Beruflich Dokumente
Kultur Dokumente
typical in these environments can make it difficult to keep a Where sprinkler piping is subjected to
sprinkler system in good operating condition. freezing temperatures, it is critical that
the sprinkler system is properly
Even though some refrigerated or frozen products themselves may not be
arranged and adequately maintained.
combustible, the associated packaging and pallets make for a combustible mixture
As displayed in the picture below, poor
that can contribute to fire spread and damage. In addition, the insulated wall and
maintenance can result in ice buildup.
ceiling panels that enclose these storage spaces can be made of combustible
The weight of the ice can cause the
materials that may significantly increase the fire load.
sprinkler piping and structural members
Automatic sprinkler systems can be designed to provide adequate fire protection for to weaken or collapse. Evidence of ice
a variety of occupancies, but freezing temperatures can make using a standard wet formation on sprinkler system piping
pipe sprinkler system impractical for freezers and coolers. Instead, most freezers may be an indication that internal ice
and coolers are protected by a dry pipe or preaction sprinkler system. Although accumulation is also present. Internal
these systems do not contain water in the sprinkler piping under normal conditions, ice accumulation in the sprinkler piping
they are subject to freezing and the formation of ice plugs if not properly installed can result in severe obstructions and
and maintained. can delay water supply to the sprinkler
heads. Ice should be immediately
system is drained, it might seem that all water has been removed. However,
P2
these systems will continue to drain to the low points for several hours, and
remaining water or moisture in the system can contribute to the formation of
Normally
ice plugs over time. Properly designed systems will limit moisture and allow open control
water to drain from all piping.
Shutoff
valve valves
Check valve
with 3/32 in.
Locating Ice Plugs (2.4 mm) hole
in clapper
Ice plugs are most commonly found where sprinkler piping passes through
a wall or floor into a refrigerated space. If water has entered the piping, ice Dry / preaction
plugs can also form in low spots where water accumulates. valve
Dry pipe or preaction sprinkler system piping that protects or passes through
Main control
freezers or coolers should be inspected annually in accordance with NFPA
valve
25, Inspection, Testing, and Maintenance of Water-Based Fire Protection
Systems. To inspect piping, shut down the sprinkler system and remove
Water supply
sections of pipe where the piping enters a refrigerated area, to verify that
there are no blockages. Riser, feed-main and cross-main fittings should be
designed with fittings strategically located to facilitate the inspection and
removal of any ice plugs. Using an ultrasound thickness gauge can also help
determine if ice is present in the piping. Impairment notification procedures
should be followed when a fire protection system is permanently or
temporarily shut down.
Annual partial trip tests of dry pipe valves, preaction systems, refrigerated
area systems and other associated equipment following NFPA 25 can also be Shutoff
valves
performed as a method of ice plug investigation. A longer-than-average trip
Pressure Air pressure
time may indicate the presence of ice plugs. During such tests, piping in gauge
regulator
heated areas should be arranged to keep water from entering the cold P1
portion of the system. Refer to Dry Pipe System Test Records (Form Air
PE1013B) for more guidance on trip testing. dryer
Insulated Panels
Wall panels with combustible insulation are often used in the construction
6 ft. (1.8 m) minimum
of freezers and coolers. These present a more significant fire hazard than
noncombustible construction materials do, because their combustible
Two easily removed insulation could increase the fire load. In all new construction, Liberty Mutual
air supply lines Property recommends Underwriters Laboratories (UL)–listed panels with a
flame-spread rating of less than 25. A flame-spread rating is the relative rate
at which a flame could spread over the surface of a material as compared to
over a controlled material (asbestos-cement board – rated 0; red oak board –
rated 100). When panels are used in walk-in freezers and coolers, it is
important to have appropriately designed sprinklers located above and inside
the refrigerated space to ensure proper protection of both the contents and
the building structure.
20 Riverside Road
Weston, MA 02493
While following the procedures and information outlined in this guide may aid in minimizing hazards associat-
TEL: 781-891-0230
ed with freezers and coolers, the procedures and information do not contemplate every potential for loss or
EMAIL: propertyengineering@libertymutual.com
damage. Therefore, every situation should be reviewed by the appropriate safety manager in an effort to take
all appropriate steps and precautions to minimize freezer and cooler hazards. No duty or undertaking is www.libertymutualproperty.com
intended or assumed by Liberty Mutual by this publication, as it is informational in purpose.
© Copyright 2007, Liberty Mutual. This brochure is for informational purposes only. PE1037 07/07