Selection of Elevator System

The selection of elevators should be made in consideration of the building type/scale, tenant
characteristics, elevator usage and the anticipated passenger carrying capacity at the
building
s traffic peak time.
Hyundai elevators are available from machine-room-less elevators to low-medium and ultra
high-speed elevators, covering the full range of vertical transportation requirements.

ELEVATORS

And a variety of functional and attractive designs per usages, such as passenger, service,
observation, hospital bed, freight and automobile elevators are offered for architectsand
customers
flexible applications.
MOVING WALKS
Speed

Operation

60

1 Car : Selective Collective


2 Cars : Duplex Selective Collective

Kinds of Building

Usage

Control

Low-Rise Apartment
Low-Rise Building

Passenger
Observation
Hospital

Gearless (*include MRL)

Mid-Rise Apartment
Mid-Rise Building

Passenger
Observation
Hospital

Gearless (*include MRL)

60 ~ 150

Geared

60, 90, 105

High-Rise Apartment
High-Rise Building

Passenger

Gearless

180, 240, 300,


360, 420, 480,
540, 600, 720,
1080

Parking Building

Automobile

General Traction

30, 45

General Traction

30, 45, 60

Hydraulic

20, 30, 45

(m/min)

Geared

ESCALATORS

Contents
Selection Of Elevator System

03

3-8 Cars : Group Supervisory

1 Car : Selective Collective


2 Cars : Duplex Selective Collective
3-8 Cars : Group Supervisory

Elevators Layout Plan


1. Passenger Elevators
Gearless Elevators60~150m/min
Machine-Room-Less Elevators60~150m/min
Geared Elevators60~105m/min
2. High-Speed/Ultra-High-Speed Elevators
3. Observation Elevators
Gearless & Geared Elevators (1, 2 side Type)60~105m/min
Gearless & Geared Elevators (3 side, Semicircle Type)60~105m/min
Machine-Room-Less Elevators (1, 2 side Type)60~105m/min
Glass Walled Elevators45~105m/min
4. Freight Elevators
General Type (2S, 2U, 3U)
Hydraulic Type (2S, 2U, 3U)
5. Automobile Elevators
General Type (2U, 3U)
6. Hospital Bed Elevators
General Type (2S, 2SD)
7. Typical Entrance Layouts

04
06
08
10
12
14
16
18
20
22

Factory, Warehouse

Single Automatic

Single Automatic
1 Car : Selective Collective
2 Cars : Duplex Selective Collective

Freight

Note : The table shows the common method of elevator system selection per usages.

Code Application of Elevator Models

F/

23

Capacity
(Persons/kgs)

24
25

Speed

No. of lnstall. Floors

(m/min)

(Including Non-Stop Floors)

ST
No. of Stop
Floors

Escalators / Moving Walks Layout Plan


1.
2.
3.
4.
5.
6.
7.

New World Class Escalators (30)


New World Class Escalators (35)
Millennium Escalators (30)
Millennium Escalators (35)
H-Series Escalators
Modular Escalators
Moving Walks

Works To Be Done By Other Contractors


Electric Power Requirements (By others)

30
31
32
33
34
36
37

Usage

39

MRL
MP
MS
MPF
MOB
MB
MF
MA

General Traction
P
S
(PF)
OB
B
F
A

40

Note : MRL (Machine-Room-Less)

Hydraulic
HP
HS
(HPF)
HOB
HB
HF
HA

Door Opening Type


Type
Passenger
Service
(Passenger & Freight)
Observation
Hospital Bed
Freight
Automobile

Single
Double
Entrance Entrance
CO
COD
2S
2SD
2CO
2COD
2U
2UD
3S
3SD
3U
3UD

Type
2-Panel Center Opening
2-Panel Side Opening
4-Panel Center Opening
2-Panel Up-Sliding
3-Panel Side Opening
3-Panel Up-Sliding

PASSENGER ELEVATORS
Gearless Elevators60~150m/min

Plan of Hoistway & Machine Room

Section of Hoistway

Standard Dimensions & Reactions


(Unit : mm)

MX1
A
M/C Room
Height (MH)

Vent Fan (By others)

CB

Vent
Grille
(By
others)
VentGrille
Grille(By
(Byothers)
others)
Vent
Vent
Grille
(By
others)
Vent
Grille
(By
others)

R1

Capacity

Speed
(m/min)

X1

Overhead (OH)

MY

Control
Panel

X1

X2

X3

450

800

1400 850

14601005

1800

3700

5600

550

800

14001030

14601185

1800

3700

600

800

14001130

14601285

1800

10

700

800

14001250

14601405

11

750

800

14001350

13

900

900

15

1000

17

1150

60

105

120

X2
A
R1

CB

Vent Grille (By others)

Beam (By others)

Vent Grille (By others)

OP

R2

R2
Control
Panel

Control
Panel

R3
Receptacle
(By others)

Distribution Board
(By others)

Ladder
(By others)

MX1 MX2 MX3

MY

R1

R2

R3

R4

1430

2000

4000

6000

3200

3600

2000

5400

4500

5600

1610

2000

4000

6000

3400

4050

2250

6000

4900

3700

5600

1710

2000

4000

6000

3500

4100

2450

6300

5100

1800

3700

5600

1830

2000

4000

6000

3600

4200

2700

6800

5400

14601505

1800

3700

5600

1930

2000

4000

6000

3700

4550

2800

7100

5600

16001350

16601505

2050

4200

6350

1980

2300

4400

6800

3750

5100

3750

8100

6300

900

16001500

16601655

2050

4200

6350

2130

2300

4400

6800

3850

5450

4300

8600

6600

1000

18001500

19001670

2350

4800

7250

2180

2600

4900

7500

3900
6600

5100

11000

8700

1100

20001350

21001520

2550

5200

7850

2030

2800

5250

8300

3800

1000

18001700

19001870

2350

4800

7250

2380

2600

4900

7500

4200
7800

6000

12200

9500

1100

20001500

21001670

2550

5200

7850

2180

2800

5250

8300

4000

20001750

21001920

2550

5200

7850

2430

2900

5400

8300

4300
8500

6800

13600 10400

21501600

22501770

2700

5500

8300

2280

3000

5650

8700

4200

1350

1600

1100

Notes : 1. Above hoistway dimensions are based on 15-storied buildings. For application to over 16-storied buildings,
the hoistway dimensions shall be at least 5% larger considering the sloping of the hoistways.
2. Above dimensions are based on center opening doors. For applicable dimensions with side opening doors, consult Hyundai.
3. When non-standard capacities and dimensions are required to meet the local code, consult Hyundai.
4. The capacity in persons is calculated at 65kg/person. (EN81=75kg/person)
5. Above dimensions are applied in case the door is standard. In case fire protection door that the clear opening is over 1000mm
is applied, hoistway size for 1 car should be applied above X1 dimension plus 100mm.
6. In case of 120m/min and 150m/min, hoistway size is above plus 100mm, the machine room size is above plus 100mm.

Pit Depth (PP)

MY

CA

OP

20

24

Ent. Height (EH)

Vent Fan (By others)

X1
R1

Note 6

150 Note 6

2100

Total Height (TH)

MX2

M/C Room Pit Reaction


(kg)
1Car 2Cars 3Cars Depth 1Car 2Cars 3Cars Depth Reaction (kg)

AB

90

Machine Room Access Door (By others)


Min. 900 (W)2000 (H)

External

CA CB

Travel (TR)

Distribution Board
(By others)

Internal

OP

CA

OP
R2

Clear
Opening

M/C Room

kg

Cinder
Concrete Min. 150
(By others)

R1

Hoistway

Persons
Suspension Hook
(By others)

R2

Car

R4
Waterproof Finish
(By others)

Machine Room Access Door (By others)


Min. 900 (W)2000 (H)

(Unit : mm)

Speed
(m/min)

MX3
X3

R1
Beam
Beam
(By
(By
others)
others)
Beam(By
(Byothers)
others)
Beam
Beam
(By
others)
Beam
Beam
(By
(By
others)
others)

B
Y

CB

Pit
(PP)

M/C Room Height


(MH)

60

4600

1500

2200

90

4800

1800

2400

105

5000

2100

2400

120

5000

2100

2600

150

5500

2400

2600

Notes : 1. Machine room temperature should be maintained below 40C


with ventilating fan and/or air conditioner (if necessary) and
humidity below 90%.
2. The minimum hoistway dimensions are shown on the above table.
Therefore, some allowances should be made considering the
sloping of the hoistways.
3. The minimum machine room height should be 2800mm in case of
the traction machine with double isolation pad.
4. For gearless (1:1 roping) elevators, the minimum machine room
height should be 2400mm.

OP

OP

OP

R2

R2

R2

Control
Panel

Control Control
Panel
Panel
Distribution Board
(By others)

MY

CA

Vent Fan (By others)

Vent Grille (By others)


Vent Grille (By others)

R1

Vent Fan (By others)


Min. 100

X2
X1
A
R1

Overhead
(OH)

Machine Room Access Door (By others)


Min. 900 (W)2000 (H)

PASSENGER ELEVATORS
Machine-Room-Less Elevators60~150m/min

Standard Dimensions (8~38 Person)

Section of Hoistway

Plan of Hoistway & Machine Room (8~38 Person)

Clear
Car
Speed Capacity Opening
(m/min) Persons kg
OP
CACB
AB
X

Lighting (By others)

Hook (By others)


R1

R4

90

Traction
Machine

CA

R2

OP

Floor without control panel

800

13001100 13601255 2050 1700

Over Head (OH)


Travel (TR)
R6

600

7000

1600

8~17

45, 60

3800

1500

530

90

3900

1800

530
530

4300

2200

530

150

4600

2400

530

45, 60

4200

1500

530

600

800

13001190 13601345 2050 1800

5.6

4100 2300 1600

600

7300

1600

13~17

6.5
4.3
10

700

800

13001300 13601455 2050 1800

6.5

4500 2300 1700

650

7800

1600

20~24

90

4300

1800

630

105

4500

2100

630
630

105

7.5

120

4800

2200

60

4.6

150

5100

2400

630

45, 60

4400

1750

530

90

11

750

800

13001400 13601555 2050 1850

6.9

105

8.1

60

5.7

13

900
930
(HC)

900

150

15601555 2200
1850
15001400 16601505 2300
16001350
16001570 2400 2100
17001520 2500 2250

60
90
105

15

1000

900

120

16001400

1900
16601555 2300
(2100)
17001570 2500

150

8.6
11.5
14.5
9.2

2100

12.3
15.4
7.1
10.6

1000

18001400 19001570

2600 2100

20

1350

1000

2650 2250

17.7

2650

12.5

18001600 19001770

2400

20.7

90

14.8

2850
24

1600

1100

120

20001600 21001770

2450
2880

150
60
1750

1200

16002300 17002507 2480 2850

1900
38

5900 3700 1800

900

11200

2300

5400 2700 1900

800

9800

2000

6100 3900 2200

900

11800

2500

6300 3400 2100

900

12500

2500

6600 4200 2300

900

14200

2700

7700 4300 2500 1100 13900

3000

8200 4600 2600 1200 16500

3100

7900 4600 2600 1200 15200

3200

8300 4900 2700 1200 17800

3300

8600 4300 2900 1300 16700

2800

9100 4700 3100 1300 19800

3300

10300 5200 3300 1600 24000

3700

1900

630

4600

2100

630

45, 60

5000

1750

630

90

5100

1900

630

105

5300

2100

630

Notes : 1. Above dimensions are applied for car height


of 2500mm (car internal height is 2300mm).
For other applicable dimensions, consult
Hyundai.
2. For car internal height (under 17 persons) of
2500mm, dimension of overhead is OH plus
200mm
3. The minimum hoistway dimensions are
shown on the above table. Therefore, some
allowances should be made considering the
sloping of the hoistways.
4. When face to face arrangement is required,
partitioning work for hoistway is required.
(EN81)
5. If the hoistway is glass, consult Hyundai as
it needs to finish laminated glass. (EN81)
6. When non-standard capacities and
dimensions are required to meet the local
code, please consult Hyundai Elevator.

17.2
19.7
24.6
17.2
20.1

60

12.3
30

2000

1200

21001900 22002107 3000 2550

105

18.4
21.5

60
105

9200

4500

11.5
27

105

90

750

90
105

9.9

60

90

5100 2500 1800

14.5
16.6

2680

150

90

27~30

8.3

120

105

1700

12.4
14.1

90
105

8100

10.8

90
1150

700

6.2

60
17

4800 2300 1750

10

2250

60

R5

4000 2100 1500

120

120

Waterproof Finish
(By others)

5.1
3.7

150
Lighting
(By others)

R6

60

90

Total Height (TH)

Notes : 1. The lighting of hoistway should be


installed less than 500mm from above
the ceiling of hoistway and within
500mm above the bottom of the pit.
(By others)
2. Machine room temperature should be
maintained below 40C with ventilating
fan and/or air conditioner (if necessary)
and humidity below 90%.

Ladder
(By others)

R5

2100

105

Pit Depth (PP)

Floor with control panel

Receptacle
(By others)

R4

Control
Panel
(CP)(*)

4000

105

OP

R3

Pit
(PP)

105

90

Control
Control
Control
Control
Control
Control
Panel
Panel
Panel
Panel
Panel
Panel

R2

Speed Overhead
(m/min) (OH)

5.9

120

CP
(*)

550

60

Entrance Height (EH)

R3

R1

Persons

3.4

105

CB

Top floor
(By others)

Motor
(kW)

( : mm)

M/C Room Reaction (kg) Pit Reaction (kg)

105
90

60

Lighting
(By others)

Distribution Board
(By others)

Hoistway

15.4
38

2500

1400

22002200 23002407 3300 3050

23
26.9

Notes : 1. When non-standard capacities and dimensions (including fire protection doors) are required to meet the local code, please
consult Hyundai.
2. The minimum hoistway dimensions are shown on the above table. Therefore, some allowances should be made considering
the sloping of the hoistways.
3. If the height of floor is over 11m, please consult Hyundai as to the needs for emergency exit.
4. Above dimensions are applied in case the door is standard. In case fire protection door that the clear opening is over
1000mm is applied, hoistway size for 1car should be applied above X1 dimension plus 100mm.
5. In case the emergency stop switch is applied to the counter weight, consult Hyundai.
6. When face to face arrangement is required, partitioning work for hoistway is required. (EN81)

PASSENGER ELEVATORS
Geared Elevators60~105m/min

Plan of Hoistway & Machine Room

Section of Hoistway

MX1

R1

Overhead (OH)

Vent Fan (By others)

CB

MY

CA

Persons kg

Cinder
Concrete Min. 150
(By others)

R2

Vent Grille (By others)

A
R1

Capacity

Speed
(m/min)

Suspension Hook
(By others)

M/C Room
Height (MH)

X1

Standard Dimensions & Reactions

60

OP
R2

90

Vent Fan (By others)


Min. 100

R1

R1

Beam
(By others)

CB

Vent Grille (By others)

A
R1

CB

Vent Grille (By others)

X2

CA

R2
Control
Panel

Control
Panel

Distribution Board
(By others)

Machine Room Access Door (By others)


Min. 900 (W)2000 (H)

X2

X3

MX1

MX2

MX3

MY

R1

R2

R3

R4

14601005

1800

3700

5600

1430

2000

4000

6000

3200

3600

2000

5200

4300

550

800

14001030

14601185

1800

3700

5600

1610

2000

4000

6000

3400

4050

2250

5800

4700

600

800

14001130

14601285

1800

3700

5600

1710

2000

4000

6000

3500

4100

2450

6100

4900

10

700

800

14001250

14601405

1800

3700

5600

1830

2000

4000

6000

3600

4200

2700

6600

5200

11

750

800

14001350

14601505

1800

3700

5600

1930

2000

4000

6000

3700

4550

2800

6900

5400

13

900

900

16001350

16601505

2050

4200

6350

1980

2300

4400

6800

3750

5100

3750

7900

6100

15

1000

900

16001500

16601655

2050

4200

6350

2130

2300

4400

6800

3850

5450

4300

8400

6400

1000

18001500

19001670

2350

4800

7250

2180

2600

4900

7500

3900

17

1150

6600

5100

10800

8500

1100

20001350

21001520

2550

5200

7850

2030

2800

5250

8300

3800

1000

18001700

19001870

2350

4800

7250

2380

2600

4900

7500

4200
7800

6000

11800

9100

1100

20001500

21001670

2550

5200

7850

2180

2800

5250

8300

4000

20001750

21001920

2550

5200

7850

2430

2900

5400

8300

4300
8500

6800

13100

9900

21501600

22501770

2700

5500

8300

2280

3000

5650

8700

4200

1350

1600

1100

OP
OP
OP
OP
OP
OP

OP
OP
OP
OP
OP
OP

OP
OP
OP
OP
OP
OP

R2

R2

R2

Control
Panel

Control
Panel

Control
Panel
Distribution Board
(By others)

Speed
(m/min)

Overhead
(OH)

Pit
(PP)

M/C Room Height


(MH)

60

4600

1500

2200

90

4800

1800

2400

105

5000

2100

2400

Notes : 1. The minimum hoistway dimensions are shown on the above table. Therefore, some allowances
should be made considering the sloping of the hoistways.
2. Machine room temperature should be maintained below 40C with ventilating fan and/or air
conditioner (if necessary) and humidity below 90%.
3. The minimum machine room height should be 2800mm in case of the traction machine with double
isolation pad.

Vent Fan (By others)

R2

Vent Grille (By others)

OP

MY

MY

CA

X1

(Unit : mm)

X1
Vent Fan (By others)

OP
Vent Grille (By others)

2100

Ent. Height (EH)

X3
R1

AB

Waterproof Finish
(By others)

MX3

Beam (By others)

Ladder
(By others)

X2
X1

CA CB

Notes : 1. Above hoistway dimensions are based on 15-storied buildings. For application to over 16-storied buildings,
the hoistway dimensions shall be at least 5% larger considering the sloping of the hoistways.
2. Above dimensions are based on center opening doors. For applicable dimensions with side opening doors, consult Hyundai.
3. When non-standard capacities and dimensions are required to meet the local code, consult Hyundai.
4. The capacity in persons is calculated at 65kg/person. (EN81=75kg/person)
5. Above dimensions are applied in case the door is standard. In case fire protection door that the clear opening is over 1000mm is applied,
hoistway size for 1 car should be applied above X1 dimension plus 100mm.

MX2

R1

OP

1400 850

24

Receptacle
(By others)

M/C Room Pit Reaction


(kg)
1Car 2Cars 3Cars Depth 1Car 2Cars 3Cars Depth Reaction (kg)

800

20

Pit Depth (PP)

Note : Machine room temperature should be maintained below 40C


with ventilating fan and/or air conditioner (if necessary) and
humidity below 90%.

M/C Room

450

105
Travel (TR)

Total Height (TH)

Machine Room Access Door (By others)


Min. 900 (W)2000 (H)

Hoistway

Control
Panel

Distribution Board
(By others)

Car
Clear
Opening Internal
External

(Unit : mm)

Machine Room Access Door (By others)


Min. 900 (W)2000 (H)

HIGH-SPEED/ULTRA-HIGH-SPEED ELEVATORS
Gearless Elevators180~600m/min

Plan of Hoistway & Machine Room (In-Line Arrangement of 3 Units)

Section of Hoistway
Hook or Trolly Beam
(By others)

MX3
X3

B Vent Fan (By others)


Y
Min. 200

R2

R2

R2

R2

Control Panel

Distribution Board (By others)

Travel (TR)

R2

Entrance
Height

Machine Room Access Door (By others)


900 (W) X 2000 (H)

Receptacle
(By others)

Ladder
(By others)

Waterproof Finish
(By others)

MX3
X3

420
480
540
600

R1
Beam
(By others)

R1
Beam
(By others)

Internal

External

1Car

M/C Room

2Cars 3Cars Depth 1Car

M/C Room
2Cars 3Cars Depth Reaction (kg)

OP

CA CB

AB

X1

X2

X3

MX1

MX2

MX3

MY

R1

R2

13

900

900

16001350

17001520

2300

4550

6900

2150

2800

5500

7900

4500

12030

6630

15

1000

900

16001500

17001670

2300

4550

6900

2300

2800

5500

7900

4700

12810

6950

17

1150

1000

18001500

19001670

2500

4950

7500

2350

3000

6100

8800

4700

1100

20001350

21001520

2700

5350

8100

2200

3200

6250

9100

4500

13080

7130

20

1350

1000

18001700

19001870

2500

4950

7500

2550

3000

6100

8900

5000

1100

20001500

21001670

2700

5350

8100

2350

3200

6250

9100

4700

14360

7650

24

1600

20001750

21001920

2700

5350

8100

2600

3200

6250

9100

5000

21501600

22501770

2850

5650

8550

2450

3400

6500

9400

4900

15090

8080

15

1000

900

16001500

17001670

4600

6950

2350

5600

8200

4900

1000

18001300

19001470

5000

7550

2150

5800

8400

4900

12810

7800

17

1150

1000

18001500

19001670

5000

7550

2350

6100

8900

4900

1100

20001350

21001520

5400

8150

2200

6200

9000

4900

14100

8000

20

1350

1000

18001700

19001870

5000

7550

2550

6100

8800

5000

1100

20001500

21001670

5400

8150

2350

6200

9000

5000

15100

8050

24

1600

20001750

21001920

5400

8150

2600

6400

9000

5000

21501600

22501770

5700

8650

2450

6500

9400

5000

15700

8100

20

1350

10 00

18001700

19001920

5100

7700

2650

6200

9100

6000

1100

20001500

21001720

5500

8300

2450

6200

9100

5900

17800

13200

24

1600

1100

20001750

21001970

5500

8300

2650

6500

9100

6300

21501600

22501820

5800

8750

2500

6500

9400

6200

18100

13500

17

1150

1000

18001500

7800

2500

8900

6000

20

1350

1100

20001500

8750

2500

9500

6300

24

1600

1100

20001750

8750

2750

9500

6300

1100

1100

CB

Vent Grille (By others)

CA

(Unit : mm)
MY

OP

Min. 200

OP

Vent Grille (By others)

OP

CP
CP

R1

Vent Fan (By others)

B
R2

Distribution Board
(By others)
Y
3600 ~ 4000
MY

OP

R2
CP
CP

Vent Fan
(By others)

OP

Machine Room
Access Door
(By others)
900 (W) X 2000 (H)

OP
R2

X1

Hoistway

Notes : 1. The minimum hoistway dimensions are shown on the above table. Therefore, some allowances should be made considering the sloping of the hoistways.
2. Above dimensions are based on center opening doors. For applicable dimensions with side opening doors, consult Hyundai.
3. For elevators with more than 28 persons capacity, consult Hyundai.
4. When non-standard capacities and dimensions are required to meet the local code, consult Hyundai.
5. The capacity in persons is calculated at 65kg/person. (EN81=75kg/person)
6. Above dimensions are applied in case the door is standard. In case fire protection door that the clear opening is over 1000mm is applied, hoistway size for 1 car should be applied
above X1 dimension plus 100mm.
7. The maximum speed capabilities of Hyundai is 1080m/min. Consult Hyundai.

MX2
X2

CA

CP
CP

Vent Grille (By others)

Vent Fan (By others)

R1

CB

Vent Grille (By others)

R1

Min. 200

X2
X1
A

Car

Clear
Opening

kg

300
360

Face-to-Face Arrangement

(Unit : mm)

Persons

210
240

Pit Depth (PP)

Note : Temperature should be maintained below 40C and humidity


below 90%, with installation of a ventilating fan, ventilating grille,
and air conditioner (if necessary). Toxic gas or dust should not be generated.

Capacity

180

Total Height (TH)

OP

Vent Fan (By others)

OP

MY

CA

OP

R1

2100

CB

R1

Overhead (OH)

R1
Beam
(By others)

Vent Grille (By others)

Vent Grille (By others)

R1

Speed
(m/min)

Suspension
Cinder Concrete
Min. 150
(By others)

M/C Room
Height
(MH)

X2
X1
A
R1

Standard Dimensions & Reactions

OP

OP

R2

R2
Control
Panel

Control
Panel
Distribution Board (By others)

Machine Room Access Door (By others)


900 (W) X 2000 (H)

Speed
(m/min)

Overhead
(OH)

Top Clearance
(TC)

Pit
(PP)

M/C Room
Height (MH)

Speed
(m/min)

Overhead
(OH)

Top Clearance
(TC)

Pit
(PP)

M/C Room
Height (MH)

180

6000

2300

2700

2500

420

8500

4200

6000

3200

210

6400

2700

3200

2800

480

9500

5700

6400

3500

240

7100

3350

3850

2800

540

9750

5950

8800

3500

300

8000

4000

4200

3000

600

10000

6200

9000

3500

360

8300

4000

4300

3000

Notes : 1. The above table shows minimum figures. Therefore, some allowances should be made considering errors that may occur during construction.
2. Above dimensions are applied in case car height is 2800mm. In case car height is over 2800mm, overhead should be applied above dimension plus additional height.

10

11

OBSERVATION ELEVATORS
Gearless & Geared Elevators60~105m/min

Plan of Hoistway & Machine Room

Section of Hoistway

MX

1 Side Type

Type

Min.
500

Pit Depth (PP)

Note : Machine room temperature should be maintained below 40C


with ventilating fan and/or air conditioner (if necessary) and
humidity below 90%.

Maintenance Deck
(By others)
Receptacle
(By others)

2 Side Type

Waterproof Finish
(By others)

60
90
105

Clear
Opening

Internal

External

Hoistway

M/C Room

M/C Room
Reaction (kg)

Pit Reaction
(kg)

Persons

kg

OP

CA CB

AB

XY

MX MY

R1

R2

450

800

1400850

14601060

22001400

26002900

5000

2700

6650

5750

550

800

14001030

14601240

22001500

26003000

5350

3000

7300

6200

600

800

14001130

14601340

22001600

26003100

5550

3100

7600

6400

10

700

800

14001250

14601460

22001750

26003200

5900

3300

8200

6800

11

750

800

14001350

14601560

22001850

26003350

6100

3400

8500

7000

13

900

900

16001350

16601560

24001850

30003350

6800

3750

9550

7750

15

1000

900

16001500

16601710

24002000

30003500

7100

3900

10100

8150

17

1150

1000

18001500

19001710

28502000

35003500

8900

5300

12800

10500

20

1350

1000

18001700

19001910

28502200

35003700

9000

6650

14100

11400

24

1600

1100

20001750

21001960

30502250

37003750

9850

7050

15500

12300

550

800

14001030

14601240

22001500

26003000

5400

3050

7500

6400

600

800

14001130

14601340

22001600

26003100

5600

3120

7800

6600

10

700

800

14001250

14601460

22001750

26003200

5950

3350

8400

7000

11

750

800

14001350

14601560

22001850

26003350

6100

3450

8700

7200

13

900

900

16001350

16601560

24001850

30003350

6850

3750

9750

7950

15

1000

900

16001500

16601710

24002000

30003500

7150

3930

10350

8350

17

1150

1000

18001500

19001710

28502000

35003500

9000

5400

13000

10700

20

1350

1000

18001700

19001910

28502200

35003700

9100

6700

14250

11600

24

1600

1100

20001750

21001960

30502250

37003750

9950

7100

15700

12500

R3 (Car) R4 (CWT)

Control
Panel
Distribution Board
(By others)

(Unit : mm)
Machine Room
Access Door (By others)
Min. 900 (W)2100 (H)

OP

Vent Grille (By others)

R2

CB

R1
Vent Fan (By others)

Y
B

A
Glass Wall
(By others)

MY

2-Side
Observation

(Unit : mm)

Car

Notes : 1. Above dimensions are based on center opening doors. For applicable dimensions with side opening doors. Consult Hyundai.
2. When non-standard capacities and dimensions are required to meet the local code, consult Hyundai.
3. The capacity in persons is calculated at 65kg/person. (EN81=75kg/person)
4. Above dimensions are applied in case the door is standard. In case fire protection door that the clear opening is over
1000mm is applied, hoistway size for 1 car should be applied above X1 dimension plus 100mm.

MX

CA

Ladder
(By others)

60
90
105

Concrete (Min. 3600) or


Glass Enclosure
(By others)

Glass Enclosure (By others)

Travel (TR)

Total Height (TH)

Distribution Board
(By others)

2100

Control
Panel

Cinder
Concrete Min. 150
(By others)

1-Side
Observation

Capacity

Speed
(m/min)

Suspension Hook
(By others)

Ent. Height (EH)

M/C Room
Height (MH)
Overhead (OH)

Vent Grille (By others)

CB

OP

Machine Room
Access Door (By others)
Min. 900 (W)2100 (H)

Vent Fan (By others)

CA

MY

R2

R1

Y
B

A
Glass Wall
(By others)

12

Standard Dimensions & Reactions

Speed
(m/min)

Overhead
(OH)

Pit
(PP)

M/C Room
Height (MH)

60

4700

1750

2200

90

4900

1800

2400

105

5000

2100

2400

Notes : 1. The minimum hoistway dimensions are shown on the above table. Therefore, some
allowances should be made considering the sloping of the hoistways.
2. The minimum machine room height should be 2800mm in case of the traction
machine with double isolation pad.
3. For gearless (1:1 roping) elevators, the minimum machine room height should be
2400mm.

13

OBSERVATION ELEVATORS
Gearless & Geared Elevators60~105m/min

Section of Hoistway

X2, MX2

M/C Room
Height (MH)

60

4800

1800

2200

5000

2050

2400

105

5100

2050

2400

Ladder
(By others)

Speed
(m/min)

60
90
105

Capacity

Clear
Opening

Internal

External

CA CB

AB

Persons

kg

OP

11

750

800

13

900

15

1000

17

1Car 2Cars Depth

1Car 2Cars Depth

X1

X2

14001400 14601610

2450

5100

2000

900

16001450 16601660

2650

5500

900

16001570 16601780

2650

5500

1150

1000

18001580 19001790

2850

20

1350

1000

18001800 19002010

24

1600

1100

18002000 19002210

Pit Reaction
(kg)

R2

R2

(1Car)

(2Cars)

6150

3450

3550

6900

3700

7200

6100

3700

9100

5450 10900 13150 10900

3500

6100

3900

9150

6750 13500 14550 11850

3500

6100

4100 10000 7150 14300 16100 12900

MX1 MX2

MY

R1

1200

2900

5100

3500

2050

1350

3300

5500

2200

1350

3300

5500

6100

2200

1600

3500

2850

6100

2400

1600

2850

6100

2600

1600

Notes : 1. Above dimensions are based on center opening doors. For applicable dimensions with side opening doors, consult Hyundai.
2. Above dimensions are applied in case the door is standard. In case fire protection door that the clear opening is over 1000mm is applied,
hoistway size for 1 car should be applied above X1 dimension plus 100mm.
3. Consult Hyundai if the capacity is 10 persons and less.

14

M/C Room
Reaction (kg)

Pit
(PP)

M/C Room
Height (MH)

60

4800

1800

2200

90

5000

2050

2400

105

5100

2050

2400

Min.
500

Maintenance
Deck
(By others)
R4 R3
Receptacle
(By others)

Ladder
(By others)

Waterproof Finish
(By others)

Note : Machine room temperature should be maintained


below 40C with ventilating fan and/or air conditioner
(if necessary) and humidity below 90%.

Standard Dimensions & Reactions


Speed
(m/min)

Capacity

External

CA CB

AB

R4

Persons

kg

OP

6900

8700

7150

11

750

800

3750

7500

9700

7900

3950

7900 10300 8300

60
90
105

Hoistway

Internal

R3

(Unit : mm)

Car

Clear
Opening

Concrete (Min. 3600) or


Glass Enclosure
(By others)

2100

Travel (TR)

Total Height (TH)

Overhead
(OH)

Ent. Height(EH)

Overhead (OH)

R1
S
Vent Fan (By others)

Speed
(m/min)

Glass Enclosure (By others)

R2

MY

Vent Grille (By others)

(Unit : mm)

M/C Room

Machine Room Access Door (By others)


Min. 900 (W)2100 (H)

Semicircle Type

Notes : 1. The minimum hoistway dimensions are shown on the above table. Therefore, some
allowances should be made considering the sloping of the hoistways.
2. The minimum machine room height should be 2800mm in case of the traction
machine with double isolation pad.
3. Above dimentions are changeable according to the car exterior design.

Note : Machine room temperature should be maintained


below 40C with ventilating fan and/or air conditioner
(if necessary) and humidity below 90%.

Hoistway

Control
Panel

Distribution Board
(By others)

Waterproof Finish
(By others)

Standard Dimensions & Reactions

Vent Grille (By others)

R1
Receptacle
(By others)

OP

Control
Panel

Vent Fan (By others)

Total Height (TH)

Ent. Height (EH)


2100

Overhead (OH)

Maintenance Deck
(By others)

OP

R4 R3

Notes : 1. The minimum hoistway dimensions are shown on the above table. Therefore, some
allowances should be made considering the sloping of the hoistways.
2. The minimum machine room height should be 2800mm in case of the traction
machine with double isolation pad.
3. Above dimentions are changeable according to the car exterior design.

Car

CA

Pit Depth (PP)

Pit
(PP)

90

CB

Overhead
(OH)

Min.
500

Pit Depth (PP)

Speed
(m/min)

Cinder
Concrete Min. 150
(By others)

Machine Room Access Door (By others)


Min. 900 (W)2100 (H)

3 Side Type

550

Glass Enclosure (By others)

Travel (TR)

Distribution Board
(By others)

Cinder
Concrete Min. 150
(By others)

Vent Fan (By others)

Control
Panel

Suspension Hook
(By others)

200

R1

OP

Control
Panel

Vent Fan (By others)

MY

OP

M/C Room
Height (MH)

550

Vent Grille (By others)

CB

R2

Vent Grille (By others)

R1

CA

Section of Hoistway

X2, MX2

Suspension Hook
(By others)

550

Glass Enclosure (By others)

200

A
Glass Enclosure
(By others)

Concrete (Min. 3600) or


Glass Enclosure
(By others)

550

Plan of Hoistway & Machine Room

M/C Room
Height (MH)

Plan of Hoistway & Machine Room

M/C Room

1Car 2Cars Depth

1Car 2Cars Depth

X1

X2

14001480 14601690

2450

5100

2000

M/C Room
Reaction (kg)
R2

R2

(1Car)

(2Cars)

6180

3450

MX1 MX2

MY

R1

1200

2900

5100

3500

Pit Reaction
(kg)
R3

R4

6900

8700

7150

9700

7900

13

900

900

16001500 16601710

2650

5500

2050

1350

3300

5500

3550

6930

3750

7500

15

1000

900

16001650 16601860

2650

5500

2200

1350

3300

5500

3700

7220

3950

7900 10300 8300

17

1150

1000

18001650 19001860

2850

6100

2200

1600

3500

6100

3700

9100

5450 10900 13150 10900

20

1350

1000

18001900 19002110

2850

6100

2400

1600

3500

6100

3900

9150

6750 13500 14550 11850

24

1600

1100

18002130 19002340

2850

6100

2600

1600

3500

6100

4100 10050 7190 14380 16100 12900

Notes : 1. Above dimensions are based on center opening doors. For applicable dimensions with side opening doors, consult Hyundai.
2. Above dimensions are applied in case the door is standard. In case fire protection door that the clear opening is over 1000mm is applied,
hoistway size for 1 car should be applied above X1 dimension plus 100mm.
3. Consult Hyundai if the capacity is 10 persons and less.

15

OBSERVATION ELEVATORS
Machine-Room-Less Elevaotrs60 ~105m/min

Section of Hoistway

Plan of Hoistway & Machine Room

Lighting (By others)


X

1 Side Type

Standard Dimensions & Reactions


Type

Hook (By others)

A
R4

R1

Top floor
(By others)

R2

Lighting
(By others)

2 Side Type

A
R1
CA

CB

Top floor
(By others)

OP

R2

Floor without control panel

Travel (TR)

2-Side
Observation
R3

90
105

Total Height (TH)

R4

60

Entrance Height (EH)

OP

1-Side
Observation

Over head (OH)

R3

Traction
Machine

CB

CA

Lighting
(By others)

60
90
105

Receptacle
(By others)
Ladder
(By others)

Pit Depth (PP)

Lighting
(By others)
Waterproof Finish
(By others)
R5

Control
Panel

Car
Internal

External

M/C Room
Reaction (kg)

Hoistway

Pit Reaction
(kg)

Persons

kg

OP

CA CB

AB

XY

R4

R5

R6

550

800

13001090

13601300

21001700

4100 1950 1800

700

7500

6400

600

800

13001160

13601370

21001800

4250 1980 1830

750

7800

6600

10

700

800

13001300

13601510

21001850

4500 2050 1900

800

8400

7000

11

750

800

13001400

13601610

21001900

4650 2080 1950

900

8700

7200

15001400

15601610

23001900

16001350

16601560

24001850

5050 2250 2100 1000

9750

7950

13

900
930 (HC)

900

R1

R2

R3

15

1000

900

16001400

16601610

23001950

5400 2350 2200 1050 10300

8350

17

1150

1000

18001400

19001610

26002150

5750 3450 2800 1100 13000

10700

20

1350

1000

18001600

19001810

26502450

6800 4800 3150 1350 14300

11600

24

1600

1100

20001600

21001810

28502500

7350 4950 3300 1450 15700

12500

550

800

13001090

14601300

22001700

4250 2000 1940

750

7700

6600

600

800

13001160

14601370

22001800

4450 2030 1980

800

8000

6800

10

700

800

13001300

14601510

22001850

4750 2100 2080

850

8600

7200

11

750

800

13001400

14601610

22001900

4900 2150 2100

950

8900

7400

15001400

15601610

24001900

16001350

16601560

25001850

5400 2300 2300 1050

9950

8150

13

900
930 (HC)

900

15

1000

900

16001400

17601610

24001950

5750 2400 2500 1100 10550

8550

17

1150

1000

18001400

19601610

27002150

6650 3500 3150 1150 13200

10900

20

1350

1000

18001600

19601810

27002450

7730 4850 3500 1400 14450

11800

24

1600

1100

20001700

21601910

29002500

8250 5000 3650 1500 15900

12700

Notes : 1. When non-standard capacities and dimensions (including fire protection doors) are required to meet the local code, please consult Hyundai.
2. The minimum hoistway dimensions are shown on the above table. Therefore, some allowances should be made considering the sloping of the hoistways.
3. The capacity in persons is calculated at 65kg / person. (EN81=75kg / person)
4. If the height of floor is over 11m, please consult Hyundai as to the needs for emergency exit.
5. Above dimensions are applied in case the door is standard. In case fire protection door that the clear opening is over 1000mm is applied, hoistway size for
1 car should be applied above X1 dimension plus 100mm.
6. In case the emergency stop switch is applied to the counter weight, consult Hyundai.
7. If the car is heavier than 1000kg because of interior decoration in case of elevator for 15 persons (1000kg), consult Hyundai.

Persons

8 ~ 15

CP
(*)

Floor with control panel

Note : The lighting of hoistway should be installed less than


500mm from above the ceiling of hoistway and within
500mm above the bottom of the pit. (By others)

16

Clear
Opening

R6

Distribution Board
(By others)

OP

Capacity

Speed
(m/min)

(Unit : mm)

17

20 ~24

Speed
(m/min)

Overhead
(OH)

Pit
(PP)

60

4250

1750

Control Panel
(CP)(*)
530

90

4350

1800

105

4400

2000

60

4250

1800

90

4350

1900

105

4400

2000

60

4850

1800

530

90

5000

1900

630

105

5000

2100

630

Notes : 1. Above dimensions are applied for car height of 2500mm (car internal height is
2300mm), For other applicable dimensions, consult Hyundai.
2. The minimum hoistway dimensions are shown on the above table. Therefore, some
allowances should be made considering the sloping of the hoistways.
3. When face to face arrangement is required, partitioning work for hoistway is
required. (EN81)
4. If the hoistway is glass, consult Hyundai as it needs to finish joining glass. (EN81)
5. The lighting should be installed at the top and bottom of hoistway.
6. When non-standard capacities and dimensions are required to meet the local code,
please consult Hyundai Elevator.

530

17

GLASS WALLED ELEVATORS


Gearless & Geared / MRL Elevators45 ~105m/min

Plan of Hoistway & Machine Room

Standard Dimensions & ReactionsGearless & Geared Elevators

Section of Hoistway
Lighting (By others)

Type

Hook (By others)

kg

XY

MX MY

R1

R2

550

800

14001030

15601240

23001500

27003000

5450

3035

7800

6700

600

800

14001130

15601340

23001600

27003100

5640

3150

8200

7000

10

700

800

14001250

15601460

23001750

27003200

6010

3370

8750

7350

11

750

800

14001350

15601560

23001850

27003350

6180

3480

9300

7800

13

900

900

16001350

17601560

25001850

31003350

6930

3795

10350

8550

15

1000

900

16001500

17601710

25002000

31003500

7220

3970

11050

9050

17

1150

1000

18001500

19601710

27502000

36003500

9100

5440

13650 11350

20

1350

1000

18001700

19601910

28902200

36003700

9144

6760

15300 12600

24

1600

1100

20001750

21601960

30902250

38003750

10020

7190

16800 13600

45
Glass walled
Elevators
Over head (OH)
Total Height (TH)
Travel (TR)

Distribution Board
(By others)

Receptacle
(By others)

4500

1500

2200

60

4700

1500

2200

90

4900

1800

2400

105

5000

2100

2400

(Machine-Room-Less)

Pit Depth (PP)

MRL

Waterproof Finish
(By others)

R5
R3

External
AB

Hoistway

M/C Room

Notes : 1. The machine room reactions are changeable according to the size of hoistway and
center of car weight.
2. The same dimension of passenger elevators apply to the others except the above.
3. For NDFL-01 (Frameless Glass-walled elevators) type, consult Hyundai Elevator
since hoistway dimension and machine room reactions for NDFL-01 type are
changeable under different conditions.

Standard Dimensions & ReactionsMRL Elevators (Machine-Room-Less)


Type

Lighting
(By others)

Internal
CA CB

M/C Room Height (MH)

45

Ladder
(By others)

Lighting
(By others)

90

Speed (m/min) Overhead (OH) Pit (PP)

Floor without control panel

Gallery Window
(By others)

60
105

Entrance Height (EH)

Machine Room
Access Door (By others)
Min. 900 (W)2100 (H)

OP

Control
Panel

Vent Fan (By others)

R2
CB

R1

CA

MY

Vent Grille (By others)

Pit
Reaction (kg)
R5
R6

MX
Traction
Machine

M/C Room
Reaction (kg)

Persons

Gearless & Geared


X

Car

Clear
Opening
OP

Capacity

Speed
(m/min)

(Unit : mm)

Speed
(m/min)

R6

(Unit : mm)

Pit
Reaction (kg)
R5
R6

Persons

kg

Clear
Opening
OP

XY

R1

R2

R3

R4

550

800

13001100

14601310

21301750

4295

1870

660

1960

8150

7050

14601400

21301800

Capacity

45
Glass walled
Elevators

Car

60
90
105

R1

Internal
CA CB

External
AB

M/C Room Reaction (kg)

Hoistway

600

800

13001190

4515

1910

740

2010

8500

7300

10

700

800

13001300

14601510

21301850

4820

2030

840

2100

9050

7650

11

750

800

13001400

14601610

21301900

4975

2030

910

2110

9450

7950

13

900

900

15001400

16601610

23301900

5480

2240

1010

2350 10500 8700

15

1000

900

16001400

17601610

24301900

5840

2385

1077

2521 11150 9150

17

1150

1000

18001400

19601610

27002150

6745

3220

1154

3185 13750 11450

20

1350

1000

18001600

19601810

27502350

7810

4515

1310

3530 15650 12950

24

1600

1100

20001700

21601910

29502400

8345

4650

1480

3720 16850 13650

Distribution Board
(By others)

CB

CA

Control
Panel
OP
R4

R2
OP

CP
(*)

Floor with control panel

Speed (m/min)
45 / 60
90
105

Floor without control panel

18

Note : The lighting of hoistway should be installed less than


500mm from above the ceiling of hoistway and within
500mm above the bottom of the pit. (By others)

Persons

Overhead (OH)

Pit (PP)

Speed (m/min)

Max.15

4200

1500

45

4850

17

4200

1600

60

4850

4300

1800

90

4400

2000

105

Max.17

Persons

20 / 24

Overhead (OH)

Pit (PP)
1600

5000

1800

5000

2100

Notes : 1. The machine room reactions are changeable according to the size of hoistway and center of car weight.
2. The same dimension of passenger elevators apply to the others except the above.
3. For NDFL-01 (Frameless Glass-walled elevators) type, consult Hyundai Elevator since hoistway dimension
and machine room reactions for NDFL-01 type are changeable under different conditions.

19

FREIGHT ELEVATORS
General Type (2S, 2U, 3U)

Plan of Hoistway & Machine Room

Section of Hoistway

Standard Dimensions & Reactions

MX

Model

X
A

M/C Room
Height (MH)

Vent Grille (By others)

Vent Fan
(By others)

F0750-2S

Cinder
Concrete Min. 150
(By others)

F1000-2S

30
45
60

2S

30
45
60

2S

30
45
60

2S

30
45
60

2S

Car
Internal

External

CA CB

AB

Standard
11002100

Double
Entrance

Double
Entrance

XY

M/C Room
Buffer
M/C Room Reaction (kg) Reaction (kg)
Overhead (MXMY)
(OH)
R1
R2
R3
R4

18001857 25002150
17001650

4800

28003200 6200

4100

5000

4300

4800

32003500 8500

5700

7100

6100

4800

36004000 10800 7100

9000

7500

4800

38004200 13300 8800 11400 9400

4600

38004200 13300 8800 11400 9400

4800

40004400 15100 10000 13200 10700

4600

40004400 15100 10000 13200 10700

4800

42004800 15200 10100 13500 10500

5000

43005200 21700 14500 19000 15500

5300

45005900 32500 21700 28700 23700

5500

47006400 36000 23000 31700 26700

18001989 25002320

Standard
14002100

Hoistway

19502078 27502400
18501850
19502226 27502600

Machine Room
Access Door (By others)
Min. 900 (W)2000 (H)

CA

OP

F1500-2S

Overhead (OH)

MY

R2

CB

R1

Suspension Hook
(By others)

Entrance
Speed
Door
(m/min) Opening WidthHeight Entrance
(OPEH)
Type
Type

(Unit : mm)

F2000-2S

Distribution Board (By others)

Note : Temperatures should be maintained below 40C with ventilating


fan and/or air conditioner (if necessary) and humidity below 90%.

F2500-2S
Travel (TR)

2-PANEL SIDE-OPENING DOORS (2S)

Total Height (TH)

F2000-2U

F3000-2U

OP

50

50

Min. 300

Min. 650

Pit Depth (PP)

Wall+Finished

200

30

Ent. Height (EH)

F2500-2U

Receptacle
(By others)

2-PANEL UP-SLIDING DOORS (2U)


Minimum floor height : Opening height3 / 2 + 700mm
Minimum entrance height : 2100mm

F3500-2U
Ladder
(By others)

R3

R4

Waterproof Finish
(By others)

F4000-3U

F5000-3U

Standard

30
45
60

2U

30
45
(60)

2S

30
45
(60)
30
45
30
45
25
30
25
30

17002100

Double
Entrance

17002100

18002100

24002928 33003250

Double
Entrance

24003076 33003450

25002100

23002700
24002898 33003250

Double
Entrance

24003016 33003490

Standard

26003228 35003600

Double
Entrance

26003376 35003750

Standard
2U

22002876 30003250

Standard

Standard
23002100

22002728 30003050
21002500

25003000
26003198 35003600

Double
Entrance

26003316 35003800

Standard
2U

27002300

Double
Entrance

28003498 37003900
27003300
28003616 37004100

Standard
2U

28002500

Double
Entrance

30203998 40504400
28003800
30204116 40504600

Standard
3U

30002800

Double
Entrance

32204758 42505250
30004500
32204936 42505520

Standard
3U

32003000

Double
Entrance

34205258 44505750
32005000
34205436 44506020

Wall+Finished

250

30

Notes : 1. Please consult Hyundai when the loading capacity is over 5000kg or the car is non-standard size.
2. The loading capacity should be over 250kg/m2 minimally.
3. The actual reaction may slightly differ from above dimensions in line with machine beam position.

50
Min. 650

OP

50

3-PANEL UP-SLIDING DOORS (3U)


Minimum floor height : Opening height4 / 3 + 750mm
Minimum entrance height : 2100mm
Note : Consult Hyundai if the dimensions are less than the minimum.

20

(Unit : mm)

Min. 300

Speed
(m/min)

Pit
(PP)

M/C Room
Height (MH)

30 / 45

1250

2400

60

1500

2600

Notes : 1. Above is minimum size.


2. Refer to standard dimensions & reactions for overhead height.
3. The minimum machine room height should be 2800mm in case
of the traction machine with double isolation pad.

21

FREIGHT ELEVATORS

AUTOMOBILE ELEVATORS

Hydraulic Type (2S, 2U, 3U)

General Type (2U, 3U)

Plan of Hoistway & Machine Room

Section of Hoistway

Section of Hoistway

X
Min. 650

Suspension Hook
(By others)
Cinder
Concrete Min. 150
(By others)

Waterproof Finish
(By others)

OP

2-PANEL SIDE-OPENING DOORS (2S)

R1

Min. 300

3-PANEL UP-SLIDING DOORS (3U)


Minimum floor height : Opening Height X 4/3+750mm
Minimum entrance height : 2100mm

Control
Panel

Pit
(PP)

M/C Room Height


(MH)

Travel
(TR)

20 / 30 / 45

2100

4100

1400

2000

20m

Notes : 1. Temperatures should be maintained below 40Cwith ventilating fan and/


or air conditioner (if necessary) and humidity below 90%.
2. The above are minimum size.
3. The overhead height can be varied in line with entrance height and door type.
4. Consult Hyundai if the travel height is 20m or more.

Travel (TR)
Waterproof Finish
(By others)

250

Speed
(m/min)

Overhead
(OH)

Pit
(PP)

M/C Room Height


(MH)

30 / 45

4400

1200

2400

Wall+Finished

Overhead
(OH)

Ladder
(By others)

(Unit : mm)

(Unit : mm)

Ent. Height
(EH)

Receptacle
(By others)

Distribution Board (By others)

Notes : 1. Consult Hyundai if the actual size is less than the above minimum floor height.
2. The left and right minimum size should be 650mm and 300mm respectively for the
installation of driving part.

Speed
(m/min)

Notes : 1. Temperatures should be


maintained below 40C with
ventilating fan and/or
air conditioner (if necessary)
and humidity below 90%.
2.The specification of car doors
are optional.

Pit Depth (PP)

Vent Grille (By others)

25
50

Ent. Height (EH)


1800

MX

30

Ladder
(By others)

130
OP

Overhead (OH)

R2

Minimum floor height : Opening height3 / 2 + 700mm


Minimum entrance height : 1800mm

250
Wall+Finished

50
Min. 650

Y
B
200
200
200
200 30
200
200

2-PANEL UP-SLIDING DOORS (2U)

30

Receptacle
(By others)

Min. 300

Vent Fan (By others)

Minimum floor height : Opening Height3/2+700mm


Minimum entrance height : 2100mm

50

OP

R2

2-PANEL UP-SLIDING DOORS (2U)

R1

Travel (TR)

Total Height (TH)

50

OP

50

50
Min. 650

MY

MX

Power Unit

Machine Room
Access Door (By others)
Min. 900 (W)2000 (H)

200 30

Vent Grille
(By others)

CA

Ent. Height (EH)

Control
Panel

Pit Depth (PP)

CB

Power Unit

MY

(Hydraulic hose)

Machine Room
Access Door
Distribution Board
[By others]
Min
Min
Min
Min 900 (W)2000 (H) [By others]
Min

R2

R1

OPB

Vent Fan (By others)

CA

CB

Overhead (OH)

M/C Room
Height (MH)

600

Total Height (TH)

Min. 300

Plan of Hoistway & Machine Room

Suspension Hook (By others)

Note : The above are minimum size.

50

OP

50

3-PANEL UP-SLIDING DOORS (3U)


Minimum floor height : Opening height4 / 3 + 750mm
Minimum entrance height : 1800mm
Note : Consult Hyundai if the dimensions are less than the minimum.

Standard Dimensions & Reactions

(Unit : mm)

Entrance
WidthHeight
(OPEH)

Internal
CACB

External
AB

XY

MXMY

HF1500-2U

21002100

21002500

22002698

30503100

25002800

4200

400

HF2000-2U

23002100

23002700

24002898

32503300

25002800

4800

400

Model

HF2500-2U

Speed
(m/min)

20 / 30 / 45

Car

Hoistway

Type

Standard
Type

(Unit : mm)

Car

Clear
Opening
OP

Internal
CACB

External
AB

XY

MXMY

A2000-2U

2350

23505300

24505350

33005800

33005800

17500

12000

A2500-2U

2750

27506300

28506350

37006800

38506800

22500

12500
12000

Model

Speed
(m/min)

Hoistway

M/C Room

Hitch Beam
Reaction (kg)
R1
R2

25002100

25003000

26003198

34503600

25002800

5400

400

A2000-3U

2350

23505300

24505350

33005800

33005800

17500

HF3000-2U

27002300

27003300

28003498

36503900

25002800

6000

450

A2500-3U

2750

27506300

28506350

37006800

38506800

22500

12500

HF3500-2U

28002500

28003800

29003998

40004450

28003200

7900

750

A2000-2UD

2350

23505300

24505300

33005800

33005800

17500

12000

30002800

30004500

31004758

42005250

28004200

8800

900

A2500-2UD

2750

27506300

28506300

37006800

38506800

22500

12500

32003000

32005000

33005258

44005750

28004200

10500

1050

A2000-3UD

2350

23505300

24505300

33005800

33005800

17500

12000

A2500-3UD

2750

27506300

28506300

37006800

38506800

22500

12500

HF4000-3U
HF5000-3U

20 / 30

Notes : 1. Please consult Hyundai when the loading capacity is over 5000kg or the car is non-standard size.
2. The loading capacity should be over 250kg/m2 minimally.
3. The actual reaction may slightly differ from above dimensions in line with machine beam position.
4. Above dimensions are based on up-sliding door available for 2-panel side-opening (2S) doors of same capacity.

22

M/C Room

Hitch Beam
Reaction (kg)
R1
R2

Standard Dimensions & Reactions

Double
Entrance
Type

30 / 45

Notes : 1. The car external size can be varied in line with entrance type.
2. When non-standard capacities and dimensions are required, consult Hyundai.
3. The car door is applied in BS code region.

23

HOSPITAL BED ELEVATORS

TYPICAL ENTRANCE LAYOUTS

General Type (2S, 2SD)

Standard/Optional

Plan of Hoistway & Machine Room

Section of Hoistway

Entrance

Structural Opening of Entrance

MX

In case of Boxless Type Buttons and Fire mans Switch

30

Suspension Hook (By others)

M/C Room
Height (MH)

Wiring Inlet :50

700

Steel Bar for


Fixing Jamb

Total Height (TH)

Concrete Opening
OP+140

Wiring Inlet :50

B1600-2S30, 45
B1600-2S60
B1750-2S30~60
B1350-2SD30, 45

Double
Entrance
Type

B1350-2SD60
B1600-2SD30, 45
B1600-2SD60
B1750-2SD30~60

Internal
CACB

External
AB

1100

13002300

14002507

XY

MXMY

21002850

23003500

15002300

16002507

23002850

27504000

1200

16002300

17002507

24002850

28504000

1100

13002300

14002634

23003000

23003500

1200

15002300

16002634

25003000

27504000

16002300

17002634

26003000

Hitch Beam
Reaction (kg)
R1
R2
10500

11500

700
700

1000

Concrete Opening : 2200

500

700

Transom Panel
Hall Position
Indicator

9500

8500

11500

9500

Steel Bar for


Fixing Jamb
96EA

Emergency
Call Switch

8500

10500

(For emergency
call, only rescue
floor is applied)

HB

(By others)

Steel Bar for


Fixing Jamb
96EA (By others)

150

Wiring Inlet :50


(By others)

80

30

Clear
Opening (OP)

Concrete Opening
OP+300

Concrete Opening
OP+300

28504000

Notes : 1. When non-standard capacities and dimensions are required, consult Hyundai.
2. Above dimension are applied in case the door is standard. In case fire protection door is applied, hoistway size for 1 car should be applied above X dimension plus 100mm.
3. Consult Hyundai in case the code applied.

24

700

700

M/C Room

1200

1200

Concrete Opening : 2200

Jamb Height (JH)

Hoistway

1900

B1350-2S60

Car

Clear
Opening
OP

1000

B1350-2S30, 45

(Unit : mm)

700

Model

Finished Floor Level


(By others)

30

Standard Dimensions & Reactions

(By others)

80

700

2100

700

5000

JP100 Type (Optional)

Concrete Opening:JH+50

105

2400

250

1800

EA

Concrete Opening
OP+300

1650

4800

1000

90

96

300

1500

Steel Bar for


Fixing Jamb

1000

4600

Concrete Opening
OP+300

700

60

Finished
Floor Level
(By others)

Notes : 1. Machine Room temperature should be maintained below


40C with ventilating fan and/or air conditioner, if necessary,
and humidity below 90%.
2. In case of special hoistway, machine room height may be
higher than above size.
3. Above is minimum size.
4. The minimum machine room height should be 2800mm in
case of the traction machine with double isolation pad.

(By others)

700

1200

96EA

700

4400

Clear
Opening (OP)

Concrete Opening:JH+50

30/45

30

M/C Room Height


(MH)

Entrance Height (EH) : 2100

Pit
(PP)

Waterproof Finish
(By others)

Jamb Height (JH)

Overhead
(OH)

Ladder
(By others)

HB With HPI

Steel Bar for


Fixing Jamb

700

Receptacle
(By others)

(Unit : mm)

Entrance Height (EH) : 2100

Pit Depth (PP)

Machine Room Access Door (By others)


900 (W)2000 (H)

Speed
(m/min)

(By others)

Ent. Height (EH)


2100

Distribution Board
(By others)

Standard
Type

Finished Floor Level


(By others)

30

Control
Panel

Type

80

JP050 Type (Standard)


Travel (TR)

OP

(By others)

700

96EA

1050

500

Concrete Opening
OP+140

700

Concrete Opening (Jamb Height + 50mm)

700

1000

700

(By others)

Finished
Floor Level
(By others)

MY

CA

Steel Bar for


Fixing Jamb
96EA

Clear
Opening (OP)

R2

30

Concrete Opening : 2200

Entrance Height (EH) : 2100

HB With HPI

(By others)

150

700

Cinder Concrete
Min. 150
(By others)

Overhead (OH)

Vent Fan (By


others)
B

CB

R1

Vent Grille (By others)

Finished Floor Level


(By others)

JP200 Type (Optional)

25

TYPICAL ENTRANCE LAYOUTS

TYPICAL ENTRANCE LAYOUTS

Only for Floor with Control Panel of the Machine-Room-Less Elevators

2-Panel Up-Sliding Doors (2U) / 4-Panel Center-Opening Doors (2CO)

Entrance Design

2-Panel Up-Sliding Doors (2U)

Structural Opening of Entrance


D
- OF CAR

Structural Opening of Entrance

30

Entrance Design

500

700

250

Indicator lamp

150
50

Hall Button
with Indicator
150

Steel Bar for


Fixing Jambs

Finished Floor Level


(By others)

Concrete Opening
Clear Opening
+ CP + 100
2

EH+100

500
500

Concrete Opening

500

500
1100

Entrance Height(EH)

Freight Elev. : 2100~3000


Automobile Elev. : 1800

500

30

Steel Bar for


Fixing Jambs
96EA
(By others)

1000

Clear Opening (OP)

700

CP
(*)

UP
700

Hall Button
with Indicator

Concrete Opening (JH)

Entrance Height (EH) : 2100

Jamb Height (JH)

96EA (By others)

Clear Opening
+ 100
2
Clear Opening (OP)

Finished
Floor Level
(By others)

Concrete Opening (OP)


OP+200

CP110 Type (Standard)

CP110 Type (Standard)

D
- OF CAR

Transom Panel

Plan of Entrance

Section of Entrance

700

100

200

Position
Indicator

300

30
Finished
Floor Level
(By others)

CP210 Type (Optional)

Concrete Opening
Clear Opening
+ CP + 100
2

200
100

Clear Opening (OP)

100

Minimum floor height : Opening Height3 / 2 + 700mm


Minimum entrance height : 1800mm
Notes : 1. The standard location of Hall Button with Indicator for automobile elevators is on left
wall but it is on the right wall for freight elevators.
2. Consult Hyundai if the demensions are less than the minimum.

Clear
Clear
Opening
Opening
ClearOpening
Opening
Clear
Opening
Clear
Opening
Clear
Opening
+100
222222

CP210 Type (Optional)

4-Panel Center-Opening Doors (2CO)


35

(*)

Hall Button
with Indicator

Entrance Height (EH)

150

1000

Clear Opening (OP)

700

CP

96EA (By others)

700

Hall Button

Concrete Opening : JH+50

Entrance Height (EH) : 2100

Jamb Height (JH)

Steel Bar for Fixing Jambs

Plan of Entrance
(Unit : mm)

Persons

Speed(m/min)

Width of
Control Panel(CP)(*)

8~17

Under 105
60
90
105

530
530
630
630

20, 24

26

200

27

TYPICAL ENTRANCE LAYOUTS


2-Panel Center-Opening Doors (CO)

2 Pannel Side-Opening Doors (2S)

Section Entrance

Plan of Entrance

Section of Entrance

(150)
Clear Opening (OP)

HB With HPI

Hall Button

70

150

150

Entrance Height (EH) : 2100

100

50

130

Jamb
Width
JambWidth
Width
Jamb
Jamb
Jamb
Width
Width

50

(180)
Clear Opening (OP)

70

Clear Opening (OP)

JP050 Type

Wall Finish
Thickness

Wall
Thickness

Jamb Width

90

JP050 Type

30

70
145

Entrance Height (EH) : 2100

30

70

Jamb Width

Wall Finish
Thickness

30

100

Wall
Thickness

Jamb Width
50

90

130

Plan of Entrance

Clear Opening (OP)

150

Hall
Button

150

JP100, JP200 Type

JP100, JP200 Type

130

90

Note : The above layout is for left side opening. Right side opening doors are available, if requested.

JP050 Type

50

50

50

50

50

50

JP050 Type

Ceiling Line
100
90
(130)

Building Structure
(By Other Contractors)

90
(130)

130

Note : The dimension in (

28

Jamb Height (JH)

Entrance Height (EH) : 2100

Jamb Width

50

50
130

Building Structure
(By Other Contractors)

130

Wall and Floor Finishing


(By Other Contractors)

Wall and Floor Finishing


(By Other Contractors)

JP100 Type

Ceiling Height (CH)

Jamb Width

50

50

90
(130)

Jamb Width

Entrance Height (EH) : 2100

Jamb Width

10

50

Jamb Width

Ceiling
Line

10

Jamb Height (JH)

Entrance Height (EH) : 2100

Jamb Height (JH)

Ceiling Height

Entrance Height (EH) : 2100

Jamb Height (JH)


Jamb Width

Upper
Frame

10

50

Entrance Height (EH) : 2100

10

Entrance Height (EH) : 2100

100

Upper
Frame

JP200 Type

JP200 Type

(with upper frame)

(without upper frame)

JP100 Type

JP200 Type

JP200 Type

(with upper frame)

(without upper frame)

) is applied for 120m/min and over.

29

NEW WORLD CLASS ESCALATORS(30


)

NEW WORLD CLASS ESCALATORS (35


)

NW-BT, NW-BB

NW-BT, NW-BB

(note 1) Floor Opening AA


C

1.732H

(note 2) B
(note 1) Floor Opening AA

(note 4) Min. 2500

2230

50

1.428H

(note 3) 2650

Floor Opening Enclosures (By Others)


(note 4) Min. 2500

1910

50

Working
Point

Qty of
Flat Step

NW-BT
NW-BB

2
3

2560
2967

2230
2637

1820
2227

1490
1897

2511
2918

2118
2525

4500
4910

612
855
1150
1100
1250

813
1056
1350
1300
1450

1014
1257
1550
1500
1650

Rise H (mm)

H 6000 5000 H 7600


7600 H 10500
1
1
2
0.65H + 2300 0.36L1 + 900
0.36L1 + 1100
0.36L1 + 1100
0.65H + 1600 0.36L2 + 300
0.36L2 + 400
0.36L2 + 450
0.36(L1 + L2) + 450 0.36(L1 + L2) + 700 0.36(L2 + L3) + 250
0.36(L1 + L3) + 600

90

R2
R3

L20020020

R4
50 50

w3
w2
w1

Typical Steel Support


935
90

150

NW1000

R4

H 6000 5000 H 7600


7600 H 10500
1
1
2
0.72H + 2600 0.41L1 + 900
0.41L1 + 1100
0.41L1 + 1100
0.72H + 1900 0.41L2 + 300
0.41L2 + 400
0.41L2 + 450
0.41(L1 + L2) + 450 0.41(L1 + L2) + 700 0.41(L2 + L3) + 250
0.41(L1 + L3) + 600

Type

NW1200

Rise H (mm)

H 6000 5000 H 7600


7600 H 10500
1
1
2
0.78H + 2900 0.45L1 + 1000
0.45L1 + 1250
0.45L1 + 1250
0.78H + 2200 0.45L2 + 300
0.45L2 + 450
0.45L2 + 500
0.45(L1 + L2) + 500 0.45(L1 + L2) + 750 0.45(L2 + L3) + 300
0.45(L1 + L3) + 650

Number of
Intermediate Support
Floor Opening
Enclosure
(By Others)

Min. 200

Type
Rise H (mm)
R1
R2
R3

Number of
Intermediate Support

R1

L20020020
50 50

R2

w4
w5

R3
R4

Top of Finish Floor


(By Others)
150

NW800

Min. 200

1070

793

950

968
Floor Opening
Enclosure
(By Others)

L20020020

Type

NW800

W1
W2
W3

(Unit : mm)

NW1000

NW1200

612

813

1014

855

1056

1257

1150

1350

1550

W4

1100

1300

1500

W5

1250

1450

1650

50 50

w4

Typical Steel Support


Top of Finish Floor
(By Others)
150

Type

Section Dimensions

w3
w2
w1

Typical Concrete Support

(Unit : kg)

935

W1
W2
W3
W4
W5

90

NW1200

W5

Min. 200

90

NW1000

11(Shim)

NW800

R1

Notes : 1. AA = 1.428 H + 2650 + 2230 + 100


When maximum floor opening exceeds AA=14,230mm, intermediate support(s) are
required. Consult Hyundai for the intermediate support data.
2. Qty of flat step : 2
3. In case inverter system is applied, dimension 2650, 2522 shall increase 500mm.
(800Type, 1000Type : increase 700mm)
4. Dimension between the end of handrail to the wall ; Min. 2500mm
5. Dimensions are based on EN115.
6. Vertical Rise H 6m.

11(Shim)

Type

Number of
Intermediate Support

Min. 4500

(Unit : mm)

Reactions

Min. 200

11 (Shim)

150

Model
(Inclination)

Section Dimensions

Typical Concrete Support

11(Shim)

Working
Point

2358

Notes : 1. AA = 1.732 H + B + C + 100


When maximum floor opening exceeds AA=14,962mm, intermediate
support(s) are required. Consult Hyundai for the intermediate support data.
2. In case inverter system is applied, dimension B, F shall increase 500mm.
(800Type, 1000Type : increase 700mm)
3. When vertical rise is over 6000mm, 3-flat step is applied.
4. Dimension between the end of handrail to the wall ; Min. 2500mm
5. Dimensions are based on EN115.
6. Vertical Rise H 10.5m.

30

1070

R2
L2

Reinforced Plate
(By Others)

Wiring Inlet
(By Others)

35

L1

L3

Top of Finish Floor


(By Others)

R1

(note 3) 2522

Intermediate
Support
(By Others)

Top of Finish Floor


(By Others)

Working
Point

H = Rise

1490

937

1070

Min. 1170

(note 4) Min. 2500

Min. 1170

937

R3
30

Soffit Guard
(By Others)
HEAD ROOM
Min. 2300

793

950
R4

50

Wiring Inlet
(By Others)

(note 2) F

R2

Floor Opening Enclosures (By Others)

R1

H = Rise

(note 4) Min. 2500

Working
Point

908

Head ROOM
Min. 2300

Soffit Guard
(By Others)

1070

50

L20020020
50 50

Reactions
Vertical Rise
Reactions
H(mm)
3000
~6000

(Unit : kg)

ML800

ML1000

ML1200

R1

0.51H + 2400 0.59H + 2700 0.66H + 3000

R2

0.51H + 1800 0.59H + 2100 0.66H + 2300

Note : When vertical rise is over 6000mm or AA is over 14230mm, consult


Hyundai for reactions data.

Reinforced Plate
(By Others)

31

MILLENNIUM ESCALATORS(30
)

MILLENNIUM ESCALATORS (35


)

ML-BT, ML-BB

ML-BT, ML-BB

(note 1) Floor Opening AA


C

(note 2) B

1.732H

(note 1) Floor Opening AA

(note 4) Min. 2500

(note 3) 2367

1.428H

2088

50
Floor Opening Enclosures (By Others)

1777

50

Model
Qty of Vertical Rise H Speed B
(Inclination) Flat Step
(mm)

1490
1897
1967
1966
2372

2116
2523
2707
3306
3712

2250
2657
2777
2727
3133

4230
4640
4750
4720
5120

Section Dimensions

Base Plate
15019

ML1200

813
1056
1349
1299
1449

1014
1257
1550
1500
1650

Rise H (mm)

R4

H 6000 5000 H 7600


7600 H 10500
1
1
2
0.73H + 2900 0.42L1 + 900
0.42L1 + 1200
0.42L1 + 1250
0.73H + 2300 0.42L2 + 350
0.42L2 + 500
0.42L2 + 450

0.42(L1 + L2) + 600 0.42(L1 + L2) + 850 0.42(L2 + L3) + 400



0.42(L1 + L3) + 700

Type

ML1200

936
90

R2
R3

Reinforced Plate
(By Others)

Notes : 1. When maximum floor opening exceeds


AA=14,835mm, intermediate support(s)
are required. Consult Hyundai for the
intermediate support data.
2. Consult Hyundai if the isolation pad is
applied.

32

w4
W5

Rise H (mm)
Number of
Intermediate Support

R1
R2
R3
R4

Min. 200

H 6000

H 6000 5000 H 7600


7600 H 10500
1
1
2
0.79H + 3200 0.47L1 + 1000
0.47L1 + 1300
0.47L1 + 1350
0.79H + 2600 0.47L2 + 350
0.47L2 + 500
0.47L2 + 500

0.47(L1 + L2) + 650 0.47(L1 + L2) + 900 0.47(L2 + L3) + 400



0.47(L1 + L3) + 750

1000

793

950

968

Section Dimensions
Floor Opening
Enclosure
(By Others)

ML800

ML1000

R1

L20020020

(Unit : kg)

Type

R3

Number of
Intermediate Support

50 50

Top of Finish Floor


(By Others)

R4

R2

w3
w2
w1

Typical Concrete Support

5000 H 7600
7600 H 10500

1
1
2
0.66H + 2600 0.37L1 + 900
0.37L1 + 1200
0.37L1 + 1250
0.66H + 2000 0.37L2 + 350
0.37L2 + 500
0.37L2 + 450

0.37(L1 + L2) + 600 0.37(L1 + L2) + 850 0.37(L2 + L3) + 400



0.37(L1 + L3) + 700

R1

Floor Opening
Enclosure
(By Others)

Min. 200

11(Shim)

ML1000

594
837
1130
1080
1230

Number of
Intermediate Support

w3
w2
w1

Typical Steel Support

Min. 150

ML800

W1
W2
W3
W4
W5

Rise H (mm)

50 50

Top of Finish Floor


(By Others)

Type

Type

Notes : 1. AA = 1.428 H + 2367 ( 2767) + 2088 + 100


2. Q'ty of flat step : 2
3. In case inverter system is applied, 2367, 2139 shall increase 500mm.
(800Type, 1000Type : increase 700mm)
4. Dimension between the end of handrail to the wall ; Min. 2500mm
5. If EN115 is applied, consult Hyundai.
6. Vertical Rise H 6m.

(Unit : mm)

Reactions

L20020020

Min. 4000

936

90

Min. 150

11 (Shim)

Min. 200

2316

L20020020
Base Plate
15019

Type

ML800

W1
W2

(Unit : mm)

ML1000

ML1200

612

813

1014

855

1056

1257

W3

1148

1349

1550

W4

1098

1299

1500

W5

1248

1449

1650

50 50

w4
w5

Vertical Rise
H(mm)

Typical Steel Support


Top of Finish Floor
(By Others)

Reactions

Min. 200

3000
~6000

Reactions

(Unit : kg)

ML800

ML1000

ML1200

R1

0.52H+2700 0.6H+3000 0.67H+3300

R2

0.52H+2200 0.6H+2500 0.67H+2700

90

Typical Concrete Support

Working
Point

90

H 6000

D
1695
2102
2237
2236
2642

11(Shim)

C
2080
2487
2606
2556
2962

Min. 150

2286
30 2693
2876
3476
30 ~ 40
3882

11(Shim)

ML-BT
ML-BB
(30)

H 6000
6000H 7600
7600H 10500

Min. 150

2
Notes : 1. AA = 1.732H + B + C + 100
2. In case inverter system is applied, B, F shall increase 500mm.
(800Type, 1000Type : increase 700mm)
3. When vertical rise is over 6000mm, 3-flat step is applied.
4. Dimension between the end of handrail to the wall ; Min. 2500mm
5. If EN115 is applied, consult Hyundai.
6. Vertical Rise H 10.5m.

Wiring Inlet
(By Others)

(note 3) 2139
H = Rise

R2

J
L2

R1

35

L1

L3

1000

Working
Point

Working
Point

Intermediate
Support
(By Others)

Top of Finish Floor


(By Others)

1498

937

1000

Min. 1100

R2

(note 4) Min. 2500

Min. 1100

937

R3
30

Soffit Guard
(By Others)
Min. 2100

793

950

50

Wiring Inlet
(By Others)

(note 2) F
R4

Floor Opening Enclosures (By Others)

R1

H = Rise

(note 4) Min. 2500

Working
Point

908

Head Room
Min. 2300

Soffit Guard
(By Others)

1000

50

(note 4) Min. 2500

Note : When vertical rise is over 6000mm or AA is over 14835mm, consult


Hyundai for reactions data.
L20020020
50 50

Reinforced Plate
(By Others)

Notes : 1. When maximum floor opening exceeds AA=14,835mm,


intermediate support(s) are required, Consult Hyundai
for the intermediate support data.
2. Consult Hyundai if the isolation pad is applied.

33

H-SERIES ESCALATORS

H-SERIES ESCALATORS

HA-BT, HA-BB

HD-BT, HD-BB

(note 1) Floor Opening AA

(note 1) Floor Opening AA


(note 3) 4464
2640

Floor Opening Enclosures


(By Others)

Working
Point

H = Rise

0
110

908

Min. 290

793

(note 3) 4342
R4
Wiring Inlet
(By Others)

0
100

Wiring Inlet
(By Others)
Intermediate Support
(By Other)

2241

1300

Working
Point
L3

R1

"B"

"B"

937

(note 1)
Intermediate
Support
(By Others)

843

Min. 2300
(note 5) H = Rise

R1

1280

937

"A"

1400

Working
Point

Min. 2300
Min. 1400

1200

50

2657

"A"

L1

"B"

30

R2

30

937

R3

(note 3) 4014

Head Room

Soffit Guard
(By Others)

2150

1.732H

2884

(note 2) Min. 2500

Floor Opening Enclosures (By Others)

(note 2) Min. 2500

50

50

937

1.732H

1210

2943

50

Working
Point
R2

R3

R4

R5

Min. 5100

3065

L 2 (Max.12000)

L 3 (Max.12000)

L 4 (Max.12000)

L 1 (Max.12000)

Min. 5700
L2

Notes : 1. N : Number of intermediate supports


Max. distance between intermediate supports is 12000mm
AA = 1.732 H + 4014 + 2884 + 100
2. Dimension between the end of handrail to the wall : Min. 2500mm
3. 4014 is a dimension of inverter applied system.
4. Dimensions are based on EN115.
5. Vertical Rise 15m < H 20m.

Notes : 1. N : Number of intermediate supports


Max. distance between intermediate supports is 12000mm
AA = 1.732 H + 4464 + 4342 + 100
2. Dimension between the end of handrail to the wall : Min. 2500mm
3. 4464, 4342 are dimensions of inverter applied system.
(800Type : 4664, 4542)
4. If EN115 is applied, consult Hyundai.
5. Vertical Rise 10.5m < H 15m.

w4
w 4 + 200

Typical Steel Support

90

11(Shim)

Min. 210

L20020020

Reinforced Plate
(By Others)

Note : Consult Hyundai if the isolation pad is applied.

W1

594

813

1014

W2

986

1205

1406

W3

1330

1549

1750

W4

1280

1499

1700

W5

1430

1650

1850

Top of Finish Floor


(By Others)

Min. 200

90

HA1200

11 (Shim)

HA1000

Min. 210

HA800

L20020020

Base Plate 
15019

Section Dimensions
Type

HD800

(Unit : mm)

HD1000

HD1200

W1

612

813

1014

W2

965

1164

1364

W3

1301

1500

1700

W4

1251

1450

1650

W5

1451

1650

1850

50 50

Reactions
Type

Min. 200

50 50

34

Type

w5
w3
w2
w1

HA800

(Unit : kg)

HA1000

Typical Steel Support

HA1200

Vertical Rise
H (mm)
R1

0.47L1 + 1200

0.51L1 + 1400

0.54L1 + 1700

R2

0.47L2 + 400

0.51L2 + 500

0.54L2 + 600

Top of Finish Floor


(By Others)

10500 H 15000

R3

0.47(L2 + L3) + 100 0.51(L2 + L3) + 150 0.54(L2 + L3) + 300

R4

0.47(L1 + L3) + 350 0.51(L1 + L3) + 450 0.54(L1 + L3) + 700

Min. 200

90

50 50

Floor Opening
Enclosure
(By Others)

Typical Concrete Support

(Unit : mm)

11 (Shim)

90
L20020020

Base Plate
15019

Top of Finish Floor


(By Others)

936

Min. 200

11(Shim)

Min. 210

Top of Finish Floor


(By Others)

Section Dimensions

Min. 210

w5
w3
w2
w1

Typical Concrete Support

L20020020
50 50
Reinforced Plate
(By Others)

w4
w5

Note : Consult Hyundai if the isolation pad is applied.

35

MODULAR ESCALATORS

MOVING WALKS

M-BB

HORIZONTAL TYPENPM-BT

5FOTJPOTUBUJPO

%SJWFTUBUJPO

Floor Opening AA = (L)

(note 1) Floor Opening AA


1770

50
(note 3) 3698

1073

Wiring Inlet
(By Others)

H=Rise

0
106

803
1073

1100

Wiring Inlet (By Other)

L 3 ~L (n-1) (Max.8000)

L n (Max.8000)

L 1 (Max.7000)

Reactions

L20020020

Inclination Floor Opening AA = (L)

Type

M800

W1

594

1014

W2
W3

895
1275

1695

W4

1244

1664

W5

1375

1795

Top of Finish Floor


(By Others)

1342

90

Rn (kg)
330 (Ln -1 + Ln)

NPM1200

420 L + 1700

420 L2 + 700

350 (L2 + L3)

340 (L3 + L4)

350 (Ln -1 + Ln)

w5
w3
w2
w1

Min. 200

R2=485(AA+0.1) + 3800 +600


AA+0.1

Section Dimensions

(Unit : mm)

Type

NPM1000

NPM1200

W1

814

1014

W2

1057

1257

W3

1350

1550

W4

1300

1500

W5

1500

1700

w4
w5

(Unit : kg)

M1200

R1=485(AA+0.1) - 3800 +1500 R1=635(AA+0.1) - 3800 + 1800


AA+0.1
AA+0.1
R2=635(AA+0.1) + 3800 + 800
AA+0.1

Typical Steel Support


Top of Finish Floor
(By Others)

Min. 200

L20020020

L20020020

50 50

Note : Consult Hyundai if the isolation pad is applied.

R4 (kg)
320 (L3 + L4)

L20020020

Min. 150

M800

Reinforced Plate
(By Others)

R3 (kg)
330 (L2 + L3)

50 50

Reactions
Min. 200

R2 (kg)
400 L2 + 400

Base Plate
15019

w4
w 4 + 200

Typical Steel Support

R1 (kg)
400 L1 + 1300

Typical Concrete Support

(Unit : mm)

M1200

Type
NPM1000

90

Floor Opening
Enclosure
(By Others)

9110~80000

11(Shim)

Section Dimensions

(L1 ~ Ln : m)

11 (Shim)

933

90

Min. 150

11(Shim)

Min. 200

11(Shim)

R1

Notes : 1. In case inverter system is applied, dim. 2190, 4000 shall increase 500mm.
(1000Type : increase 700mm)
2. Dimension between the end of handrail to the wall : Min. 2500mm
3. Dimensions are based on EN115.

Min. 150

w5
w3
w2
w1

50 50

Min. 150

Rn

(note 1) Min. 4000

L 2 (Max.7000)

Notes : 1. AA=1.732 x H + 3698 + 2709 + 100


2. Dimension between the end of handrail to the wall : Min. 2500mm
3. 3698, 3427 are dimensions of inverter applied system.
4. If EN115 is applied, consult Hyundai.

Typical Concrete Support

36

Working
Point

90

933
Min. 1173

R1

Top of Finish Floor


(By Others)

Intermediate Support Beam

Working
Point

Min. 5000

Base Plate
15019

R4~R(n-1)

"B"

Min. 3000

(note 1)
Intermediate
Support
(By Others)

400R

2967

Top of Finish Floor


(By Others)

"B"

(note 3) 3427

699

Min. 2300

Working
Point

30

R2

"B"

Working
Point

R2

R3

2074

(note 2) Min. 2500

"A"

1200

1200

Floor Opening Enclosures (By Others)

660
719

"A"

937

660

(note 2) Min. 2500

937

2763

Soffit Guard
(By Others)

50

(note 1) 2190

50

1100

1.732H

2709

50

50 50
Reinforced Plate
(By Others)

Note : Consult Hyundai if the isolation pad is applied.

37

MOVING WALKS

WORKS TO BE DONE BY OTHER CONTRACTORS

HORIZONTAL & INCLINED TYPENPM-BT

The following works are not included in the elevator contract, and shall be done by other contractors
in accordance with the Hyundai Elevator's drawings and the applicable codes and regulations.
The reference rules shown are from Code ANSI.

Floor Opening AA (L) = 4.70465 H + 5187


50

1787

4.70465H

(note 1) 3300

50

2643

Head Room
790
719

R1

"B"
Wiring Inlet
(By Others)

Hoistway

1. Clear, plumb hoistway with fire resistant hatch walls as required by the applicable

1. Light outlet for each elevator, in center of hoistway (or in machine room) as

2. 75 bevel guards on all projections, recesses, or setbacks over 50mm except on


side used for loading or unloading. (Rule 100.6)

Working
Point

3. Venting of the hoistway as required by the applicable code or responsible


R2

authority. (Rule 100.4)


Min. 6000

R3

R4

L 2 (Max.10000)

L 3 (Max.10000)

Maximum allowable vertical spacing of rail supports without backing. (Rule 200.4

L 1 (Max.10000)

guide rail bracket supports. (Rule 200.4, 200.9 and 301.1)

4. Lighting, convenience outlets, ventilation, heating of machine room, and

5. Recesses supports and patching as required to accommodate hall button boxes,


signal fixtures, etc.

Reactions

(L1 ~ Ln Unit : m)

NPM1000

10
&
12

1430
~
7000

R3 (kg

R2 (kg)

R3 (kg)

7. Dry pit reinforced to sustain normal vertical forces from rails and buffers. (Rule
106.1b and 109) Consult Hyundai Elevator Company for rail forces and buffer

NPM1200
R1 (kg)

R4 (kg)

R5 (kg)

503 L1 + 780 487 L2 + 50 498 (L1 + L2)

R4 (kg)

R5 (kg)

503 L1 + 780 487 L2 + 50 489 (L2 + L3) 498 (L1 + L3)

453 L1 + 700 439 L2 + 45 449 (L1 + L2)

453 L1 + 700 439 L2 + 45 440 (L2 + L3) 449 (L1 + L3)

453 L1 + 700 439 L2 + 45 440 (L2 + L3) 440 (L3 + L4) 449 (L1 + L4) 503 L1 + 780 487 L2 + 50 489 (L2 + L3) 489 (L3 + L4) 498 (L1 + L4)

impacts. Where there is space below the pit floor that can be occupied, consult
Hyundai Elevator Company for special requirements. (Rule 300.4) Cylinder hole,
casings under the pit as required, and backfilling around the cylinder casings when
direct plunger type is to be installed.
ladder extending 1060mm minimum above sill of access door. (Rule 106.1d)
and sills are in place. Door frames are to be anchored to walls and properly

Typical Concrete Support


Min. 200

90

Min. 150

11(Shim)

Top of Finish Floor


(By Others)

L20020020

Base Plate
15019

Section Dimensions

(Unit : mm)

Type

NPM1000

NPM1200

W1

814

1014

W2

1057

1257

W3

1350

1550

W4

1300

1500

W5

1500

1700

grouted in place to maintain legal fire rating.


10. For application as indoor or outdoor observation elevator, a glass enclosure of at
least 3.6m in height at the bottom landing is recommended for safety. For use as
an outdoor observation elevator, a full-height glass enclosure is required.

conditioner, if necessary, and humidity below 90%.


6. A fused disconnect switch or circuit breaker for each elevator and light switch
located per the applicable code and where practicable located adjacent to the
door of the machine room. (Rule 210.5 and 306.7)
7. Feeder and branch wiring to the controller, including main-line switch and
convenience outlets.
8. Suitable power feeder and branch wiring circuits as required for elevators with
power-operated doors, including disconnect switch or circuit breaker.

Emergency Provisions
9. Elevator firemans and other emergency services wiring and interconnections to
automatic sprinkler systems or heat and smoke sensing devices furnished by
others and installed to terminal points on the elevator controllers.
10. When emergency power operation of elevators is required, the electrical
contractor should coordinate with Hyundai Elevator Company or local distributor
for operation requirements.

Machine Room
11. Enclosed and protected machine room. (Rule 101.1)
12. Access to the machine room and machinery space as required by the applicable

50 50

machinery space. (Rule 101.5)


5. Temperature should be maintained below 40 by a ventilating fan and/or air

8. Where access to the pit is by means of the lowest hoistway entrance, vertical iron
9. Entrance walls and finished floor are not to be constructed until after door frames

w5
w3
w2
w1

and the machine room.

Machine Room

required.

R2 (kg)

access door. (Rule 106.1e)


3. Wiring and piping work of emergency bell, interphone, etc. Outside the hoistway

and 301.1) Divider beams 100mm between hoistway at each floor and roof, for

6. All barricades either outside elevator hoistways or between inside hoistways as

R1 (kg)

indicated by Hyundai Elevator Company.


2. Convenience outlet and light fixture in pit with switch located adjacent to the

4. Supports for rail brackets at each floor, roof, and machine room. (Rule 200.9)

Notes : 1. In case inverter system is applied, dim. 3300 shall increase 500mm.
(1000Type : increase 700mm)
2. Dimension between the end of handrail to the wall : Min. 2500mm
3. Dimensions are based on EN115.

Number of
Incli- Vertical intermediate
nation H Rise
(mm) Support

Electrical Work

Hoistway
code. (Rule 100.1a)

Intermediate Support
(By Others)

"B"

12

940

"A"

1100

1200

Working
Point

Min. 2300

Height (H)

1129

Building Work

1100

"A"

940

Floor Opening Enclosures (By Others)

code or responsible authority. (Rule 101.3)

11. Elevator firemans and other emergency service requirements may differ from
each country. Consult Hyundai Elevator Company or local distributor for other
local requirements.
12. When provisions for earthquake protection are required, consult Hyundai Elevator
Company for special requirements.

13. Reinforced concrete machine room floor slab or grating, as specified, which must
not be placed over the hoistway until elevator machinery is set in position. (Rule

Typical Steel Support


Min. 200

100.3 for Traction Elevator)

90

Heat Emission of Machine Room

Clear access above ceiling or trench in floor, for oil line and wiring duct from
machine room, if machine room is remote from elevator hoistway. (For Hydraulic

11(Shim)

Min. 150

Top of Finish Floor


(By Others)

w4
w5

Q (Kcal/H) = WVFN

Elevator) Cutout through machine room wall, for oil line and wiring duct as

W : Capacity (kg)

V : Speed (m/min)

required by Hyundai Elevators shop drawings. (For Hydraulic Elevator)

F : Factor ; 1/40 (VVVF)

N : Number of cars

14. Hoisting beams, trap doors, and other means of access to machine room for
L20020020
50 50
Reinforced Plate
(By Others)

maintenance and equipment removal purposes. (Rule 101.3d)


15. Cable guards in the machine room or secondary level. (Rule 104.1)
16. Supports for machine and sheave beams and reactions including wall pockets and
patching after beams are set in place. (Rule 105.1 to 105.5)

Note : Consult Hyundai if the isolation pad is applied.

38

39

ELECTRIC POWER REQUIREMENTS (By others)


(50/60Hz, 380V)

Persons / Kg

6 / 450

8 / 550

9 / 600

10 / 700

11 / 750

13 / 900

15 / 1000

17 / 1150

20 / 1350

24 / 1600

MCCB (A)

Cable (mm2)

Earth (mm2)

Motor
(kW)

1Car

2Cars

1Car

2Cars

1Car

2Cars

1Car

2Cars

60

5.5 (2.8)

20 (20)

30 (20)

4 (3)

7 (5)

4 (4)

6 (4)

4 (6)

4 (6)

90

7.5 (4.2)

20 (20)

30 (40)

6 (4)

10 (8)

4 (4)

6 (10)

4 (6)

6 (6)

105

7.5 (4.9)

20 (20)

40 (40)

7 (5)

12 (9)

4 (4)

10 (10)

4 (6)

6 (6)

60

5.5 (3.4)

20 (20)

30 (20)

5 (4)

9 (6)

4 (4)

6 (4)

4 (6)

4 (6)
4 (6)

90

7.5 (5.1)

20 (20)

30 (40)

7 (5)

13 (10)

4 (4)

6 (10)

4 (6)

105

11 (5.9)

30 (20)

50 (40)

8 (6)

15 (11)

6 (4)

16 (10)

4 (6)

6 (6)

60

5.5 (3.7)

20 (20)

30 (30)

5 (4)

9(7)

4 (4)

6 (6)

4 (6)

4 (6)

90

11 (5.6)

30 (20)

50 (40)

8 (6)

14 (11)

6 (4)

16 (10)

4 (6)

6 (10)

105

11 (6.5)

30 (20)

50 (40)

9 (7)

16 (12)

6 (4)

16 (10)

4 (6)

6 (10)
6 (6)

60

7.5 (4.3)

20 (20)

40 (30)

6 (5)

11 (8)

4 (4)

10 (6)

4 (6)

90

11 (6.5)

30 (20)

50 (40)

9 (7)

16 (12)

6 (4)

16 (10)

4 (6)

6 (6)

105

11 (7.6)

30 (20)

60 (40)

11 (9)

19 (14)

6 (4)

16 (10)

4 (6)

10 (6)

60

7.5 (4.6)

20 (20)

40 (30)

6 (5)

12 (9)

4 (4)

10 (6)

4 (6)

6 (6)

90

11 (6.9)

30 (20)

50 (40)

10 (7)

17 (13)

6 (4)

16 (10)

4 (6)

6 (10)

105

11 (8.1)

30 (30)

60 (50)

11 (9)

20 (15)

10 (6)

16 (16)

4 (6)

10 (10)

120

(9.2)

(30)

(50)

(10)

(18)

(6)

(16)

(6)

(10)

60

11 (5.6)

30 (20)

50 (30)

8 (6)

14 (11)

6 (4)

10 (6)

4 (6)

6 (6)

90

15 (8.3)

40 (30)

60 (50)

12 (9)

21 (16)

10 (6)

16 (16)

6 (6)

10 (10)

105

15 (9.7)

40 (30)

75 (50)

14 (10)

24 (18)

10 (6)

25 (16)

6 (6)

10 (10)

120

(11.1)

(30)

(60)

(12)

(21)

(6)

(16)

(6)

(10)

150

(13.8)

(50)

(100)

(15)

(28)

(10)

(25)

(6)

(16)

60

11 (6.2)

30 (20)

50 (40)

9 (7)

15 (12)

6 (4)

16 (10)

4 (6)

6 (10)

90

15 (9.2)

40 (30)

75 (50)

13 (10)

23 (18)

10 (6)

25 (16)

6 (6)

10 (10)

105

15 (10.8)

40 (30)

75 (60)

15 (11)

27 (20)

10 (6)

25 (16)

6 (6)

10 (10)

120

(12.3)

(40)

(75)

(13)

(23)

(10)

(25)

(6)

(16)

150

(15.4)

(50)

(100)

(17)

(31)

(10)

(25)

(6)

(16)

60

11 (7.1)

30 (20)

50 (40)

10 (8)

18 (13)

6 (4)

16 (10)

4 (6)

6 (10)

90

15 (10.6)

40 (30)

75 (60)

15 (11)

27 (20)

10 (6)

25 (16)

6 (6)

10 (10)

105

18.5 (12.4)

50 (30)

100 (60)

17 (13)

31 (23)

16 (6)

35 (16)

6 (6)

10 (16)

120

(14.1)

(40)

(75)

(15)

(27)

(10)

(25)

(6)

(16)

150

(17.7)

(60)

(100)

(20)

(35)

(10)

(25)

(6)

(16)

60

15 (8.3)

30 (20)

60 (40)

12 (9)

21 (16)

10 (4)

16 (10)

6 (6)

6 (6)

90

18.5 (12.5)

50 (40)

100 (75)

17 (13)

31 (24)

16 (10)

25 (25)

6 (6)

10 (10)

105

22 (14.5)

50 (40)

100 (75)

20 (15)

37 (28)

16 (10)

35 (25)

6 (6)

10 (10)

120

(16.6)

(40)

(100)

(17)

(31)

(10)

(25)

(6)

(10)

150

(20.7)

(75)

(125)

(23)

(41)

(16)

(35)

(10)

(25)

60

15 (9.9)

40 (30)

75 (50)

14 (10)

25 (19)

10 (6)

25 (16)

6 (6)

10 (6)

90

22 (14.8)

50 (50)

100 (75)

21 (16)

37 (28)

16 (10)

35 (25)

6 (6)

10 (10)

105

22 (17.2)

60 (50)

125 (100)

24 (18)

43 (33)

16 (16)

35 (25)

10 (6)

16 (10)

120

(19.7)

(50)

(100)

(21)

(37)

(16)

(25)

(6)

(10)

150

(24.5)

(75)

(150)

(27)

(49)

(16)

(50)

(10)

(35)

Notes : 1. Above power feeder sizes are for the length of electric wire up to 50m from
elevator machine room to power.
For the length being 50m or more, the following formular should be applied.
2. Above cable sizes are for copper wires inside electrometallic tubings.
Cable length (m)
Size in the above (mm2)
Cable sizes (mm 2) =
50
3. For power requirement of 3 cars or more, consult Hyundai.

40

Power (KVA)

Speed
(m/min)

4. Machine room temperature should be maintained below 40C with ventilating fan
and air conditioner, and humidity below 90%.
5. Data shown in ( ) is applied to the Machine-Room-Less elevators and gearless elevators.

AC-Gearless180~600m/min
N.F.B. Rated Transformer
Speed
Persons
Motor Current (A) Capacity (kVA)
(m/
/ kg
(kW)
min)
1Car 2Cars 1Car 2Cars
13 /
180 16.6
50
100
18
33
900
180 18.4
60
100
20
37
15 /
210
23
75
125
26
46
1000
240
26
100 150
29
52
180 21.2
75
125
24
42
210
25
75
150
28
50
240
30
100 175
33
60
300
36
125 200
40
72
17 /
360
43
125 200
48
86
1150
420
50
125 225
56
100
480
57
150 300
63
114
540
64
175 300
71
128
600
71
175 350
79
142

(50/60Hz, 380V)

Power Feeder
(mm2)

Earth Wire
(mm2)

1Car

2Cars

1Car

2Cars

10

25

16

10
16
25
16
16
25
35
35
35
50
50
50

25
35
50
35
50
50
70
70
70
120
120
150

6
10
16
10
10
16
25
25
25
35
35
35

16
25
35
25
35
35
50
50
50
95
95
120

Notes : 1. The above power sizes are for lengths of electric wire up to 50m from the elevator
machine room to the transformer.
For lengths of 50m or more, the following formula should be applied :
Power feeder length (m)
size in the above (mm2)
Power feeder size (mm2) =
50

Number of elevator (N)


Diversity factor

1.00

0.91

0.85

0.80

0.76

N.F.B. Rated Transformer


Speed
Persons
Motor Current (A) Capacity (kVA)
(m/
/ kg
(kW)
min)
1Car 2Cars 1Car 2Cars
180
25
75
150
28
50
210
30
100 175
33
60
240
35
125 200
39
70
300
42
125 225
47
84
20 /
360
50
150 300
56
100
1350
420
58
150 300
64
116
480
67
175 300
74
134
540
75
200 350
83
150
600
83
225 400
92
166
180
30
100 175
33
60
210
35
125 200
39
70
240
40
125 225
44
80
300
50
150 300
56
100
24 /
360
60
175 350
67
120
1600
420
69
175 350
77
138
480
79
200 350
88
158
540
89
225 400
99
178
600
98
250 500 109 196

Power Feeder
(mm2)
1Car
16
25
35
35
50
50
50
70
70
25
35
35
50
50
50
70
70
95

2Cars
50
50
70
70
120
120
120
150
185
50
70
70
120
150
150
150
185
240

6 / 450
8 / 550
9 / 600
10 / 680
11 / 750
13 / 900
15 / 1000
17 / 1150
20 / 1350
24 / 1600

Speed
(m/min)

Motor (kW)

30
45
30
45
30
45
30
45
30
45
30
45
30
45
30
45
30
45
30
45

15
22
18.5
30
18.5
30
18.5
30
18.5
30
30
37
30
37
37
52
37
52
37
52

1Car
10
16
25
25
35
35
35
50
70
16
25
25
35
35
35
50
70
95

2Cars
35
35
50
50
95
95
95
120
150
35
50
50
95
120
120
120
150
185

2. Above power feeder sizes are for copper wires inside electro-metallic tubing.
3. It is recommended a larger diameter earth wire be used.
4. For installing several elevators, apply the following formula.
Transformer Capacity (kVA) = Number of elevator X Diversity factor
5. Consult Hyundai if you need electric power requirements for 220V.
6. For AC-Geared elevators, consult Hyundai.
7. For AC-Gearless elevators(300m/min ~ 1080m/min), consult Hyundai.

Hydraulic30~45m/min
Persons / kg

Earth Wire
(mm2)

(50/60Hz, 380v)

N.F.B. Rated
Current (A)

Transformer
Capacity (kVA)

Power Feeder
(mm2)

1Car

2Cars

1Car

2Cars

1Car

2Cars

1Car

2Cars

1Car

2Cars

1Cars

2Cars

50
75
75
100
75
100
75
100
75
100
100
125
100
125
125
175
125
175
125
175

100
150
125
175
125
175
125
175
125
175
175
225
175
225
225
300
225
300
225
300

25
38
30
49
30
49
30
49
30
49
49
62
49
62
62
81
62
81
62
81

45
70
56
90
56
90
56
90
56
90
90
113
90
113
113
148
113
148
113
148

10
16
16
25
16
25
16
25
16
25
25
35
25
35
35
50
35
50
35
50

25
50
35
70
35
70
35
70
35
70
70
95
70
95
95
150
95
150
95
150

6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
10
6
10
6
10

6
10
6
10
6
10
6
10
6
10
10
10
10
16
16
25
16
25
16
25

3000
3900
3500
5500
3500
5500
3500
5500
3500
5500
5500
6900
5500
6900
6900
9700
6900
9700
6900
9700

6000
7800
7000
11000
7000
11000
7000
11000
7000
11000
11000
13800
11000
13800
13800
19400
13800
19400
13800
19400

1000
1300
1100
1900
1100
1900
1100
1900
1100
1900
1900
2300
1900
2300
2300
3500
2300
3500
2300
3500

2000
2600
2200
3800
2200
3800
2200
3800
2200
3800
3800
4600
3800
4600
4600
7000
4600
7000
4600
7000

Earth Wire
(mm2)

Heat Emission of Machine


Room (kcal/h)

Ventilation of
Machine Room (m2/h)

Notes : 1. Above power feeder sizes are for the length of electric wire up to 50m from elevator machine room to transformer.
For the length being 50m or more, the following formular should be applied:
2. Above power feeder sizes are for copper wires inside electrometallic tubings. Power feeder sizes (mm2) = Power feeder length (m) Size in the above (mm2)
50
3. For power requirement of 3 cars or more, consult Hyundai.
4. Machine room temperature should be maintained below 40C with ventilating fan and air conditioner, and humidity below 90%.
5. The heat emission and ventilation of machine room on above dimensions may vary slightly with the machine room size and
peripheral environment.
6. Consult Hyundai if you need electric power requirements for 220V.

41

ELECTRIC POWER REQUIREMENTS (By others)


There are some building and electrical work which is necessary for a normal escalator
installation, but is not done by the escalator contractor. Please consult Hyundai for it.
Electric Power
Type

New World
Class
/
Millennium
/
Modular

Motor
(kW)

Power Supply Power Supply Voltage


Capacity (kVA)
(AC-3Phase)

5.5

12

7.5

14

5.52/11

19

7.52

27

7.53

40

7.54

52

7.55

65

7.56

78

11

19

16

25

18.5

31

22

36

26

46

30

52

37

60

H-Series

Power Feeder (mm2) (from power room to escalator controller)

C.B. Rated
Current (A)

20m

40m

60m

80m

100m

120m

50
30
30
60
40
30
75
50
40
125
75
60
175
100
100
225
150
125
300
175
150
350
200
175
100
50
40
125
60
50
150
75
75
175
100
75
175
125
100
200
125
100
300
150
125

10
6
6
10
6
6
16
6
6
25
6
6
35
10
6
35
16
10
50
16
16
50
25
16
16
6
6
25
6
6
25
10
6
25
10
6
35
16
6
35
16
10
50
16
16

16
6
6
25
6
6
25
10
6
35
16
10
50
25
16
95
25
25
95
35
25
120
35
25
25
10
6
35
16
10
35
16
16
50
16
16
50
25
16
95
25
25
95
35
25

25
10
6
35
10
6
35
16
10
50
25
16
50
35
25
120
35
25
120
50
35
150
50
35
35
16
10
50
25
16
50
25
16
95
25
25
95
35
25
120
35
25
120
50
35

35
16
10
35
16
10
35
25
16
95
25
25
120
35
25
120
50
35
185
70
35
185
95
50
50
25
16
70
25
16
95
35
25
120
35
25
120
35
25
120
50
35
185
70
35

35
16
10
50
16
16
50
25
16
95
35
25
120
50
35
185
70
35
185
95
50
240
95
70
50
25
16
95
35
25
120
35
25
120
35
35
120
50
35
185
70
35
185
95
50

35
16
16
50
25
16
70
25
25
120
35
25
150
50
35
185
95
50
240
95
70
300
120
95
95
25
25
120
35
25
120
35
35
150
50
35
150
50
35
185
95
50
240
95
70

Lighting Power
Balustrade Vertical Power Supply Power Supply C.B. Rated
Voltage
Type
Rise (m) Capacity (kVA) (AC-1phase) Current (A)
1.83-4.27
With Handrail 4.28-7.6
Lighting
(BTL Type) 1.83-4.27
4.28-7.6
Without Handrail
Lighting

1.4(3)
2(6)
1.4(3)
2(6)
1.2

100-110
200-265
100-110
200-265

30(40)
40(70)
20
20(40)
20

Notes : 1. Consult Hyundai when the rise over 7600mm.


2. The capacity shown by ( ) mark shall be applied to moving walks.

42

Power Feeder (mm2)


40m
60m 80m 100m 120m

20m
6
6

10

16

10
4
4

2.5

16
6
4

2.5

25
10
10

6
6
4

10
10

3, 200V, 50Hz

3, 220V, 60Hz

3, 346V, 50Hz

3, 380V, 60Hz

3, 415V, 50Hz

3, 460V, 60Hz