FLUE GAS
Analyzers
2 April 2014
PMI Revision 00
Presentation outline
Monitoring Requirement of analyzers in
thermal plant
Sampling and Conditioning Circuit
Measuring principles of Analyzers
Flue gas and emission Monitoring
Analyzers
2 April 2014
PMI Revision 00
2 April 2014
PMI Revision 00
2 April 2014
PMI Revision 00
CORROSION
MAY BE DEFINED AS REVERSION OF METAL TO A
MORE STABLE OXIDISED STATE.
WHEN THE ENVIRONMENT FAVOURS
CONVERSION OF THE METAL TO OXIDE BY
REACTION WITH OXYGEN OR A SOURCE OF
OXYGEN SUCH AS WATER THE CORROSION
OCCURS.
CORROSION INCLUDES GENERAL CORROSION,
ALKALI CORROSION, STRESS CORROSION,
STRESS CRACKING AND PITTING.
2 April 2014
PMI Revision 00
2 April 2014
PMI Revision 00
ff
HINDERS HEAT TRANSFER REDUCING BOILER EFFICIENCY.
ADHERES ON THE INNER WALL OF WATER PIPE AND
DISTURBS WATER CIRCULATION.
CAUSES OVERHEATING OF HEAT TRANSFER SURFACE
AND PIPE EXPLOSION.
BOILER UNDER HIGH TEMPERATURE AND HIGH PESSURE
IS LARGELLY AFFECTED BY SCALE TO A DANGEROUS
EXTENT. THEREFORE CONTENTS OF SULPHATES,
SILICATES AND CARBONATES ARE TO BE LIMITED WITH
RISE IN TEMPERATUE AND PRESSURE.
2 April 2014
PMI Revision 00
CARRYOVER
DISSOLVED OR SUSPENDED SOLIDS IN BOILER
WATER AND MOISTURE BROUGHT OUT OF
THE BOILER TOGETHER WITH THE STEAM
STREAM IS CALLED CARRY OVER.
SILICA UNLIKE DISSOLVED SOLIDS OF BOILER
WATER, DISSOLVE IN THE STEAM AND
SOLUBILITY STEEPLY INCREASES AS THE
PRESSURE RISES. SILICA DISSOLVED IN THE
VAPOUR GETS CARIED OVER AND GETS
DEPOSITED ON THE TURBINE BLADES.
CARRYOVER CAUSES THE FOLLOWING:
contd.
2 April 2014
PMI Revision 00
2 April 2014
PMI Revision 00
PMI Revision 00
10
2 April 2014
PMI Revision 00
11
PMI Revision 00
12
PMI Revision 00
13
2 April 2014
PMI Revision 00
14
1.MAKE UP DM WATER
CONDUCTIVITY.
2. HOTWELL CONDENSATE
(BOTH SIDES)
3. CEP DISCHARGE
b)SODIUM(TO PROVIDE
WARNING OF CONDENSER
LEAKAGE)
c)DO (TO ESTABLISH
ADEQUACY OF OXYGEN
REMOVAL)
2 April 2014
PMI Revision 00
15
4.CONDENSATE POLISHER
a) Cond
b)PH
c)SILICA
d)SODIUM
(PERFORMANCE OF THE
PLANT AND THE NEED FOR
RESIN BED REGENERATION)
2 April 2014
PMI Revision 00
16
6)
FEEDWATER ECONOMISER
COND
.
PH
(FINAL
ON QUALITY &
ACCEPTABILITY)
D.O.
HYDRAZINE
(EFFECTIVENESS OF
HYDRAZINE
DOSING)
7) BOILER DRUM
.
a)COND.
b)PH
c)SILICA
d)PHOSPHATE
e)CHLORIDE
(TO ENSURE PROPER
BOILER WATER CONDITIONS)
2 April 2014
PMI Revision 00
17
8)BOILER SATURATED
STEAM
a)COND.
b)SODIUM
(CRITERIA TO MINIMISE
SALT DEPOSITION IN THE SH IS
MET).
9)BOILER SUPERHEATED
STEAM
a) COND
b) PH
c) SODIUM
(CRITERION TO MINIMISE
SALT IN THE RH IS MET)
2 April 2014
PMI Revision 00
18
10)CONDENSER COOLING
WATER
2 April 2014
a) PH
b) COND.
PMI Revision 00
19
PMI Revision 00
20
2 April 2014
PMI Revision 00
21
PMI Revision 00
22
A:
B:
C:
D:
2 April 2014
PMI Revision 00
23
2 April 2014
PMI Revision 00
24
CHEMICAL
DEOXIDATION
N2H4 (HYDRAZINE)
(DOSING AT CEP DISCH AND/ OR BFP SUCTION)
PH ADJUSTMENT
NH4OH
(DOSING AT CEP DISCH AND / OR BFP SUCTION)
CACO3 REMOVAL
(DOSING AT BOILER DRUM WATER)
2 April 2014
PMI Revision 00
NA3PO4
25
PANELS
2 April 2014
secondary coolers
Conductivity & pH cells
bulk head type fittings,
removable cartridge type filters,
pressure reducing elements, flow rate control,
grab sample valve and other sample conditioning
equipments.
26
2 April 2014
PMI Revision 00
27
2 April 2014
PMI Revision 00
28
Primary Cooler
2 April 2014
PMI Revision 00
29
2 April 2014
PMI Revision 00
30
2 April 2014
CHILLER SYSTEM
PMI Revision 00
31
ANALYSERS
Accuracy
Response Time
(90 % of Full Scale)
Range
Temperature Comp.
2 April 2014
32
ANALYSERS
pH ANALYSER:
Type
Accuracy
<= +/- 1 %
Range
6-11 pH
freely programmable
Temperature Comp.
Automatic
2 April 2014
PMI Revision 00
33
ANALYSERS
PHOSPHATE ANALYSER:
Type
Accuracy
Response Time
(90 % of Full Scale)
Colourimetric
<= +/- 5 % of reading
<= 6 min
Range
0-10 ppm
freely programmable
Temperature Comp.
Automatic
2 April 2014
PMI Revision 00
34
ANALYSERS
HYDRAZINE ANALYSER:
Type
Accuracy
Response Time
(90 % of Full Scale)
Range
Automatic Continuous
Electrochemical Type
<= +/- 5 %
<= 3 Min.
0-50, 0-100 ppb freely
programmable
PMI Revision 00
35
ANALYSERS
SILICA ANALYSER:
Type
Accuracy
Response Time
(90 % of Full Scale)
Continuous Colorimetric
Type - Multi stream
<= +/- 5 % of reading
<= 15 min( including sample
switching)
Range
Temperature Comp.
Automatic
PMI Revision 00
36
ANALYSERS
SODIUM ANALYSER:
Type
Accuracy
Response Time
(90 % of Full Scale)
Range
Temperature Comp.
2 April 2014
37
ANALYSERS
Accuracy
Response Time
(90 % of Full Scale)
Range
Temperature Comp.
Automatic/
2 April 2014
PMI Revision 00
38
2 April 2014
PMI Revision 00
39
2 April 2014
PMI Revision 00
40
Combustion Efficiency
2 April 2014
PMI Revision 00
41
Stoichiometric Combustion
2 April 2014
PMI Revision 00
42
Efficient combustion
2 April 2014
Therefore, more air than ideal must be supplied to burn all fuel
completely. The amount of air more than the theoretical
requirement is referred to as excess air.
PMI Revision 00
43
Fuel
Excess of Air (%)
Anthracite
40
Coke oven gas
5 10
Natural Gas
5 10
Coal, pulverized
15 20
Coal, stoker
20 30
Oil (No. 2 and No. 6)
10 to 20
Semi anthracite, hand firing
70 to 100
Semi anthracite, with stoker
40 to 70
Semi anthracite, with traveling 30 to 60
grate
2 April 2014
PMI Revision 00
44
Stoichiometric Combustion
To determine the excess air at which the
combustion system will operate we have to start
with the stoichiometric air-fuel ratio, known as the
perfect, correct or ideal fuel ratio, the stoichiometric
combustion. During stoichiometric combustion there
are a chemically correct mixing proportion between
the air and the fuel. During the stoichiometric
combustion process no fuel or air are left over.
Process heating equipment almost never run
stoichiometric. Even so-called "on-ratio"
combustion, used in boilers and high temperature
process furnaces, incorporates a modest amount of
excess air, 10 to 20% more than needed to burn
the fuel completely.
2 April 2014
PMI Revision 00
45
2 April 2014
PMI Revision 00
46
2 April 2014
PMI Revision 00
47
COMPLETE COMBUSTION
IT IS IMPORTANT TO MAINTAIN THE AIR-FUEL
RATIO AT ITS MOST ECONOMIC LEVEL, IN SUCH A
WAY THAT COMPLETE COMBUSTION IS ENSURED
WITH MINIMUM AMOUNT OF EXCESS AIR.
AS CAN BE SEEN FROM THE CURVE DEPICTING THE
EXCESS OXYGEN, CARBON MONOXIDE (CO) LEVEL,
AND UNBURNT CARBON, THERE EXISTS A
STOICHIOMETRIC POINT WHERE CO LEVEL IS
MINIMUM.
THUS MEASUREMENT OF OXYGEN AND CO LEVELS
IN THE FLUE GAS GIVES A GOOD FEEL OF THE
COMBUSTION PROCESS.
HENCE, BOTH CO AND O2 ARE MEASURED IN
POWER PLANTS TO ENSURE PROPER COMBUSTION
AT THE MOST ECONOMIC MODE.
2 April 2014
PMI Revision 00
48
2 April 2014
PMI Revision 00
49
O2 MEASUREMENT
TYPICALLY O2 IS MEASURED AT TWO LOCATIONS IN THE
FLUE GAS PATH:
AT PLATEN SUPERHEATER ZONE.
AT ECONOMISER OUTLET.
THE MEASUREMENT AT PLATEN SH ZONE IS CLOSE TO COMBUSTION
PROCESS AND GIVES A FEEL OF THE SAME. HOWEVER, ONE
ARGUMENT MAY BE THERE THAT THE COMBUSTION PROCESS IS NOT
COMPLETE AT THAT ZONE AND THE GAS MIXTURE IS NOT
HOMOGENOUS.
HENCE, ANOTHER MEASUREMENT IS DONE DOWN THE PATH AT
ECONOMISER OUTLET. THESE TWO MEASUREMENTS TOGETHER GIVE
AN INDICATION OF THE COMBUSTION PROCESS.
AS AN OVERSHOOT, AN ADDITIONAL INFORMATION MAY BE
GATHERED FROM THESE TWO MEASUREMENTS I.E. AIR LEAKAGE
(INGRESS) IN THE FLUE GAS PATH.
2 April 2014
PMI Revision 00
50
SH ZONE MEASUREMENT
THE O2 MEASUREMENT AT SH ZONE IS DONE USING NONHEATED TYPE ZIRCONIA PROBE. THIS IS BASED ON NERNST
EQUATION WHEREIN,
EMF a T LOGN P1/P2
WHERE,
P1 = PARTIAL PRESSURE OF OXYGEN IN REFERENCE GAS.
P2 = PARTIAL PRESSURE OF OXYGEN IN SAMPLE GAS.
T = ABSOLUTE TEMPERATURE.
2 April 2014
PMI Revision 00
51
2 April 2014
PMI Revision 00
52
CO MEASUREMENT
TYPICALLY CO IS BEING MEASURED USING IN-SITU TYPE
ANALYSER AT STACK. THIS MEASUREMENT IS USED IN THE
COMBUSTION CONTROL LOOP TO OPTIMISE COMBUSTION
PROCESS.
ANALYSER
USES
PRINCIPLE
OF
SPECIFIC
RADIATION
ABSORPTION, TYPICALLY IN INFRA-RED SPECTUM. IT USES A
RADIATION SOURCE AND A RECEIVER UNIT ACROSS THE DUCT.
USING THE RATIO OF THE MEASURING & REFERENCE SIGNALS
ALONGWITH PATH LENGTH AND TEMPERATURE, THE CO IN FLUE
GAS IS CALCULATED.
THE
OPTICS
ARE
PROTECTED
FROM
GETTING
CONTAMINATED WITH DUST USING SUITABLE AIR
CURTAINS/ BLOWERS.
2 April 2014
PMI Revision 00
53
ENVIRONMENTAL MONITORING
IT IS IMPERATIVE THAT THE STATUTORY
NORMS STIPULATED BY CENTRAL & STATE
POLLUTION CONTROL BOARDS WITH
RESPECT TO EMISSIONS ARE MET.
THE MAJOR COMPONENTS FOR WHICH
REQUIREMENTS ARE STIPULATED ARE:
DUST OR SUSPENDED PARTICULATE
MATTER (SPM)
SULPHUR DIOXIDE (SO2)
OXIDES OF NITROGEN (NOX)
2 April 2014
PMI Revision 00
54
2 April 2014
PMI Revision 00
55
SULPHUR DIOXIDE
AS THIS GAS IS ONE OF MAIN GASEOUS POLLUTANTS EMITTED DURING
THE COMBUSTION OF SULPHUR-BEARING FUEL, CONTINOUS ON-LINE
MEASUREMENT OF THE SAME IS ENVISAGED IN THERMAL POWER
PLANTS. HIGHER LEVELS OF SO2 MAY CAUSE ACID RAIN.
TYPICALLY IN NTPC, EXTRACTIVE TYPE (I.E. SAMPLING TYPE) ANALYSER
IS EMPLOYED. THESE ANALYSERS ALSO GENERALLY OPERATE ON
SPECIFIC RADIATION ABSORPTION PRINCIPLE (IN UV OR IR SPECTRUM).
TYPICALLY THEY CONSIST OF A SAMPLE CELL AND A REFERENCE CELL
AND THE RATIO/ DIFFERENTIAL OF THE IR/UV INTENSITIES OF REFERENCE
AND SAMPLE (MEASURING) CELL GIVES A MEASURE OF THE COMPONENT
I.E. SO2.
FOR CONDITIONING OF THE SAMPLE BEFORE IT REACHES THE
ANALYSER,
SUITABLE
CONDITIONING
SYSTEM
COMPRISING
REFRIGERANT TYPE OF COOLER, FILTERS, ANTI-CONDENSATION
EQUIPMENT VIZ. HEAT TRACING ETC. IS PROVIDED.
2 April 2014
PMI Revision 00
56
2 April 2014
PMI Revision 00
57
CHEMILUMINISCENCE TYPE
2 April 2014
PMI Revision 00
58
2 April 2014
PMI Revision 00
59
TYPICAL SPECIFICATIONS OF
FLUE GAS ANALYSIS INSTRUMENTS
Common Requirements
Output signals
Analog :4-20 mA DC galvanically isolated. If analyser
provides superimposed HART signal on 4-20 mA DC
output, It shall also be connected to PC based station.
Binary: 2 NO + 2 NC for high alarm
Zero & span Adjustment : To be provided with range
selection facility.
Ambient temp.: 50C
Indication : Digital Alphanumeric Display. Diplay of
reading in engineering units shall be provided.
Enclosure Type/MaterialWeather & Dust proof (IP 55) : Die
cast Aluminium/SS
Type of Electronics: Microprocessor based with self
diagnostic.
2 April 2014
PMI Revision 00
60
TYPICAL SPECIFICATIONS OF
FLUE GAS ANALYSIS INSTRUMENTS
2 April 2014
PMI Revision 00
61
2 April 2014
62
2 April 2014
PMI Revision 00
63
2 April 2014
PMI Revision 00
64
2 April 2014
CO
Analyser
specs
Type of Instrument : In-situ type
Principle of Measurement :IR absorption
Measurement Range: 0-200, 0-1000 ppm,
programmable.
Accuracy : +/- 5% of F.S.
Linearity : +/- 2% of F.S.
Repeatibility: < 0.5% of Span
Response time(upto 90% of full scale) < 5 secs
Operating Temperature Range : 0-300 deg.C
Accessories : Purging system to be provided with
heavy duty blowers and shutter mechanism for
automatic isolation of lens during purge air failure .
Compensation for temperature.: Automatic
Location: Chimney
PMI Revision 00
65
Dust/
SPM
Analyzer
specs
Type of Instrument : In-Situ dry type visible light
2 April 2014
PMI Revision 00
66
THANK YOU
2 April 2014
PMI Revision 00
67