Beruflich Dokumente
Kultur Dokumente
Site:
Site
Date:
August 5, 2002
This guide is based upon testing and analysis of the hazard presented by incident energy.
The potentially hazardous effects of molten metal splatter, projectiles, pressure impulses,
and toxic arc by-products have not been considered in these methods. It is expected that
future work will provide guidance for these other electrical hazards.
Available bolted fault currents should be determined at the point of each potential fault.
Do not use overly conservative bolted fault current values. A conservatively high value
may result in lower calculated incident energy than may actually be possible depending on
the protective devices time-current response. The lower results would be caused by using
a faster time-current response value from the protective devices time-current curve.
Where used, PPE for the arc-flash hazard is the last line of defense. The protection is not
intended to prevent all injuries but to mitigate the impact of an arc flash upon the
individual, should one occur. In many cases, the use of PPE has saved lives or prevented
injury. The calculations in this guide will lead to selection of a level of PPE that is a
balance between the calculated estimated incident energy exposure and the work activity
being performed while meeting the following concerns:
The desire to provide enough protection to prevent a second degree burn in all cases.
The desire to avoid providing more protection than is needed. Hazards may be introduced
by the garments such as heat stress, poor visibility, and limited body movement.
Professional judgement must be used in the selection of adequate PPE.
While it is outside the scope of this document to mandate PPE, some examples of where
PPE may be required are: during load interruption, during the visual inspection that
verifies that all disconnecting devices are open, and during the lockout/tagout. Adequate
PPE is required during the tests to verify the absence of voltage after the circuits are
deenergized and properly locked out/tagged out.
This information is based on technical data believed by the IEEE Std 1584-2002 working
group to be reliable. It is offered as a tool for conducting an arc-flash hazard analysis. It is
intended for use only by those experienced in power system studies and is not intended to
substitute for the users judgment or review in such studies. It is subject to revision as
additional knowledge and experience is gained. IEEE, those companies that contributed
test data, and those people who worked on development of this standard make no
guarantee of results and assume no obligation or liability whatsoever in connection with
this information.
This guide is not intended to imply that workers be allowed to perform work on exposed
energized equipment or circuit parts. It must be emphasized that the industryrecommended way to minimize electrical injuries and fatalities is to ensure that equipment
is deenergized and in an electrically safe work condition. But even this act, creating an
electrically safe work condition, subjects the worker to potential hazards, which if they
occur, require PPE for protection against arc-flash burns.
IEEE Standards documents are developed within the IEEE Societies and the Standards
Coordinating Committees of the IEEE Standards Association (IEEE-SA) Standards Board.
The IEEE develops its standards through a consensus development process, approved by
the American National Standards Institute, which brings together volunteers representing
varied viewpoints and interests to achieve the final product. Volunteers are not necessarily
members of the Institute and serve without compensation. While the IEEE administers the
process and establishes rules to promote fairness in the consensus development process,
the IEEE does not independently evaluate, test, or verify the accuracy of any of the
information contained in its standards.
Use of an IEEE Standard is wholly voluntary. The IEEE disclaims liability for any
personal injury, property or other damage, of any nature whatsoever, whether special,
indirect, consequential, or compensatory, directly or indirectly resulting from the
publication, use of, or reliance upon this, or any other IEEE Standard document.
The IEEE does not warrant or represent the accuracy or content of the material contained
herein, and expressly disclaims any express or implied warranty, including any implied
warranty of merchantability or fitness for a specific purpose, or that the use of the material
contained herein is free from patent infringement. IEEE Standards documents are supplied
AS IS.
The existence of an IEEE Standard does not imply that there are no other ways to produce,
test, measure, purchase, market, or provide other goods and services related to the scope
of the IEEE Standard. Furthermore, the viewpoint expressed at the time a standard is
approved and issued is subject to change brought about through developments in the state
of the art and comments received from users of the standard. Every IEEE Standard is
subjected to review at least every five years for revision or reaffirmation. When a
document is more than five years old and has not been reaffirmed, it is reasonable to
conclude that its contents, although still of some value, do not wholly reflect the present
state of the art. Users are cautioned to check to determine that they have the latest edition
of any IEEE Standard.
In publishing and making this document available, the IEEE is not suggesting or rendering
professional or other services for, or on behalf of, any person or entity. Nor is the IEEE
undertaking to perform any duty owed by any other person or entity to another. Any
person utilizing this, and any other IEEE Standards document, should rely upon the advice
of a competent professional in determining the exercise of reasonable care in any given
circumstances.
USA
Note: Attention is called to the possibility that implementation of this standard may
require use of subject matter covered by patent rights. By publication of this standard, no
position is taken with respect to the existence or validity of any patent rights in connection
therewith. The IEEE shall not be responsible for identifying patents for which a license
may be required by an IEEE standard or for conducting inquiries into the legal validity or
scope of those patents that are brought to its attention.
Authorization to photocopy portions of any individual standard for internal or personal
use is granted by the Institute of Electrical and Electronics Engineers, Inc., provided that
the appropriate fee is paid to Copyright Clearance Center. To arrange for payment of
licensing fee, please contact Copyright Clearance Center, Customer Service, 222
Rosewood Drive, Danvers, MA 01923 USA; +1 978 750 8400. Permission to photocopy
portions of any individual standard for educational classroom use can also be obtained
through the Copyright Clearance Center.
Site
August 5, 2002
Normal Operation
Columns A-C
Column D
Columns E, F, I
Column G
Bus name, voltage and bolted fault current from short circuit study
Portion of bolted fault current that flows through protective device from study (at faulted bus voltage)
Calculated by the spreadsheet.
If cell is blue, enter time-- For relay or breaker with integral trips, enter Trip Time at the Calculated Arcing
Fault Current from column F.
If cell is blue, enter time-- For relay operated breaker, enter breaker Opening Time. For fuses, enter
the total clearing time at the calculated Arcing Fault Current from column F.
If cell is blue, enter Trip Time for relay or breaker at the Reduced Arcing Fault Current
If cell is blue, enter breaker opening time or fuse clearing time at the reduced arcing fault current (col I.)
Enter Working Distance between worker's body and the possible arcing location.
Enter Equipment Class from the list.
Enter Grounding Type from the list.
Enter Protective Device Type from the list. Cell turns orange if out or range or if device is CB and I t isnot entered in Col P.
If cell is blue, enter Instantaneous Trip current for Circuit Breakers (See CB Reference Tab)
Column H
Column J
Column K
Column L
Column M
Column N
Column O
Column P
Boundary Energy
Motor Contribution Factor:
Name of bus
CUBCULOS CARGILL
J/cm2
Equipment Class:
1 - Open Air
2 - Cable
3 - Switchgear
4 - MCCs, Panels
1.2 cal/cm2
Grounding Type:
1 - Solid Grounded
2 - Ungrounded,
Resistance
Grounding, Other
Impedance
Enter one of these values to determine arc flash boundary distance at that incident energy.
0 Enter typical portion of bolted fault from motor contribution. Example: 0.03
If you leave column D blank, motor contribution factor will be used to calculate Column E.
Bolted fault
current of bus
kV of in kA (from
bus
study)
13.8
8.75
Arcing fault
current in
protective
device, in kA
(Calculated)
8.51
Trip
Time
0.688
Reduced arcing
fault current in Trip Time at
Opening protective device,
Reduced
Time
in kA
Current
0.045
Not required
Opening
Time at
reduced
current
It of
Working
Distance
in mm
610
Equipment Class
1
Circuit
Breaker
in kA
0
25
Site:
Normal Operation
Results of arc flash calculations for determination of PPE and flash boundary
Bus Information
Name of Location
CUBCULOS CARGILL
Bolted
kV of
Fault
bus Current
Total Arcing
Fault Current
Equipment
Class
Grounding
Protective
Device
Type
Gap
Protective
Device Arc
Working
Fault
Distance
Current
Arc
Clearing
Time
Reduced
Current
Clearing
Time
Incident
Energy
kV
kA
kA
1 to 4
1 or 2
0 to 14
mm
mm
kA
sec
sec
J/cm2
13.8
8.75
8.51
153
610
8.51
0.73
0.00
28.46
Incident
Energy
Arc Flash
PPE per
Boundary NFPA 70E
cal/cm2
6.8
mm
1452
Category
2
Site
Voltage
13.8
0.48
0.48
68.8
4.16
4.16
0.4
0.4
0.59
0.48
0.48
0.48
0.48
0.48
0.48
0.48
0.48
0.48
0.48
0.48
0.48
0.48
0.48
0.48
0.48
0.48
0.48
0.48
0.48
0.48
0.48
0.48
0.48
0.48
0.48
0.48
0.48
0.48
0.48
0.48
0.48
0.48
0.48
0.48
13.8
Normal
Operation
J/cm2
1.9
219.6
10.6
61.7
11.1
101.0
96.6
54.4
2.9
43.4
25.4
12.7
20.2
35.1
38.8
19.2
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
28.5
Normal
Operation
cal/cm2
0.4
52.5
2.5
14.8
2.6
24.1
23.1
13.0
0.7
10.4
6.1
3.0
4.8
8.4
9.3
4.6
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
6.8
Working
Distance
mm
1825.0
610.0
610.0
1825.0
483.0
610.0
610.0
610.0
610.0
457.0
457.0
457.0
457.0
457.0
610.0
610.0
610.0
610.0
610.0
610.0
610.0
610.0
610.0
610.0
610.0
610.0
610.0
610.0
610.0
610.0
610.0
610.0
610.0
610.0
610.0
610.0
610.0
610.0
610.0
610.0
610.0
610.0
610.0
610.0
610.0
Arc Flash
Boundary
mm
1112.6
7930.5
887.8
6399.5
717.5
13339.3
3697.2
2605.2
464.4
1701.9
1227.2
803.6
1066.9
1493.7
1694.7
1192.8
984.1
984.1
984.1
984.1
984.1
984.1
984.1
984.1
984.1
984.1
984.1
984.1
984.1
984.1
984.1
984.1
984.1
984.1
984.1
984.1
984.1
984.1
984.1
984.1
984.1
984.1
984.1
984.1
1452.4
Reference Tables
Gap and Distance Exponent Tables
kV
Type
0.208 to 1
Open air
Switchgear
MCC and Panels
Cable
Equipment Number
1
3
4
2
Gap
32
32
25
13
kV
1 to 5
Type
Open air
Switchgear
Cable
Equipment Number
1
3
2
4
Gap
102
102
13
102
kV
5 to 15
Type
Open air
Switchgear
Cable
Equipment Number
1
3
2
4
Gap
153
153
13
153
Risk Category
0
1
2
3
4
X
Device Type
480V& lower, K1
9
10
11
12
13
14
480V&lower, K2
0.045
0.053
0.09
0.107
0.15
1.09
600V K1
0.13
0.38
0.324
0.72
0.88
6.51
0.065
0.08
0.112
0.164
0.23
1.64
K1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0.0143
0
0
7
7
7
7
7
7
8
8
8
8
0
15.7
31.800001
44.1
65.900001
106.000001
0
22.6
65.900001
106.000001
15.699999
31.8
44.099999
65.9
106
1000
22.599999
65.9
106
1000
0
0
0
0
0
0
0
0
0
0
Note A: Must change to device type 0 if bolted fault current is below lower limit; use time-current curves
Note B: Contact manufacturer for additional information above upper limit.
X
2
1.473
1.641
2
X
2
0.973
2
0.973
X
2
0.973
2
0.973
600V K2
0.04
0.09
11
0.04
0.07
0.519
K2
0
-11.176
-1.4583
0
0
0
-18.409
-4.2628
0
0
0
-19.053
-0.0302
0
0
0
-3.0545
0
-0.0507
0
0
0
-0.0601
0
0
0
-0.1928
-1.3919
0
0
K3
Note A
13.565
2.2917
0.25
Note B
Note A
36.355
13.721
0.25
Note B
Note A
96.808
0.9321
0.25
Note B
Note A
43.364
0.6
1.3964
0.25
Note B
Note A
2.8992
0.25
Note B
Note A
14.226
34.045
0.39
Note B
0
-0.1863
-1.5504
0
-0.0631
0
0
-0.1284
-0.5177
0
Note A
27.926
71.303
2.93
7.0878
Note B
Note A
32.262
57.917
Note B
To find I1, use the manufacturers time-current curve if it is available and take the instantaneous trip
value, It, from the curve as shown in Figure 1 and insert it in Column P. If the curve is not available,
but the instantaneous trip setting is shown on the breaker, use that setting. Alternatively, the default
value noted in B below must be used. Where an LS trip unit is used, It is the short-time pick-up current.
Figure 1 It Shown on Time-Current Characteristic
T ypical time-current characteristic
10000
Time (sec)
1000
100
10
1
0.1
0.01
100
It
1000
10000
100000
Current
B. It Default Value
When the tripping current, It, is not known, use a default value of 10 times the continuous current rating
of the CB, except for CBs rated 100 A and below. For CBs rated 100 A and below, use a default value
of It = 1300 A.
I1 = 10^[0.0281 + 1.09 Log((1.3 It)] at 600 V and,
I1 = 10^[0.0407 + 1.17 Log((1.3 It)] at 480 V and lower.}
(Eq. 5)
(Eq. 6)
Spreadsheet compares I1 to Bolted Fault current; if I1<Ib, then CB equations can be used; trip and
operating times are not required. The entry cells for the trip and operating times are changed to 'white'
to show that no entry is needed. If I1>Ib, then the CB equations are not used to calculate incident
energy.