fibro13_en2
1. SCOPE
This standard specifies a method for the determination of both the first crack strength
fIf (Part I, clause 3.3.1) and the ductility indexes D0 and D1 (Part I, clause 3.3.3) of
test specimens of Steel Fibre-Reinforced Concrete (SFRC).
2. STANDARD REFERENCES
prEN 12350-1:1999.Testing fresh concrete Part1: Sampling
prEN 12390-1:1999.Testing hardened concrete- Part 1: Shape, dimensions and other
requirements for specimens and moulds
prEN 12390-2:1999.Testing hardened concrete: Part2: Making and curing
specimens for strength tests
3. PRINCIPLE
Prismatic test specimens with a central notch are loaded in a four point flexure; the
test shall be carried out at prescribed CMOD1 rate.
The first crack strength (fIf ) and the ductility indexes D0 and D1 are calculated on the
basis of load - CTODnet2 curve.
4. TEST SPECIMENS
The test specimens3 can be obtained either from basic concrete 4 and/or SFRC; they
can be cast or cut out.
The test specimens are not intended for aggregate with maximum nominal size of 32
mm.
4.1 Cast specimens
Concerning the making and curing of test specimens by casting of basic concrete
and/or SFRC, prEN 12390-2 shall apply. In addition the procedure of filling the
mould with SFRC must comply with the following items (Figure 1):
1. cast portion 1 in the centre of the mould;
2. cast portion (2) and making sure that portions (1) and (2) are properly covered;
1
11/08/01
fibro13_en2
3. the volume of portion (1) must be about twice that of portion (2).
The SFRC must be compacted on a vibrating table; compaction through internal
vibrator is not allowed.
the test can be carried out on condition that such lack of data concerning curing
and/or transport, i.e., any known deviation from the EN 12390-2, are recorded in the
test report.
4.4 Shape, dimensions and tolerances
The reference test specimens are square-base right prisms with nominal dimensions
150x150x600mm; test specimens with different dimensions can be used just for the
only purpose of having an indication, on condition that the following terms are met:
11/08/01
fibro13_en2
the specimen length (l) must be at least 3.5 times the height (h); anyway it cannot
be lower than 350 mm;
the shorter side of the specimen cross section must be at least 3.5 times the
maximum size of the aggregate.
The size tolerance of the test specimens shall comply with the prEN12390-1
specifications.
4.5 Notch
A notch shall be made in the central line of a test specimen face adjacent to the
trowelled face by using a diamond saw down to a depth a0 so that a0/h = 0.3 0.01.
The notch width must range from 3 to 5 mm. The notch end must be V-shaped (Part
I; Figure 1).
5. EQUIPMENT
5.1 Test equipment
With reference to the points below, the test equipment must comply with EN 123904:
force measure;
accuracy of the force indication;
frequency of calibration;
safety.
The test equipment must be provided with a proper device which allows to carry out
the tests under displacement control.
5.1.1 Device for load application
The load application device (Figure 2) shall consist of:
two upper rollers;
an articulated cross member able to equally divide the load applied by the testing
machine between the two upper rollers;
two lower supporting rollers.
11/08/01
fibro13_en2
1
1
h
3
h
h
l=3h
l3,5h
b(=h)
1
2
3
All rollers shall be manufactured from steel and shall have a circular cross-section
with a diameter of 20 mm to 40 mm; they shall be at least 10 mm longer than the
width of test specimen.
Each upper roller shall be free to rotate around its axis with a rotation ( 3) within
the plane perpendicular to the longitudinal axis of the specimen.
The distance between the lower rollers (l) shall be equal to 3h and in any case it
cannot be shorter than 300 mm. The distance between the two upper rollers shall be
equal to h. The upper rollers shall be equally spaced between the lower rollers, as
shown in Figure 1. Each roller shall be positioned to the indicated location (Figure 2)
with an accuracy of 1 mm.
5.2 Force gauge
The load shall be measured with a load cell; the load shall be shown by a digital
and/or analogic display, with the required accuracy (Table 1). The system shall allow
the read value to be recorded by a special device (clause 5.4) with the metrologic
tolerance given in Table 1.
11/08/01
fibro13_en2
Relative accuracy
Relative
Zero relative error Machine resolution 6
error
repeatability error
%5
(% of full scale) 5
%5
%5
1.0
0.2
0.5
1
Table 1. Metrologic tolerance allowed for load measurement
CMOD or CTOD
gauge
Gauge holders
d
d 10 mm
Figure 3. Example of full bridge resistive gauge for CMOD and CTOD measurement.
5.3.2 Gauges for the displacement measurement of the load application points
(optional)
The displacement of the load application points, if required, shall be measured by
means of a gauge having a measurement range 10 mm.
5.4 Recording system
The load and displacement values shall be measured by a suitable analogic or digital
data acquisition system. The data shall be recorded on a magnetic support
5
6
11/08/01
fibro13_en2
Taking into account the numeric computations required by the present standard, a
data acquisition system provided with an analogic/digital converter with resolution
12 bit is recommended. The indicated resolution must be guaranteed on an input
signal range equal to that of the amplified signal output of the load and displacement
gauges.
6. Procedure
The test specimens shall be checked before being tested and any anomaly be
recorded.
A
l = 3h
L 3.5 h
b (=h)
Section
A-A
a0
CTOD gauges
CMOD gauges
Figure 4. Layout for the application of the gauge-holders and the relevant CTOD and CMOD gauges.
11/08/01
fibro13_en2
Hinge
Displacement
gauge
Carriage
Sensing pin
Figure 5. Layout for the application of the gauge-holders and the relevant gauges
for the measurement of the displacement of the load application points
Main crack stands for the trace of the cracking plane on a side face of the test specimen.
11/08/01
fibro13_en2
Pmax
Load
CTOD0
CTODm
The maximum load value P max cannot be taken into consideration for the calculation of the flexural strength.
CTOD0 mean value measured on a set of 45 samples of basic concrete whose compressive strength
ranges from 20 to 90 MPa.
11/08/01
fibro13_en2
PIf
PIf
Load
Load
If the CTODm value corresponding to the maximum load point in the Load-CTODm
diagram is lower than 10 m, it shall be reported in the test report.
CTOD0
CTODm
CTOD0
CTODm
f If =
PIf l
b(h a 0 )
[MPa]
where:
PIf = first crack load [N];
l = interaxial distance between the axis of the lower rollers [mm];
b = specimen width [mm];
h = specimen height [mm];
a0 = measured notch depth [mm].
7.3 Calculation of the ductility indexes D0 and D1.
The ductility indexes D0 and D1 are calculated according to the following formulas:
9
11/08/01
D0 =
D1 =
fibro13_en2
feq , (0 0 ,6 )
fI f
feq , (0.6 3)
f eq,
( 0 0, 6)
where:
feq(0-0.6)= equivalent strength [MPa] in the CTODnet range 0-0.6mm (Part I, clause
3.3.2.1);
feq(0.6-3)= equivalent strength [MPa] in the CTODnet 0.6-3mm (Part I, clause3.3.2.2)
The equivalent strengths are calculated through the following formulas:
f
eq, (0 0.6)
U1
b(h a0 )2 0.6
eq, (0.6 3)
U2
b(h a0 )2 2.4
where:
l = distance between the axis of the lower cylinders [mm];
b = specimen width [mm];
h = specimen height [mm];
a0 = measured notch height [mm];
U1, U2 = areas [10-3 joule] subtended to the Load-CTODm curve (Figure 8)10 in the
CTODnet (Part I, clause 3.2.5) 0 to 0.6mm and 0.6 to 3mm 11 respectively; the
U1 and U2 values are obtained with the following formulas:
U1 =
U1 =
0, 6
0,6
P (CTOD )d (CTOD )
P(CTOD )d (CTOD )
10
The equivalent strength in the CTODnet range between 0 and 3 mm is given by:
f eq, ( 0 3) = 0 ,2 f eq, ( 0 0, 6) + 0,8 f eq, ( 0, 6 3)
11
The U1 and U2 values are approximately proportional to the energy dissipated in the CTODnet ranges taken
into consideration.
10
fibro13_en2
LOAD
11/08/01
PIf
U1
U2
CTOD0 + 3 mm
CTODm
Figure 8. Example of Load-CTODm curve in which are highlighted the areas corresponding
to crack openings (CTODnet ) up to 0.6 and 3 mm.
8. Test report
11/08/01
fibro13_en2
9. Precision
Tables 2a and 2b contain the precision data for the first crack strength fIf and the
ductility indexes D0 and D1 in terms of repeatability standard deviation (sr) and
repeatability limit (r) (ISO 5725-1:1994, clause 3.15 e clause 3.16) for the SFRC and
basic concrete respectively.
Tables 3a and 3b give the precision data for the first crack strength fIf and the
ductility indexes D0 and D1 in terms of repeatability standard deviation (sr) and
repeatability limit (r) referred to the mean values.
Absolute values
fIf [MPa]
D0
D1
Prospect 2
Absolute values
fmax [MPa]
Absolute values
sr
( r = 2 2 s r2 )
0.1
0.3
fmax [MPa]
sr
( r = 2 2 s r2 )
0.3
0.8
12
11/08/01
Relative values
fibro13_en2
fIf
D0
D1
Relative values
Direct
method
6
6.0
5.0
Indirect
method
6
6.6
5.0
( r = 2 2 s r2 )
Direct
Indirect
method
method
17
17
17.0
18.7
14.1
14.1
fmax [MPa]
Relative values
sr [%]
( r = 2 2 s r2 )
2.6
7.3
fmax [MPa]
sr [%]
( r = 2 2 s r2 )
6.5
18.4
13