Outdoor Unit
Indoor Unit
Controller
Wiring
Wire
Cool Only
Heat Pump
Inverter
Earth
Earth
Earth
Live
Live
Live
Neutral
Neutral
Neutral
N/A
Heating
Comms
N/A
Defrost
N/A
136
Sensor
Indoor Air All
Indoor Pipe All
Outdoor Air Singles
Outdoor Pipe Singles
Compressor Singles
All Outdoor Multis
At 10C
30K 0hms
40K 0hms
30K 0hms
10K 0hms
100K 0hms
40K 0hms
At 20C
18K 0hms
25K 0hms
18K 0hms
6K 0hms
60K 0hms
25K 0hms
At 30C
12K 0hms
16K 0hms
12K 0hms
3K 0hms
40K 0hms
16K 0hms
All prices shown are retail and are exclusive of VAT at 17.5%
Code
Reference
H11
H12
H14
H15
H16
H19
H21
H23
H27
H28
H30
H32
H33
H34
H36
H37
H39
H41
H97
H98
H99
F11
F17
F90
F91
F93
F95
F96
F97
F98
F99
None
Off
Off
Off
Off
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
Off
Off
On
On
Off
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
On
Off
On
Off
On
On
Off
Off
On
Off
On
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
Off
Off
Off
Off
Off
On
On
Off
On
On
On
Off
Off
Off
On
On
Off
On
Meaning
Likely Cause
Comms Failure
ID/OD Compatibility Problem
Indoor Air Sensor Faulty
Compressor Sensor Faulty
Current Transformer Problem
Indoor Fan Motor Locked
Float Switch Operated
Indoor Pipe Sensor Faulty
Outdoor Air Sensor Faulty
Outdoor Pipe Sensor Faulty
Outdoor Discharge Sensor 1 Faulty
Outdoor Discharge Sensor 2 Faulty
Incorrect Connection Voltage
Outdoor Heat Sink Sensor Faulty
Outdoor Gas Sensor Faulty
Outdoor Liquid Sensor Faulty
Abnormal Indoor Operation
Abnormal Wiring or Piping
Outdoor Fan Failure
Indoor Coil Overheat (Heat Mode)
Indoor Coil De-Ice (Cool Mode)
Reversing Valve Failure
Standby Units Freezing
PFC Failure
Refrigeration Cycle Problem
Compressor Abnormal Revolution
Outdoor Coil Overheat (Cool Mode)
IPM or Compressor Overheating
High Discharge/Compressor Temp
Overcurrent Protection
DC Overcurrent Protection
Control Box Overheating
For models CU3E23 & CU4E27 only there is a Green LED which normally flashes
If this is LIT then turn the power Off then On again. If it still does not flash the Outdoor PCB is Faulty.
If this is Off then there is a problem with the power supply.
All prices shown are retail and are exclusive of VAT at 17.5%
137
Wiring Schedule
Series
R22/R407C
R410a
E
Earth
Earth
1
Live
Live
2
Neutral
Neutral
3
Comms
Comms
4
Comms
Comms
R22/407C
R22/407C
R410a
R410a
R410a
R410a
Sensor
Air Sensor
Pipe Sensor
Air Sensor
ID Pipe
OD Disch
OD Pipe (X3)
At 0C
67K
67K
51K
67K
168K
16K
At 10C
40K
40K
30K
40K
101K
10K
At 20C
25K
25K
19K
25K
63K
6K
At 30C
16K
16K
12K
16K
40K
4K
Sensor Resistances
Use these to check sensors
All values in KOhms
LED1
Flash
Lit
Meaning
Of Fault Code
Signal from RC to ID Unit faulty
Float Switch
Air Sensor Faulty
Pipe sensor Faulty
LED3
Flash
Lit
Lt
LED1
Lit
LED2
Lit
Lit
Lit
Lit
Lit
Lit
Lit
Lit
Lit
Lit
Lit
Lit
Lit
Lit
Lit
Lit
LED1
Lit
Lit
Lit
Lit
Lit
Lit
Lit
Lit
Lit
LED2
Lit
Lit
Lit
Meaning
Of Fault Code
Float switch
Indoor Air Sensor Faulty
Indoor Air Sensor Faulty
Signal from RC to ID faulty
No Signal from ID to RC
Signal from ID to OD faulty
No Signal from Od to ID
OD Unit Overcurrent Protection
HP Switch
Outdoor Pipe Sensor Faulty
138
All prices shown are retail and are exclusive of VAT at 17.5%
F Code
Display
F15
F16
F17
F17
F20
F20
F21
F25
F26
F27
F27
F27
F27
F27
F27
F29
F30
F30
F31
F31
F31
F31
F31
F31
F32
F32
F32
F32
F32
F32
F32
F33
F33
F35
F40
F40
F40
F40
F40
F40
F40
F41
F41
F41
F42
F42
F44
F49
F49
Detail
Display
O1
O1
O1
O2
O1
O2
O1
O1
O1
O1
O2
O5
O1
O2
O5
O1
O1
O2
O1
O2
O6
O8
O9
10
O3
O4
O5
O6
O8
O9
10
O1
O2
2
O1
11
21
31
51
41
61
O2
O3
11
O1
11
O1
O1
O2
302
303
Flash
304
Flash
Outdoor LED
305
Flash
306
Flash
307
Flash
Flash
Flash
Flash
Flash
Only for Older
Flash
Only for Older
Flash
Flash
Flash
Only for Older
Flash
Flash
Flash
Models with LEDS 1-6
Flash
Flash
Models with LEDS 1-6
Flash
Flash
Models with LEDS 1-6
Flash
Flash
Flash
Flash
Flash
Flash
Flash
Flash
Flash
Flash
Flash
Flash
Only for Older Models with LEDS 1-6
Flash
Flash
Flash
Flash
Flash
Flash
Flash
Flash
Flash
Flash
Flash
Flash
Flash
Flash
Flash
Flash
Flash
Flash
Flash
Flash
Flash
Flash
Flash
Flash
Flash
Flash
Flash
Flash
Flash
Only for Older Models with LEDS 1-6
Only for Older Models with LEDS 1-6
Flash
Flash
Flash
Flash
Flash
Flash
Flash
Flash
Flash
Flash
Only for Older Models with LEDS 1-6
Only for Older Models with LEDS 1-6
Flash
Flash
Only for Older Models with LEDS 1-6
Flash
Only for Older Models with LEDS 1-6
Flash
Flash
Flash
Flash
Only for Older Models with LEDS 1-6
Only for Older Models with LEDS 1-6
Flash
Flash
Flash
Flash
Flash
Flash
Flash
308
See
See
See
See
See
See
See
See
See
See
See
See
309
Note 1
Note 1
Note 1
Note 1
Note 1
Note 1
Note 1
Note 1
Note 1
Note 1
Note 1
Note 1
Meaning
Of Code
Drain Failure
Louvre Failure
Option Problem
DC Fan Motor Failure
ID Air Sensor
RC Air Sensor
ID Pipe Sensor
Addressing Incorrect
RC Comms Problem
ID - OD Comms Disconnected ID
ID - OD Comms Connection ID
ID - OD Comms Connection ID
ID - OD Comms Disconnected OD
ID - OD Comms Connection OD
ID - OD Comms Connection OD
ID PCB Setting
ID/OD Capacity Incorrect
Phase Rotation
Low Pressure
High Pressure
Reversing Valve
Indoor Coil Iced
Gas Leak
Low Gas, Valve Shut or Blockage
Inverter Low dc Volts
Inverter IPM
Compressor Overcurrent
Compressor Disch Temp High
Inverter PFC
Inverter High dc Volts
Compressor Rotation Problem
Compressor High Current
High Discharge Temp
OD dc Fan Motor Locked
OD Outlet Sensor
Suction Temp
OD Liquid Sensor
Defrost Sensor
Discharge Sensor
Discharge Sensor
OD Pipe Sensor
HP Switch
Heating HP Switch
Low Pressure Sensor
Compressor Current Sensor
Current Sensor Open
Inverter IPM Sensor
OD PCB Setting Faulty
OD PCB Setting Faulty
Note 1: LED308 is lit if the master unit is the problem or 309 for the slave
LED 301 is lit when power is supplied to the PCB
All prices shown are retail and are exclusive of VAT at 17.5%
139
Outdoor Unit
Indoor Unit
Controller
Wiring
Wire
All
E
Earth
1
Live
2
Neutral
3
Comms
Sensor
Air Sensor
Pipe Sensor
Discharge Sensor
At 10C
40K 0hms
40K 0hms
480K 0hms
At 20C
25K 0hms
25K 0hms
293K 0hms
At 30C
16K 0hms
16K 0hms
184K 0hms
TECHNICAL SUPPORT:
08705 218218
140
All prices shown are retail and are exclusive of VAT at 17.5%