enclosure
Hinge
Handle
Lifting
rod
Fuse
holder
Fuse tray
Upper
end of
fuse
Lower
end of
fuse
Upper
fuse
holder Fuse
clip
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 9Maintenance 07/2009
20032009 Schneider Electric All Rights Reserved 112
5. Lower the handle. If the fuse was fully inserted at the top, the lower end
will naturally swing into place against the opening of the lower fuse clip.
6. Rotate the pusher into position toward the hinge.
Figure 94: Inserting Fuse Into Upper Clip
Figure 95: Swinging Lower End of Fuse Into Place
Upper fuse clip
Handle
Lower
fuse clip
Lower end
of fuse
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 9Maintenance
20032009 Schneider Electric All Rights Reserved 113
E
N
G
L
I
S
H
7. Raise the handle again to push the fuse into the lower fuse clip.
Figure 96: Rotating Pusher
Figure 97: Pushing Fuse Into Lower Clip
Pusher
Hinge
Handle
Fuse
Lower
fuse clip
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 9Maintenance 07/2009
20032009 Schneider Electric All Rights Reserved 114
Installing Front Fuses
1. Align the fuse tool so that the hook is toward the handle end and the
pusher is in the opposite position, toward the hinge.
2. Insert the hinge in the narrow vertical space in front of the fuseholder,
between the holder and the fuse tray. In some cases, this may be a tight
fit. The tool should rest on the fuse tray and the handle should hang
down.
3. Bring the fuse into the enclosure. With the upper end of the fuse behind
the upper fuseholder, bring the lower end of the fuse to rest on the
V-notch in the pusher. The bulk of the fuse should be on the hinge side
of the pusher.
Figure 98: Inserting Fuse Tool
.
Figure 99: Bringing Fuse Into Enclosure
Pusher
Handle
Fuse tray
Fuse end
resting on
V-notch
Pusher
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 9Maintenance
20032009 Schneider Electric All Rights Reserved 115
E
N
G
L
I
S
H
4. Visually align the upper end of the fuse with the upper clip, and raise the
tool handle to push the fuse into the upper clip. Verify that the fuse is
fully inserted into the upper clip.
5. Lower the handle. If the fuse was fully inserted at the top, the lower end
will naturally swing into place against the opening of the lower fuse clip.
6. Raise the handle again to push the fuse into the lower fuse clip.
Figure 100: Swinging Lower End of Fuse Into Place
Figure 101: Pushing Fuse Into Lower Clip
Lower
fuse clip
Fuse tool
Fuse
Handle
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 9Maintenance 07/2009
20032009 Schneider Electric All Rights Reserved 116
Removing Fuses This process is the same for all fuses.
1. Align the fuse tool so that the hook is toward the hinge end of the tool
and the pusher rests in the opposite direction, toward the handle.
2. Insert the hinge in the narrow vertical space in front of the fuseholder,
between the holder and the red base material. In some cases, this may
be a tight fit.
3. Support the handle in one hand and place the hook around the back of
the fuse as low as possible. See Figure 102.
4. Lower the handle to extract the fuse from the lower fuse clip.
5. Manually pull the fuse from the upper fuse clip.
Figure 102: Removing Fuses with the Fuse Tool
Hook
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 9Maintenance
20032009 Schneider Electric All Rights Reserved 117
E
N
G
L
I
S
H
Removing and Installing Voltage
Transformer (VT) Primary and Current
Power Transformer (CPT) Fuses
For steps 14, see Figure 64 on page 79. If supplied with an LDA, see
Figure 66 on page 81.
1. Press the STOP/OFF or OPEN button on the operator panel.
2. Move the IM to the grounded position.
3. CLOSE/Ground the LDA, if supplied.
4. Open the medium voltage compartment door.
To Disassemble Fuse Tube For steps 12, see Figure 103 on page 117.
1. Push the fuse tube end (A) and rotate
counterclockwise.
2. Loosen the screw holding the fuse retainer plate (B). Remove the fuse (C).
To Assemble Fuse Tube For steps 13, see Figure 103 on page 117.
1. Replace the fuse (C).
2. Realign the fuse retainer plate (B) and torque the screw to 8.85 in-lb
(1 Nm).
3. Align the tube (A) in housing slot, push and rotate clockwise.
Figure 103: Replacing VT and CPT Fuses
A. Fuse tube end
B. Fuse retainer plate screw
C. Fuse

B
C
A
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 10Troubleshooting 07/2009
20032009 Schneider Electric All Rights Reserved 118
Section 10Troubleshooting
DANGER
HAZARD OF ELECTRIC SHOCK, BURN, OR EXPLOSION
This equipment must be installed and serviced only by qualified personnel.
Qualified persons performing diagnostics or troubleshooting that require electrical conductors to be energized must comply
with NFPA 70 E Standard for Electrical Safety Requirements for Employee Workplace and OSHA Standards 29 CFR
Part 1910 Subpart S Electrical.
Failure to follow these instructions will result in death or serious injury.
Table 15: General Troubleshooting
Condition Action
Cannot open the medium voltage door latch
Check that the IM is fully OPEN/Grounded.
Check that the IM access port is closed.
Cannot open the medium voltage door after
unlatching handle
Check that the optional LDA is fully in grounded position (automatic latch will retract).
Cannot fully close the medium voltage door Check that the optional LDA is fully in grounded position (automatic latch will retract).
Cannot close the IM (access port blocked)
Check that the MV door is closed and latched (handle vertical).
Check that optional LDA is fully open (not grounded), LDA port is closed, and shuttle
handle is in its full left hand position.
Check that the contactor is open (optional mechanical latch released).
Check that the optional IM keylock is unlocked.
Cannot open the IM (access port blocked)
Check that the contactor is open (optional mechanical latch released).
Check that the optional IM keylock is unlocked.
Cannot open ungrounded optional LDA (access port
blocked)
Check that optional LDA keylock is unlocked.
Cannot close/ground optional LDA (access port
blocked)
Check that the IM is fully OPEN/Grounded, IM port is closed, and shuttle handle is in
its full right hand position.
Check that the optional LDA keylock is unlocked.
Live Line Indicator (LLI) (Optional) will not illuminate
Test for voltage using a properly rated voltage sensing device on two of the test ports on
the LLIs.
Verify that the incoming cables are live.
Table 16: Mechanism Troubleshooting
Condition Action
Cannot close the contactor electrically
Verify that the isolation means is closed.
Verify that the isolation means access port is closed.
Check for loose terminal connections.
Check for loose plug connector in low voltage compartment.
Check the coil circuit.
Check control fuses.
Check the electrical interlocks (see equipment drawings).
Check linkage to the contactor, and contactor interlock arm assembly on the contactor
for binding or hanging.
Cannot open a mechanically latched contactor
electrically
Check for loose terminal connections.
Check for loose plug connector in low voltage compartment.
Check the coil circuit.
Check control fuses.
Check the electrical interlocks (see equipment drawings).
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 11Replacement Parts
20032009 Schneider Electric All Rights Reserved 119
E
N
G
L
I
S
H
Section 11Replacement Parts
When ordering renewal or spare parts, include as much information as
possible. In many cases, the part number of a new part can be obtained by
identifying the old part. Always include the description of the part. Specify
the rating, vertical section, and factory order number of the equipment in
which the part is used.
Table 17: Replacement Parts
Description Part Number
Auxiliary switch (blown fuse) 25713203
Auxiliary switch-contacts (isolation means) S48198
Control plugcontactor (female) MIP30F00830
Control plugcontactor (male) MIP30M0000
Control plug12 pin (female) 1925799
Control plug12 pin (male) 1925964
Control plug7 pin (female) 1925744
Control plug7 pin (male) 1925919
Control plug7 pin assembly frame 1852079
Control plug12 pin assembly frame 1852121
Fuse removal tool 46033-250-51
Handle, operator 3728693
Heater, 500 W 46028-126-03
Heater, 1200 W 46028-127-01
Inlet, test power 5278.OEN
Mobil

28 red grease 1615-100950


Other electrical components Refer to specific order bill of materials
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 12Type 3R Non-Walk-In Switchgear 07/2009
20032009 Schneider Electric All Rights Reserved 120
Section 12Type 3R Non-Walk-In Switchgear
Introduction This section contains instructions for the proper receiving, handling, and
installation (including site preparation) of Motorpact

Type 3R non-walk-in
switchgear manufactured by Schneider Electric.
The outdoor non-walk-in enclosure is built around the standard Motorpact
indoor equipment.
NOTE: For detailed instructions regarding the operation and maintenance
of indoor equipment, please refer to the preceding sections of this bulletin.
Figure 79: Type 3R Non-Walk-in Enclosure
Roof
Roof caps
Front View Rear View
Front air
filter
Front
door
Front door
wind latch
Base
Mounting
lug
Padlockable
handle
Rear air
filter
Handle
Rear
cover
Mounting/
lifting lugs
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 12Type 3R Non-Walk-In Switchgear
20032009 Schneider Electric All Rights Reserved 121
E
N
G
L
I
S
H
Safety Precautions
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Only qualified personnel familiar with medium voltage equipment are to
perform work described in this set of instructions. Workers must
understand the hazards involved in working with or near medium
voltage circuits.
Perform such work only after reading and understanding all of the
instructions contained in this bulletin.
Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See NFPA 70E.
Turn off all power before working on or inside equipment.
Use a properly rated voltage sensing device to confirm that the power
is off.
Before performing visual inspections, tests, or maintenance on the
equipment, disconnect all sources of electric power. Assume that all
circuits are live until they have been completely de-energized, tested,
grounded, and tagged. Pay particular attention to the design of the
power system. Consider all sources of power, including the possibility
of backfeeding.
Handle this equipment carefully and install, operate, and maintain it
correctly in order for it to function properly. Neglecting fundamental
installation and maintenance requirements may lead to personal injury,
as well as damage to electrical equipment or other property.
Do not make any modifications to the equipment or operate the system
with the interlocks removed. Contact your local field sales
representative for additional instruction if the equipment does not
function as described in this manual.
Carefully inspect your work area and remove any tools and objects left
inside the equipment.
Replace all devices, doors, and covers before turning on power to
this equipment.
All instructions in this manual are written with the assumption that the
customer has taken these measures before performing maintenance
or testing.
Failure to follow these instructions will result in death or serious injury.
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 12Type 3R Non-Walk-In Switchgear 07/2009
20032009 Schneider Electric All Rights Reserved 122
Receiving, Handling, and Storage Motorpact Type 3R enclosures are carefully inspected and packaged at
the assembly plant. The switchgear is shipped on skids with protective
wrapping to prevent damage during normal transit.
Receiving Check the packaging list against the equipment received to ensure the order
and shipments are complete. Make claims for shortages or other errors in
writing within 30 days after receipt of shipment. Failure to do so constitutes
unqualified acceptance and a waiver of all such claims by the purchaser.
Inspect the equipment for damage. If you find suspected damage,
immediately file a claim with the carrier and notify Schneider Electric.
Identification Check indoor identification nameplate(s) as shown in Figure 8 on page 23.
Handling Equipment is shipped in an upright position on a pallet and wrapped in plastic.
Lifting Provisions Review the shipping documentation to verify the actual weight of the
Motorpact enclosure shipping section. Ensure that your lifting equipment is
adequate for the weight. When an overhead crane is not available, rollers,
pipes, or a forklift can be used.
CAUTION
HAZARD OF PERSONAL INJURY OR EQUIPMENT DAMAGE
Do not remove the skids until the shipping sections are at the final
location.
Always use the skids to move shipping sections to prevent equipment
distortion.
Failure to follow these instructions can result in injury or equipment
damage.
WARNING
LIFTING HAZARD
Possible unbalanced load.
Use the four outermost corner lifting angles for slingpoints.
Keep area below equipment clear of any personnel or property
Before lifting enclosure:
Inspect lifting straps for damage.
Do not pass cables or chains through holes in lifting angles.
Use only load-rated cables or chains with safety hooks or shackles.
Use a rated spreader bar and side protection.
Failure to follow these instructions can result in death, serious injury
or equipment damage.
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 12Type 3R Non-Walk-In Switchgear
20032009 Schneider Electric All Rights Reserved 123
E
N
G
L
I
S
H

Using a Forklift
This equipment is shipped up to a maximum of three vertical sections
88.50 in. (2250 mm) wide.
Figure 80: Lifting Provisions
Spreader bar
Lifting lugs
(both sides)
WARNING
UNSTABLE LOAD
If lifting the motor controller by forklift, stabilize the shipping section with a
safety strap to reduce the possibility of tipping.
Failure to follow this instruction can result in death or serious injury.
Figure 81: Handling Using a Forklift
Safety strap
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 12Type 3R Non-Walk-In Switchgear 07/2009
20032009 Schneider Electric All Rights Reserved 124
Storage When storing this equipment, keep it in a clean, dry place that is free from
corrosive elements and mechanical abuse. Energize the heaters inside the
equipment, or add heat from a separate source, such as a light bulb or
blower. Use a minimum of 125 watts of heat per vertical section to keep the
equipment dry during storage.
Cover the equipment with a tarpaulin when necessary to protect it from
contaminants and moisture.
Monitor the equipment closely in areas with high humidity. If necessary, use
additional heat to keep the equipment dry. Contact the factory if the internal
heaters do not adequately prevent condensation.
Installation
Preparing the Site
Foundation Requirements The standard Motorpact Type 3R non-walk-in enclosure is designed for
installation on a concrete pad. Refer to the factory order drawings for any
additional mounting details which may be required on specific orders.
The concrete pad must be flat and level to within 1/8 in. (3.2 mm) per square
yard to prevent distortion of the equipment.
The recommended available space for the concrete pad in front of the
equipment is 60 in. (1525 mm). This will allow adequate work space for
installation or removal of contactors. The minimum recommended space on
the rear and sides of the equipment is 12 in. (305 mm) to allow space for the
anchor bolts.
Allow working space clearance per National Electrical Code

(NEC

) article
110-34, Work Space and Guarding. Minimum clearances for positioning
equipment must meet all local and national requirements.
Conduit Locations Figures 82-84 illustrate the typical floor plan for each of the Motorpact
Type 3R non-walk-in enclosures. Compare the site plan and specifications
with the motor controller assembly drawings to be sure there are no
discrepancies.
Conduits should be stubbed a maximum of 1 in. (25 mm) above floor steel,
or 7 in. (178 mm) above the concrete pad.
Equipment Ground An equipment ground is required on the first or last bay in a lineup. A cable
with a minimum length of 6 ft. (1.8 m) should be supplied by the customer in
the same floor cutout used for power cables. Refer to the motor controller
drawings for ground lug locations.
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 12Type 3R Non-Walk-In Switchgear
20032009 Schneider Electric All Rights Reserved 125
E
N
G
L
I
S
H
Figure 82: 29.5-inch Floor PlanControllers
Figure 83: 29.5-inch Floor PlanIncoming and Auxiliary
450 A Controller
Plan View
29.6 (751.8)
(cubicle width)
12.0 (304.8) 12.0 (304.8)
1.4 (34.9)
(typical)
14.3 (362.0)
25.0 (635.0)
6.0 (152.4)
11.9 (302.8)
7.0 (177.8)
2.0 (50.8)
6.0 (152.4)
4.7 (119.0)
2.0 (50.8)
7.0 (177.8)
11.9 (302.8)
14.3 (362.0)
12.0 (304.8)
5.2 (133.1)
720 A Controller
Plan View
29.6 (751.8)
(cubicle width)
C C
26.0 (660.4)
3.0 (76.2)
5.5 (139.7)
11.0 (279.4)
Incoming Cubicle
Plan View
29.6 (751.8)
(cubicle width)
14.3 (362.0)
11.9 (302.8)
7.0 (177.8)
2.0 (50.8) 2.0 (50.8)
7.0 (177.8)
11.9 (302.8)
14.3 (362.0)
Auxiliary Cubicle
Plan View
29.6 (751.8)
(cubicle width)
C C
Conduit Area Definitions
Medium Voltage Incoming Conduit Entrance (controller line side)
Medium Voltage Outgoing Conduit Entrance (controller load side)
Low Voltage Conduit Entrance
Dimensions = Inches (mm)
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 12Type 3R Non-Walk-In Switchgear 07/2009
20032009 Schneider Electric All Rights Reserved 126
Figure 84: 73.75-inch/88.5-inch Floor PlanRVSS/RVAT
6.0 (152.4)
12.0 (304.8)
29.5 (749.4)
59.2 (1503.7)
(cubicle width)
16.1 (409.6)
2.8 (71.9)
RVSS only
E
F
30.94 (785.88)
25.0 (635.0
Conduit Area
29.50 (750) RVAT/RVSS
14.3 (362.0)
7.0 (177.8)
2.0 (50.8)
C C
7.0 (177.8)
2.0 (50.8)
25.0 (635.0
14.3 (362.0)
6.0 (152.4)
12.0 (304.8)
Conduit Area
44.25 (1125) 59.00 (1500) RVAT
16.1 (409.6)
7.0 (177.8)
2.0 (50.8)
E F
44.25-inch (1125 mm) RVAT cubicle 23.5 (596.9) 73.9 (1876)
59-inch (1500 mm) RVAT cubicle 30.9 (784.9) 88.6 (2250.4)
Conduit Area Definitions
Medium Voltage Outgoing Conduit Entrance (controller load side)
Low Voltage Conduit Entrance
Dimensions = Inches (mm)
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 12Type 3R Non-Walk-In Switchgear
20032009 Schneider Electric All Rights Reserved 127
E
N
G
L
I
S
H
Joining and Anchoring Shipping
Sections
Follow the steps below and refer to Figures 8589 for joining and anchoring
shipping sections.
1. Review the assembly drawings to ensure the shipping sections are
assembled in the correct order
NOTE: For multiple bay lineups, start with the center shipping section
and work toward the end.
2. Remove the two conduit cover plates from inside each switchgear
enclosure (see Figure 85).
3. Inspect the factory-installed gasket attached to the side of each shipping
section. See Figure 86. Replace any gaskets that are damaged.
4. Position the initial shipping section over the stubbed conduit on the
concrete pad.
5. Level the shipping section and correctly position the mounting lugs. See
Figure 85. Verify typical mounting dimensions in the concrete pad as
shown in Figures 87 and 88 on page 128.
6. If this is the first shipping section in a lineup, anchor the mounting lugs to
the concrete pad using customer-supplied anchoring hardware.
Additional sections will be anchored after they are joined to the lineup.
(See step 9.)
NOTE: For seismic rated equipment, refer to Seismic Certification of
Motorpact Medium Voltage (MV) Motor Controllers on page 36.
7. As necessary, remove mounting lugs from the side of the section to
allow additional shipping sections to be connected.
CAUTION
HAZARD OF EQUIPMENT DAMAGE
Install the shipping section bus connectors
only after the shipping sections are securely
anchored in place.
Failure to follow this instruction can result
in equipment damage.
Figure 85: Conduit Plates Location
Low voltage
conduit plate
Medium voltage
conduit plate
Mounting lug
NOTE: Anchoring hardware
to be supplied by customer.
Figure 86: Factory-Installed Gasket
Gasket
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 12Type 3R Non-Walk-In Switchgear 07/2009
20032009 Schneider Electric All Rights Reserved 128
Figure 87: FVNR/FVR Cubicle Anchoring Dimensions
Figure 88: RVAT/RVSS Cubicle Anchoring Dimensions
32.0 (812.8)
41.0 (1041.4)
52.0 (1321.1)
5.5 (139.9)
5.5 (139.8)
29.6 (751.8)
1.0 (25.4)
Bolt down (4 places)
(end cubicle only)
Shipping split lug
1.0 (25.4)
Bolt down (2 places)
32.0 (812.8)
Plan View
Shipping Split
Plan View
Single Bay
1.0 (25.4)
Bolt down (4 places)
(end cubicle only)
41.0 (1041.4)
34.3 (872.1)
Dimensions = Inches (mm)
Plan View
29.50 (750) RVAT/RVSS
Plan View
44.25 (1125) and 59.00 (1500) RVAT
64.2 (1630.7)
59.2 (1502.5)
(cubicle width)
2.0 (50.8)
Ref.
2.5 (63.5)
Ref.
41.0 (1041.4) 52.0 (1321.1)
19.0
(482.6)
D
C
B
(cubicle width)
41.0 (1041.4)
5.5 (139.6)
5.5 (140.6)
A
1.0 (25.4)
Bolt down (4 places)
(end cubicle only)
1.0 (25.4)
Bolt down (4 places)
1.0 (25.4)
Bolt down (4 places)
(end cubicle only)
A B C D
44.25-inch (1125 mm) RVAT cubicle 76.9 (2004) 73.9 (1876) 17.1 (434.3) 14.6 (370.8)
59-inch (1500 mm) RVAT cubicle 93.6 (2377) 88.6 (2250.4) 22.5 (571.5) 20.0 (508.0)
Dimensions = Inches (mm)
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 12Type 3R Non-Walk-In Switchgear
20032009 Schneider Electric All Rights Reserved 129
E
N
G
L
I
S
H
8. J oin shipping sections with factory-supplied M10 (10 mm) hardware.
See Figure 89. Torque hardware to 20 lb-ft (27.1 Nm).
9. Once a shipping section has been added to an existing lineup, anchor it
to the concrete pad using customer-supplied anchoring hardware.
10. To join and anchor another section, position it over the stubbed conduit
on the concrete pad and repeat steps 49.
11. Once all shipping sections have been joined and anchored, attach a roof
cap (supplied) to each location where two sections were joined. See
Figure 90. Fasten each roof cap with the M6 (6 mm) hardware provided,
and torque to 20 lb-ft (27.1 Nm).
12. See the indoor installation instructions in Section 6 for the following:
Seismic Certification of Motorpact Medium Voltage (MV) Motor
Controllers on page 36
Accessing the Bus Compartment on page 44
Through Bus Splice Connections on page 47
Ground Bus Splice Connections on page 49
Cable Terminations on page 49
Control Wiring Terminations and Routing on page 56
Figure 89: Lineup Alignment
Gasket
M10 (10 mm) hardware
(16 locations)
Figure 90: Attaching Roof Caps
M6 (6 mm)
hardware
(4 locations)
Roof
caps
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 12Type 3R Non-Walk-In Switchgear 07/2009
20032009 Schneider Electric All Rights Reserved 130
Connecting a Transition Throat If the switchgear will be connected to a transformer or other piece of
equipment, a factory-installed transition throat will be supplied.
Follow the steps below for connecting a transition throat.
1. Inspect the factory-installed gasket. See Figure 91. If the gasket is
damaged, replace it before joining equipment sections.
2. J oin the transition throat to the transformer cubicle or other equipment
with factory-supplied M10 (10 mm) hardware. See Figure 91. Torque to
20 lb-ft (27.1 Nm).
3. Apply supplied caulk, as required, for any visible cracks in the throat
enclosure.
CAUTION
HAZARD OF EQUIPMENT DAMAGE
Apply caulk to any roof and throat openings to prevent water ingress.
Failure to follow this instruction can result in equipment damage.
Figure 91: Transition Throat
Transition throat
M10 (10 mm) hardware
(16 locations)
Gasket
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 12Type 3R Non-Walk-In Switchgear
20032009 Schneider Electric All Rights Reserved 131
E
N
G
L
I
S
H
Operation, Inspection, and
Maintenance
Operation For operational information about Motorpact

motor controllers housed in an


outdoor non-walk in enclosure, refer to the section Features and Operation
on page 61.
Inspection and Maintenance
Inspection and maintenance for the non-walk-in enclosure should be
performed on the basis of environmental conditions and experience.
Abnormal operation or conditions may require immediate corrective action.
The inspection of indoor switchgear is outlined in detail in section 9 of this
bulletin. In addition, during regular maintenance intervals, perform the
following for outdoor enclosures:
Check for possible leaks in the front and in each cable compartment.
Inspect the air filters at the front and rear of each cubicle roof. Clean
every 6 months (sooner, if necessary) with mild soap and water. If any
air filters are damaged, contact your Schneider Electric representative
for replacement.
Check the thermostat or de-humidistat settings. Verify the space heaters
are operating and the equipment remains dry. Contact your Schneider
Electric representative if condensation is evident; an additional heater
package may be required.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
This equipment must be installed and serviced only by qualified
electrical personnel.
Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See NFPA 70E.
Turn off all power supplying this equipment before working on or inside.
Always use a properly rated voltage sensing device to confirm that the
power is off.
Inspection and maintenance should only be performed with the primary
source(s) of power disconnected and locked open. Be absolutely sure
there is no back-feeding through any circuit.
Replace all devices, doors, and covers before turning on power to
this equipment.
Failure to follow these instructions will result in death or serious injury.
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 12Type 3R Non-Walk-In Switchgear 07/2009
20032009 Schneider Electric All Rights Reserved 132
Outlines
Figure 92: 29.5-inch FVNR Sections
Figure 93: 59-inch RVSS and RVAT; 73.75-inch and 88.5-inch RVAT
Front View
(Single Bay)
36.8 (935.6) 49.5 (1259.8)
56.9 (1445.2)
4.3 (108.1)
Ref.
(door front)
7.9 (201.7)
Ref.
30.1 (764.2)
103.2 (2622.0)
101.3 (2571.8)
Center of
gravity
23.2 (590.7)
52.0 (1320.8)
13.8 (351.4)
Center of
gravity
Side View
Shipping split lug
29.6 (751.8)
Front View
(Lineup)
Dimensions = Inches (mm)
Front View
(59.0/1500 RVAT)
59.6 (1513.6) 74.3 (1887.9) 89.1 (2262.7)
66.2 (1680.3) 81.1 (2059.3)
59.2 (1503.7) 73.9 (1877.1) 88.7 (2253.4)
25.0 (635.0) 28.0 (711.2) 34.0 (863.6)
Front View
(44.25/1125 RVAT)
Front View
(29.50/750 RVAT/RVSS)
20032009 Schneider Electric All Rights Reserved 133
46032-700-06E Motorpact Medium Voltage Motor Controllers
07/2009 Section 13Glossary
E
N
G
L
I
S
H
Section 13Glossary
Arc Plenum
An air compartment or chamber to
which one or more ducts are connected
and which forms part of an air
distribution system.
Auxiliary Contact
A contact included in an auxiliary circuit
and mechanically operated by the
switching device.
Auxiliary Section
An additional enclosure section that
contains components not enclosed
within the main controller section.
Bus Bars
A conductor, or group of conductors,
that serve as a common connection for
two or more circuits.
Bus Compartment
The compartment in a medium voltage
controller that contains the main,
vertical, line, and load bus.
Capacitive Divider
A capacitor attached to the phase bus
bar that drops the voltage to a level that
can illuminate a neon light.
Contactor
A device for repeatedly establishing
and interrupting an electric power
circuit.
Controller
A device, or group of devices, which
serves to govern, in some
predetermined manner, the electrical
power delivered to the apparatus to
which it is connected.
Control Power Transformer (CPT)
A transformer that reduces medium
voltage to low voltage for control circuit
use.
Control Terminal Block
An insulating base equipped with
terminals for connecting control wiring.
Current Transformer (CT)
An instrument transformer intended to
have its primary winding connected in
series with the conductor carrying the
current to be measured or controlled.
Enclosure
A surrounding case designed to protect:
Personnel against injury due to
accidental contact with electrical or
moving mechanical parts of the
enclosed device(s).
Internal device(s) against specified
external conditions.
Full Voltage Starter
A starter which connects the line
voltage across the motor terminals in
one step.
Fuse, Medium Voltage
A fuse, intended for use in medium
voltage circuits, capable of interrupting
all currents from the rated maximum
interrupting current down to the rated
minimum current of that fuse.
Fuse Ferrule
A cylindrical fuse terminal at the end of
a cartridge fuse.
Fuseholder
An assembly of a fuse tube or tubes
together with parts necessary to enclose
the contacting element and provide
means of making contact with the
conducting element and the fuse clips.
The fuseholder does not include the
contacting element (fuse link or refill unit).
Insulator
A device intended to give flexible or
rigid support to electrical conductors or
equipment and to insulate these
conductors or equipment from ground
or from other conductors or equipment.
An insulator comprises one or more
insulating parts to which connecting
devices (metal fittings) are often
permanently attached.
Interlock
A device actuated by the operation of
some other device with which it is
directly associated, to govern
succeeding operations of the same or
allied devices. Interlocks are classified
into three main divisions: mechanical,
electrical, and key interlocks, based on
the type of interconnection between the
associated devices.
Isolation Means (IM)
A rotating, two-position device with
parallel blades, fixed contacts, and
hinge castings. The IM is connected to
the main power source in the closed
position and is connected to the
equipment ground in the second
position.
The IM is intended for isolating an
electric circuit from the source of power.
It is not required to have an interrupting
rating, and is intended to be operated
only after the circuit has been opened
by some other means.
E
N
G
L
I
S
H
Motorpact Medium Voltage Motor Controllers 46032-700-06E
Section 13Glossary 07/2009
20032009 Schneider Electric All Rights Reserved 134
Lifting Device
A mechanical means to aid in lifting
heavy objects.
Live Line Indicator (LLI)
An ac rated capacitor which is
connected in series with the neon
indicator between the phase and
ground lines. It advises the operator
that the connections are live.
Load Discharge Assembly (LDA)
A sliding two-position device (open or
grounded). It is designed to discharge
the cable capacitance to ground and is
capable of discharging up to 5 kA faults.
Low Power Current Transformer
(LPCT)
A device that transforms a medium
voltage circuit current into a
proportional low voltage signal.
Medium Voltage Compartment
A compartment containing one or more
medium voltage components.
Shipping Split
Sections of a motor control center
connected together in sizes capable of
being shipped.
Starter
The combination of all the switching
means necessary to start and stop a
motor in combination with suitable
overload protection. Starters may be
designated according to the method by
which the force for closing the main
contacts is provided.
Stress Cone
Pre-manufactured insulator or layers of
tape where the cable connects to the
bus bar.
Surge Arrester
A device that protects equipment from
electrical surges.
Voltage Transformer (VT)
An instrument transformer intended to
have its primary winding connected in
shunt with a power supply circuit, the
voltage of which is to be measured or
controlled.
Wiring Harness
Pre-manufactured wire
interconnections.
Electrical equipment should be installed, operated, serviced, and maintained only by qualified
personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of
the use of this material.
46032-700-06E 07/2009
Replaces 46032-700-06D 12/2008
20032009 Schneider Electric All Rights Reserved
Schneider Electric USA
330 Weakley Road
Smyrna, TN 37167 USA
1-888-SquareD
(1-888-778-2733)
www.schneider-electric.us
Motorpact Medium Voltage Motor Controllers
Instruction Bulletin
Square D

is a trademark or registered trademark of Schneider Electric. Other trademarks used


herein are the property of their respective owners.

Das könnte Ihnen auch gefallen