C60

Electrical auxiliaries

IEC
They remotely trip or indicate circuit breakers or
supplementary protectors.

Compliance with electrical auxiliaries standards


b
b
b
b
b
b

For UL 489 circuit breaker File #217688.


For CSA C22.2 No. 5.2 circuit breakers File #179014.
For UL 1077 Supplementary Protectors File #E90509.
For CSA C22.2 No. 235-M04 Supplementary Protectors File #179014.
For IEC 60947-2 and IEC 60947-5-1 circuit-breakers.
CE Marked.

Possible electrical auxiliary combinations

Auxiliaries are mounted to the left of the circuit breaker and/or the supplementary
protectors for a total width of 2.13 in (54 mm) max. :
b they are fixed using clips (no tools)
b a maximum of 3 indication auxiliaries (OF), (SD) on the same device
b a maximum of 2 tripping auxiliaries (MX + OF) or (MN) on the same device.
2.13 in. (54 mm): 6 modules of 0.354 in. (9 mm) max.

SD Alarm
Switch

OF auxiliary
Switch

PB100992-35

PB100993-35

PB100994-35

PB100995-35

PB100977A_SE

releases

auxiliaries contact

MX + OF Shunt
trip and
auxiliary switch

MN
Undervoltage
release

C60
Supplementary
protectors
or C60
circuit breaker

Connection for copper cables UL 486A file #E216919


b Terminal pads for:
v two #16 AWG (1.5 mm2) cables, or one #14 AWG (2.5 mm2) cable
v torque 9 Ib.in.
Type

Control voltage
Va
Vc

Width in
modules
0.354 in.
(9 mm)

Cat. no.
UL/CSA

26925

26928

12 to 24
48
110 to 130

2
2
2

27118
27110
27109

24
48
-

2
2
2
2

27108
27106
27107
27105

OF auxiliary switch

SD alarm switch

MX + OF shunt trip
24
48
110 to 277

MN undervoltage release
Instantaneous

version: 3.2

24
48
120
220 to 240

90081E.indd

OF, SD, MX + OF, MN


C60

Electrical auxiliaries

IEC

Remote tripping

Remote tripping is possible by means of a shunt trip (MX+OF) or undervoltage


release (MN). A tripped device is indicated by a red indicator flag on the front panel.

MX + OF shunt trip

DB100993-35

b When energized, trips the associated device:


v equipped with an O + F switch that indicates the open or closed position of the
device
v realize a self-interrupting allowing the control circuit to remain on.

u>

14 12 C2

DB112939

08603083

Wiring diagrams

C1

DB100992-35

MN Undervoltage Release

b When the voltage drops to 7035% of the supply voltage, the associated device
trips and is prevented from reclosing until the supply voltage is restored:
v uses emergency stop via push button
v uses safety feature on circuit supplying several machines preventing uncontrolled
restarting of the motors.

u<

08603146a

08603084

Wiring diagrams

u<

D1

D2

D1

D2
L or +
N or -

90081E.indd

version: 3.2

OF, SD, MX + OF, MN


C60

Electrical auxiliaries

IEC

Remote Indication

Operation test button on the front panel of the auxiliary (OF) and alarm switches (SD)
allows simulation of the OF and SD functions without operating the device.

OF auxiliary switch

b Indicates the open or closed position of the device.


DB112940

08603086

PB100994-35

Wiring diagrams

14 12 11

SD Alarm Switch

b Indicates the tripped-on-fault position of the device with a red indicator flag on
the front panel.
DB112941

08603085

PB100995-35

Wiring diagrams

92 94 91

OF and SD position contact depending on status


of combinated circuit breaker:
C60 Position

Switch
OF
Switch
SD

version: 3.2

ON
OFF
Trip
11/14
11/12
91/94
91/92

b
b
b
ON
OFF
OFF
ON

OFF
ON
OFF
ON

OFF
ON
ON
OFF

90081E.indd

OF, SD, MX + OF, MN


C60

Electrical auxiliaries

IEC

MN, MX + OF releases technical data


Releases
Cat. no.

Nominal line voltage (V) (10, -20%)


Alternating current (a)
Direct current (c)
Operating frequency
50/60 Hz
Min. cut-in voltage (V)
Min. tripping voltage (V)
Holding current (A)
Power consumption (VA)
Min. voltage dip time (ms)

Releases

MN

27105
220 to 240
b

27106
48
b

187

40.8

40.8

Between 0.35 and 0.70 Un


0.014
0.03
3.3
1.6
30
8

0.02
1.1
8

MX+OF
27109
120
b

240
b

277
b

60.5

60.5

Inrush current (A)


Inrush power (VA)
Min. control impulse duration (ms)
Power circuit breaking time (ms)

0.4
44
8
18

0.8
184

OF contact rated operational current Ie (A)

See the auxiliary contact table

Nominal line voltage (V) (+10, -20%)


Alternating current (a)
Direct current (c)
Operating frequency
50/60 Hz
Min. cut-out voltage (V)

48
b

110
b

125
b

60.5

60.5

60.5

1
277

0.3
38

0.3
45

27107
120
b

27108
24
b

102

20.4

20.4

0.011
1.3
8

0.04
1
10

0.02
0.5
10

27110
48
b
b
26.4
1
48
8
18

48
b

27118
12
b

26.4

6.6

0.7
33.6

2.5
30
8
18

24
b

24
b
b

24
b

6.6

6.6

7.7
185

5.6
135

OF, SD auxiliary contacts technical data


b
b
v
v

Degree of protection: IP20.


Rating of auxiliary contact short-circuit protection device:
circuit breaker: C60 - 2P - C curve - 6 A - limitation class 3
fuse: 6 A, 500 V, type Gg, 10.3 x 38 mm.

Contact rated operational current Ie (A) to IEC 60947-5


Auxiliary contacts

Cat. no.

Rated operational
voltage Ue (V)

Cat. AC12

Cat. DC12

277 V
220 to 240 V
12 to 24 V
48 V
60 V
130 V

OF, SD
26925 / 26928
3
6
6
2
1.5
1

Common technical data of auxiliary contacts


and releases
Common technical data

Operating temperature when live (C)

-25C to +50C

Storage temperature

-40C to +85C

DB110258

Dimensions

MN, MX+OF

90081E.indd

version: 3.2

OF, SD