overdoor indicator
(room in use).

The controlled version of this drawing should be viewed in DWF or PDF


format not DWG or other formats.

03.B.10
WC

Where this drawing has been based upon Ordnance Survey data, it has
been reproduced under the terms of Ryder Licence No. 100000144.
Reproduction of this drawing in whole or in part is prohibited without
the prior permission of Ordnance Survey.

2 m

Do not scale the drawing. Use figured dimensions in all cases. Check
all dimensions on site. Report any discrepancies in writing to Ryder
before proceeding.

03.B.09
MH Interview
11 m

Single Socket
Chair, easy (fixed)

B09-2

Twin Socket
TV Outlet

TV

B09-1

B09-3

Single Data Socket


Clock, battery
2

Double Data Socket

B09-4

Switch, PIR Key Override

Switch, Light
Connection Unit, Switched
Connection Unit, Unswitched

overdoor indicator linked


to emergency call
Overdoor indicator linked to nurse call
within adjoining WC

Key operated reset to panic strips

2700

2700

2400

2400

2100

2100

1800

1800

1500

1500

1200

1200

900

900

600

600

300

300

Drainage connection. Refer


to mechanical services
drawings for details.

Emergency call 'panic strips'


around room perimeter at
high and low level
T

Thermostat

CR

Wall Mounted Swipe Card Reader

PB

Push Button Door Release

BG

Break Glass Point


Overdoor Indicator
Fire Alarm Repeater Panel

F.A.R.P.

Nurse Call Panel

N.C.P.

Note
WiFi units generally positioned above ceilings

Elevation B09-1

Elevation B09-3

1 : 50

1 : 50

All furniture, fixtures and fittings to


be procured by others in
accordance with trust guidance on
patient safety,
'Panic Strips' linked to security and
independent of emergency call.

Emergency call / reset unit


2700

2700

2400

2400

2100

2100

1800

1800

1500

1500

1200

1200

900

900

600

600

300

300

Revision

Date

Drawn By

18/11/13

PMil

First Construction Issue


Amendment
Status

Construction
Project

Gateshead Health NHS Foundation


Trust
Emergency
Care Centre
Queen Elizabeth Hospital, Gateshead
Drawing

Room Loaded Drawing


MH Interview
03.B.09

Elevation B09-2

Elevation B09-4

1 : 50

1 : 50

Project No.

Drawing No.

2544:01

403-B09-RevA

Scale at A3

Drawn By

1 : 50

RWils

info@ryderarchitecture.com
www.ryderarchitecture.com

Room Data Sheet


Project:
Department:
Room Name:
Room Number
Drawing Number

Room Data Sheet

RDS 03.B.09

2544:01 Gateshead QEH - Emergency Care Centre

PRELIMINARY
Revision
A
Date
15/11/2013

MH Interview
03.B.09

2544:01 Gateshead QEH - Emergency Care Centre

Project:
Department:
Room:
Room Number
Drawing Number

PRELIMINARY
Revision
A
Date
15/11/2013

MH Interview
03.B.09

AIR

Activities:
1) Confidential and informal discussions with patients, relatives or staff.
2) Telephone(s) may be used.

RDS 03.B.09

Winter Temperature (DegC):


Summer Temperature (DegC):
Mechanical Ventilation (Supply ac/hr):
Mechanical Ventilation (Extract ac/hr):
Pressure Relative to Adjoining Space:
Filtration (% DSE and % Arrestance):
Humidity (%RH)
Cooling
Water Supply
General Notes:

Notes

Requirements
21

Ventilation to suit occupancy


and heat gains

LIGHTING

1 x Staff
Up to 4 others, including wheelchair person.

Personnel:

Service Illumination (Lux):


Service Illumination Night (Lux):
Local Illumination (Lux):
Colour Rendering Required:
Standby Lighting Grade:

300

Lighting Control:
General Notes:

(V) dimmable

Ra (80)
B

NOISE
Planning Relationships

Space Data:
Notes:

Area (m)

11

Height (mm)

Privacy Factor Required (dB):

80

Mechanical Services (NR):


Intrusive Noise (NR Leq):
* Acceptable sound Level [L10dB(A)]:
*Speech Privacy Required:
* Quality Which Cannot Be Tolerated:
(* alternative format)
General Notes:
SAFETY

30
35

Hot Surface Max. Temp (DegC):


Hot Water Max. Temp (DegC):
General Notes:

43

Ref
HTM 08-01

2700

Lamp indicator call situated over door outside room.


Furniture subject to project specific requirements (e.g. settee or chairs).
This space may also function as a small group room.
A telephone should have direct access to outside line .
Wall alarm as per existing or similar required.
Observation provisions.

Requirements

FIRE
Enclosure:

Automatic Detection:

Smoke

Notes

Room Data Sheet


Project:
Department:
Room:
Room Number
Drawing Number
Walls:

Floor:
Ceiling:

Doorsets:
Window:
Internal Glazing:
Hatch:
Observation
Observation
Signage:
Notes:

2544:01 Gateshead QEH - Emergency Care Centre


MH Interview
03.B.09

Surface Finish (HTM 56): 5


Moisture Resistance (HTM 56): N i.e. Normal humidity.
Cleaning Routine (HTM 56): To manufacturers recommendations

Room Data Sheet

RDS 03.B.09
PRELIMINARY
Revision
A
Date
15/11/2013

RDS 03.B.09

2544:01 Gateshead QEH - Emergency Care Centre

Project:
Department:
Room:
Room Number
Drawing Number

MH Interview
03.B.09

Description

Quantity

PRELIMINARY
Revision
A
Date
15/11/2013

Code

Group

New Trans Total


2

PUSH STRIP staff emergency call and integral/adjacent indicator lamp

CAL007

SOCKET outlet, telephone / data

OUT215

CLOCK battery, wall mounted ( secured to wall)

CLO001

CHAIR, easy, low back, upholstered (secured to floor)

CHA005

Cleaners socket

(HTM 58) 2x 1000mm, single leaf, plain flush, lockable


Two way opening doors in room & wc

SOCKET outlet, switched, 13amp, twin

Overdoor indicator sign - Room in Use

(HTM 55) N/A

Overdoor indicator linked to nurse call system

(HTM 57) N/A

Key switch, panic strip reset unit

Push button patient / staff call with integral reset unit

Surface Finish (HTM 61): 6 i.e. Soft, impervious, jointless


Cleaning Routine (HTM 61): To manufacturers recommendations
Surface Finish (HTM 60): 5: Imperforate
Moisture Resistance (HTM 60): N: Normal humidity.
Cleaning Routine (HTM 60): To manufacturers recommendations

Durable finishes required.


Anti ligature requirements needed to room and en-suite.
Observation provision
Two way opening door required