Reference Manual
PRIMARY TEST SYSTEM
FOR SUBSTATION EQUIPMENT
Accessories included
Contents
Contents
Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
About this Reference Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Glossary of Symbols and Terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Used Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Used Terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Safety Instructions for CPC 100 and its Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
Principle Use According to Regulations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
Orderly Measures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
Operator Qualifications and Primary Responsibilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Safe Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Changing Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-11
CPC 100 in combination with CP TD1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-12
Designated Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-13
Functionality of CPC 100 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-13
CPC 100 Versions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-15
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Functional Components of CPC 100 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
High-Voltage and High-Current Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
ePC Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Functional Components in Detail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
CPC 100 Block Diagram (Simplified). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
Built-in ePC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
How to Use the CPC 100 Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-17
The principles of test cards and test procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-17
Starting the Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-20
View Selector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-21
Accelerator Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-22
Test Card View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-22
Current Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Scope of Current Transformer Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
CT Ratio (and Burden). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Testing Ratio, Polarity (and Burden) with Injection to Current Input. . . . . . . . . . . . . . . . . . 4-3
Testing Ratio, Polarity (and Burden) with a Current Clamp . . . . . . . . . . . . . . . . . . . . . . . 4-10
CT Burden . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11
Test settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12
Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12
Automatic Test vs. Manual Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13
CT Excitation (Kneepoint) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-15
Test Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-16
Automatic Test vs. Manual Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-17
Demagnetization. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-19
Winding Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-20
Test settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-22
Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-23
The "Temperature Compensation for Cu" Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-24
ii
Contents
Voltage Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Scope of Voltage Transformer Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
VT Ratio. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Test Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
Automatic Test vs. Manual Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
VT Burden . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8
Test Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-9
Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-10
Automatic Test vs. Manual Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-10
Voltage Withstand Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-13
iii
Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Scope of Transformer Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
TRRatio (per Tap) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
Test Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7
Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-10
Carrying Out a TR Ratio Test (per Tap) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-11
Winding Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-13
Test settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-15
Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-16
The "Temperature Compensation for Cu" Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-17
TRTapCheck (for OLTC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-18
Test settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-20
Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-21
Examples using the TRTapCheck test card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-22
Voltage Withstand Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-25
Test Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-26
Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-27
TanDelta . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-28
Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Scope of Resistance Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
iv
Contents
Others . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Scope of Others. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-2
Sequencer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-3
Defining a Sequence of States . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-4
Testing an Overcurrent Relay with ARC Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-11
Measuring a CT Ratio at Different Current Magnitudes . . . . . . . . . . . . . . . . . . . . . . . . . 8-14
Generating an Intermittent High-Current Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-16
Ramping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-18
Defining a Ramp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-19
Testing PickUp/DropOff Value of an Overcurrent Relay . . . . . . . . . . . . . . . . . . . . . . . . 8-27
Amplifier. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-29
Amplifier Use Case: GPS-Synchronized 3-Phase System for End-To-End Testing . . . . 8-31
Comment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-33
Form Editor - Text Editor: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-34
TanDelta . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-36
File Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
The CPC 100 File System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-1
Navigating Through the File System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-2
The Menus. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-2
vi
Contents
vii
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Test Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-2
Earth Resistance Accessory Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-3
Current Booster CP CB2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-4
Technical Data of CP CB2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-5
Operation Modes of CP CB2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-6
Ordering Information for CP CB2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-8
Polarity Checker CPOL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-9
Technical Data of CPOL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-10
Ordering Information for CPOL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-10
Changing the Batteries in CPOL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-11
Current Clamp C-Probe 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-13
Ordering Information for C-Probe 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-13
CP SA1 Discharge Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-14
Ordering Information for CP SA1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-14
Reference Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-15
viii
Contents
Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-15
Clamps. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-16
Plugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-16
Assembly Instructions for Odu MINI-SNAP Plug . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-17
ix
Preface
Preface
Contents of this section
About this Reference Manual.......................................................... page 1-1
Glossary of Symbols and Terms ..................................................... page 1-2
Safety Instructions for CPC 100 and its Accessories...................... page 1-5
Principle Use According to Regulations ..................................... page 1-5
Orderly Measures ...................................................................... page 1-5
Operator Qualifications and Primary Responsibilities ................ page 1-6
Safe Operation........................................................................... page 1-6
Power Supply........................................................................ page 1-6
General ................................................................................. page 1-7
DC output to test objects with a high inductance .................. page 1-8
High-voltage and high-current outputs.................................. page 1-9
Changing Fuses ....................................................................... page 1-11
Designated Use............................................................................. page 1-13
Functionality of CPC 100 .............................................................. page 1-13
CPC 100 Versions......................................................................... page 1-15
1-1
The Reference Manual always has to be available at the site where CPC 100 is
used.
It should be read and used by all people working with CPC 100.
In addition to the Reference Manual and the applicable regulations for accident
prevention in the country and at the site of operation, the accepted technical
procedures for safe and competent work should be heeded.
Used Symbols
Note
Indicates notes with special meaning, i.e., additional important
information.
Caution
Indicates sections with special safety-relevant meaning.
Electrical Danger - Caution
Emphasizes actions or instructions that hold potential risk to
health and life. To be carried out by authorized personnel with
extreme caution and full awareness of the safety regulations
only.
Reference Information
Indicates an important cross-reference.
1-2
Preface
Used Terms
Booster
Combo box
DHCP
ePC
Ethernet
fs
Focus
IP address
LCD
NIC
1-3
PC Card
Press
The term "press" in the context of working with the CPC 100
software (e.g., press the I N S E R T C A R D key) means:
a) pressing a menu or an accelerator key
b) or setting the focus ( Glossary) onto a UI ( Glossary)
element by navigating to it with the handwheel, and
pressing the handwheel to execute the E N T E R function
Quantity
rd
sel
Test object
Trigger
User
Operational surface of a software. A user interface contains all
interface (UI) control elements necessary to work with the software.
1-4
V0
V1
Preface
DANGER!
CPC 100 should only be used in a safe manner, mindful of the dangers while
paying attention to the Reference Manual, and when it is in a technically
sound condition and when its use is in accordance with the regulations. In
particular, avoid disruptions that could in turn affect safety.
If you have a cardiac pacemaker, do not use CPC 100! Before operating
CPC 100, make sure there is no person with a cardiac pacemaker in the
immediate vicinity.
CPC 100 is exclusively intended for the application fields specified in detail
in Designated Use on page 1-13.
Any other use is deemed not to be according to the regulations. The
manufacturer/distributor is not liable for damage resulting from improper
usage. The user alone assumes all responsibility and risk.
Orderly Measures
Personnel assigned to use CPC 100 should carefully read the Reference
Manual - in particular this section on safety instructions - before beginning to
work with it. On principle this also applies to personnel who only occasionally
work with CPC 100.
1-5
Testing with CPC 100 should only be carried out by authorized and qualified
personnel. Clearly establish the responsibilities!
Safe Operation
When setting CPC 100 into operation, follow the instructions in Putting
CPC 100 into Operation on page 2-46.
DANGER!
If you have a cardiac pacemaker, do not use CPC 100! Before operating
CPC 100, make sure there is no person with a cardiac pacemaker in the
immediate vicinity.
Never use CPC 100 without a solid connection to ground with at least 6mm.
Use a ground point as close as possible to the test object.
Power Supply
1-6
Supply CPC 100 only from a power outlet that has protective earth (PE).
Instead of supplying CPC 100 from phase - neutral (L1-N, A-N), it may also
be supplied from phase - phase (e.g., L1-L2; A-B). However, the voltage
must not exceed 240V AC.
Preface
If the power supply is 190V AC, CPC 100 cannot provide the full output
power at the 800A AC output.
The same applies when an external current booster is used. Therefore, in
order to gain the full output power, provide a sufficient power supply
(190V ... 240V AC).
Caution: The connector "Ext. Booster" is always galvanically connected to
mains, regardless whether or not an external booster is selected on
the software tab Options | Device Setup, the green warning
warning light (0) is on, the outputs are turned off or the Emergency
Stop button is pressed.
Handle with extreme caution. Do not use any other booster cables
than the ones supplied by OMICRON.
General
Even if you switched off CPC 100, wait until the red I/O warning
light is fully extinguished.
As long as this warning light is lit, there is still voltage and/or
current potential on one or more of the outputs.
Make sure that a test objects terminals that are to be connected to CPC 100
do not carry any voltage potential. During a test, the only power source for a
test object may be CPC 100.
Do not insert objects (e.g., screwdrivers, etc.) into any input/output socket.
Never use the test cards Quick and Resistance to measure the resistance
of windings with a high inductance because turning off the DC source results
in life-threatening voltage levels.
For this kind of measurement only use the special winding resistance test
card RWinding!
1-7
When measuring the ratio of voltage and power transformers make sure that
the test voltage is connected to the corresponding primary winding, and the
voltage of the secondary winding is the one that is measured. Accidentally
mixing up the windings can generate life-threatening voltages within the
transformer.
For example: feeding a voltage of 100V/ 3 to the secondary winding of a
voltage transformer that has a ratio of 400000V/ 3 : 100V/ 3, induces a
voltage of 400000V/ 3 in the transformers primary winding.
Make sure that when testing a current transformer by feeding a test current
into its primary winding, all secondary windings are shorted. On open
secondary windings, life-threatening voltages can be induced!
1-8
Preface
All AC and DC output sockets of CPC 100 can carry life-hazardous voltage
potential and provide life-hazardous currents. Therefore:
While connecting cables to the CPC 100 high-voltage or high-current
outputs or other conducting parts that are not protected against accidental
contact, press the Emergency Stop button, and keep it pressed as long
as an output signal is not absolutely necessary for the test.
When connecting to the front panel input/output sockets, use wires with
either 4 mm safety "banana" connectors and plastic housing or, where
applicable, with the especially manufactured counterpart supplied by
OMICRON electronics (e.g., for the V2 AC measuring input).
For the high-voltage and high-current output connectors on the left-hand
side of the test set (2kV AC, 400A DC and 800A AC, ext. Booster), only
use the specially manufactured cables supplied by OMICRON electronics
(refer to Cables on page 16-15).
One end of the high-voltage cable has a coaxial safety plug that is
certified for a voltage level of 2kV AC. The other end is equipped with a
safety banana plug that is insulated with a shrink tube.
When CPC 100 is switched on consider this part of the cable a
hazard of electric shock!
If you do not use the high-current 400A DC or 800A AC outputs or the
high-voltage 2kV AC output, disconnect any cable that may be plugged
in to these sockets.
The 400A DC or 800A AC outputs are not switched off by internal
relays. Therefore, if a test mode is selected that does not use either
one of these two outputs, they still generate current.
Do not stand right next to or directly underneath a connection point
because the clamps may fall off and touch you.
This is a physical and an electrical hazard.
The red warning light on the CPC 100 front panel indicates hazardous
voltage and/or current levels at the CPC 100 outputs (red light "I" on or
flashing). The green warning light indicates that the CPC 100 outputs are
not activated.
Note: If none or both warning lights are on, the unit is defective and
must not be used anymore.
Both of the high-current output sockets on the left-hand side of the test set
(400A DC and 800A AC) usually carry a relatively low-voltage potential.
1-9
Do not operate CPC 100 under ambient conditions that exceed the
temperature and humidity limits listed at Technical Data on page 15-1.
If CPC 100 or any add-on device or accessory does not seem to function
properly, do not use it anymore. Please call the OMICRON hotline.
1 - 10
Preface
Changing Fuses
Turn off CPC 100, unplug the power cord and/or press the Emergency Stop
button.
We recommend to wait for about 30 seconds. This time is necessary for the
internal electrolytic capacitors to fully discharge.
Ground the test object, and disconnect it from CPC 100. By disconnecting it
you prevent a possibly faulty test object feeding power back into CPC 100.
Locate the blown fuse on the front panel of CPC 100, and replace it:
6.3A T (6.3 Amps slow-acting wire fuse 5x20mm) for AC OUTPUT in 6A
operation mode1 or for DC OUTPUT.
3.15A T (3.15 Amps slow-acting wire fuse 5x20mm) for AC OUTPUT in
130V operation mode.
10A FF (10 Amps very-quick-acting wire fuse 5x20mm) for measuring
inputs.
Note: Replace with identical fuse type only.
1. For detailed information about the difference between the 6A and the 130V operation mode refer
to Functional Components of CPC 100 on page 2-2.
1 - 11
This is due to a new standard and does not symbolize any functional difference.
Note:
1 - 12
Both symbols mean exactly the same, i.e., protective earth (PE) or
equipotential ground.
Preface
Designated Use
CPC 100, in conjunction with its accessories or as a stand-alone unit, is a multipurpose primary test set for commissioning and maintaining substation
equipment. It performs current transformer (CT), voltage transformer (VT) and
power transformer (TR) tests. Furthermore it is used for contact and winding
resistance testing, polarity checks as well as primary and secondary protection
relay testing.
The various, partly automated tests are defined and parameterized via the front
panel control of a built-in ePC ( Glossary).
1 - 13
Resistance testing
measuring contact resistance ()
measuring winding resistance ( - k)
measuring earth resistance ( - k)
dielectric withstand voltage test (2kV AC)
Other applications
Ramping, a pogrammable ramping generator and determination of
thresholds
Sequencer for automatic testing with different states in real time
Comment card to hold a user-defined comment and/or note regarding the
actual test procedure.
When using the Amplifier test card, an input signal fed into a
synchronization input drives the high-current outputs magnitude,
frequency and phase angle.
CPC 100 provides a "dead man" function, i.e., the possibility to install an
additional push-button that stops remote operation if released (refer to ePC
Interfaces on page 2-4).
Any other use of CPC 100 but the one mentioned above is considered improper
use, and will not only invalidate all customer warranty claims but also exempt the
manufacturer from its liability to recourse.
1 - 14
Preface
CPC 100
Version
Processor
V0
V1
ePC Interfaces
PC
1. CPC 100 V1 units are equipped with one socket for connecting CPC 100 to both a PC and a
network hub.
For detailed information on the ePC interfaces, see ePC Interfaces on page
2-4.
1 - 15
1 - 16
Introduction
Introduction
Contents of this section
Functional Components of CPC 100............................................... page 2-2
Front Panel ................................................................................ page 2-2
High-Voltage and High-Current Outputs .................................... page 2-3
ePC Interfaces ........................................................................... page 2-4
Functional Components in Detail ............................................... page 2-6
CPC 100 Block Diagram (Simplified) ............................................ page 2-13
Built-in ePC ................................................................................... page 2-14
How to Use the CPC 100 Software............................................... page 2-17
The principles of test cards and test procedures ..................... page 2-17
Starting the Software ............................................................... page 2-20
View Selector ........................................................................... page 2-21
Accelerator Keys ...................................................................... page 2-22
Test Card View ........................................................................ page 2-22
Inserting Test Cards............................................................ page 2-23
Setting Up a Test Card ....................................................... page 2-25
Settings Page...................................................................... page 2-28
Starting a Test..................................................................... page 2-29
Temperature Monitoring...................................................... page 2-30
Test Procedure Overview ........................................................ page 2-31
File Operations......................................................................... page 2-32
Options..................................................................................... page 2-33
Creating Defaults and Templates ............................................ page 2-42
Putting CPC 100 into Operation.................................................... page 2-46
Principle Steps to Carry Out a Test with CPC 100 .................. page 2-47
2-1
Front Panel
AC OUTPUT
I/0
Built-in ePC
INPUT
Measuring inputs
DC OUTPUT
6A DC output
Safety
key lock
Emergency
stop button
Soft-touch
keyboard
Navigation
elements
Test
Start /Stop
Note:
With the CPC 100 V0, the number of test cards in one test procedure
should be limited to 15 to avoid memory problems. The CPC 100 V1 allows
using more test cards in one test procedure but we recommend not to use more
than 15 test cards to keep the tests clearly structured.
2-2
Introduction
Grounding
terminal
400A DC
(4-4.5V DC)
High DC current output
800A AC
2kV AC
(6.1-6.5V AC)
High-voltage
output
High AC current
output
Ext. Booster
e.g., for the
connection of the
CP CB2 current
booster option for
output currents of
up to 2000A
Caution:
Automatic circuit
breaker I > 16A
POWER ON /OFF
switch
2-3
ePC Interfaces
The ePC interfaces are located on the right-hand side of the CPC 100 housing.
The PC and network interfaces differ depending on the CPC 100 version as
described below.
Figure 3:
ePC interfaces of the
CPC 100 V0
1. For more information on the PC and network interfaces, see CPC 100 in a
Network on page 11-1.
2. For the pin assignment of the RS232 serial interface connector, see ePC
Interfaces on page 15-29.
3. The connector for external safety functions allows connecting:
The attached plug contains a jumper for the emergency stop or "dead man"
function, and as long as the plug is placed on the connector, these functions
are bridged. If the plug is removed, emergency stop is active.
For the plugs pin assignment and a wiring scheme, see Connector for
External Safety Functions on page 15-31.
2-4
Introduction
Figure 4:
ePC interfaces of the
CPC 100 V1
The CPC 100 V1 supports the USB interface 1.1 and 2.0 for connecting the USB
memory stick shipped with the CPC 100.
Note:
The full functionality is guaranteed only for the stick delivered with the
CPC 100.
The serial and safety interfaces are identical with the CPC 100 V0 version (see
above). The network interface is an auto-crossover Ethernet connector that can
be connected to a network hub or directly to a PC or a notebook.
The CPC 100 V1 provides the following LEDs on the ePC interface:
2-5
2-6
Introduction
2-7
DC OUTPUT
Programmable DC current output.
Figure 6:
Functional group
DC OUTPUT
2-8
Introduction
INPUT
Analog precision measuring inputs
Figure 7:
Functional group INPUT
2-9
For details about the accuracy of the individual ranges, please refer to 10V
V DC Input on page 15-27.
Note:
BIN IN
Binary input for trigger signal
Figure 8:
Functional group BIN IN
1. Test not yet started, turn the key and remove it from key lock:
the software does not accept any more entries and/or
commands via the soft-touch keys and/or the handwheel. The
test cannot be started by pushing the I/O (test start/stop) pushbutton.
2. Test running, turn the key and remove it from key lock:
the current or voltage quantities presently applied are "frozen",
i.e., can neither be changed by commands via the soft-touch
key keys and/or the handwheel, nor turned off by pushing the
I /O (test start/stop) push-button.
Exception: the Emergency Stop button. An emergency stop is
possible at any time.
2 - 10
Introduction
Warning lights
The warning lights indicate an either safe or dangerous operating condition.
Figure 10:
Warning lights
Dangerous
operating condition!
safe operating condition
1. Outputs are
switched OFF
Safe operating
condition
Dangerous voltage
and/or current at
output.
3. Output is switched
ON
Dangerous voltage
and/or current at
output.
2 - 11
Ext. Booster
Socket to connect an external booster, for example, the CP CB2 current booster
for output currents of up to 2000A.
Enable any external booster in the CPC 100 software on the tab
Options | Device Setup (refer to Device Setup on page 33 of this chapter).
Note:
2 - 12
Introduction
Ext.
Booster
Rectifier
& power
factor
corrector
500V
R
500V
500V
Switched
mode
amplifier
Mains
100-240V
50/60Hz
N
500V
500V 4A
1kV 2A
2kV 1A
2kV
R
Filter
I
U
I
PE
ADC U
U
DSP
(Digital
Signal
Processor)
2kV
800A
65V
130V / 6A AC
65V
3.15A
6.3A
65V / 6A DC
I
U
O
u
t
p
u
t
s
6V / 800A AC
Ethernet
to
ext.
PC
RS 232
optional
Built-in
ePC
+
5V / 400A DC
300V AC
3V AC
10A AC/DC
10V DC
BIN IN
I
n
p.
2 - 13
Built-in ePC
The built-in ePC ( Glossary) of CPC 100 runs under Microsoft Windows CE
operating system and provides front panel control.
This section provides a brief overview of the front panel control components.
Section How to Use the CPC 100 Software on page 17 of this chapter
describes in detail how to work with the front panel control components, how to
set up a test, execute it and save it for later use.
Via the built-in ePC, CPC 100 can be accessed from a stand-alone PC, e.g., a
notebook, via a PC network and via the Internet (refer to CPC 100 in a Network
in chapter 11).
Figure 13:
CPC 100s built-in ePC,
components overview
Accelerator keys
View selector
LCD monitor
Context-dependent menu keys
Tab selector
Test start/stop
U P / D O W N keys
Jog-dial handwheel
Soft-touch keyboard
2 - 14
Introduction
LCD monitor
The monitor is a high-contrast gray-scale graphical LCD display with a resolution
of 320x240 pixels.
Accelerator keys
Let you add the test card of your choice, e.g., Quick, CT, VT... etc. (refer to
Accelerator Keys on page 22 of this chapter).
View Selector
Lets you select the view of your choice, e.g., Test Card View, Test Procedure
Overview, File Operations or Options (refer to View Selector on page 21 of this
chapter).
Jog-dial handwheel
Advanced jog-dial handwheel with "click" (E N T E R ) function.
In "navigation" mode, turning the handwheel navigates you through the UI
( Glossary) elements within one test card. Pressing the U P / D O W N keys
has the same effect.
In "data entry" mode, i.e., if the focus ( Glossary) is set onto a data entry field
or a combo box, and the handwheel was pressed to "enter" the field and to
enable data entry, turning the handwheel increases/decreases the entry fields
value or browses through the preset values of the combo box, respectively.
Pressing the handwheel corresponds to the E N T E R function of the soft-touch
keyboard.
Furthermore, the wheel comprises an adaptive acceleration function, i.e., if the
focus is, for example, set onto a data entry field, fast turning increments/
decrements a value in increasingly bigger steps, slow turning in decreasingly
smaller steps.
U P / D O W N keys
Soft-touch keys supplementing the handwheel. Depending on the current focus
in the software user interface, pressing these keys either navigates through the
UI elements within one test card, or - if in a data entry field, for example increments/decrements a value.
Contrary to the handwheel, the U P / D O W N keys change a value in fixed
coarse increments /decrements in order to ease a quick approximation to the
end value. The fine adjustment is then done with the handwheel.
2 - 15
Stopping a test does not shut off the CPC 100 outputs
instantaneously. First, the currently running test sequence finishes,
then the test execution is stopped.
Most test cards finish the running test sequence with a predefined
ramp function.
Therefore, in a hazardous situation never press "Stop Test". Instead,
use Emergency Stop.
Tab selector
If a test procedure comprises more than one test card, use these keys to change
between the single test cards.
2 - 16
Introduction
This manual refers to the CPC 100 software version V 1.4. Information
about the software version of your CPC 100 can be found at the
Options tab System Info (refer to System Info on page 41 of this
chapter).
Test cards
The CPC 100 software comprises a number of test cards. A test card carries
out one specific test, e.g., measuring a CT excitation curve, or testing the
ratio of a voltage transformer.
A test card holds a number of user-definable test settings and - after the test
was run - test results.
2 - 17
Test procedure
A test procedure contains multiple test cards.
The composition of such a test procedure and the settings of all single test
cards can be freely defined by the user. Within a test procedure, each test
card and its associated test is executed individually in a user-defined order.
Note:
With the CPC 100 V0, the number of test cards in one test
procedure should be limited to 15 to avoid memory problems. The CPC 100
V1 allows using more test cards in one test procedure but we recommend not
to use more than 15 test cards to keep the tests clearly structured.
Report
For archiving or reporting purposes, or later processing, a test procedure with
all of its test cards, specific settings and - after the test was run - test results
and assessments can be saved. It is then considered a report.
Such a report can later be opened any time in CPC 100 File Operations
menu.
2 - 18
Introduction
Figure 14:
The principles of test
cards, defaults and test
procedures
Test Card
settings
settings
+
Test Card
Test Card
+ Test
+
Test Card
settings
+
results
+
...
= Test
Procedure
settings
settings
Test Procedure
name.xml
(in file system)
Test Procedure
Default
settings
Test Procedure
Template
name.xmt
settings
(1) One Test Card Default for each type of test card
The following sections emphasize on test cards, defaults and templates in more
detail. Also refer to Creating Defaults and Templates on page 42 of this
chapter.
2 - 19
2 - 20
Introduction
View Selector
Figure 15:
View selector
2 - 21
Accelerator Keys
With the exception of Quick, pressing an accelerator key opens the according
Insert a new test card dialog box and lets you select the test card of your
choice. Pressing Quick opens the Quick test card directly.
Quick test card
select from current transformer (CT) test cards
select from voltage transformer (VT) test cards
select from power transformer test cards
select from resistance test cards
select from other test applications...
Ramping (primary / secondary protection relay testing)
Sequencer (primary / secondary protection relay testing)
Amplifier card (refer to page 8-29).
Comment card (refer to page 8-33).
TanDelta (refer to the CP TD1 Reference Manual available on
the CPC Explorer CD-ROM).
2 - 22
Introduction
Note:
2 - 23
Due to usability reasons, some test cards, such as Winding Resistance, Voltage
Withstand Test or Polarity Check, appear in more than one test mode, e.g.,
Winding Resistance appears in Current Transformer, Power Transformer
and Resistance.
With regard to their functionality, these test cards are identical.
To expand a collapsed group of tests
, e.g., CT, set the focus onto this
group, and press E N T E R or the handwheel.
The group of tests expands and displays all of its associated test
cards.
Browse to the test card of your choice, and when its highlighted press
ENTER.
This will switch from the Insert a new test card dialog to the Test Card View,
inserting the test card of your choice after the last selected test card in the Test
Card View.
Note:
You can insert as many test cards as needed and of all types of your choice by
repeating this process.
Note:
With the CPC 100 V0, the number of test cards in one test procedure
should be limited to 15 to avoid memory problems. The CPC 100 V1
allows using more test cards in one test procedure but we recommend
not to use more than 15 test cards to keep the tests clearly structured.
If you need more test cards in one test procedure, we recommend not
to save all cards in one, e.g., the test procedure default, but to combine
a smaller number of cards to logical groups, and to save these logical
groups as test procedure templates with individual names (refer to
Test Procedure Templates on page 45 of this chapter).
Pressing E S C closes Insert a new test card, and brings you back to the
previous view without inserting a new test card.
2 - 24
Introduction
As shown above, the value itself is highlighted, the unit is not, and at the values
end a blinking caret (cursor) indicates "ready for data entry".
Now either
use the U P / D O W N keys to approximate the value of your choice quickly in
coarse predefined steps
rotate the handwheel to fine-adjust the value in precision steps
type in the value of your choice using the numeric soft-touch keys to the left
of the handwheel (refer to figure17).
2 - 25
Figure 17:
Soft-touch keys to enter
numerical values
: backspace
Esc: cancels the current
action without saving
Soft-touch keys to
enter numerical
values.
If a number key is pressed with the focus set onto a data entry field,
this number is automatically written to the data entry field, and the field
is enabled for data entry.
press the handwheel (to "enter" the combo box for selection)
and either navigate through the list of available parameters by rotating the
handwheel, or by using the U P / D O W N keys.
Pressing E S C while scrolling through the list of values closes the combo box
and returns to the previous value.
Check Box
Set the focus onto the check box, e.g.,
and press either the
E N T E R key or the handwheel to select /clear a check box.
2 - 26
Introduction
List Box
Figure 18:
Example of a list box
List boxes are differentiated between read-only and editable list boxes:
In a read-only list box (figure 18), turning the handwheel scrolls from line to
line.
When using the U P / D O W N keys, a read-only list box is treated as one UI
element, i.e., pressing one of the keys exits the list box, and sets the focus
onto the next /previous UI element.
In an editable list box, turning the handwheel scrolls from table cell to table
cell. Press either the handwheel or E N T E R to "enter" a cell and to edit the
value.
When using the U P / D O W N keys, the focus proceeds to the same table cell
one line above or below.
2 - 27
Settings Page
Some test cards include the S E T T I N G S menu key. Pressing the S E T T I N G S
menu key opens the Settings page.
Figure 19:
Main page with
SETTINGS menu key
The Settings page with the exception of the TRRatio test card looks as shown
below.
Figure 20:
Settings page
The Settings page allows setting the test cards individually. At the
Device Setup tab in the Options view (see Options on page 33 of this
chapter), the same properties can be set for all test cards of a test procedure.
As a rule, do not use the Settings page described here but the Device Setup
tab in the Options view to set the test cards. Making different settings for the
test cards is rarely a good idea. Set the test cards individually using the Settings
page only in well-founded cases.
If a test card contains results, the settings cannot be changed. When a file
containing results is loaded, the Settings page can be used to view the settings
of the test procedure.
2 - 28
Introduction
Starting a Test
Note:
Tests can only be started and stopped with the I/O (test start/stop)
push-button while in the Test Card View.
Each test card represents a separate test, and is started individually.
Stopping a test does not shut off the CPC 100 outputs
instantaneously. First, the currently running test sequence finishes,
then the test execution is stopped.
Most test cards finish the running test sequence with a predefined
ramp function.
Therefore, in an emergency situation never press "Stop Test".
Instead, use Emergency Stop.
While a test is running, several functions such as changing the test card,
changing the view etc., are disabled.
To repeat the test, the test results need to be cleared beforehand. Otherwise the
start is blocked.
2 - 29
Temperature Monitoring
Each test card contains a progress bar-like temperature gauge that displays
CPC 100 actual temperature condition. When the temperature limit is reached,
i.e., before an overheating condition occurs, the output is switched off
automatically.
In addition, if an output is activated both CPC 100 current consumption from the
power supply and the current emitted at the high-current outputs is monitored
and, together with the temperature, displayed by this temperature gauge. The
temperature gauges bar therewith represents an indicator for the remaining
time CPC 100 can output power.
Just as with over-temperature, if these limit values are exceeded the output is
switched off automatically.
With deactivated outputs, the temperature gauges bar represents an indicator
how much the device has already cooled off.
Note:
To reach a maximum output time, we suggest to let CPC 100 cool off
completely before switching it on again.
Note:
2 - 30
Introduction
The Test Procedure Overview lists all test cards of the currently active test
procedure in a list box showing the cards name, its creation date and time,
whether test results are available and the test cards assessment status.
Pressing I N S E R T C A R D switches to the Insert a new test card dialog. After
inserting a new test card, the software automatically switches to the Test Card
View, inserting the test card of your choice after the last selected test card in the
Test Card View.
Pressing E S C at Insert a new test card brings you back to the previous view
without inserting a new test card.
D E L E T E C A R D deletes the currently highlighted test card from the test
procedure.
With S A V E A S D E F A U L T , Test Procedure Overview provides a function to
save the current test procedure as the test procedure default, i.e., that default
the CPC 100 software will start with in future.
To learn more about defaults, refer to section Creating Defaults and Templates
on page 42 of this chapter.
Unlike in Test Card View, where all context-dependent menu keys apply for that
particular card only, the Test Procedure Overview has an additional menu item
that applies for all test cards: whereas C L E A R R E S U L T S clears the test results
of the currently highlighted test card only (in figure 21 thats "Comment"),
C L E A R A L L R E S U L T S applies to all test cards, i.e., clears the results of all
cards listed in the Test Procedure Overview.
After both C L E A R R E S U L T S and C L E A R A L L R E S U L T S , re-start the test in
the Test Card View by pressing the I/O (test start/stop) push-button.
2 - 31
Automatically switches back to the Test Card View, and opens the test
procedure default. If the current test procedure contains unsaved data, you will
be asked whether or not you want to save them before you proceed.
File Operations
The CPC 100 File Operations resemble the functionality known from the
Windows Explorer. File Operations comprises a F I L E and an E D I T submenu
with additional menu items as well as an O P E N and various S A V E . . . functions.
The highest hierarchical level of the CPC 100 file system, the "root", is named
CPC 100. Below this, you can create additional folders in a tree-structure of your
choice, save tests in these folders, and carry out file operations, such as open,
save, rename, copy, paste etc. For CPC 100 V1 units with a USB memory stick
plugged in, a second tree root USB Disk is displayed as shown above.
The CPC 100 file system differentiates two file types:
name.xml A test procedure with all of its test cards and specific settings.
An .xml file may also contain test results and assessments that
were stored together with the settings as report in the CPC 100
file system for archiving purposes.
name.xmt Test procedure template, i.e., a user-defined template
containing one or more test cards with all of their specific test
settings but without test results.
For a detailed description of the CPC 100 File Operations refer to File
Operations in chapter 9.
2 - 32
Introduction
Options
Note:
Changes made in the Options view are automatically saved when the
view is changed (e.g., when Options is left to change to Test Card
View).
Alternatively changes can be saved instantly by pressing S A V E
OPTIONS.
At a power supply loss or an accidental switching off of CPC 100,
unsaved changes are lost, and the old values are restored.
Device Setup
The Device Setup tab in the Options view allows you to change the settings of
all test cards of the test procedure running on CPC 100 and all test cards
inserted afterwards. The test cards can be instantiated in different ways and for
different purposes. Table 1: Instantiation procedures below displays the
instantiation procedures and the associated default values.
Table 1:
Instantiation procedures
Procedure
Default values
Because the settings of a test card containing results cannot be changed, the
settings made at the Device Setup tab in the Options view apply only to new
test cards if the currently loaded procedure contains results. To change the
settings of a test procedure containing results (e.g. after pressing the K E E P
R E S U L T S menu key or after loading a file), clear the results by pressing the
C L E A R R E S U L T S menu key in all test cards before setting the test procedure
in the Options view.
It is strongly recommended to set the test cards using the Options view. In wellfounded cases, you can set alternatively a test card individually using the
S E T T I N G S menu key (see Settings Page on page 28 of this chapter).
2 - 33
Figure 22:
Options tab Device
Setup
External booster
The "External booster" combo box allows to set the external booster:
For the default value associated with different instantiation procedures, see
Table 1: Instantiation procedures on page 33.
Clamp & input transformer settings
When an input is not connected to the device under test directly but using a
current clamp, a CT or a VT, the ratio of these devices can be set here.
The "Clamp & input transformer settings" group box displays and, if required,
allows you to change settings for external devices:
Per default, the transformation ratios of the current and voltage transformers for
the selected external device are preset. For the default value associated with
different instantiation procedures, see Table 1: Instantiation procedures on
page 33.
2 - 34
Introduction
After CPC 100 has been rebooted, the "Disable ground check" check
is cleared for safety reasons.
Default freq.
The "Default freq." data entry field allows you to enter the default frequency. For
the default value associated with different instantiation procedures, see
Instantiation procedures on page 33 of this chapter.
Auto Save
As the name implies, the "Auto Save" feature automatically saves the current
test settings in fixed intervals. These intervals can be set in the Auto Save box.
There are three time intervals available (10, 30 or 60 minutes), and the option
OFF that disables Auto Save.
Auto Save saves all actual data to a file named lastmeas.xml. So depending
on the set time interval, in case of a system crash, lastmeas.xml may contain
more actual data than you last manually saved test. The file is created during the
next booting process.
When Auto Save saves test settings, it pops up a dialog notifying you about it.
Auto Save works in Test Procedure Overview, File Operations or Options
without any restrictions. In Test Card View, Auto Save does not work as long as
a test is running, or as long as inputs are measured (e.g., in Quick).
In a case like this, Auto Save repeats the attempt to save the test settings in
intervals of minute until it succeeds, i.e., until the test is finished and it can save
the data. After this, Auto Save returns to the set time interval.
2 - 35
Restore Defaults
Pressing the R E S T O R E D E F A U L T S menu key resets all user-specific settings
made in the CPC 100 software to factory-defined defaults including:
2 - 36
all settings made at the Device Setup tab (sets external booster to CB2, sets
CT and VT to "OFF", and sets the value in the "Default freq." data entry field
to 50 Hz)
Introduction
Network
Figure 23:
Options tab Network
Via the built-in ePC, CPC 100 can be accessed from a stand-alone PC, e.g., a
notebook and via a PC network. At the Network tab the communication settings
are specified.
In the combo box select between
DHCP/Auto IP
Static IP
2 - 37
Display
Figure 24:
Options tab Display
The "sliding" regulator brightens or darkens the monitor display and the contrast
within it. Adding contrast increases the difference in shading between areas.
Date / Time
Figure 25:
Options tab Date/Time
2 - 38
Introduction
Regional Settings
Figure 26:
Options tab Regional
Settings
Choose a regional setting for language, temperature unit, date and time style.
These settings affect the way the CPC 100 software displays and sort dates,
times, numbers and decimal points.
Service
Figure 27:
Options tab Service
During operation, CPC 100 creates a log file with a user-definable logging level
(see below).
Every time CPC 100 is switched on, it generates a new log file, and saves the
existing one as the "previous" log file. This way, the occurrences of the previous
and the current session can be viewed (refer to Viewing the log file on page 1211).
2 - 39
The logging level specifies the occurrences to be recorded in the log file:
Logging level:
records
None
nothing
Error
Warning
Info
If the log file gets quite long, use either the scroll bar or the buttons P A G E U P /
P A G E D O W N to navigate up and down in the list of logged occurrences.
C L E A R L O G deletes all log file entries and starts recording occurrences anew.
2 - 40
Introduction
System Info
Figure 28:
Options tab System
Info
OS Version:
Software Version:
Hardware:
Free memory:
2 - 41
Each card of this type, here Quick, that will later be inserted to a test procedure
will already hold these new settings.
Note:
In the CPC 100 file system, a test card default is not visible as a "file" (refer to
The CPC 100 File System in chapter 9).
2 - 42
Introduction
With the CPC 100 V0, the number of test cards in one test procedure
should be limited to 15 to avoid memory problems. The CPC 100 V1
allows using more test cards in one test procedure but we recommend
not to use more than 15 test cards to keep the tests clearly structured.
If you need more test cards in one test procedure, we recommend not
to save all cards in one, e.g., the test procedure default, but to combine
a smaller number of cards to logical groups, and to save these logical
groups as test procedure templates with individual names (refer to
Test Procedure Templates on page 45 of this chapter).
In the CPC 100 file system, the test procedure default is not visible as a "file"
(refer to The CPC 100 File System in chapter 9).
2 - 43
Figure 29:
Creating a user-defined
default by customizing
the test procedure
default
Step 3
Switch to the Test
Procedure
Overview...
A number of test
cards are inserted
to the currently
open test
procedure.
Step 1
test card 1
2 - 44
test card 2
test card 3
Step 1
In the test card view, insert as many test cards as needed to the
currently open test procedure default.
Step 2
At the CPC 100 front panel view selector, switch to the Test Procedure
Overview.
Step 3
Introduction
2 - 45
Before setting CPC 100 into operation and carrying out a test, it is
essential that you have read and understood the section Safety
Instructions for CPC 100 and its Accessories on page 1-5.
Always be aware that all AC and DC output sockets of CPC 100 can
carry life-hazardous voltage potential and provide life-hazardous
currents.
Safety Aspects
We strongly advise you to obey the following legal safety aspects:
Tests with such high voltages and currents must only be carried out by
authorized and qualified personnel.
Personnel receiving training, instructions, directions, or education on highvoltage/current tests should remain under the constant supervision of an
experienced operator while working with the equipment. The instructions
have to be renewed at least once per year.
The instructions must be available in written form and signed by each person
assigned to do high-voltage/current tests.
Preparations in Substation
Prior to connecting a test object to CPC 100, the following steps need to be
carried out by an authorized employee of the utility.
Turn off and disconnect the high voltage from the test object.
Protect yourself and your working environment against an accidental reconnection of high voltage by other persons and circumstances.
Verify a safe isolation of the test object.
Earth-connect and shorten out the test objects terminals using a grounding
set.
Protect yourself and your working environment with a suitable protection
against other (possibly live) circuits.
Protect others from accessing the dangerous area and accidentally touching
live parts by setting up a suitable barrier and, if applicable, warning lights.
If there is a longer distance between the location of CPC 100 and the area of
danger (i.e., the test object), a second person with an additional "Emergency
Stop" button is required.
2 - 46
Introduction
3. Connect CPC 100 to the mains power supply using the provided cable.
4. With the test object grounded and shorted out, connect CPC 100 to the
test object according to your requirements.
5. Remove the grounding set from the test object.
6. Turn on CPC 100 at its POWER switch at the left-hand side.
The green warning light "O" lights up, showing that none of CPC 100 outputs
carries a dangerous voltage or current yet.
7. Set up your test in the CPC 100 software, and, where applicable, determine
whether you want to perform an automatic or a manual test.
The following chapters of this manual comprise an example for each
available test.
For a detailed description of how to use the software refer to section How to
Use the CPC 100 Software on page 17 of this chapter.
8. Once all test cards are prepared and the parameters set, make sure the
safety key lock is in position "release" (horizontal).
2 - 47
9. Start the test by pressing the green I/O (test start/stop) push-button on
CPC 100 front panel.
Notes:
A test can only be started in the Test Card View and with all
preconditions met (refer to Starting a Test on page 29 of this
chapter).
2 - 48
About Quick
Quick is the most basic mode to operate all of the CPC 100 outputs in a manuallike mode with front panel control.
Figure 1:
Quick test card
CPC 100 starts in the Test Card View (refer to Test Card View on page 2-22)
with the test procedure default. Initially, the test procedure default contains
one empty Quick test card. However, this template can be customized according
to your specific requirements with as many test cards as needed and of all types
of your choice.
By creating a user-defined test procedure default, CPC 100 starts up loading
your most frequently used test cards already containing specific values.
To learn more about defining such a template, refer to Creating Defaults and
Templates on page 2-42.
3-1
3-2
Measurement Settings
Measured quantities ( Glossary)
Combo boxes to select the first and second quantity to
measure. Possible choices at each combo box:
V1 AC
1
I Out
I Out sel
V1 AC sel
V2 AC
I Clamp
V2 AC sel
I Clamp sel
V Out
CT
V Out sel
CT sel
VT
V DC
VT sel
I DC
I AC
f V1 AC
I AC sel
f Out
Note:
3-3
Table 1:
Display of calculated
value in measurement
table
Measured
quantities
(m1) (m2)
V
For AC: Z or R, X
Impedance Z (magnitude in and phase
angle in ) or R and X in .
For DC: R
Resistance R (in )
else "n/a"
For AC: P, Q, S
Real power P (in W) and cos , apparent
power S (in VA) and cos , reactive power
Q (in var) and cos .
For DC: P
Real power P (in W)
else "n/a"
3-4
Measured
quantities
(m1) (m2)
V
3-5
Amplitude in dB
Figure 2:
Characteristics of the
frequency-selective
measurement
f in Hz
VT
CTRatio
VTRatio
CTBurden
VTBurden
CTRatioV
VTElectronics
CTLowPower
Transformer
Others
Sequencer
Ramping
TRRatio
3-6
Note:
3-7
Range
Combo box to select between the output ranges
AC 800A, AC 6A, AC 3A, DC 400A, DC 6A,
AC 2kV, AC 1kV, AC 500V, AC 130V and
CB2:1000A, CB2:2000A or
CU20:10A, CU20:20A or
CU1:10A, CU1:20A, CU1:50A, CU1:100A
Either CB2:, CU20: or CU1: output ranges are available
if the respective external booster was selected at the
Options tab Device Setup (see Options on page 2-33)
or on the Settings page of the Quick test card.
Each range has an associated minimum and maximum
value, a fixed precision value as well as a preset number
of decimal characters (refer also to Setting Up a Test
Card on page 2-25).
If Quick operates in the "on" state, the output range
setting is locked and cannot be changed.
While in the "measuring" state with de-activated outputs,
when a range is changed, the output changes
accordingly to a new value within the allowed range
between minimum and maximum.
After having pressed K E E P R E S U L T S , the output
range setting and the measurements settings are locked
and cannot be changed.
3-8
3-9
Sync w/ V1AC
Set S Y N C W / V 1 A C by pressing the menu key that
appears when the focus is on the frequency/phase angle
data entry field.
This synchronizes the CPC 100 output frequency with
the V1AC input frequency. In this case the phase angle
of the output is displayed rather than the frequency. Set
the phase angle value relative to the phase angle of the
V1 AC input signal (we recommend a minimum input
voltage of 10V on V1 AC, possible range 48 - 62Hz).
The icon next to the frequency/phase angle data entry
field reflects the actual setting.
If "Sync w/ V1AC" is disabled, the frequency returns to
the previously set frequency value and the icon changes.
If Quick operates in the "on" state, the status of "Sync w/
V1AC" cannot be changed.
Due to the PLL (phase-locked loop) technology, the
synchronization with V1AC needs about 100ms.
If for the particular test object the synchronism within the
first 100ms is relevant, start with a reduced magnitude of
the output signal. Then enter the full magnitude of your
choice, and press E N T E R .
This procedure assures that the high-level output signal
is synchronized with V1AC right from the beginning.
3 - 10
Trigger Settings
A trigger is the occurrence of a selected event, for example, a binary trigger is
the first change of the state at the binary input.
1
3
2
4
Trigger on:
Selection of trigger event
no trigger (default)
binary trigger = CPC 100 input BIN IN is monitored for a trigger event
trigger = first measurement value (m1) > set threshold value
trigger = first measurement value (m1) < set threshold value
trigger = second measurement value (m2) > set threshold value
trigger = second measurement value (m2) < set threshold value
overload = the trigger event is an overload condition that occurs at
the selected output.
What is an "Overload" trigger?
At the 800A AC output, an overload trigger is a condition in which the
set current cannot be reached any longer, for example, because of
an opening contact or circuit breaker.
Note: Current values < 50A do not initiate an "Overload" when the
current circuit opens. Therefore, if you use the trigger condition
"Overload", chose a nominal current value of 50A.
Quick differentiates two "Overload" trigger conditions:
1. the occurrence of an overload (as described above)
2. the clearing of an overload condition (clearing is delayed by
100 ms to debounce).
3 - 11
Bin.In:
Indicates the signal condition at the binary input Bin In. 4 different
characteristics are possible:
Closed: potential-free contact between BinIn+ and BinIn
closed.
Open: potential-free contact between BinIn+ and BinIn
open.
Come:
trigger signal with rising edge
occurred at BinIn.
Go:
trigger signal with falling edge
4
occurred at BinIn
3 - 12
3 - 13
3 - 14
Current Transformer
Current Transformer
Contents of this section
Scope of Current Transformer Tests............................................... page 4-2
CT Ratio (and Burden) .................................................................... page 4-3
Testing Ratio, Polarity (and Burden)
with Injection to Current Input ..................................................... page 4-3
Testing Ratio, Polarity (and Burden) with a Current Clamp ..... page 4-10
CT Burden..................................................................................... page 4-11
CT Excitation (Kneepoint) ............................................................. page 4-15
Winding Resistance ...................................................................... page 4-20
Voltage Withstand Test ................................................................. page 4-25
Polarity Check ............................................................................... page 4-28
CT RatioV (with Voltage)............................................................... page 4-33
CT Rogowski (Ratio) ..................................................................... page 4-38
CT Low Power (Ratio)................................................................... page 4-43
TanDelta........................................................................................ page 4-48
Note:
4-1
Highlight the test card of your choice either by navigating with the handwheel or
by using the context-dependent U P /D O W N menu keys, and press E N T E R .
Note:
CTBurden
CTLowPower (Ratio)
4-2
Current Transformer
4-3
Test settings
Figure 3:
CTRatio test card with
test results
Navigate to the parameter fields, and enter the values according to your test
requirements:
Range:
output range
Iprim:
Isec:
Itest:
f:
output frequency
Auto
select check box for automatic test (default), clear for manual
test (refer to page 4-7).
Note:
Measure
Burden
Pressing the S E T T I N G S menu key opens the Settings page. The Settings
page allows setting the test cards individually. As a rule, do not use the Settings
page but the Device Setup tab in the Options view (see Device Setup on
page 2-33) to set the test cards. For more information, see Settings Page on
page 2-28.
4-4
Current Transformer
Select "Manual input" prior to starting the test. If the test card still
contains results, clear them by pressing C L E A R R E S U L T S .
When "Manual input" is selected, there is no phase available.
Consequently, the polarity and cos cannot be calculated.
Measurements
Iprim:
Isec:
Ratio:
Polarity:
4-5
This option is only useful as long as the injected current Itest is about
of the magnitude of the nominal current Iprim.
Note:
For CTs that have a hole rather than a primary busbar just loop the
high-current cable through the hole and connect the high-current
clamps together.
Figure 4:
Setup for testing ratio,
polarity and burden with
injection to current input
4-6
Current Transformer
Figure 5:
CTRatio test card with
selected "Measure
burden" option and test
results
Burden:
cos
TO
4-7
Manual test
Clearing "Auto" lets you set the test current Itest manually with the handwheel.
Press the I/O (test start/stop) push-button to start the test. The focus is set
onto the "I test:" entry field.
Set the value of your choice either by turning the handwheel and/or by
entering it with the numerical keys.
Note:
A value set with the numerical keys needs to be fully entered and
acknowledged by pressing either E N T E R or the handwheel before
it is applied to the output. If needed, it can then be adjusted using
the handwheel.
Values set by turning the handwheel are applied instantaneously.
4-8
TO
Current Transformer
Select "Manual input" prior to starting the test. If the test card still
contains results, clear them by pressing C L E A R R E S U L T S .
When "Manual input" is selected, there is no phase available.
Consequently, neither the polarity nor the phase angle nor cos can
be calculated.
Since an automatic test only lasts a very short period of time, and a
manual measurement is rather difficult, an automatic test with a
manual measurement is not useful. Therefore, this Reference Manual
will not cover this subject.
Manual test
Clearing "Auto" lets you set the test current Itest manually with the handwheel.
Press the I/O (test start/stop) push-button to start the test. The focus is set
onto the "I test:" entry field.
Set the value of your choice either by turning the handwheel and/or by
entering it with the numerical keys.
Note:
A value set with the numerical keys needs to be fully entered and
acknowledged by pressing either E N T E R or the handwheel before
it is applied to the output. If needed, it can then be adjusted using
the handwheel.
Values set by turning the handwheel are applied instantaneously.
TO
To learn more about test assessment, refer to Test Assessment on page 10-2.
4-9
The test itself is carried out in the same way as the test described at Testing
Ratio, Polarity (and Burden) with Injection to Current Input on page 3 of this
chapter. Please refer to this section.
4 - 10
Current Transformer
CT Burden
Use the CTBurden test card to measure a current transformers secondary
burden with AC current injection into the load (up to 6A).
To do so, open the circuit as shown in figure 7, and inject the AC current from
CPC 100 6A ACoutput into the burden.
The IAC input measures the current that flows into the burden, and the V1AC
input measures the voltage at the burden.
From these measurements, the burden (in VA) and the power factor cos are
calculated.
This is the preferred method in cases, when the current of max. 800A that
CPC 100 can feed into the CTs primary side is not sufficient.
Figure 7:
Setup for a CT burden
measurement
4 - 11
Test settings
Figure 8:
CTBurden test card
with test results
Navigate to the parameter fields, and enter the values according to your test
requirements:
Isec:
Itest:
f:
output frequency
Auto
select check box for automatic test (default), clear for manual
test (refer to page 4-13).
Selecting the check box "Manual input" lets you enter the value for Vsec
manually, e.g., when Vsec was measured with an external volt meter rather than
at input V1AC.
Measurements
4 - 12
Isec:
Vsec:
Burden:
cos
Current Transformer
TO
Manual test
Clearing "Auto" lets you set the test current Itest manually with the handwheel.
Press the I/O (test start/stop) push-button to start the test. The focus is set
onto the "I test:" entry field.
Set the value of your choice either by turning the handwheel and/or by
entering it with the numerical keys.
Note:
A value set with the numerical keys needs to be fully entered and
acknowledged by pressing either E N T E R or the handwheel before
it is applied to the output. If needed, it can then be adjusted using
the handwheel.
Values set by turning the handwheel are applied instantaneously.
TO
4 - 13
Select "Manual input" prior to starting the test. If the test card still
contains results, clear them by pressing C L E A R R E S U L T S .
When "Manual input" is selected, there is no phase available.
Consequently, neither the phase angle nor cos can be calculated.
Since an automatic test only lasts a very short period of time, and a
manual measurement is rather difficult, an automatic test with a
manual measurement is not useful. Therefore, this Reference Manual
will not cover this subject.
Manual test
Clearing "Auto" lets you set the test current Itest manually with the handwheel.
Press the I/O (test start/stop) push-button to start the test. The focus is set
onto the "I test:" entry field.
Set the value of your choice either by turning the handwheel and/or by
entering it with the numerical keys.
Note:
A value set with the numerical keys needs to be fully entered and
acknowledged by pressing either E N T E R or the handwheel before
it is applied to the output. If needed, it can then be adjusted using
the handwheel.
Values set by turning the handwheel are applied instantaneously.
TO
To learn more about test assessment, refer to Test Assessment on page 10-2.
4 - 14
Current Transformer
CT Excitation (Kneepoint)
Use the CTExcitation test card to record the excitation curve of a current
transformer. This test performs an automatic injection of a test voltage of up to
2kV to the current transformers secondary side.
Figure 9:
Setup for recording a
CT excitation curve
4 - 15
Test Settings
Figure 10:
Blank CT Excitation
test card
Navigate to the parameter fields for "Imax:", "Vmax:" and "f:", and enter the
values according to your test requirements.
Select check box "Auto" for automatic test (default), clear it for manual test
(refer to page 4-17).
Set the focus onto the combo box underneath "I:".
The options of this combo box let you determine the method for the knee
point calculation:
IEC/BS
ANSI 45
ANSI 30
Once the test is finished and the knee point calculated according to the selected
method, it is possible to switch between IEC/BS, ANSI 45 and ANSI 30. The
knee point is recalculated accordingly.
Note:
4 - 16
Current Transformer
Manual test
Clearing "Auto" lets you set the test voltage Vtest manually with the handwheel.
Press the I/O (test start/stop) push-button to start the test. The focus is set
onto the "V:" entry field.
Set the first value of your choice (rms value) either by turning the handwheel
or by entering this value with the numerical keys.
Note:
"I:" shows the corresponding current value and indicates it with the crosshair
cursor in the graphics.
Press A D D P O I N T to add the test point to the graph.
Repeat this procedure for all additional test points.
The points you set are automatically connected (interpolated) with linear line
segments.
Press R E M O V E L A S T P . to undo the adding of the last test point. Press
the key repeatedly to remove more than one point.
4 - 17
Press R E M O V E A L L to clear all points at once. This does not terminate the
test but lets you set new test points.
Once all test points are set, press the I/O (test start/stop) push-button to stop
the manual test. The knee point is calculated, and its values are displayed at
"Iknee:" and "Vknee:".
The test can now be assessed
Both cases, an automatic stop after the test and stopping the test manually
during the sweep, reduce the test voltage to the minimum (Vmin) within approx.
1s of time, and demagnetize the transformer core.
Figure 11:
CT Excitation test card
- test points set in
automatic test mode
The graph displays the test results in form of an interpolated curve with test point
markers.
Turn the handwheel to set the focus onto the graph, and press it. This will bring
up a crosshair cursor that lets you navigate through the list of test points by using
the keys P R E V I O U S P O I N T and N E X T P O I N T . Turning the handwheel has
the same effect. The fields "V:" and "I:" display the value pair of each test point.
4 - 18
Current Transformer
Figure 12:
CT Excitation test card
- using the crosshair
cursor
Demagnetization
Both direct currents (DC) or unsymmetrical AC currents (e.g., asymmetries
when the CT is switched off) can cause a residual induction in CT cores.
Residual induction can result in an high increase of the ratio error.
To reduce the residual induction to zero, the CT cores should be demagnetized
after all CT tests with DC, e.g., after a measurement of the CT winding
resistance, or the measurement of the contact resistances of the primary circuit.
Also demagnetize the core before carrying out ratio measurements.
If the limit values for current and voltage (Imax and Vmax) at the CTExcitation
test card are high enough to bring the core into saturation during the recording
of an excitation curve, slowly decreasing the testing voltage demagnetizes the
CT automatically.
Demagnetization can also be done without recording an excitation curve by
pressing the D E M A G . button.
4 - 19
Winding Resistance
Note:
Some test cards are available in more than one test mode. For
example, the test card RWinding can be selected in CT, Resistance
and Transformer.
This is solely related to usability. With regard to functionality, the test
card RWinding is identical in all test modes.
Never open the measuring circuit while current flows. Dangerous voltage may
occur! Check whether the red warning light I and the discharge LED are off
before disconnecting the device under test. Before disconnecting from
CPC 100, connect the device under test to protective earth.
Figure 13:
Setup for a winding
resistance test
4 - 20
Current Transformer
4 - 21
Test settings
Figure 14:
RWinding test card
with test results
Navigate to the parameter fields, and enter the values according to your test
requirements:
Range:
Itest:
R min:
R max:
4 - 22
Current Transformer
Measurements
IDC:
VDC:
R meas:
Time:
Dev:
Note:
The VDC voltage is limited to 10 V. If n/a appears in the VDC box,
decrease the test current to lower the voltage generated at the transformers
secondary winding below 10 V.
4 - 23
ambient temperature
Tref:
In Centigrade:
Rref = (VDC / IDC) x (235C + Tref) / (235C + Tmeas)
In Fahrenheit:
Rref = (VDC / IDC) x (391F + Tref F) / (391F + Tmeas F)
Note: Formula according to IEC 60076-1.
Option cleared
For the winding resistance measurement there is no temperature compensation
taken into consideration.
Once all settings are defined, press the I/O (test start/stop) push-button to start
the test.
When the measurements are taken, finish the test by assessing it.
To learn more about test assessment, refer to Test Assessment on page 10-2.
4 - 24
Current Transformer
Some test cards are available in more than one test mode. For
example, the test card VWithstand can be selected in CT, VT,
Resistance and Transformer.
This is solely related to usability. With regard to functionality, the test
card VWithstand is identical in all test modes.
Use the test card VWithstand to measure the voltage withstand capability of the
secondary winding and secondary wiring.
To do so, disconnect the burden. As shown in figure 15, connect one cable of
the 2kV output to the transformers secondary (1S1) winding connection and the
other cable to earth and the transformers primary connection (P1). Open the
secondary ground connection and ground the burden for safety reasons.
Warning: be aware that the terminal that is connected to the transformers
secondary connection "1S1" leads life-hazardous voltage!
Figure 15:
Setup for a voltage
withstand test
4 - 25
Test Settings
Figure 16:
VWithstand test card
with test results
Navigate to the parameter fields, and enter the values according to your test
requirements:
Vtest:
f:
output frequency
Time:
Option "Auto"
Select this combo box and specify a duration time for the voltage withstand test
to run (default = 60 seconds). After this time, the test is turned off automatically.
Clear this combo box if you prefer to either turn off the test manually, or have it
turned off by the option "Switch off on I AC>" without a duration time involved.
Note:
4 - 26
If both options "Switch off on I AC>" and "Auto" are selected, they act
as an OR operation, i.e., whatever occurs first will turn off the voltage
withstand test.
Current Transformer
Measurements
VAC:
injected voltage from 2kV AC output at the time the test turned
off
IAC:
Imax:
Once all settings are defined, press the I/O (test start/stop) push-button to start
the test.
The test voltage increases in a ramp characteristic from 0V to Vtest. Vtest is
then applied to the output for the specified time span. The measurements are
continuously taken. Afterwards Vtest decreases in a ramp characteristic.
When the measurements are taken, finish the test by assessing it.
To learn more about test assessment, refer to Test Assessment on page 10-2.
4 - 27
Polarity Check
Note:
Some test cards are available in more than one test mode. For
example, the PolCheck test card can be selected in CT and VT.
This is solely related to usability. With regard to functionality, the
Polarity Check test card is identical in all test modes.
Use the PolCheck test card to check a series of test points for correct polarity.
To do so, CPC 100 injects a special polarity test signal at a certain location. This
signal can either be a voltage or a current signal from CPC 100, and has a signal
characteristic similar to a saw-tooth signal with a different steepness for the
rising and the falling slope.
The polarity check itself is then done with the accessory CPOL, a portable easyto-use polarity checker.
Figure 17:
Illustrated setup for a
polarity check
4 - 28
polarity checker
CPOL
Current Transformer
If CPOL detects the same signal characteristic at a test point, it considers the
polarity as OK, and lights up the green LED.
If the signal characteristic is inverted or distorted, CPOL considers the polarity
not OK, and lights up the red LED.
If CPOL detects a signal that is too low, both LEDs light up at the same time.
Remedy: increase the signal magnitude.
Note:
If you detect a wrong polarity in the current path, turn off CPC 100 first,
and only then disconnect the terminals.
If you are not quite certain whether your measurement is correct, you can
confirm it by reversing the probes of CPOL. In that case, the other LED should
light up.
If the capacity of CPOLs battery gets low, the LEDs start flashing. As long as
the LEDs are flashing, CPOLs battery provides sufficient power to continue
working. However, the battery should be changed as soon as possible.
Never operate CPOL with an open battery compartment. A life-hazardous
voltage level may occur in the battery compartment if CPOLs probe touches a
test point with high-voltage potential!
4 - 29
Test Settings
Figure 18:
PolCheck test card with
test points
Navigate to the parameter fields, and enter the values according to your test
requirements:
Range:
output range
Ampl.:
Select the option "Intermittent" to define a pulse duty cycle for the output signal:
T on:
T off:
Clear the option "Intermittent" to apply the polarity check output signal
continuously.
Note:
Please observe the allowed duty cycles that may apply to the selected
AC output range. The allowed pulse duty cycle, i.e., the typical time
tmax, depends on the selected range, the ambient temperature, the
operating conditions of CPC 100 etc.
For more information please refer to CPC 100 Outputs on page 15-5.
4 - 30
Current Transformer
Pressing the S E T T I N G S menu key opens the Settings page. The Settings
page allows setting the test cards individually. As a rule, do not use the Settings
page but the Device Setup tab in the Options view (see Device Setup on
page 2-33) to set the test cards. For more information, see Settings Page on
page 2-28.
4 - 31
4 - 32
Current Transformer
4 - 33
Test settings
Figure 21:
CTRatioV test card with
test results
Navigate to the parameter fields, and enter the values according to your test
requirements:
Iprim:
Isec:
Vtest:
f:
output frequency
Auto
select check box for automatic test (default), clear for manual
test (refer to page 4-36).
Note:
4 - 34
Current Transformer
Measurements
Vsec:
Vprim:
Iout
Ratio:
Polarity:
Selecting the check box "Manual input" lets you enter the value for Vprim
manually, e.g., when Vprim was measured with an external volt meter.
4 - 35
TO
Manual test
Clearing "Auto" lets you set the test voltage Vtest manually with the handwheel.
Press the I/O (test start/stop) push-button to start the test. The focus is set
onto the "V test:" entry field.
Set the value of your choice either by turning the handwheel and/or by
entering it with the numerical keys.
Note:
A value set with the numerical keys needs to be fully entered and
acknowledged by pressing either E N T E R or the handwheel before
it is applied to the output. If needed, it can then be adjusted using
the handwheel.
Values set by turning the handwheel are applied instantaneously.
4 - 36
TO
Current Transformer
Select "Manual input" prior to starting the test. If the test card still
contains results, clear them by pressing C L E A R R E S U L T S .
When "Manual input" is selected, there is no phase available.
Consequently, neither the polarity nor the phase angle nor cos can
be calculated.
Since an automatic test only lasts a very short period of time, and a
manual measurement is rather difficult, an automatic test with a
manual measurement is not useful. Therefore, this Reference Manual
will not cover this subject.
Manual test
Clearing "Auto" lets you set the test voltage Vtest manually with the handwheel.
Press the I/O (test start/stop) push-button to start the test. The focus is set
onto the "V test:" entry field.
Set the value of your choice either by turning the handwheel and/or by
entering it with the numerical keys.
Note:
A value set with the numerical keys needs to be fully entered and
acknowledged by pressing either E N T E R or the handwheel before
it is applied to the output. If needed, it can then be adjusted using
the handwheel.
Values set by turning the handwheel are applied instantaneously.
TO
To learn more about test assessment, refer to Test Assessment on page 10-2.
4 - 37
CT Rogowski (Ratio)
Use the CTRogowski test card to measure a Rogowski coils ratio by injecting
current up to 800 A from CPC 100 800A AC output or up to 2000 A using the
CP CB2 current booster connected to the "EXT. BOOSTER" output into the
current-carrying conductor, and by measuring the induced voltage at the end of
the Rogowski coil windings.
A Rogowski coils induced voltage is proportional to the conductor current
differentiated with respect to time. Therefore, in order to acquire a direct
equivalent of the conductors current, the induced voltage needs to be
integrated. In general, a Rogowski coils output signal is either lead via an
integrating amplifier or fed into an electronic protection relay with integrator. The
CTRogowski test card integrates the Rogowski coils output signal at the
CPC 100 input V2AC.
Disconnect the Rogowski coils output signal from the electronic protection relay,
and plug it into CPC 100 V2AC input.
The CTRogowski test card measures the amplitude of the injected current
Iprim and the Rogowski coils output voltage Vsec, integrates this signal, and
calculates the secondary current Isec, its phase angle as well as the actual ratio
and the deviation.
Figure 22:
Setup for a CT ratio test
of a Rogowski coil
P2
P1
4 - 38
electronic
protection
relay with
integrator
(e.g.,
150mV at
Inominal)
Current Transformer
Test Settings
Figure 23:
CTRogowski test card
with test results
Navigate to the parameter fields, and enter the values according to your test
requirements:
Range:
output range
Iprim:
(upper field)
Vsec:
fnom:
Itest:
f:
Auto
select check box for automatic test (default), clear for manual
test (refer to page 4-41).
Note:
4 - 39
Pressing the S E T T I N G S menu key opens the Settings page. The Settings
page allows setting the test cards individually. As a rule, do not use the Settings
page but the Device Setup tab in the Options view (see Device Setup on
page 2-33) to set the test cards. For more information, see Settings Page on
page 2-28.
Measurements
Iprim:
(lower field)
Vsec:
Isec:
k V sec dt
Ratio:
Polarity:
Selecting the check box "Manual input" lets you enter the value for Vsec
manually, e.g., when Vsec was measured with an external volt meter rather than
at input V2AC.
4 - 40
Current Transformer
TO
Manual test
Clearing "Auto" lets you set the test current Itest manually with the handwheel.
Press the I/O (test start/stop) push-button to start the test. The focus is set
onto the "I test:" entry field.
Set the value of your choice either by turning the handwheel and/or by
entering it with the numerical keys.
Note:
A value set with the numerical keys needs to be fully entered and
acknowledged by pressing either E N T E R or the handwheel before
it is applied to the output. If needed, it can then be adjusted using
the handwheel.
Values set by turning the handwheel are applied instantaneously.
TO
4 - 41
Select "Manual input" prior to starting the test. If the test card still
contains results, clear them by pressing C L E A R R E S U L T S . When
"Manual input" is selected, there is no phase available. Consequently,
neither the polarity nor the phase angle can be calculated.
Since an automatic test only lasts a very short period of time, and a
manual measurement is rather difficult, an automatic test with a
manual measurement is not useful. Therefore, this Reference Manual
will not cover this subject.
Manual test
Clearing "Auto" lets you set the test current Itest manually with the handwheel.
Press the I/O (test start/stop) push-button to start the test. The focus is set
onto the "I test:" entry field.
Set the value of your choice either by turning the handwheel and/or by
entering it with the numerical keys.
Note:
A value set with the numerical keys needs to be fully entered and
acknowledged by pressing either E N T E R or the handwheel before
it is applied to the output. If needed, it can then be adjusted using
the handwheel.
Values set by turning the handwheel are applied instantaneously.
TO
To learn more about test assessment, refer to Test Assessment on page 10-2.
4 - 42
Current Transformer
built-in burden
electronic
protection
relay with
low
voltage
input (e.g.,
22.5mV at
Inom)
4 - 43
Test Settings
Figure 25:
CT LowPower test card
with test results
Navigate to the parameter fields, and enter the values according to your test
requirements:
Range:
output range
Iprim:
Vsec:
Itest:
f:
output frequency
Auto
select check box for automatic test (default), clear for manual
test (refer to page 4-46).
Note:
Pressing the S E T T I N G S menu key opens the Settings page. The Settings
page allows setting the test cards individually. As a rule, do not use the Settings
page but the Device Setup tab in the Options view (see Device Setup on
page 2-33) to set the test cards. For more information, see Settings Page on
page 2-28.
4 - 44
Current Transformer
Measurements
Iprim:
actual output current at the output that is injected into the low
power current transformers primary side
Vsec:
Ratio:
Polarity:
Selecting the check box "Manual input" lets you enter the value for Vsec
manually, e.g., when Vsec was measured with an external volt meter rather than
at input V2AC.
4 - 45
TO
Manual test
Clearing "Auto" lets you set the test current Itest manually with the handwheel.
Press the I/O (test start/stop) push-button to start the test. The focus is set
onto the "I test:" entry field.
Set the value of your choice either by turning the handwheel and/or by
entering it with the numerical keys.
Note:
A value set with the numerical keys needs to be fully entered and
acknowledged by pressing either E N T E R or the handwheel before
it is applied to the output. If needed, it can then be adjusted using
the handwheel.
Values set by turning the handwheel are applied instantaneously.
4 - 46
TO
Current Transformer
Select "Manual input" prior to starting the test. If the test card still
contains results, clear them by pressing C L E A R R E S U L T S . When
"Manual input" is selected, there is no phase available. Consequently,
neither the polarity nor the phase angle can be calculated.
Since an automatic test only lasts a very short period of time, and a
manual measurement is rather difficult, an automatic test with a
manual measurement is not useful. Therefore, this Reference Manual
will not cover this subject.
Manual test
Clearing "Auto" lets you set the test current Itest manually with the handwheel.
Press the I/O push-button (test start/stop) to start the test. The focus is set
to the "I test:" entry field.
Set the value of your choice either by turning the handwheel and/or by
entering it with the numerical keys.
Note:
A value set with the numerical keys needs to be fully entered and
acknowledged by pressing either E N T E R or the handwheel before
it is applied to the output. If needed, it can then be adjusted using
the handwheel.
Values set by turning the handwheel are applied instantaneously.
TO
To learn more about test assessment, refer to Test Assessment on page 10-2.
4 - 47
TanDelta
The test card TanDelta was especially developed for CP TD1.
CP TD1 is an optionally available high precision test system for on-site
insulation tests of high-voltage systems like power and measuring transformers,
circuit breakers, capacitors and isolators. CP TD1 works as an add-on device to
CPC 100 and is described in the CP TD1 Reference Manual available on the
CPC Explorer CD-ROM.
The TanDelta test card can be accessed from CT, VT, Transformer and Others.
4 - 48
Voltage Transformer
Voltage Transformer
Contents of this section
Scope of Voltage Transformer Tests .............................................. page 5-2
VT Ratio .......................................................................................... page 5-3
VT Burden ....................................................................................... page 5-8
Voltage Withstand Test ................................................................. page 5-13
Polarity Check ............................................................................... page 5-16
VT Electronics ............................................................................... page 5-21
TanDelta........................................................................................ page 5-26
Note:
5-1
Highlight the test card of your choice either by navigating with the handwheel or
by using the context-dependent U P /D O W N menu keys, and press E N T E R .
Note:
VTRatio
VTBurden
VTElectronics
5-2
Voltage Transformer
VT Ratio
Use the VTRatio test card to measure a voltage transformers ratio with injection
on the VTs primary side with up to 2kV from AC OUTPUT.
It measures amplitude and phase angle of the voltage (at V1AC) and the current
on the transformers secondary side, and calculates the actual ratio and the
deviation from the nominal ratio.
Figure 2:
Setup for testing ratio
5-3
Test Settings
Figure 3:
VTRatio test card with
test results
Navigate to the parameter fields, and enter the values according to your test
requirements:
Vprim:
Vsec:
Vtest:
5-4
f:
output frequency
Auto
select check box for automatic test (default), clear for manual
test (refer to page 5-5).
Voltage Transformer
Measurements
Vprim:
Vsec:
Ratio:
Polarity:
Selecting the check box "Manual input" lets you enter the value for Vsec
manually, e.g., when Vsec was measured with an external volt meter rather than
at input V1AC.
TO
Manual test
Clearing "Auto" lets you set the test voltage Vtest manually with the handwheel.
Press the I/O (test start/stop) push-button to start the test. The focus is set
onto the "V test:" entry field.
5-5
Set the value of your choice either by turning the handwheel and/or by
entering it with the numerical keys.
Note:
A value set with the numerical keys needs to be fully entered and
acknowledged by pressing either E N T E R or the handwheel before
it is applied to the output. If needed, it can then be adjusted using
the handwheel.
Values set by turning the handwheel are applied instantaneously.
TO
Select "Manual input" prior to starting the test. If the test card still
contains results, clear them by pressing C L E A R R E S U L T S .
When "Manual input" is selected, there is no phase available.
Consequently, neither the polarity nor the phase angle can be
calculated.
Since an automatic test only lasts a very short period of time, and a
manual measurement is rather difficult, an automatic test with a
manual measurement is not useful. Therefore, this Reference Manual
will not cover this subject.
Manual test
Clearing "Auto" lets you set the test voltage Vtest manually with the handwheel.
Press the I/O (test start/stop) push-button to start the test. The focus is set
onto the "V test:" entry field.
Set the value of your choice either by turning the handwheel and/or by
entering it with the numerical keys.
Note:
A value set with the numerical keys needs to be fully entered and
acknowledged by pressing either E N T E R or the handwheel before
it is applied to the output. If needed, it can then be adjusted using
the handwheel.
Values set by turning the handwheel are applied instantaneously.
5-6
Voltage Transformer
TO
To learn more about test assessment, refer to Test Assessment on page 10-2.
5-7
VT Burden
Use the VTBurden test card to measure a voltage transformers secondary
burden with voltage injection on the VTs secondary side with up to 130V from
AC OUTPUT.
To do so, open the circuit as shown in figure 4, and inject the AC voltage from
CPC 100 130V ACoutput into the burden.
Input IAC measures the current that flows into the burden, and input V1AC the
voltage at the burden.
From these measurements, the burden (in VA) and the power factor cos are
calculated.
Figure 4:
Setup for a VT burden
measurement
5-8
Voltage Transformer
Test Settings
Figure 5:
VTBurden test card
with test results
Navigate to the parameter fields, and enter the values according to your test
requirements:
Vsec:
f:
output frequency
Auto
select check box for automatic test (default), clear for manual
test (refer to page 5-10).
Vtest:
Note 1:
Note 2:
Pressing the S E T T I N G S menu key opens the Settings page. The Settings
page allows setting the test cards individually. As a rule, do not use the Settings
page but the Device Setup tab in the Options view (see Device Setup on
page 2-33) to set the test cards. For more information, see Settings Page on
page 2-28.
5-9
Measurements
Vsec:
Isec:
Burden:
cos
Selecting the check box "Manual input" lets you enter the value for Isec
manually, e.g., when Isec was measured with a current clamp rather than at
input IAC.
TO
Manual test
Clearing "Auto" lets you set the test voltage Vtest manually with the handwheel.
Press the I/O (test start/stop) push-button to start the test. The focus is set
onto the "V test:" entry field.
Set the value of your choice either by turning the handwheel and/or by
entering it with the numerical keys.
Note:
A value set with the numerical keys needs to be fully entered and
acknowledged by pressing either E N T E R or the handwheel before
it is applied to the output. If needed, it can then be adjusted using
the handwheel.
Values set by turning the handwheel are applied instantaneously.
5 - 10
Voltage Transformer
Stop the manual test by pressing the I/O (test start/stop). The test can now
be assessed.
To repeat the test, first press B A C K
CLEAR RESULTS.
TO
Select "Manual input" prior to starting the test. If the test card still
contains results, clear them by pressing C L E A R R E S U L T S .
When "Manual input" is selected, there is no phase available.
Consequently, neither the phase angle nor cos can be calculated.
Since an automatic test only lasts a very short period of time, and a
manual measurement is rather difficult, an automatic test with a
manual measurement is not useful. Therefore, this Reference Manual
will not cover this subject.
Manual test
Clearing "Auto" lets you set the test voltage Vtest manually with the handwheel.
Press the I/O (test start/stop) push-button to start the test. The focus is set
onto the "V test:" entry field.
Set the value of your choice either by turning the handwheel and/or by
entering it with the numerical keys.
Note:
A value set with the numerical keys needs to be fully entered and
acknowledged by pressing either E N T E R or the handwheel before
it is applied to the output. If needed, it can then be adjusted using
the handwheel.
Values set by turning the handwheel are applied instantaneously.
5 - 11
TO
To learn more about test assessment, refer to Test Assessment on page 10-2.
5 - 12
Voltage Transformer
Some test cards are available in more than one test mode. For
example, the test card VWithstand can be selected in CT, VT,
Resistance and Transformer.
This is solely related to usability. With regard to functionality, the test
card VWithstand is identical in all test modes.
Use the test card VWithstand to measure the voltage withstand capability of the
secondary winding and secondary wiring.
To do so, disconnect the burden. As shown in figure 6, connect the 2kV output
socket without point to the transformers secondary (a) winding connection, and
the output socket marked with a point to earth and the transformers primary
connection (N).
Warning: Be aware that the terminals connected to the transformers secondary
connection "a"and "n" lead life-hazardous voltage!
Figure 6:
Setup for a voltage
withstand test
5 - 13
Test Settings
Figure 7:
VWithstand test card
with test results
Navigate to the parameter fields, and enter the values according to your test
requirements:
Vtest:
f:
output frequency
Time:
Option "Auto"
Select this combo box and specify a duration time for the voltage withstand test
to run (default = 60 seconds). After this time, the test is turned off automatically.
Clear this combo box if you prefer to either turn off the test manually, or have it
turned off by the option "Switch off on I AC>" without a duration time involved.
Note:
5 - 14
If both options "Switch off on I AC>" and "Auto" are selected, they act
as an OR operation, i.e., whatever occurs first will turn off the voltage
withstand test.
Voltage Transformer
Measurements
VAC:
injected voltage from 2kV AC output at the time the test turned
off
IAC:
Imax:
Once all settings are defined, press the I/O (test start/stop) push-button to start
the test.
The test voltage increases in a ramp characteristic from 0V to Vtest. Then Vtest
is kept and injected for the time period set in the "Time" data entry field and the
measurements are taken. Next, the ramp decreases again.
When the measurements are taken, finish the test by assessing it.
To learn more about test assessment, refer to Test Assessment on page 10-2.
5 - 15
Polarity Check
Note:
Some test cards are available in more than one test mode. For
example, the test card PolCheck can be selected in CT and VT.
This is solely related to usability. With regard to functionality, the test
card PolCheck is identical in all test modes.
Use the PolCheck test card to check a series of test points for correct polarity.
To do so, CPC 100 injects a special polarity test signal at a certain location. This
signal can either be a voltage or a a current signal from CPC 100, and has a
signal characteristic similar to a saw-tooth signal with a different steepness for
the rising and the falling slope.
The polarity check itself is then done with the accessory CPOL, a portable easyto-use polarity checker.
Figure 8:
Illustrated setup for a
polarity check
5 - 16
polarity checker
CPOL
polarity checker
CPOL
Voltage Transformer
If CPOL detects the same signal characteristic at a test point, it considers the
polarity as OK, and lights up the green LED.
If the signal characteristic is inverted or distorted, CPOL considers the polarity
not OK, and lights up the red LED.
If CPOL detects a signal that is too low, both LEDs light up at the same time.
Remedy: increase the signal magnitude.
Note:
If you detect a wrong polarity in the current path, turn off CPC 100 first,
and only then disconnect the terminals.
If you are not quite certain whether your measurement is correct, you can
confirm it by reversing the probes of CPOL. In that case, the other LED should
light up.
If the capacity of CPOLs battery gets low, both LEDs start flashing
simultaneously. As long as the LEDs are flashing, CPOLs battery provides
sufficient power to continue working. However, the battery should be changed
as soon as possible.
Never operate CPOL with an open battery compartment. A life-hazardous
voltage level may occur in the battery compartment if CPOLs probe touches a
test point with high-voltage potential!
5 - 17
Test Settings
Figure 9:
PolCheck test card with
test points
Navigate to the parameter fields, and enter the values according to your test
requirements:
Range:
output range
Ampl.:
5 - 18
Voltage Transformer
5 - 19
5 - 20
Voltage Transformer
VT Electronics
Use the VTElectronics test card to test the ratio of non-conventional electronic
voltage transformers with a very low level secondary voltage.
To carry out this test, disconnect the plug of the electronic transformers
secondary side from the protection relay, plug it into CPC 100 V2AC input, and
inject voltage from the 2kV AC output to the electronic transformers primary
side.
Figure 11:
Setup for an electronic
voltage transformer
ratio test
electronic
protection
relay with
low
voltage
input
5 - 21
Test Settings
Figure 12:
VTElectronics test
card with test results
Navigate to the parameter fields, and enter the values according to your test
requirements:
Vprim:
Vsec:
Vtest:
5 - 22
f:
output frequency
Auto
select check box for automatic test (default), clear for manual
test (refer to page 5-24).
Voltage Transformer
Measurements
Vprim:
Vsec:
Ratio:
Polarity:
Selecting the check box "Manual input" lets you enter the value for Vsec
manually, e.g., when Vsec was measured with an external volt meter rather than
at input V1AC.
5 - 23
TO
Manual test
Clearing "Auto" lets you set the test voltage Vtest manually with the handwheel.
Press the I/O (test start/stop) push-button to start the test. The focus is set
onto the "V test:" entry field.
Set the value of your choice either by turning the handwheel and/or by
entering it with the numerical keys.
Note:
A value set with the numerical keys needs to be fully entered and
acknowledged by pressing either E N T E R or the handwheel before
it is applied to the output. If needed, it can then be adjusted using
the handwheel.
Values set by turning the handwheel are applied instantaneously.
5 - 24
TO
Voltage Transformer
Select "Manual input" prior to starting the test. If the test card still
contains results, clear them by pressing C L E A R R E S U L T S .
When "Manual input" is selected, there is no phase available.
Consequently, neither the polarity nor the phase angle can be
calculated.
Since an automatic test only lasts a very short period of time, and a
manual measurement is rather difficult, an automatic test with a
manual measurement is not useful. Therefore, this Reference Manual
will not cover this subject.
Manual test
Clearing "Auto" lets you set the test voltage Vsec manually with the handwheel.
Press the I/O (test start/stop) push-button to start the test. The focus is set
onto the "V test:" entry field.
Set the value of your choice either by turning the handwheel and/or by
entering it with the numerical keys.
Note:
A value set with the numerical keys needs to be fully entered and
acknowledged by pressing either E N T E R or the handwheel before
it is applied to the output. If needed, it can then be adjusted using
the handwheel.
Values set by turning the handwheel are applied instantaneously.
TO
To learn more about test assessment, refer to Test Assessment on page 10-2.
5 - 25
TanDelta
The test card TanDelta was especially developed for CP TD1.
CP TD1 is an optionally available high precision test system for on-site
insulation tests of high-voltage systems like power and measuring transformers,
circuit breakers, capacitors and isolators. CP TD1 works as an add-on device to
CPC 100 and is described in the CP TD1 Reference Manual available on the
CPC Explorer CD-ROM.
The TanDelta test card can be accessed from CT, VT, Transformer and Others.
5 - 26
Transformer
Transformer
Contents of this section
Scope of Transformer Tests............................................................ page 6-2
TRRatio (per Tap) ........................................................................... page 6-3
Winding Resistance ...................................................................... page 6-13
TRTapCheck (for OLTC)............................................................... page 6-18
Voltage Withstand Test ................................................................. page 6-25
TanDelta........................................................................................ page 6-28
Note 1: With regard to software handling, this section confines to test-relevant
issues, and does not go into detailed procedural descriptions.
It is assumed that you have read and understood the section How to
Use the CPC 100 Software on page 2-17.
Note 2: We strongly advise you to carefully read the transformer-specific
safety instructions at General on page 1-7 before carrying out
transformer tests.
6-1
Highlight the test card of your choice either by navigating with the handwheel or
by using the context-dependent U P /D O W N menu keys, and press E N T E R .
Note:
The test card TRRatio (per Tap) employs the method of frequencyselective measurement, which is used to filter out interferences as
they usually occur in substations.
To learn more about frequency-selective measurement, please refer
to The Frequency-Selective Measurement on page 3-6.
6-2
Transformer
6-3
Figure 3:
Setup for testing a
power transformer ratio:
Yd5 transformer,
primary side star
connection, secondary
side delta connection
with a 5x30=150
phase shift.
6-4
Transformer
Figure 4:
Setup for a power
transformer ratio tap
changer test
Table 1 shows the Vprim and Vsec settings on the TRRatio test card for different
connections of the transformer under test.
Table 1:
TRRatio test card
settings for different
transformers windings
connections
IEC 60076
vector
group
Winding
HV/H
LV/X
2 kV output
Dd0
v
V
U
Yy0
W u
V
Dz0
v
W u
V
U
w
v
W u
TRRatio
settings
V1 AC input
red
black
red
black
U/H1
V/H2
u/X1
v/X2
V/H2
W/H3
v/X2
w/X3
W/H3 U/H1
w/X3
u/X1
U/H1
V/H2
u/X1
v/X2
V/H2
W/H3
v/X2
w/X3
W/H3 U/H1
w/X3
u/X1
U/H1
V/H2
u/X1
v/X2
V/H2
W/H3
v/X2
w/X3
W/H3 U/H1
w/X3
u/X1
Vprim Vsec
6-5
IEC 60076
vector
group
Winding
HV/H
Dy5
LV/X
V
U
Yd5
2 kV output
u
W
u
w
Yz5
u
w
Dd6
W
V
Yy6
w
W
V
U
Dz6
u
v
u
v
W
V
Dy11
v
w
Yd11
W u
V
Yz11
6-6
W u
V
v
w
v
W u
TRRatio
settings
V1 AC input
red
black
red
black
U/H1
V/H2
n/X0
u/X1
V/H2
W/H3
n/X0
v/X2
W/H3 U/H1
n/X0
w/X3
U/H1
N/H0
w/X3
u/X1
V/H2
N/H0
u/X1
v/X2
W/H3 N/H0
v/X2
w/X3
U/H1
V/H2
n/X0
u/X1
V/H2
W/H3
n/X0
v/X2
W/H3 U/H1
n/X0
w/X3
U/H1
V/H2
v/X2
u/X1
V/H2
W/H3
w/X3
v/X2
W/H3 U/H1
u/X1
w/X3
U/H1
V/H2
v/X2
u/X1
V/H2
W/H3
w/X3
v/X2
W/H3 U/H1
u/X1
w/X3
U/H1
V/H2
v/X2
u/X1
V/H2
W/H3
w/X3
v/X2
W/H3 U/H1
u/X1
w/X3
U/H1
V/H2
u/X1
n/X0
V/H2
W/H3
v/X2
n/X0
W/H3 U/H1
w/X3
n/X0
U/H1
N/H0
u/X1
w/X3
V/H2
N/H0
v/X2
u/X1
W/H3 N/H0
w/X3
v/X2
U/H1
V/H2
u/X1
n/X0
V/H2
W/H3
v/X2
n/X0
W/H3 U/H1
w/X3
n/X0
Vprim Vsec
Transformer
Test Settings
Figure 5:
TR Ratio test card with
test results
Navigate to the parameter fields, and enter the values according to your test
requirements:
Vprim:
Vsec:
Ratio:
Vtest:
f:
output frequency
6-7
Tap:
Data entry field to enter the transformers tap number for each
measurement. If the transformers ratio was specified on the
Settings page (see page 6-8), the Vprim and Vsec values for
the tap are taken from there. The possible entry range from
-999999 allows the first digit to be used as a phase identifier.
Example for 3 phases:
phase L1 (A):
phase L2 (B):
phase L3 (C):
Pressing the S E T T I N G S menu key opens the Settings page. The Settings
page of the TRRatio test card has another functionality as on other test cards.
Figure 6:
Settings page of the
TTRatio test card
The Settings page allows adding the transformers ratio per tap as follows. After
pressing the A D D T A P menu key first, the Vprim and Vsec values for the first
tap are taken from the main page. Change the tap number to the lowest tap of
the transformer under test (e.g. 16 or 0). Add the next tap by pressing the
A D D T A P menu key and enter the corresponding Vprim and Vsec values. After
6-8
Transformer
then, pressing the A D D T A P menu key repeatedly adds more taps with a step
calculated from the values for the first two taps. After adding all taps, press the
M A I N P A G E menu key to transfer the data to the main page.
Note: After the transformers ratio was specified on the Settings page for one
phase, by pressing the S A V E A S D E F A U L T menu key you can save the data.
Then a new test card for the next phase will be inserted with the transformers
ratio preset.
6-9
Measurements
The TRRatio test card displays the measurement results in two display fields
and a table:
Figure 7:
Multiple measurement
results, e.g., from a
power transformer ratio
tap changer test
Iprim
Tap: (in table) displays the transformer tap number for the measurements in
the respective line of the table. This tap number in specified in
the data entry field "Tap:" above the table.
Vprim
Vsec
Note:
Ratio
6 - 10
Transformer
5. When all test points are measured, press the I/O (test start/stop) pushbutton to stop the test. Vtest decreases in a ramp characteristic within
1 second, and the last unsaved line, i.e., the line that was not saved by
pressing K E E P R E S U L T , will be discarded.
6 - 11
6 - 12
Transformer
Winding Resistance
Note:
Some test cards are available in more than one test mode. For
example, the test card RWinding can be selected in CT, Resistance
and Transformer.
This is solely related to usability. With regard to functionality, the test
card RWinding is identical in all test modes.
Never open the measuring circuit while current flows. Dangerous voltage may
occur!
Figure 8:
Setup of a winding
resistance test
Use the RWinding test card to measure the resistance of a power transformers
winding. To do so, loop the I DC current signal from CPC 100 6A DC output via
IAC/DC as shown in figure 8 and inject it into the transformers winding.
IAC/DC measures the injected current, and V DC input measures the voltage
generated at the transformers winding. From these values the winding
resistance is calculated.
Alternatively, inject the current directly from the 400A DC output (see figure 9).
6 - 13
CP SA1
Due to the significant time span needed for the transformers inductance to finish
its loading process, this test evaluates the deviation of measured values within
a time interval of 10 seconds. The winding resistance is continually measured
and stored in CPC 100 internal memory. The calculated difference between the
maximum and minimum measured values in % within the last 10 seconds is
displayed.
Furthermore, this test comprises the option to take a temperature compensation
for copper (Cu) into consideration (refer to page 6-17).
6 - 14
Transformer
Test settings
Figure 10:
RWinding test card
with test results
Navigate to the parameter fields, and enter the values according to your test
requirements:
Range:
output range
Note:
Itest:
R min:
R max:
6 - 15
Measurements
IDC:
VDC:
R meas:
Time:
Dev:
6 - 16
Transformer
ambient temperature
Tref:
In Centigrade:
Rref = (VDC / IDC) x (235C + Tref) / (235C + Tmeas)
In Fahrenheit:
Rref = (VDC / IDC) x (391F + Tref F) / (391F + Tmeas F)
Note: Formula according to IEC 60076-1.
Option cleared
For the winding resistance measurement there is no temperature compensation
taken into consideration.
Once all settings are defined, press the I/O (test start/stop) push-button to start
the test.
When the measurements are taken, finish the test by assessing it.
To learn more about test assessment, refer to Test Assessment on page 10-2.
6 - 17
taps
OLTC
6 - 18
Transformer
Never open the measuring circuit while current flows. Dangerous voltage may
occur!
6 - 19
Test settings
Figure 13:
TRTapCheck test card
with test results
Navigate to the parameter fields, and enter the values according to your test
requirements:
Range:
output range
Note:
Itest:
Tmeas:
Tref:
Tap:
Data entry field to enter the transformers tap number for each
measurement. The possible entry range of -999 ... 0 ... 999
allows for the first digit to be used as a phase identifier.
Example for 3 phases:
phase L1 (A):
phase L2 (B):
phase L3 (C):
6 - 20
Transformer
Tap combo
box:
Measurements
IDC:
VDC:
Rref in :
Ripple in %:
Slope in A/s: Samples and holds the biggest measured steepness of the
falling edge of the actual test current.
6 - 21
4. At the transformer, set the tap displayed in the last result line.
5. Repeat steps 3 and 4 for all taps you want to measure.
6. Press the I/O (test start/stop) push-button to stop the test and wait until the
transformer windings are discharged.
Caution: Before disconnecting the transformer under test, ground all
transformers connections.
6 - 22
Transformer
Figure 14:
Measurement table relevant columns for
winding resistance
measurement
For the winding resistance, the first 4 columns (Tap, Rmeas in , Dev. in % and
Rref in ) of the measurement table are relevant.
After the test has been finished, you can delete a result line by
selecting the result line you want to delete and pressing the
D E L E T E R E S U L T menu key.
To move the tap changer in the same direction for all measurements since,
in general, properly functioning tap changers can show quite different results
depending on the direction of movement.
On the contrary, an interruption caused by a defective tap changer results in
comparatively high measured values for ripple and slope; in this case the
direction does not matter.
The perform the tap changer test, follow the instructions on page 22 of this
chapter.
6 - 23
Figure 15:
Measurement table with
results of tap changer
and winding resistance
test
For the tap changer test, the last 2 columns of the table are relevant.
1
3
5
2
4
6
Note:
In figure 15, you notice significantly higher values for ripple and slope in line 7.
Compared to the properly functioning tap changer of line 5, at this transformer
the ripple is about 30 times and the slope about 15 times higher.
Note:
6 - 24
Transformer
Some test cards are available in more than one test mode. For
example, the test card VWithstand can be selected in CT, VT,
Resistance and Transformer.
This is solely related to usability. With regard to functionality, the test
card VWithstand is identical in all test modes.
Use the test card VWithstand to measure the voltage withstand capability of the
secondary winding and secondary wiring.
As shown in figure 16, connect the 2kV output socket without point to the
transformers secondary (a) winding connection, and the output socket marked
with a point to earth and the transformers primary connection (A).
Warning: Be aware that all the terminals of the transformers secondary side
carry life-hazardous voltage!
Figure 16:
Setup for a power
transformer voltage
withstand test
6 - 25
Test Settings
Figure 17:
VWithstand test card
with test results
Navigate to the parameter fields, and enter the values according to your test
requirements:
Vtest:
f:
output frequency
Time:
Option "Auto"
Select this combo box and specify a duration time for the voltage withstand test
to run (default = 60 seconds). After this time, the test is turned off automatically.
Clear this combo box if you prefer to either turn off the test manually, or have it
turned off by the option "Switch off on I AC>" without a duration time involved.
Note:
6 - 26
If both options "Switch off on I AC>" and "Auto" are selected, they act
as an OR operation, i.e., whatever occurs first will turn off the voltage
withstand test.
Transformer
Measurements
VAC:
injected voltage from 2kV ACoutput at the time the test turned
off
IAC:
Imax:
Once all settings are defined, press the I/O (test start/stop) push-button to start
the test.
The test voltage increases in a ramp characteristic from 0V to Vtest. Vtest is
then applied to the output for the specified time span. The measurements are
continuously taken. Afterwards Vtest decreases in a ramp characteristic.
When the measurements are taken, finish the test by assessing it.
To learn more about test assessment, refer to Test Assessment on page 10-2.
6 - 27
TanDelta
The test card TanDelta was especially developed for CP TD1.
CP TD1 is an optionally available high precision test system for on-site
insulation tests of high-voltage systems like power and measuring transformers,
circuit breakers, capacitors and isolators. CP TD1 works as an add-on device to
CPC 100 and is described in the CP TD1 Reference Manual available on the
CPC Explorer CD-ROM.
The TanDelta test card can be accessed from CT, VT, Transformer and Others.
6 - 28
Resistance
Resistance
Contents of this section
Scope of Resistance Tests ............................................................. page 7-2
Resistance - Measurement ....................................................... page 7-3
Winding Resistance ........................................................................ page 7-9
RGround........................................................................................ page 7-14
Voltage Withstand Test ................................................................. page 7-22
Note:
7-1
Highlight the test card of your choice either by navigating with the handwheel or
by using the context-dependent U P /D O W N menu keys, and press E N T E R .
7-2
Resistance
Resistance - Measurement
Use the Resistance test card to measure test objects with very low resistance,
such as a contacts, windings etc.
To do so, CPC 100 injects DC current into the test object, measures the current
that flows through the test object, and calculates the test objects resistance.
The Resistance test card provides a total of three output ranges:
400A DC
6A DC
V DC (2 wire)
Inject current from 400A DCoutput to both sides of the test object. Input VDC
measures the voltage drop at the test object, the current is measured internally
by CPC 100, and from these values the software calculates the test objects
resistance.
7-3
Figure 3:
Setup for a m
measurement in the
6A DC range
Inject current from 6A DC output to both sides of the test object. To measure this
current, route it via the IAC/DC input as shown in figure 3. Input VDC measures
the voltage drop at the test object, and from these values the software calculates
the test objects resistance.
Figure 4:
Setup for a ...k
measurement in the
VDC (2 wire) range
7-4
Resistance
Test Settings
Figure 5:
Resistance test card in
400A DC range with
test results.
Navigate to the parameter fields, and enter the values according to your test
requirements:
Range:
output range
Itest:
Rmin:
Rmax:
Auto
select check box for automatic test (default), clear for manual
test (refer to page 7-6).
7-5
Measurements
IDC:
VDC:
R:
Selecting the check box "Manual input" lets you enter the value for VDC
manually, e.g., when VDC was measured with an external volt meter rather than
at input VDC.
Note:
TO
Manual test
Clearing "Auto" lets you set the test current Itest manually with the handwheel.
Press the I/O (test start/stop) push-button to start the test. The focus is set
onto the "I test:" entry field.
Set the value of your choice either by turning the handwheel and/or by
entering it with the numerical keys.
Note:
A value set with the numerical keys needs to be fully entered and
acknowledged by pressing either E N T E R or the handwheel before
it is applied to the output. If needed, it can then be adjusted using
the handwheel.
Values set by turning the handwheel are applied instantaneously.
7-6
Resistance
TO
Select "Manual input" prior to starting the test. If the test card still
contains results, clear them by pressing C L E A R R E S U L T S .
When "Manual input" is selected, there is no phase available.
Consequently, neither the polarity nor the phase angle nor cos can
be calculated.
Since an automatic test only lasts a very short period of time, and a
manual measurement is rather difficult, an automatic test with a
manual measurement is not useful. Therefore, this Reference Manual
will not cover this subject.
Manual test
Clearing "Auto" lets you set the test current Itest manually with the handwheel.
Press the I/O (test start/stop) push-button to start the test. The focus is set
onto the "I test:" entry field.
Set the value of your choice either by turning the handwheel and/or by
entering it with the numerical keys.
Note:
A value set with the numerical keys needs to be fully entered and
acknowledged by pressing either E N T E R or the handwheel before
it is applied to the output. If needed, it can then be adjusted using
the handwheel.
Values set by turning the handwheel are applied instantaneously.
7-7
TO
To learn more about test assessment, refer to Test Assessment on page 10-2.
7-8
Resistance
Winding Resistance
Note:
Some test cards are available in more than one test mode. For
example, the test card RWinding can be selected in CT, Resistance
and Transformer.
This is solely related to usability. With regard to functionality, the test
card RWinding is identical in all test modes.
Never open the measuring circuit while current flows. Dangerous voltage may
occur!
Figure 6:
Setup for a winding
resistance test
7-9
7 - 10
Resistance
Test settings
Figure 7:
RWinding test card
with test results
Navigate to the parameter fields, and enter the values according to your test
requirements:
Range:
output range
Note:
Itest:
R min:
R max:
7 - 11
Measurements
IDC:
VDC:
R meas:
Time:
Dev:
7 - 12
Resistance
ambient temperature
Tref:
In Centigrade:
Rref = (VDC / IDC) x (235C + Tref) / (235C + Tmeas)
In Fahrenheit:
Rref = (VDC / IDC) x (391F + Tref F) / (391F + Tmeas F)
Note: Formula according to IEC 60076-1.
Option cleared
For the winding resistance measurement there is no temperature compensation
taken into consideration.
Once all settings are defined, press the I/O (test start/stop) push-button to start
the test.
When the measurements are taken, finish the test by assessing it.
To learn more about test assessment, refer to Test Assessment on page 10-2.
7 - 13
RGround
A good substation grounding system is crucial to prevent people injury and
damage of equipment. International standards such as DIN VDE 0101/
CENELEC HD637S1, IEEE Std 80-2000 or IEEE Std 81-1983 give guidelines
how to measure such impedances.
Smaller grounding systems with a diameter of 100 m (300 ft) or smaller can be
tested with the RGround test card and CPC 100 alone, for large systems the
CP CU1 coupling unit and the Sequencer test card is a better choice. Note that
no other grounding system must be close by.
The current-voltage method as called in CENELEC HD637S1 or fall of potential
method as called in IEEE standards is a good solution to measure the ground
impedance of a substation. The current is fed via a long cable into a remote
ground. This ground can be any ground from a simple test probe to another large
grounding system. The distance between this probe and the grounding system
under test shall be at least 10 times the diameter of the grounding system, 15 to
20 times is better. Then measure the voltages with a second test probe at
various distances around the substation. If possible, choose the measurement
points in a 90 angle (birds-eye view) relative to the current path. In any case,
avoid measuring close (< 60) to the current path.
Measurement data at a large distance (typically three times the length of the
substation) from the substation allow the calculation of the overall substation
ground impedance Zground as defined in VDE 0101. Measurements at different
distances are recommended. The measurement points should all show similar
results. If the points are set too close to the substation or close to other
grounding systems or over buried pipes, the results obtained are not stable.
Figure 8:
Theoretical resistance
characteristic of an
earth electrode
Earth resistance m
600
500
400
300
200
100
0
Distance
7 - 14
Resistance
Note:
Do not touch the test probe without insulating gloves outside of the
substation area. In case of a high-current ground fault within the
substation during the test, considerably high voltages could arise in
any wire connected to the substation and leading away from it.
Figure 9:
Measuring the ground
resistance of small
ground systems
Auxiliary
electrode
U
U
3 ... 5 x a
Auxiliary
electrode
I
90
(Birds-eye view)
10 x a
Substation ground
a = size of the earthing system
7 - 15
Note 1: The "Auxiliary electrode I" carries life threatening voltages during the
test. Also the step voltage around the electrode can be quite high.
Therefore it is recommended to mark an area of 10 m (30 ft) around
the electrode as dangerous zone and to position a guard outside this
area to keep people from entering the dangerous zone.
Note 2: If the desired current cannot be reached or an overload occurs, the
contact resistance to the soil of the "Auxiliary electrode I" might be too
high. Then it is a good idea to place several electrodes in a distance of
few meters and connect them all together to keep the resistance to the
soil low. This also reduces the hazard due to high voltages around the
electrode.
7 - 16
Resistance
Figure 10:
Measuring the ground
resistance of large
ground systems
> 1km
Auxiliary
electrode
U
U
3 ... 5 x a
90
(Birds-eye view
I
a = size of the earthing system
a
Substation A ground
Substation B ground
You can use existing power cables. However, special precautions such as the
use of the CP GB1 grounding box are required. For more information on
CP GB1, contact OMICRON electronics sales office.
7 - 17
Figure 11:
Measuring the soil
resistivity
Auxiliary
electrode
I
Auxiliary
electrode
U
d
U
d
Auxiliary
electrode
U
Auxiliary
electrode
I
1 20 d
d = distance
=2dR
Legend:
= soil resistivity
d = distance between auxiliary electrodes (identical between all electrodes)
R = calculated resistance as indicated at the RGround test card (R(f))
With the spacing of "d", the test measures the average soil resistivity between
the U auxiliary electrodes down to a depth of "d". Therefore, varying "d" also
varies the depth of the volume for which the soil resistivity is to be measured.
The following table lists typical resistivity of some common soil types.
7 - 18
Resistance
Table 1:
Typical resistance of
common soil types
Soil Type
Soil Resistivity
150 m
Loess, clay
20100 m
Humus, acre
10200 m
Sandy clay
50500 m
Glass sand
2003000 m
Rock
3005000 m
100300 m
Granite, freestone
150010000 m
Figure 12:
Measuring the
resistance of a single
ground rod
Substation
ground
ground
rod 1
ground
rod 2
ground
rod 3
ground
rod n
7 - 19
Test settings
Figure 13:
RGround test card with
test results
Navigate to the parameter fields, and enter the values according to your test
requirements:
Itest:
f:
7 - 20
Resistance
Measurements
IRMS:
VRMS:
R(f):
X(f):
7 - 21
Some test cards are available in more than one test mode. For
example, the test card VWithstand can be selected in CT, VT,
Resistance and Transformer.
This is solely related to usability. With regard to functionality, the test
card VWithstand is identical in all test modes.
Use the test card VWithstand to measure the voltage withstand capability of the
secondary winding and secondary wiring. To do so, disconnect the burden.
As shown in figure 14, connect the 2kV output socket without point to the
transformers secondary (1S1) winding connection, and the output socket
marked with a point to earth and the transformers primary connection (P1).
Warning: be aware that the terminal that is connected to the transformers
secondary connection "1S1" leads life-hazardous voltage!
Figure 14:
Setup for a voltage
withstand test with a
current transformer
7 - 22
Resistance
Test Settings
Figure 15:
VWithstand test card
with test results
Navigate to the parameter fields, and enter the values according to your test
requirements:
Vtest:
f:
output frequency
Time:
Option "Auto"
Select this combo box and specify a duration time for the voltage withstand test
to run (default = 60 seconds). After this time, the test is turned off automatically.
Clear this combo box if you prefer to either turn off the test manually, or have it
turned off by the option "Switch off on I AC>" without a duration time involved.
Note:
If both options "Switch off on I AC>" and "Auto" are selected, they act
as an OR operation, i.e., whatever occurs first will turn off the voltage
withstand test.
7 - 23
Measurements
VAC:
injected voltage from 2kV ACoutput at the time the test turned
off
IAC:
Imax:
Once all settings are defined, press the I/O (test start/stop) push-button to start
the test.
The test voltage increases in a ramp characteristic from 0V to Vtest. Vtest is
then applied to the output for the specified time span. The measurements are
continuously taken. Afterwards Vtest decreases in a ramp characteristic.
When the measurements are taken, finish the test by assessing it.
To learn more about test assessment, refer to Test Assessment on page 10-2.
7 - 24
Others
Others
Contents of this section
Scope of Others .............................................................................. page 8-2
Sequencer....................................................................................... page 8-3
Testing an Overcurrent Relay with ARC Function ................... page 8-11
Measuring a CT Ratio at Different Current Magnitudes ........... page 8-14
Generating an Intermittent High-Current Output ...................... page 8-16
Ramping........................................................................................ page 8-18
Testing PickUp/DropOff Value of an Overcurrent Relay......... page 8-27
Amplifier ........................................................................................ page 8-29
Comment....................................................................................... page 8-33
TanDelta........................................................................................ page 8-36
Note:
8-1
Scope of Others
Go to the Test Card View and press I N S E R T C A R D .
Use the context-dependent U P /D O W N menu keys to the right, or the
handwheel, to browse through the structure. On Others, press E N T E R .
Alternatively, press the accelerator key to open Insert a new test card.
Others comprises the following test cards:
Figure 1:
Inserting test cards from
Others
Highlight the test card of your choice either by navigating with the handwheel or
by using the context-dependent U P /D O W N menu keys, and press E N T E R .
Note:
Sequencer
Ramping
8-2
Others - Sequencer
Sequencer
Use the Sequencer test card to define a sequence of states to be applied to a
connected test object.
A state represents an output quantity with defined settings, e.g., a certain
magnitude and frequency, for a preset period of time.
A sequence of up to 7 states can be defined. The states within that sequence
execute sequentially. For each state, a trigger signal can be specified to
prematurely terminate this state and execute the next one.
A sequence of states can either be executed once from state 1 to state x, or
repeated continuously. Furthermore, the complete sequence can prematurely
be terminated if during the execution of one of its states this states specified
trigger condition occurs.
The test objects characteristic is measured, and the values are displayed in the
measurement table.
The Sequencer test card can be subdivided into three sections:
Figure 2:
Sequencer test card
Range selection
Repeat sequence
trigger specification
duration of state
Measurement table
8-3
Pressing the S E T T I N G S menu key opens the Settings page. The Settings
page allows setting the test cards individually. As a rule, do not use the Settings
page but the Device Setup tab in the Options view (see Device Setup on
page 2-33) to set the test cards. For more information, see Settings Page on
page 2-28.
From the range combo box select the CPC 100 output range of your
choice.
8-4
Others - Sequencer
Next set the state(s) parameters, i.e., the parameters that apply to this particular
state only. Each line of the states table represents one state.
Figure 4:
Step 2 - Set the state
parameters
Turn the handwheel to set the focus onto the states tables first cell; in
figure 4 above thats the output current. Then press the handwheel. The
cell turns into an entry field. Now set the output current value of your
choice by turning the handwheel, or use the number keys of CPC 100
soft-touch keyboard. Press E N T E R or the handwheel to acknowledge
your setting and move to the next table cell by turning the handwheel.
Note that the units of the states table (the tables columns) depend on
the selected output range.
On applications with overload it is recommended not to use currents
above 600A without a current booster.
8-5
No Trigger: the state runs for the pre-defined period of time, no trigger
signal will terminate this state.
Binary: a trigger signal is fed into the Binary trigger input Bin In. The
state is terminated as soon as this signal occurs.
8-6
Others - Sequencer
Trigger threshold.
Only available if a trigger ">" or "<" was selected (refer to 7 ).
State duration. After this period of time the state terminates and the
sequence continues with the next state (if any). If a trigger signal occurs
before this time has elapsed, the currently running state terminates and
the sequence continues with the next state. If "SOOT" is selected, the
trigger signal terminates the complete sequence.
The default state duration time is 2s.
A current state has a minimal time of 250ms if the "Repeat" check box is
cleared.
Note: Do not set the state duration shorter than 500 ms if the "Repeat"
check box is selected.
A voltage state has a minimal time of 2s.
Setting a time of 0.000s makes the state infinite. Only a trigger signal will
terminate it.
8-7
Specify the values that the measurement table will eventually show.
Figure 5:
Step 3 - Specify the
values that the
measurement table will
eventually show
10
11
12
10 Turn the handwheel to set the focus onto the measurement tables first
combo box. Press the handwheel to display the available quantities to
measure, and select the one of your choice.
11 Repeat this step at the combo box for the second quantity to measure.
Possible choices of each combo box:
V1 AC
1
I Clamp
V1 AC sel
I Clamp sel
V2 AC
CT
V2 AC sel
CT sel
VT
V DC
VT sel
I DC
I AC
f V1 AC
I AC sel
f Out
8-8
Others - Sequencer
12 Calculated value
Both the items to select from in this combo box and the corresponding
display at the measurement table below depend on the selected
measured quantities.
In this combo box you determine whether the measurement table
displays trigger signal characteristic / elapsed state time until trigger
signal occurrence, ratio and phase angle difference, impedance Z or
resistance R, real power P, apparent power S or the power factor cos .
Table 1:
Display of calculated
value in measurement
table
Measured
quantities
(m1) (m2)
Bin/Time
occurred at BinIn.
Go:
trigger signal with falling edge
V
occurred at BinIn
For AC: Z or R, X
Impedance Z (magnitude in and phase angle in ) or R
and X in .
8-9
Measured
quantities
(m1) (m2)
For DC: R
Resistance R (in )
else "n/a"
V
For AC: P, Q, S
Real power P (in W) and cos , apparent power S (in VA)
and cos , reactive power Q (in var) and cos .
For DC: P
Real power P (in W)
else "n/a"
Press the I/O (test start/stop) push-button to start the output of the sequence of
states (or the single state, if only one was defined).
In the states table, the first state is highlighted and its values are output. The
measurement table displays the measured values, and updates them as well as
the indication of the binary inputs signal status with an interval of approx. 0.5s.
At the end of each state - either after the state time has elapsed at the transition
to the next state, or at the occurrence of the states trigger signal - the values in
the measurement table are once more updated.
8 - 10
Others - Sequencer
I>
OFF
ON
ON
OFF
8 - 11
Figure 7:
Sequencer test card
with parameters and
measurements of the
four states
Like state 1.
Current values < 50A do not initiate an "Overload" when the current circuit opens. For this
reason, a nominal current value of 50A was chosen here, even though the CB is open.
Note:
8 - 12
Others - Sequencer
CB opens
CB autoreclosure
CB opens again
100ms
state 1
*)
state 2 *)
short
dead time
100ms
state 3
state 4 *)
long dead time
State 2 and 4 incl. the additional 100ms CPC 100 adds to compensate for the debounce
(see note above).
8 - 13
Hz
Trigger
Thresh
20 (= 5%)
50.00
No Trigger
n/a
2.000
80 (= 20%)
50.00
No Trigger
n/a
2.000
200 (= 50%)
50.00
No Trigger
n/a
2.000
400 (= 100%)
50.00
No Trigger
n/a
2.000
480 (= 120%)
50.00
No Trigger
n/a
2.000
Each of the five states injects a current with a different magnitude into the CTs
primary winding. There is no trigger specified, so each state runs exactly 2s.
8 - 14
Others - Sequencer
Since the "Repeat" check box is cleared, the sequence of five states executes
exactly one time and then terminates.
Figure 10:
Sequencer test card
with parameters and
measurements of the
five states (states 2...5
shown)
IAC
Ratio:1
:1
20
0.051
0.11
392.2
-0.11
80
0.201
0.12
398.0
-0.12
200
0.502
0.11
398.4
-0.11
400
1.004
0.13
398.4
-0.13
480
1.205
0.15
398.3
-0.15
8 - 15
Set the states in such a way that they constantly repeat: select "Repeat".
8 - 16
Others - Sequencer
state 1
state 2
state 1
state 2
"on" cycle
"off" cycle
"on" cycle
"off" cycle
The lower the averaged value of the output current I rms over the time the longer
CPC 100 can be operated in that mode. This value is calculated with the
following formula:
I rms = I test x
I test
t on
(t on + t off)
= 600A x
3s
(3s + 12s)
= 268.3A
t on
t off
For more application examples, see the AN 0504 Application Note "Basic Circuit
Breaker Tests Using CPC 100".
8 - 17
Ramping
Use the Ramping test card to define a series of ramps to be applied to a
connected test object.
Figure 13:
A typical ramp
characteristic: q / t,
a linear change of either
amplitude or frequency
of one specified output
signal within a defined
period of time.
A ramp represents a
linear change of either
amplitude or frequency
of one specified output
signal whereas the
other quantity remains
fixed.
q (output quantity)
t
A series of up to 5 ramps can be defined. The ramps within that series execute
sequentially, and run from a start to an end value within a set period of time.
It is possible to specify a trigger signal that prematurely terminates either
or the actual ramp only, and then continues with the next one (if any).
The test objects characteristic is measured, and the values are displayed in the
measurement table.
The Ramping test card can be subdivided into three sections:
Figure 14:
Ramping test card
duration of ramp
trigger specification
Measurement table
8 - 18
Others - Ramping
Pressing the S E T T I N G S menu key opens the Settings page. The Settings
page allows setting the test cards individually. As a rule, do not use the Settings
page but the Device Setup tab in the Options view (see Device Setup on
page 2-33) to set the test cards. For more information, see Settings Page on
page 2-28.
Defining a Ramp
First set the series parameters, i.e., the parameters that apply to the entire
series of ramps.
Figure 15:
Step 1 - Set the series
parameters
1
3
2
4
5
6
From the range combo box select the CPC 100 output range of your
choice.
During the output of a ramp, this field displays the currently output value
of the signals quantity selected at 3 .
From the combo box, select the output signals quantity to be ramped:
"Amplitude" or "Frequency".
Enter the ramps start value here. If a series contains more than one
ramp, this is the start value of the first ramp of that series. The second
ramp starts with the end value of the first one, and so on (refer to
Example of a series of ramps on page 23 of this chapter).
8 - 19
Next set the ramp(s) parameters, i.e., the parameters that apply to this particular
ramp only. Each line of the ramps table represents one ramp.
Figure 16:
Step 2 - Set the ramp
parameters
10
Turn the handwheel to set the focus onto the ramps tables first cell; in
figure 16 above thats the output current. Then press the handwheel. The
cell turns into an entry field. Now set the output current value of your
choice by turning the handwheel, or use the number keys of CPC 100
soft-touch keyboard. Press E N T E R or the handwheel to acknowledge
your setting and move to the next table cell by turning the handwheel.
Note that the units of the ramps table (the tables columns) depend on
the selected output range.
Duration of ramp, i.e., the time this particular ramp sweeps the selected
signal from the start to the end value.
After this period of time the ramp terminates and the series continues
with the next ramp (if any).
If a trigger signal occurs before this time has elapsed, the currently
running ramp terminates and the series continues with the next ramp. If
"SOOT" is selected, the trigger signal terminates the complete series of
ramps.
8 - 20
Others - Ramping
No Trigger: the ramp sweeps the selected signal from the start to the
end value within the pre-defined period of time, no trigger signal will
terminate this ramp.
Binary: a trigger signal is fed into the Binary trigger input Bin In. The
ramp is terminated as soon as this signal occurs.
8 - 21
9
cont.
10 Trigger threshold.
Only available if a trigger ">" or "<" was selected (refer to 9 ).
Press the A D D R A M P button, and repeat steps 7 to 10 to define additional
ramps. Note that the maximum possible number of ramps is 5.
8 - 22
Others - Ramping
Ramp 1
Ramp 2
Ramp 3
The three ramps defined in the ramps table shown above result in an output
signal like this:
I
Ramp 2
200A
Ra
mp
mp
Ra
1A
t
0s
5s
15s
20s
Ramp 1
Ramp 2
Ramp 3
from 1A
(set at "Start val:")
to end value 0A
(set in line 3 at column "A")
in 5 s
for 10 seconds
in 5 seconds
(set in line 3 at column "s")
from 200A
(end value of ramp 1)
from 200A
(end value of ramp 2)
8 - 23
Specify the values that the measurement table will eventually show.
Figure 18:
Step 3 - Specify the
values that the
measurement table will
eventually show
11
12
13
11 Turn the handwheel to set the focus onto the measurement tables first
combo box. Press the handwheel to display the available quantities to
measure, and select the one of your choice.
12 Repeat this step at the combo box for the second quantity to measure.
Possible choices of each combo box:
V1 AC
1
I Clamp
V1 AC sel
I Clamp sel
V2 AC
CT
V2 AC sel
CT sel
VT
V DC
VT sel
I DC
I AC
f V1 AC
I AC sel
f Out
8 - 24
Others - Ramping
13 Calculated value
Both the items to select from in this combo box and the corresponding
display at the measurement table below depend on the selected
measured quantities.
In this combo box you determine whether the measurement table
displays trigger signal characteristic / elapsed ramp time until trigger
signal occurrence, ratio and phase angle difference, impedance Z or
resistance R, real power P, apparent power S or the power factor cos .
Table 2:
Display of calculated
value in measurement
table
Measured
quantities
(m1) (m2)
Bin/Time
occurred at BinIn.
Go:
trigger signal with falling edge
V
occurred at BinIn
For AC: Z or R, X
Impedance Z (magnitude in and phase angle in ) or R
and X in .
8 - 25
Measured
quantities
(m1) (m2)
For DC: R
Resistance R (in )
else "n/a"
V
For AC: P, Q, S
Real power P (in W) and cos , apparent power S (in VA)
and cos , reactive power Q (in var) and cos .
For DC: P
Real power P (in W)
else "n/a"
Press the I/O (test start/stop) push-button to start the output of the series of
ramps (or the single ramp, if only one was defined).
In the ramps table, the first ramp is highlighted and its values are output. The
measurement table displays the measured values, and updates them as well as
the indication of the binary inputs signal status with an interval of approx. 0.5s.
At the end of each ramp - either after the ramp time has elapsed at the transition
to the next ramp state, or at the occurrence of the trigger signal - the values in
the measurement table are once more updated.
8 - 26
Others - Ramping
I>
The CPC 100 AC OUTPUT feeds the ramped current signal into a CT, which is
connected to an overcurrent relay. The overcurrent relays trip contact is fed into
CPC 100 binary input BinIn, and acts there as a trigger signal (as described on
page 21 of this chapter).
8 - 27
Figure 20:
Ramping test card with
parameters and
measurement values of
the three ramps
Ramp 1:
Set to output a ramped current
signal from 100.0A to either 200.0A
in 10s, or until the trigger condition
"Binary" occurs.
Here, trigger condition "Binary"
means: the relay contact picks up. In
this moment, ramp 1 terminates and
the series continues with ramp 2.
The measurement table shows for
ramp 1 that the relay contact picked
up after 7.175s at a current value of
170.29A.
Ramp 3:
Because ramp 1 did not reach the 200A due to the
trigger signal, ramp 3 starts with 170.29A, and then
ramps down to zero with the set steepness (200.0A to
0.0A in 10s) until the trigger condition "Binary" occurs.
Ramp 2:
Pause time. Test current is output
for 1s.
ramp 2
I
200A
ramp 3
pick up
170.29A
152.35A
100A
8 - 28
1s
0A
0s
drop off
p1
ram
7.175s
1.1s 10s
21s
Others - Amplifier
Amplifier
Use the Amplifier test card to set CPC 100 to an "amplifier-like" mode. In this
mode, an input signal fed into a synchronization input drives the high-current
outputs magnitude, frequency and phase angle.
Select between IAC, V1AC and V2ACas synchronization inputs.
To prevent saturation, the output signal follows sudden magnitude changes at
the synchronization input slowly. This smoothening effect delays the follow-up
of the output current up to 250ms.
Both the "amplification" factor and the phase angle between input and output are
set by the user in the Amplifier test card.
Note 1: Changes in frequency and phase angle may result in unwanted
effects. Both frequency and phase must be held stable.
Note 2: The input frequency is limited to a range of 48 ... 62Hz.
Figure 22:
The Amplifier test card
Set range
Set phase
angle
between input
and output
signal
Value
measured at
synchronization input
Select
synchronization input
8 - 29
Pressing the S E T T I N G S menu key opens the Settings page. The Settings
page allows setting the test cards individually. As a rule, do not use the Settings
page but the Device Setup tab in the Options view (see Device Setup on
page 2-33) to set the test cards. For more information, see Settings Page on
page 2-28.
8 - 30
Others - Amplifier
GPS synchronization
unit CMGPS
Test set
CMC 256-3
CT 2
CT 3
Protection
relay
CT 1
8 - 31
Figure 24:
Settings of Amplifier
test card for this
example use case
8 - 32
Others - Comment
Comment
The Comment card is inserted to a test procedure in the same manner like a
test card. Its purpose is to hold a user-defined comment and / or note regarding
the actual test procedure or other important information such as operational data
of a transformer, for example.
Figure 25:
The Comment card
8 - 33
Buers
TR24
Siemens
KFRM 1863A / 22E
1955
T-54953
100 MVA
YN/yn0
220.000V
262.5A
110.000V
525.0A
10.2%
Enter the first word "Substation" and then a tab. Proceed with "Buers" and a
carriage return. Proceed accordingly:
Sub.
Buers
Trans.
TR24
Manuf.
Siemens
Type
a.s.o.
8 - 34
Others - Comment
Clear All:
Clear Text: Deletes all to the right of the tab, i.e., everything but the lefthand side column.
8 - 35
TanDelta
The test card TanDelta was especially developed for CP TD1.
CP TD1 is an optionally available high precision test system for on-site
insulation tests of high-voltage systems like power and measuring transformers,
circuit breakers, capacitors and isolators. CP TD1 works as an add-on device to
CPC 100 and is described in the CP TD1 Reference Manual available on the
CPC Explorer CD-ROM.
The TanDelta test card can be accessed from CT, VT, Transformer and Others.
8 - 36
File Operations
File Operations
Contents of this section
The CPC 100 File System............................................................... page 9-1
Navigating Through the File System ............................................... page 9-2
The Menus ...................................................................................... page 9-2
Submenu File ............................................................................. page 9-3
Submenu Edit ............................................................................ page 9-3
9-1
The folder expands and displays its subfolders (if any) and the tests
it contains.
Browse to the test card of your choice, and when its highlighted press
the handwheel or E N T E R .
The Menus
Main File Operations menu
Opens the submenu File (refer to page 9-3)
Opens the submenu Edit (refer to page 9-3)
Saves the currently open test, i.e., the test card(s) previously
opened in the Test Card View (refer to Note below).
Opens the String Editor. You can save the currently open test
under a new name of your choice (15 characters max.).
Use the handwheel or the U P / D O W N keys to select a test,
and press O P E N to open it. Changes to Test Card View.
Closes the current test card(s), changes to Test Card View and
opens the test procedure default.
Note:
Unlike the other menu items, the two S A V E . . . functions of the main
File Operations menu directly effect the currently open test, i.e., the
test procedure that was composed in the Test Card View, or the test
that was loaded in the CPC 100 file system beforehand.
Therefore, pressing S A V E , for example, does not save the test that
you may have highlighted in the folder tree, but the one that is currently
open.
9-2
File Operations
Submenu File
Opens the String Editor. You can create a new folder with any
name of your choice.
Appends the contents of a test file (.xml) or template (.xmt) of
your choice to the currently open test.
Deletes the currently selected test or folder from CPC 100 disk
space.
Opens the String Editor that enables you to rename the current
test to any new name of your choice.
(for future use)
Closes the submenu and returns to the main File Operations
menu.
Submenu Edit
Select the test of your choice. Press C U T to put the selected
test or folder to the Clipboard. Proceed with P A S T E ...
Select the test of your choice. Press C O P Y to copy test or
folder to the CPC 100 Clipboard. Proceed with P A S T E ...
Move to the destination folder of your choice. Press P A S T E to
insert the contents of the CPC 100 Clipboard to this folder.
Press P A S T E A S T E M P L . to make the contents of the
CPC 100 Clipboard a test procedure template.
(for future use)
Closes the E D I T submenu and returns to the main File
Operations menu.
Note:
For more information about the String Editor, please refer to The String Editor
in chapter 10.
9-3
9-4
Common Functions
Common Functions
This chapter describes functions and procedures that repeat in all or various test
cards. Since these functions are operated in the same fashion on all test cards,
they are explained only once in a central place.
10 - 1
Test Assessment
The test assessment is a manual procedure carried out by the user.
The example below shows an assessment made at a VTRatio test card.
However, the assessment procedure is carried out in the same fashion on all
test cards.
Figure 1:
Example:
VTRatio test card - test
assessment
After the test, set the focus on the assessment symbol by turning the handwheel.
If this symbol is selected, the test cards bottom line shortly shows "Change test
assessment [OK/ Failed]", and then returns to "Assessed: n/a".
The scale symbol designates that no manual assessment was done yet.
The context-dependent menu keys now provide the option to manually assess
the test as either O K or F A I L E D .
Assessing the test appends the actual date and time to the bottom line string
"Assessed:" and displays a corresponding icon on the screen:
Test OK
Test failed
Pressing C L E A R A S S E S S . clears both the assessment and the assessments
date/time stamp in the bottom line, and lets you renew your assessment.
10 - 2
Common Functions
When started from Test Card View, Test Procedure Overview or File
Operations, the String Editors respective entry field shows a default name.
To accept the default name, press the menu key O K or S A V E .
To change the default name, and to enter a name of your choice
delete the default name by repeatedly pressing the backspace key
enter the new test or folder name by consecutively selecting the characters
of your choice from the "on-screen keyboard" with the U P / D O W N keys or
by navigating to it with the handwheel
acknowledge every selected character by pressing the handwheel or
ENTER
Use the String Editors arrow buttons to move the cursor to the position of your
choice. These buttons are only available if the focus ( Glossary) is on the
character selection.
On the Comment Card, pressing C A R R I A G E R E T U R N starts a new line. Else,
C A R R I A G E R E T U R N is disabled.
Once the new name is entered, press the context-dependent menu key O K or
S A V E - depending on the mode - to exit the String Editor.
Pressing C A N C E L closes the String Editor discarding all changes.
10 - 3
TO
10 - 4
Common Functions
FROM
10 - 5
10 - 6
11 - 1
General
The interface to access the CPC 100 built-in ePC is an Ethernet ( Glossary)
board. CPC 100 can be connected with a 10BaseT ("twisted pair") connection
cable to either a stand-alone PC, or an existing PC network.
For this, the Ethernet board provides two RJ-45 connectors:
the upper socket labelled "PC" connects CPC 100 to either a PCs Ethernet
network card or a notebooks PC Card ( Glossary)
Figure 1:
CPC 100 connected to
a stand-alone PC (here
a notebook)
"PC"
the lower socket labelled "to Network" connects CPC 100 to a PC network
hub.
Figure 2:
CPC 100 in a PC
network
"Network"
11 - 2
These two connectors only differ in one cross-connection in the upper RJ-45
connector "PC".
Note:
For both RJ-45 sockets the same 10BaseT connection cable type can be used.
Therefore make sure to insert your 10BaseT connection cable into the correct
CPC 100 socket.
The communication protocol is the TCP/IP protocol.
DHCP/Auto-IP
Most PC networks have a DHCP (Dynamic Host Configuration Protocol) server
that provides an address for every device connected to the network and defines
the subnet mask. When connected to such a network, setting CPC 100 to
DHCP/Auto-IP mode enables it to obtain an address from the DHCP server. If
there is no DHCP server (e.g., because CPC 100 is directly connected to a PC),
CPC 100 generates its address automatically (Auto-IP).
Older versions of Microsoft Windows, such as Windows 95 or NT 4.0, support
DHCP but not Auto-IP. For details about how to establish a communication via
a direct connection, refer to the section Setup for Windows 95 & NT 4.0 on
page 8 of this chapter.
Static IP
In smaller PC networks, all computers have individual static IP addresses. The
system administrator has to assure that no IP address is used twice. He
provides you with an unique address and all other settings for CPC 100.
If, by mistake, an IP address is used twice in the network, communication of
one or both of the devices will fail to work.
If you are in doubt, set PC and CPC 100 to DHCP/Auto-IP.
11 - 3
IP address
This is the unique network address of CPC 100. You need this setting only if
static IP addresses are used. Your system administrator will provide you with a
valid static IP address.
Subnet mask
This is the filter for the IP address. It has to be identical for all devices within one
network. You need this setting only if static IP addresses are used. Your system
administrator will provide you with a valid subnet mask.
Default gateway
This is the address of a local IP router on the same network the CPC is in. It is
used to enable data traffic to destinations beyond the local network.
Commonly, the default gateway is not needed and can therefore be set to
0.0.0.0. This setting is only accessible if static IP addresses are used. Your
system administrator will provide you with details.
DNS
This is the address of the Domain Name System server.
Commonly, this address is not needed and can therefore be set to 0.0.0.0. This
setting is only accessible if static IP addresses are used. Your system
administrator will provide you with details.
11 - 4
PC or Notebook
If your PC or notebook is capable of communicating in a PC network,
communication with your CPC 100 either within a network or via a direct
connection to CPC 100, should function without changing any of your PC
settings.
To avoid possible communication problems, we recommend to first fully boot
CPC 100, then connect CPC to the PC and eventually start CPC Explorer.
Computers with a Windows 95 or a NT 4.0 operating system need a special
setup. These details are explained in chapter Setup for Windows 95 & NT 4.0
on page 8 of this chapter.
In a network with static IP addresses, your system administrator will provide you
with valid settings for CPC 100.
In a network with dynamic address configuration (DHCP or Auto-IP), set your
CPC 100 to "DHCP/Auto-IP". This way, both the addresses of your PC and
CPC 100 will be generated automatically.
11 - 5
If you still dont get a connection, try another 10BaseT connection cable.
If that still does not work, connect CPC 100 "Network" port and your PC to a
network hub (as shown in figure 2 on page 2 of this chapter).
If the link indicator LED works but you still cannot establish communication,
try to deactivate firewall and/or anti-virus software on your computer since
applications like these may interfere and prevent proper communication.
If it still does not work, call the OMICRON hotline (+43 5523 507-333).
2. Connection of CPC 100 and PC via a network hub
Connect and disconnect the 10BaseT connection cable several times and
check whether the "link indicator" LED near the PCs port turns on and off.
Note:
If you still dont get a connection, try another 10BaseT connection cable on a
different port of the hub.
If the link indicator LED works but you still cannot establish communication,
try to deactivate firewall and/or anti-virus software that is installed on your
computer since applications like these may interfere and prevent proper
communication.
If it still does not work, call the OMICRON hotline (+43 5523 507-333).
1. LED close to your PCs Ethernet connector that displays data traffic by going on and off.
11 - 6
By default, CPC Explorer uses port 4987 to find connected CPC sets,
and port 21 (FTP port) to download data from the CPC. It also needs
the possibility to send and receive ICMP data packages ("PING"
command has to work).
During installation of CPC Explorer you are asked to open some parts on
Windows firewalls. It is recommended to allow this, otherwise the "find"
algorithm will not work.
11 - 7
IP address:
169.254.77.33,
Subnet Mask:
255.255.0.0,
Default Gateway:
0.0.0.0
DNS:
0.0.0.0
This way it is possible to connect your PC to the network using the first
network cards port, and directly to CPC 100 using the second network cards
port.
Set CPC 100 to DHCP/Auto-IP to connect it to the network or directly to the
PC.
11 - 8
CPC Explorer
CPC Explorer
Contents of this section
General ......................................................................................... page 12-2
Installation of the CPC Explorer Software..................................... page 12-2
Computer Requirements .......................................................... page 12-2
Installing CPC Explorer ............................................................ page 12-3
Using CPC Explorer ...................................................................... page 12-4
Starting CPC Explorer.............................................................. page 12-5
Finding Connected CPC 100 Units .......................................... page 12-6
Viewing Files ............................................................................ page 12-6
Viewing test reports ............................................................ page 12-6
Viewing test reports and editing them by
opening them with CPC Editor............................................ page 12-8
Viewing the log file ............................................................ page 12-11
Viewing the license file...................................................... page 12-11
Transferring Files and Folders ............................................... page 12-12
Downloading files from CPC 100 to your PC .................... page 12-12
Uploading files from your PC to CPC 100......................... page 12-12
Upgrading the CPC 100 Software.......................................... page 12-13
Options................................................................................... page 12-15
Language .......................................................................... page 12-15
Default Stylesheet............................................................. page 12-15
Saving a Test to PDF Format...................................................... page 12-16
12 - 1
General
CPC Explorer is a PC-based software program that is shipped with CPC 100. It
is used to browse the tests stored in the CPC 100 file system, transfer tests
between the PC and CPC 100, and upgrade the software of CPC 100.
CPC Explorer can also be used for remote trouble-shooting of CPC 100.
Computer Requirements
Minimum Computer Requirements
Pentium 200MHz
64MB RAM
CD-ROM drive
Ethernet connection
Windows 2000/XP
Note:
12 - 2
CPC Explorer
3. On the start screen, click the language of your choice and follow the onscreen instructions.
Note:
The selected language affects all subsequent dialog boxes and all
installed files.
Refer to Options on page 15 of this chapter to learn how to
change the language of the CPC Explorer user interface after the
installation.
12 - 3
12 - 4
CPC Explorer
Apart from the pull-down menus and the toolbar, CPC Explorer interface
consists of three panes:
1
the top left-hand side pane displays the files of all connected CPC 100 units
the right-hand side pane displays the contents of any CPC 100 HTML or XML
document selected in either one of the left-hand side panes.
Navigate through the tree structure in the left-hand side panes as you would in
Windows Explorer. Double-clicking a closed folder or clicking on the plus sign
beside it opens it. Double-clicking an open folder or clicking on the minus sign
beside it closes it.
12 - 5
WITH
IP ADDRESS...
In the Connect CPC with IP Address dialog box enter the corresponding
address and click O K .
Figure 2:
Connect CPC with IP
Address dialog box connecting to a
CPC 100 of an different
subnet
Note:
CPC 100 test sets operating with software version 1.12 or older have
to be connected by using the method of manually entering the
IP address, too. They are not found automatically.
Viewing Files
Viewing test reports
The tests generated by CPC 100 are saved in XML1 format for portability
reasons. In the right-hand side pane, CPC Explorer displays the test report in
HTML format2 (visual rendering).
This HTML representation is generated from the XML test data automatically by
means of a stylesheet (also refer to Default Stylesheet on page 15 of this
chapter).
12 - 6
CPC Explorer
Figure 4:
File contents displayed
in right-hand side pane
The test report contents are then displayed in the right-hand side pane.
If you select a folder rather than a single test, right-click the folder name and
select V I E W from the context-menu, the contents of all tests of the entire folder
structure will be displayed in the right-hand side pane.
12 - 7
Note:
An example, how CPC Explorer and CPC Editor work together is outlined at
Preparing a Test Offline with a PC on page 13-10.
To learn how to save a test report to the "portable" PDF format, please refer to
Saving a Test to PDF Format on page 16 of this chapter.
12 - 8
CPC Explorer
12 - 9
2. Choose E D I T W I T H M S H T M L
WYSIWYG1 HTML editor.
EDITOR
Contrary to editing the report with MS Word for Windows, the MSHTML mode
does not start an application. Instead, the cursor moves directly to the
beginning of the first line of the report displayed in the right-hand side pane,
and enables direct editing of the test report.
About the MSHTML editor:
A right mouse click into the test report view opens a context menu which
provides a cut/copyand paste functionality as known from other Windows
applications.
Note that the MSHTML editor does not support the short-key functions
Ctrl + X for cut, Ctrl + C for copy and Ctrl + V for paste.
Regardless whether MS Word for Windows or the MSHTML editor is used for
editing, to prevent changes to test results, CPC Explorer will not allow you to
directly modify the original test report. The only way to save your changes is
saving the file with a new name (F I L E | S A V E A S . . . ).
12 - 10
CPC Explorer
12 - 11
12 - 12
CPC Explorer
Software upgrades for CPC 100 are distributed in the form of package files. A
package file is a compressed self-extracting archive with the file name extension
.upg, that contains one or more single files. Prior to a software upgrade,
CPC Explorer extracts this package file, and then transfers it to CPC 100.
A possible license file upgrade is handled the same way as a CPC 100 software
upgrade.
To upgrade the CPC 100 software:
1. Select N E T W O R K | U P G R A D E C P C . . . to display the Upgrade CPC
dialog box.
Figure 9:
Upgrade CPC dialog
box
12 - 13
The dialog box lists all available CPC 100 test sets with their individual
IP addresses 1 .
Note:
For CPC 100 test sets operating with software version 1.12 or
older, contact OMICRON technical support.
2. From the list, select the CPC 100 test set to be upgraded.
3. Click the B R O W S E button to navigate to the CPC 100 software upgrade file.
4. Select the CPC 100 software upgrade file and click the O P E N button to
return to the Upgrade CPC dialog box. The selected file is displayed 2 .
5. Click on the U P G R A D E button to begin upgrading the software of the
selected CPC 100 unit(s).
When the CPC 100 software has been successfully upgraded, you will be
asked to reboot CPC 100.
Only after the upgrade is finished, and CPC 100 is rebooted, the new
software version is active.
Note:
12 - 14
The process of upgrading the CPC 100 software may take some time.
Do not interrupt the upgrade process.
CPC Explorer
Options
Figure 10:
Options dialog box
The O P T I O N S menu provides two features to customize the CPC Explorer user
interface:
1. Language
You can change the language of the CPC Explorer user interface "on the fly".
Click on the "down" symbol of the combo box to display the available
languages, select the language of your choice, and click O K .
CPC Explorer re-starts automatically showing the user interface in the
selected language.
2. Default Stylesheet
Stylesheets describe how test reports are represented on screens or in print.
A stylesheet contains formatting information, and offers the possibility to
influence the presentation of test reports.
Upon request, OMICRON can provide you with customized XSL
stylesheets1.
To apply a stylesheet, enter the path to this file into the entry field
"Stylesheet", or click B R O W S E to search for it.
To finish and to close the Options dialog box, click O K .
You can specify your own stylesheet in order to customize the HTML
representation of the test reports in the right-hand side pane.
This documentation, however, will not describe how to create new
stylesheets. For more detailed information about XML, XSL and HTML
please refer to specialized literature and/or special websites, or contact the
OMICRON customer support.
1. EXtensible Stylesheet Language
12 - 15
PDF Generators
There is a variety of PDF generating software available, some free of charge or
for a reasonable price, others, providing a larger number of options and features,
more expensive.
Heres a little selection of PDF generators:
PDFFactory
http://www.fineprint.com/
PDF995
http://www.PDF995.com
Adobe Distiller
http://www.Adobe.com
PDF generators are generally operated like printer drivers, i.e., to save a file to
PDF you need to select the menu item F I L E | P R I N T . . . and specify the
location for the PDF file. The available options and settings depend on the used
PDF generator.
12 - 16
CPC Editor
CPC Editor
Contents of this section
General ......................................................................................... page 13-1
Installation of the CPC Editor Software......................................... page 13-2
Computer Requirements .......................................................... page 13-2
Installing CPC Editor ................................................................ page 13-3
Working with CPC Editor............................................................... page 13-4
Preparing a Test Offline with a PC......................................... page 13-10
General
CPC Editor is an optionally available PC-based software program.
It is used for offline test preparation, i.e., to set up single test cards and/or entire
tests with all of their test-specific settings on a PC, independent from the
availability of a CPC 100.
The prepared test file (.xml file1) is then uploaded to CPC 100 using
CPC Explorer (refer to Uploading files from your PC to CPC 100 on page 1212). Therefore, CPC Editor requires an installation of CPC Explorer.
CPC Editor also opens executed and assessed test files that were downloaded
from CPC 100 to your computer to view them, edit them, and, if required, save
them on your computers hard disk.
Additionally, a test file can be saved as test procedure template, i.e., a userdefined template containing one or more test cards with all of their specific test
settings. To learn more about templates in general, please refer to Creating
Defaults and Templates on page 2-42.
1. An .xml file is a test with all of its test cards and specific settings. It may also contain test results
and assessments that were stored together with the settings as report in the CPC 100 file
system for archiving purposes.
13 - 1
Computer Requirements
Minimum Computer Requirements
Pentium 200MHz
64MB RAM
CD-ROM drive
Ethernet connection
Windows 2000/XP
Please note that Windows 95 is not supported.
Note:
13 - 2
CPC Editor
3. On the start screen, click the language of your choice and follow the onscreen instructions.
Note:
The selected language affects all subsequent dialog boxes and all
installed files.
13 - 3
To start CPC Editor, double-click the CPC Editor icon on your desktop, or click
on S T A R T | P R O G R A M S | C P C E D I T O R .
Figure 1:
CPC Editor user
interface holding one
blank Quick test card
Apart from the pull-down menus and the toolbar, the CPC Editor interface
consists of two panes:
13 - 4
The left-hand side list view pane resembles the Test Procedure Overview of
the CPC 100 software (refer to Test Procedure Overview on page 2-31),
and lists test cards showing the cards name, its creation date and time,
whether test results are available and the test cards assessment status.
The right-hand side test card pane resembles the user interface of the
selected test card as it is laid out in the CPC 100 software. Here, the test
card-specific parameters are specified.
CPC Editor
When CPC Explorer starts, the list view pane is empty. To insert a test card,
either
right-click the list view pane to open the context-menu and click I N S E R T
TEST CARD...
Figure 2:
Context menu of the list
view pane
I N S E R T only
becomes available
if there are already
test cards in the list
(refer to Inserting a
Test Card on page
6 of this chapter).
13 - 5
Select
VTRatio
INSERT
VTRatio is inserted
before the selected
TRRatio test card.
previously created with CPC Editor, and saved to the computers hard disk
or previously created (and even executed and assessed) with CPC 100, and
then uploaded to the computers hard disk by means of CPC Explorer.
Just like inserting a single test card, inserting an .xml file means, positioning its
entire contents (one or more test cards) in the list right before the currently
selected test card.
13 - 6
CPC Editor
13 - 7
Saving a Test
Click the S A V E icon or select F I L E | S A V E with the "Save as type:" option
"CPC files (*.xml)" to save the currently open test, i.e., the test card(s) listed in
the list view with all of their settings, under its actual name.
If this test does not have a name yet, the Save As dialog box opens. Browse to
the destination folder of your choice, and name your test accordingly.
Note:
13 - 8
CPC Editor
To delete an entire test or template, i.e., an .xml or .xmt file, from your
computer, use Windows Explorer.
13 - 9
13 - 10
CPC Editor
For example:
In CPC Explorer, single test cards or
even the entire structure with all
subfolders and test files from
Feeder Klaus\L1 can be copied to
Feeder Klaus\L2 and L3. Use the
context-menus commands C O P Y and
PASTE.
Afterwards, the test files in
Feeder Klaus\L2 and L3. can be
renamed accordingly in CPC Explorer
(context-menu command R E N A M E ) .
Right-clicking a test file in CPC Explorer on your computers hard disk and
selecting the context-menus command E D I T . . . automatically starts CPC
Editor, loads the file and lets you edit it.
Once all tests are composed, use CPC Explorers upload function to transfer
the entire tree structure from your PC to CPC 100 at once.
13 - 11
13 - 12
General
Excel CPC 100 File Loader allows loading XML files into Microsoft Excel
templates for post processing. Excel CPC 100 File Loader is installed with
CPC Explorer. After the installation, a shortcut to start Excel CPC 100 File
Loader appears on your desktop.
Computer Requirements
For the installation requirements, see Computer Requirements on page 12-2.
14 - 1
14 - 2
Template Usage
Templates are pairs of XML documents and Microsoft Excel templates designed
by OMICRON electronics or end users for designated applications. The XML
templates are predefined test procedures, often with comments, that run on
CPC 100 and guide the user through the test. Once completed, the XML file is
saved, downloaded to the PC using CPC Explorer and then loaded with
CPC100 File Loader into the corresponding Microsoft Excel template. There the
results are post processed and a final test report is generated. The template
pairs facilitate and speed testing with CPC 100 and the evaluation of results.
Some template pairs allow version control. If an error message appears after
loading the XML template, use a template pair of the same version. The
template usage requires the CPC Explorer software to be installed on your PC.
CPC Explorer enables you to transfer files (templates and test results) between
the PC and CPC 100.
To run a test procedure according a template:
1. Using CPC Explorer, upload a single XML template or a whole folder of
templates for the intended application from the PC to CPC 100.
The XML templates (*.xmt files) are available on the CPC Explorer
CD-ROM in the Templates directory or in the customer area of
www.omicron.at.
2. Open the template on CPC 100.
3. Run the test procedure according to the template.
4. After completing the test procedure, save the test as a new file.
5. Using CPC Explorer, download the test results from CPC 100 to your
preferred working directory on the PC.
6. Open the corresponding Microsoft Excel template by double-clicking the
*.xlt file in the folder labeled with the test procedure name in the
Templates\CPC 100 directory.
A Microsoft Excel workbook appears.
7. Click the Load XML-File button and open the *.xml file saved in your
preferred working directory before to load the test results.
Excel CPC 100 File Loader loads the test results from the XML file to the
Microsoft Excel template.
8. After all worksheets are filled with data, the test results are calculated and
displayed.
14 - 3
14 - 4
Technical Data
Technical Data
Contents of this section
General ......................................................................................... page 15-2
Power Supply ................................................................................ page 15-4
CPC 100 Outputs .......................................................................... page 15-5
High-Current and High-Voltage Outputs .................................. page 15-5
800A AC output................................................................... page 15-5
400A DC output .................................................................. page 15-7
2kV AC output..................................................................... page 15-8
Outputs on the CPC 100 Front Panel .................................... page 15-15
6A / 130V AC output - all ranges...................................... page 15-15
6A DC current output ........................................................ page 15-18
Output "Ext. Booster" (option) ................................................ page 15-19
Output to Input Synchronization............................................. page 15-20
CPC 100 Inputs........................................................................... page 15-21
BIN IN Binary Input ................................................................ page 15-21
10A IAC/DC Input .................................................................. page 15-22
300V V1 AC Input .................................................................. page 15-23
3V V2 AC Input ...................................................................... page 15-25
10V V DC Input ...................................................................... page 15-27
CPC 100 Combined Specifications ............................................. page 15-28
ePC Interfaces ............................................................................ page 15-29
PC and Network Interfaces (CPC 100 V0 only) ..................... page 15-29
USB Interface (CPC 100 V1 only).......................................... page 15-29
Network Interface (CPC 100 V1 only) .................................... page 15-29
RS 232 Serial Interface Connector ........................................ page 15-30
Connector for External Safety Functions ............................... page 15-31
Environmental Conditions ........................................................... page 15-32
Safety Standards, CE Conformity ............................................... page 15-34
Weight and Dimensions .............................................................. page 15-34
15 - 1
General
In the following tables, all guaranteed input data are specified for an ambient
temperature of 23C 5, a power supply of 230V AC, and after a warm-up
time greater than 25min.
All guaranteed output data are valid for the period of one year after factory
adjustment.
The error values of each measurement range (listed under "Accuracy" in the
following tables) are specified in
% of the reading (rd) + % of full scale (fs)
To obtain the exact measurement error, multiply the displayed measured
value with the given reading error (rd), and add the full scale value multiplied
with the given full scale error (fs).
Example:
CPC 100 is set to the 800A AC range.
The display shows a measured value of 720A at I Out.
The guaranteed error is specified as 0,2% (rd) + 0,2% (fs).
Therefore, the error is 720A x 0,2% (rd) + 800A x 0,2% (fs)
= 1.44A + 1.6A = 3.04A.
Note:
The listed value of the typical maximum output time "typical time tmax" applies
at the high-current 800A AC and 400A DC outputs to a load consisting of
2x6m cables
at the other outputs to the respective typical output power.
Note:
15 - 2
Never connect the 2kV output to any of the inputs! The 2kV output is
measured internally.
Technical Data
When loaded with a high burden, the 800A AC, 400A DC, 6A AC (also in
the 3A AC mode) and 6A DC outputs can generate noise. This noise,
however, is normal and no reason to worry.
Note:
amplitude [dB]
Figure 1:
Typical frequency
response of analog
inputs:
amplitude =
f (frequency)
frequency [Hz]
15 - 3
Power Supply
Important: for safety-relevant issues regarding CPC 100 power supply, also
refer to Power Supply on page 1-6.
Table 1:
Main power supply
technical data
permitted range
85 ... 264V AC
Power fuse
Power consumption
< 3500VA
< 7000VA short-term (< 10s)
Frequency
nominal
frequency
50 / 60Hz
permitted range
45 ... 65Hz
Note:
15 - 4
If the power supply is 190V AC, CPC 100 cannot provide the full
output power at the 800A AC output. The same applies when an
external booster is used. Therefore, in order to gain the full output
power, provide a sufficient power supply (190V ... 240V AC).
Technical Data
800A AC output
While using the 800A AC output, disconnect any cables that may be plugged in
to the 400A DC output. These outputs are internally connected.
Table 2:
800A AC output
technical data
800A AC output
Connection
10mm connectors
Insulation
typical app.
power Smax
typical time
tmax
duty cycle
ton / toff
frequency
50 ... 60Hz
800A
4800VA
25s
5s / 55s
600A
3780VA
200s
5s / 25s
400A
2560VA
500s
5s / 5s
300A
1940VA
15min
10s / 5s
200A
1300VA
> 2hrs
cont. ON
15 - 5
800A AC output
Measurement
Accuracy:
Phase
tolerance at
full scale:
Resolution:
Measurement
Display
100 mA/bit
10 mA
Figure 2:
Typical maximum
output voltage of
800A AC output
depending on frequency
and current
voltage in Vrms
frequency in Hz
Note:
15 - 6
one period of the signal, regardless of the size of the change for an
increase ramp
Technical Data
400A DC output
While using the 400A DC output, disconnect any cables that may be plugged in
to the 800A AC output. These outputs are internally connected.
Table 3:
400A DC output
technical data
400A DC output
Connection
10mm connectors
Insulation
400A
2600W
140s
300A
1950W
3min
200A
1300W
> 2hrs
100A
630W
>> 2hrs
Measurement
Resolution:
Measurement
Display
100 mA/bit
10 mA
Connection:
internally connected
15 - 7
2kV AC output
While using the 2kV AC output, disconnect any cables that may be plugged in
to any of the high-current outputs (800A AC or 400A DC).
Table 4:
Technical data of
2kV AC output - all
ranges
High-voltage sockets
Insulation
Measurement
Table 5:
Technical data of
2kV AC output at a
voltage range of 2000V
internally connected
15 - 8
typical apparent
power Smax
frequency
2000V / 1.25A
2500VA
60s
50200Hz
2000V / 1A
2000VA
130s
50...200Hz
2000V / 0.5A
1000VA
> 2hrs
50...400Hz
Technical Data
Voltage Range:
Accuracy:
0 ... 2000V AC
typ. error < 0.05%(rd) 0.05%(fs),
guaranteed < 0.1% (rd) 0.1% (fs)
Possible crest factor: < 1.5
Phase tolerance
at full scale:
Resolution:
Measurement
Display
100 mV/bit
10 mV
Current Ranges
0 ... 5A AC
(automatic range 0 ... 500mA AC
selection):
0 ... 50mA AC1
Accuracy:
5A:
typ. error
< 0.2% (rd) 0.05% (fs),
guaranteed
< 0.4% (rd) 0.1% (fs)
500mA:typ. error
< 0.05% (rd) 0.05% (fs),
guaranteed
< 0.1% (rd) 0.1% (fs)
50mA1: typ. error
< 0.1% (rd) 0.1% (fs),
guaranteed
< 0.2% (rd) 0.2% (fs)
Possible peak value: 20A
Resolution:
Measurement Display
5A:
1 mA/bit
1 A
1. Available for the CPC 100 serial number Dxxxxx and higher.
15 - 9
Table 6:
Technical data of
2kV AC output at a
voltage range of 1000V
typical apparent
power Smax
frequency
1000V / 2.5A
2500VA
60s
50200Hz
1000V / 2A
2000VA
130s
50...200Hz
1000V / 1A
1000VA
> 2hrs
50...400Hz
Measurement
Voltage Range:
Accuracy:
0 ... 1000V AC
typ. error < 0.05%(rd) 0.05%(fs),
guaranteed < 0.1% (rd) 0.1% (fs)
Possible crest factor: < 1.5
Phase tolerance
at full scale:
15 - 10
Technical Data
5A:
typ. error
< 0.2% (rd) 0.05% (fs),
guaranteed
< 0.4% (rd) 0.1% (fs)
500mA:typ. error
< 0.05% (rd) 0.05% (fs),
guaranteed
< 0.1% (rd) 0.1% (fs)
50mA1: typ. error
< 0.1% (rd) 0.1% (fs),
guaranteed
< 0.2% (rd) 0.2% (fs)
Possible peak value: 20A
Resolution:
Measurement Display
5A:
1 mA/bit
1 A
1. Available for the CPC 100 serial number Dxxxxx and higher.
15 - 11
Table 7:
Technical data of
2kV AC output at a
voltage range of 500V
typical apparent
power Smax
frequency
500V / 5A
2500VA
60s
50200Hz
500V / 4A
2000VA
130s
50...200Hz
500V / 2A
1000VA
> 2hrs
50...400Hz
Measurement
Voltage Range:
Accuracy:
0 ... 500V AC
typ. error < 0.05%(rd) 0.05%(fs),
guaranteed < 0.1% (rd) 0.1% (fs)
Possible crest factor: < 1.5
Phase tolerance
at full scale:
15 - 12
Technical Data
5A:
typ. error
< 0.2% (rd) 0.05% (fs),
guaranteed
< 0.4% (rd) 0.1% (fs)
500mA:typ. error
< 0.05% (rd) 0.05% (fs),
guaranteed
< 0.1% (rd) 0.1% (fs)
50mA1: typ. error
< 0.1% (rd) 0.1% (fs),
guaranteed
< 0.2% (rd) 0.2% (fs)
Possible peak value: 20A
Resolution:
Measurement Display
5A:
1 mA/bit
1 A
1. Available for the CPC 100 serial number Dxxxxx and higher.
15 - 13
Figure 3:
Typical maximum
output voltage of
2kV AC output
depending on frequency
and power
frequency in Hz
Note:
15 - 14
Technical Data
The outputs of the CPC 100 front panel are not controlled.
Furthermore, there is no internal measurement provided. To measure
a front panel output signal, connect it to a measuring input:
current measurement:
to IAC/DC input
voltage measurement:
6A / 130V AC output
While using the 6A / 130V AC output, disconnect any cables that may be
plugged in to any of the high-current outputs (800A AC or 400A DC), or to the
6A DC output.
Table 8:
Technical data of
6A / 130V AC output all ranges
Insulation
Measurement
at IAC/DC input
voltage measurement:
at V1AC input
15 - 15
Table 9:
Technical data of
6A / 130V AC output in
130V AC mode
typical apparent
power Smax
390VA
frequency
50 ... 400Hz
Type: 3.15A T
The 3.15 Amps slow-acting wire fuse 5x20mm,
situated at the front panels AC OUTPUT group,
protects the AC OUTPUT in 130V voltage mode.
6.3A T
If the 6.3 Amps fuse is blown, the 130V AC output
mode does not work either.
Figure 4:
Typical maximum
output voltage of
6A / 130VAC output in
130V AC mode
depending on frequency
The 130V AC output has a setting range of 150V. The set voltage
represents the no-load voltage, i.e., when a load is connected the
voltage at the 130V output will reduce by approx. 5V / A.
voltage Vrms
Note:
frequency in Hz
15 - 16
Technical Data
Table 10:
Technical data of
6A / 130V AC output in
6A AC mode
Table 11:
Technical data of
6A / 130V AC output in
3A AC mode
typical apparent
power Smax
330VA
frequency
50 ... 200Hz
Type: 6.3A T
The 6.3 Amps slow-acting wire fuse 5x20mm, situated
at the front panels AC OUTPUT group, protects the
AC OUTPUT in 6A AC and 3A current mode and the
DC OUTPUT
typical apparent
power Smax
330VA
frequency
50 ... 200Hz
Type: 3.15A T
The 3.15 Amps slow-acting wire fuse 5x20mm,
situated at the front panels AC OUTPUT group,
protects the AC OUTPUT in 3A current mode.
Figure 5:
Typical maximum
output voltage of
6A / 130V AC output in
3 and 6A AC mode
depending on frequency
and current
voltage Vrms
6.3A T
If the 6.3 Amps fuse is blown, the 3A AC output mode
does not work either.
frequency in Hz
15 - 17
6A DC current output
While using the 6A DC output, disconnect any cables that may be plugged in to
any of the high-current outputs (800A AC or 400A DC), or to the 6A / 130V AC
output.
Table 12:
6A DC output technical
data
6A DC output
Connection
Insulation
Protection
Current / voltage
measurement
15 - 18
at IAC/DC input
voltage measurement:
at VDC input
typical power
Pmax
6.0A
360W
> 2hrs
3.0A
180W
>> 2hrs
Technical Data
6A DC output
Fuse
Type: 6.3A T
The 6.3 Amps slow-acting wire fuse 5x20mm, situated
at the front panels AC OUTPUT group, protects both
the AC OUTPUT in 3A and 6A current mode and the
DC OUTPUT
Note 1: If a test object with a large inductance is connected to CPC 100, earth
both ends of the test object before you disconnect it from CPC 100.
Note 2: Do not connect a large inductance to this output in any other test card
but RWinding (winding resistance) and TRTapCheck (tap changer
winding resistance and on-load tap changer interruption check).
Unlike other test cards, RWinding and TRTapCheck provide special
additional safety functions.
15 - 19
V1AC
Input magnitude
Output magnitude
Settling time
100ms after 5% of
output magnitude is
reached
1000ms after 5% of
output magnitude is
reached
Signal changes
No changes of
frequency and phase.
Magnitude changes
without limitation. Output
follows within 250ms.
Phase tolerance
15 - 20
The output ramps linear, therefore reaches 5% of its full magnitude after 5%
of 1200ms = 60ms
Technical Data
Insulation
Sampling frequency
1kHz
Max. voltage
330Vrms
Resolution
1ms
Operation
ext. DC voltage
potential-free
Input resistance
inactive:
Ron
< 10k
Roff
> 1 M
> 100k
15 - 21
Do not connect the 2kV output to this input! The 2kV output is
measured internally.
Measurement
0 ... 10A
ranges (autoranging)
0 ... 1A
Insulation
Protection
Maximum current
11Arms
Accuracy
AC operation
(autoranging)
10A:
1A:
15 - 22
10A:
1A:
Technical Data
DC operation
(autoranging)
Input resistance
10A:
1A:
< 100m
Resolution
Fuse
Measurement
10A:
1 mA/bit
1A:
100 A/bit
Display
10 A
Type: 10A FF
The 10 Amps very quick-acting wire fuse 5x20mm,
situated at the front panels INPUT group, protects the
10A IAC/DC current measuring input.
Make sure the fuse you use is a 10A FF fuse. Do not
use any other type of fuse!
300V V1 AC Input
Note:
Table 16:
300V V1AC input
technical data
Do not connect the 2kV output to this input! The 2kV output is
measured internally.
Measurement
0 ... 300V / 0 ... 30V / 0 ... 3V / 0 ... 300mV
ranges (autoranging)
15 - 23
N
N
Apart from this, the input is insulated against all other
inputs and outputs. Voltage with reference to earth
must not exceed 300Vrms and 420Vpeak on either input
socket.
Reinforced insulation against mains power supply, all
interfaces and other safety low-voltage circuits.
Maximum voltage
330Vrms / 470Vpeak
Accuracy
300V:
30V:
3V:
500k
Resolution
15 - 24
Measurement
300V:
15 mV/bit
30V:
1.5 mV/bit
3V:
150 V/bit
0.3V:
15 V/bit
Display
5 V
Technical Data
3V V2 AC Input
Table 17:
3V V2AC input
technical data
3V V2AC input
Connection
Measurement
0 ... 3V / 0 ... 300mV / 0 ... 30mV
ranges (autoranging)
Insulation
N
N
Apart from this, the input is insulated against all other
inputs and outputs. Voltage with reference to earth
must not exceed 300Vrms and 420Vpeak on either input
socket.
Reinforced insulation against mains power supply, all
interfaces and other safety low-voltage circuits.
Maximum voltage
10Vrms / 15Vpeak
Accuracy
3V:
Input resistance
3V
300mV
30mV
10M
15 - 25
3V V2AC input
Resolution
Measurement
3V:
Display
150 V/bit
300mV: 30 V/bit
30mV:
Note:
3 V/bit
10 V
When using the CTRogowski test card, the 3V V2AC input uses an
additional software based integration method.
In the range of 50Hz < f < 60Hz, this results in a phase shift of 90 as
well as an additional phase error of +/- 0.1 and an additional
amplitude error of +/- 0.01%.
For frequencies in the range of 15Hz < f < 400Hz, the phase error is
not specified, and the amplitude error can be up to +/- 0,50% higher.
15 - 26
Technical Data
10V V DC Input
Table 18:
10V VDC input
technical data
Measurement
0 ... 10V
ranges (autoranging) 0 ... 1V
0 ... 100mV
0 ... 10mV
Insulation
Maximum voltage
50Vrms / 75Vpeak
Accuracy
10V:
1V:
500k
Resolution
Measurement
10V:
400 V/bit
1V:
75 V/bit
Display
100mV: 4 V/bit
10mV:
0.4 V/bit
0.1 V
15 - 27
Resistance
Voltage
Typ. error
Guaranteed
400A
10
4mV
0.70%
1.35%
400A
100
40mV
0.55%
1.10%
400A
1m
400mV
0.50%
0.95%
400A
10m
4V
0.50%
0.95%
Resistance
Voltage
Typ. error
Guaranteed
6A
100m
0.6V
0.35%
0.60%
6A
6V
0.35%
0.60%
1A
10
10V
0.25%
0.40%
15 - 28
Resistance
Voltage
Typ. error
Guaranteed
< 5mA
100
0.60%
1.20%
< 5mA
1k
0.51%
1.02%
< 5mA
10k
0.50%
1.00%
Technical Data
ePC Interfaces
PC and Network Interfaces (CPC 100 V0 only)
CPC 100 V0 supports the 10BaseT (twisted pair) Ethernet ( Glossary)
interface for connecting CPC 100 to a PC, a notebook or a network hub.
CPC 100 V0 is equipped with two RJ-45 connectors. The connector labeled
"PC" connects CPC 100 to a PC or a notebook, and the connector labeled
"Network" connects CPC 100 to a network hub. These two connectors differ only
in one cross-connection in the "PC" connector.
Note:
15 - 29
DSR (in)
RTS (out)
CTS (in)
RI (in)
Legend:
15 - 30
DCD
RXD
Receive Data
TXD
Transmit Data
DTR
GND
Ground
DSR
RTS
Request To Send
CTS
Clear To Send
RI
Ring Indicator
DCD (in)
RXD (in)
TXD (out)
DTR (out)
GND
Technical Data
ground
ground
ground
emergency stop
warning
light
green
warning
light
red
external Start
button (n/o)
15 - 31
Environmental Conditions
Climate
Table 19:
Environmental
conditions - climate
Climate
Operating temperature
Humidity
Drip-water protection
Note:
Since the AC and DC output sockets of CPC 100 can carry lifehazardous voltage potential and provide life-hazardous currents, we
strongly advise you not to carry out tests with a wet CPC 100.
Before switching on CPC 100, make sure it is completely dry.
Shock
15 - 32
Technical Data
EMC
CE conformity, requirements
Emission
Europe
International
Immunity
Europe
EN 50082-2
International
IEC 61000-4-2/3/4/8
15 - 33
EN 60950
IEC 61010-1
Dimensions (w x h x d):
15 - 34
Accessories
Accessories
This chapter lists test cards that are optionally available to extend the
functionality of the CPC 100 packages.
It furthermore describes hardware equipment that is optionally available for the
CPC 100 primary test system, and provides ordering information for spare parts.
For information on the CP CU1 coupling unit and the CP TD1 high-precision test
system, see the CP CU1 Reference Manual and the CP TD1 Reference Manual
respectively on the CPC Explorer CD-ROM.
16 - 1
Test Cards
Table 1:
Ordering information for
test cards
Article number
CT test cards
VESM0610
Scope:
CT Ratio (and Burden)
CT Burden
CT Excitation (Kneepoint)
CT RatioV
CT Rogowski (Ratio)
CT Low Power (Ratio)
Winding Resistance
Voltage Withstand (2kV)
VT test cards
VESM0615
Scope:
VT Ratio
VT Burden
Voltage Withstand (2kV)
VT Electronics
Transformer test cards
VESM0620
Scope:
TRRatio (per tap)
TRTabCheck (for OLTC)
Winding Resistance
Voltage Withstand (2kV)
Resistance test cards
Scope:
Contact Resistance ( ... m )
Winding Resistance ( ... k )
16 - 2
VESM0625
Accessories
Article number
Earth Resistance
VESM0640
Scope:
software (test card RGround)
earth resistance accessory set (see below)
CPOL (Polarity Checker)
VESM0645
Scope:
Polarity checker CPOL + bag + software
Hardware only1:
Polarity checker CPOL + bag
Ramping
VEHZ0650
VESM0630
VESM0635
Article number
VEHZ0660
Consists of:
4 electrodes
cable reel red, 50m
cable reel black, 100m
Note:
16 - 3
High-current
cable with a plug
on one end and a
clamp on the
other end
Connection cable
CPCB2 CPC 100
current booster
CPCB2
16 - 4
Accessories
Weight:
16kg (35.3lbs)
Dimensions (w x h x d):
16 - 5
Table 4:
Technical data of
current booster CPCB2
in 2000A mode
Input:
Output:
16 - 6
typ. apparent
power Smax
typical time
tmax
duty cycle
ton / toff
frequency
50 ... 60Hz
2000A
4900VA
25s
5sec / 55sec
1800A
4400VA
3min
5sec / 40sec
1600A
3950VA
5min
5sec / 30sec
1400A
3450VA
10min
5sec / 25sec
1200A
2950VA
18min
5sec / 15sec
1000A
2500VA
30min
5sec / 9sec
600A
1500VA
> 2hrs
cont. ON
1500A
3500VA
5min
5sec / 30sec
15 ... 150Hz
Accessories
Figure 3:
Current booster CPCB2
in 1000A mode
Table 5:
Technical data of
current booster CPCB2
in 1000A mode
Input:
Output:
typ. apparent
power Smax
typical time
tmax
duty cycle
ton / toff
1000A
4900VA
25s
5sec / 55sec
900A
4400VA
3min
5sec / 40sec
800A
3950VA
5min
5sec / 30sec
700A
3450VA
10min
5sec / 25sec
600A
2950VA
18min
5sec / 15sec
500A
2500VA
30min
5sec / 9sec
300A
1500VA
> 2hrs
cont. ON
750A
3500VA
5min
5sec / 30sec
frequency
50 ... 60Hz
15 ... 150Hz
16 - 7
Article number
VEHZ0630
VEHK0611
VEHK0615
16 - 8
Accessories
Notes:
1. If you detect a wrong polarity in the current path, turn off CPC 100
first, and only then disconnect the terminals.
2. Never operate CPOL with an open battery compartment. A lifehazardous voltage level may occur in the battery compartment if
CPOLs probe touches a test point with high-voltage potential!
16 - 9
typical:
guaranteed:
typical:
52.6Hz
possible:
40 ... 60Hz
Power consumption:
key pressed:
25mA
0mA
Input impedance:
400 k
Operating temperature
Weight:
Dimensions (w x h x d):
Batteries:
Article number
Scope:
Polarity checker CPOL + cover + software
VESM0645
Hardware only1:
Polarity checker CPOL + cover
VEHZ0650
16 - 10
Accessories
16 - 11
3. Insert the two lower batteries first (next to the coverss "" symbol), and
push them all the way in. Make sure you insert them with the "plus pole" going
in first, the "minus" pole pointing towards the compartments open cover.
Then insert the two upper batteries (next to the coverss "+" symbol), and
push them all the way in. Make sure you insert them with the "minus" pole
going in first, the "plus" pole pointing towards the compartments open cover.
4. Close the battery compartments cover tightly until it snaps into position.
5. Press CPOLs ON push-button. Both polarity LEDs +
should light up
steadily, and the red LED above the product designation CPOL flashes
shortly.
16 - 12
Accessories
Article number
VEHZ4000
For additional information about the current clamp C-Probe 1, please refer to its
user manual.
16 - 13
Fuse 1 A
super flink, leaded
Surge
arrester
270 k
Socket to
power transformer
Fuse 1 A
super flink, leaded
Before using the CP SA1 discharge box, check whether it is intact as follows:
1. Select the Resistance test card.
2. Select the V DC (2-wire) output range.
3. Connect CP SA1 to the CPC 100 V DC input.
4. Short-circuit the CP SA1s output and measure the resistance.
If the measured resistance < 1 , the test is passed.
5. Remove the short circuit and measure the resistance again.
If the measured resistance > 20 k, the test is passed.
16 - 14
Article number
VEHZ0665
Accessories
Reference Manual
Table 11:
Ordering information for
CPC 100 Reference
Manual
Ordering description
Article number
VESD0600
Cables
Table 12:
Ordering information for
cables
Article number
2 x 6m, 70mm
VEHK0612
Alternative:
2 x 9m, 70mm
VEHK0617
2 x 6m, 0.5mm
VEHK0613
Alternative:
2 x 10m, 0.5mm
VEHK0618
6 x 6m, 2.5mm
VEHK0614
1 x 0.5m, 2.5mm
Alternative:
6 x 10m, 2.5mm
VEHK0619
1 x 0.5m, 2.5mm
Grounding cable (GR/YE), 1 x 6m, 6mm with
connection clamps
VEHK0615
VEHK0622
16 - 15
Article number
VEHK0621
VEHK0616
Clamps
Table 13:
Ordering information for
clamps
Article number
VEHZ0610
VEHZ0620
Plugs
Table 14:
Ordering information for
plugs
Article number
VEHS0610
16 - 16
VEHK0623
Accessories
Plug housing
EMI gasket
collet
Half shells
backnut
Soldering insert
16 - 17
16 - 18
Accessories
4. Bend cable screen outwards, and place the two half shells on either side of
the insulation body.
half shell
5. Slide gasket and collet against the half shells, and clamp the screen between
gasket and half shells.
6. Trim protruding screen strands, and push the cable assembly into the
housing, orientating the guides to the slots.
Guides
16 - 19
16 - 20
E-Mail:
support@omicron.at
Web:
www.omicron.at
Asia, Pacific
OMICRON electronics Asia Ltd, Hong Kong
Phone:
E-Mail:
support@asia.omicron.at
Web:
www.omicron.at
E-Mail:
techsupport@omicronusa.com
Web:
www.omicronusa.com
21
22
Index
Index
Section-page number
Numerics
0...3V AC input . . . . . . . . . . . . . . . . . . . . . . 2-9
technical data . . . . . . . . . . . . . . . . . . . 15-25
100ms debounce compensation . . . . . . . . 8-12
10A I AC/DC input . . . . . . . . . . . . . . . . . . . . 2-9
synchronizing Amplifier test card . . . . . 8-29
technical data . . . . . . . . . . . . . . . . . . . 15-22
10V DC input . . . . . . . . . . . . . . . . . . . . . . . . 2-9
technical data . . . . . . . . . . . . . . . . . . . 15-27
2kV AC output . . . . . . . . . . . . . . . . . . . . . . . 2-6
technical data . . . . . . . . . . . . . . . . . . . . 15-8
300V AC/DC input . . . . . . . . . . . . . . . . . . . . 2-9
synchronizing of Amplifier test card . . . 8-29
technical data . . . . . . . . . . . . . . . . . . . 15-23
3V AC input
synchronizing Amplifier test card . . . . . 8-29
400A DC output . . . . . . . . . . . . . . . . . . . . . 2-8
CAUTION, output is NOT switched off . 1-9
technical data . . . . . . . . . . . . . . . . . . . . 15-7
6A DC output . . . . . . . . . . . . . . . . . . . . . . . 2-8
technical data . . . . . . . . . . . . . . . . . . . 15-18
6A/130V AC output . . . . . . . . . . . . . . . . . . . 2-6
technical data . . . . . . . . . . . . . . . . . . . 15-15
800A AC output . . . . . . . . . . . . . . . . . . . . . . 2-6
technical data . . . . . . . . . . . . . . . . . . . . 15-5
800A DC output
CAUTION, output is NOT switched off . 1-9
A
AC OUTPUT
description . . . . . . . . . . . . . . . . . . . . . . . 2-6
accelerator keys
selecting a test . . . . . . . . . . . . . . . . . . . 2-15
add test card. Refer to Insert Card
address
manufacturer . . . . . . . . . . . . . . . . . . . . 17-21
Adobe
Distiller . . . . . . . . . . . . . . . . . . . . . . . . 12-16
Reader . . . . . . . . . . . . . . . . . . . . . . . . 12-16
Amplifier
synchronization inputs . . . . . . . . . . . . . . 8-29
Amplifier test card . . . . . . . . . . . . . . . . . . . 8-29
anti-virus software . . . . . . . . . . . . . . . . . . . 11-7
applications overview . . . . . . . . . . . . . . . . . 1-13
ARC
testing an OVC relay w/ ARC function . 8-11
article number
cable . . . . . . . . . . . . . . . . . . . . . . . . . . 16-15
clamps . . . . . . . . . . . . . . . . . . . . . . . . . 16-16
current booster CP CB2 . . . . . . . . . . . . 16-8
current clamp C-Probe1 . . . . . . . . . . . 16-13
earth resistance accesory set . . . . . . . . 16-3
plugs . . . . . . . . . . . . . . . . . . . . . . . . . . 16-16
polarity checker CPOL . . . . . . . . . . . . . 16-9
Reference Manual . . . . . . . . . . . . . . . . 16-15
assessment . . . . . . . . . . . . . . . . . . . . . . . . 10-2
Auto Save . . . . . . . . . . . . . . . . . . . . . . . . . . 2-35
B
battery
changing CPOL batteries . . . . . . . . . . 16-11
BIN IN (binary input) . . . . . . . . . . . . . . . . . . 2-10
for trigger signal in Quick . . . . . . . . . . . 3-11
status display in Quick . . . . . . . . . . . . . 3-12
technical data . . . . . . . . . . . . . . . . . . . 15-21
binary trigger
in Quick . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
block diagram CPC 100 . . . . . . . . . . . . . . . 2-13
booster. Refer to ext. booster
built-in PC. Refer to ePC
C
cable
18 - 1
18 - 2
Download . . . . . . . . . . . . . . . . . . . . 12-12
Find CPC . . . . . . . . . . . . . . . . . . . . . 12-6
License File . . . . . . . . . . . . . . . . . . 12-11
Log File . . . . . . . . . . . . . . . . . . . . . 12-11
Specify an IP address . . . . . . . . . . . 12-6
Upgrade CPC . . . . . . . . . . . . . . . . . 12-13
Upload . . . . . . . . . . . . . . . . . . . . . . 12-12
usage . . . . . . . . . . . . . . . . . . . . . . . . . . 12-4
used communication ports . . . . . . . . . . 11-7
viewing
license file . . . . . . . . . . . . . . . . . . . 12-11
log file . . . . . . . . . . . . . . . . . . . . . . . 12-11
test reports . . . . . . . . . . . . . . . . . . . . 12-6
CPC Explorer . . . . . . . . . . . . . . . . . . . . . . . 14-3
CPOL polarity checker
changing batteries . . . . . . . . . . . . . . . . 16-11
ordering information . . . . . . . . . . . . . . . 16-9
C-Probe1. Refer to current clamp
CSS in CPC Explorer . . . . . . . . . . . . . . . . 12-15
CT
burden . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11
excitation, demagnetization . . . . . . . . . . 4-19
excitation, test . . . . . . . . . . . . . . . . . . . . 4-15
low power (ratio) . . . . . . . . . . . . . . . . . . 4-43
polarity check . . . . . . . . . . . . . . . . . . . . 4-28
ratio/burden . . . . . . . . . . . . . . . . . . . . . . . 4-3
ratio/burden with current clamp . . . . . . . 4-10
ratio/burden with current injection . . . . . . 4-3
Rogowski (ratio) . . . . . . . . . . . . . . . . . . 4-38
voltage withstand . . . . . . . . . . . . . . . . . 4-25
CT ratio measurement with Sequencer . . . 8-14
current
max. current at AC OUTPUT . . . . . . . . . 2-6
max. current at DC OUTPUT . . . . . . . . . 2-8
output
how much for how long? . . . . . . . . . . 2-3
current booster
operation modes . . . . . . . . . . . . . . . . . . 16-6
ordering information . . . . . . . . . . . . . . . 16-8
specify in Device Setup dialog . . . . . . . 2-34
where to define in software . . . . . . . . . . 2-21
current clamp
CT ratio/burden test . . . . . . . . . . . . . . . 4-10
ordering information . . . . . . . . . . . . . . 16-13
settings in Device Setup dialog . . . . . . . 2-34
Index
D
DANGER
cardiac pacemaker: DO NOT USE
CPC100 . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
DC OUTPUT
description . . . . . . . . . . . . . . . . . . . . . . . 2-8
dead man function . . . . . . . . . . . . . . . . . . 1-14
debounce
compensation when measuring CB closing
time . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-12
default
creating defaults and templates . . . . . . 2-42
Restore Factory Defaults . . . . . . . . . . . 2-36
test card default . . . . . . . . . . . . . . 2-17, 2-42
test procedure default . . . . . . . . . . 2-18, 3-1
on start-up . . . . . . . . . . . . . . . . 2-20, 2-43
time of state duration in Sequencer . . . . 8-7
delay time
in Quick . . . . . . . . . . . . . . . . . . . . . . . . 3-12
demagnetization . . . . . . . . . . . . . . . . . . . . 4-19
DHCP / Auto-IP . . . . . . . . . . . . . . . . . . . . . 11-3
dimensions
CPC . . . . . . . . . . . . . . . . . . . . . . . . . . 15-34
CPC CB2 . . . . . . . . . . . . . . . . . . . . . . . 16-5
DIN VDE 0101 . . . . . . . . . . . . . . . . . . . . . 7-14
downloading files with CPCExplorer . . . . 12-12
duty cycle
800A AC output . . . . . . . . . . . . . . . . . . 15-5
ext. booster 1000A mode . . . . . . . . . . . 16-7
ext. booster 2000A mode . . . . . . . . . . . 16-6
intermittent output of high current
(Sequencer) . . . . . . . . . . . . . . . . . . . . . 8-16
E
earth resistance accesory set
ordering information . . . . . . . . . . . . . . . 16-3
earth resistance. Refer to RGround
Edit menu in File Operations . . . . . . . . . . . . 9-3
editor
CPC Editor . . . . . . . . . . . . . . . . . 13-1, 14-1
form editor (Comment card) . . . . . . . . . 8-33
String Editor . . . . . . . . . . . . . . . . . . . . . 10-3
text editor (Comment card) . . . . . . . . . . 8-33
electromagnetic compatibility . . . . . . . . . . 15-33
electronic manual (PDF) . . . . . . . . . . . . . . . 1-5
electronic voltage transformers . . . . . . . . . 5-21
embedded PC. Refer to ePC
EMC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-33
Emergency Stop . . . . . . . . . . . . . . . . . . . . . 2-16
dead man function . . . . . . . . . . . . . . . . . 1-14
external e.s. button . . . . . . . . . . . . . . . 15-31
front panel button . . . . . . . . . . . . . . . . . 2-11
end-to-end test
using Amplifier test card . . . . . . . . . . . . 8-29
environmental conditions
climate, tecnical data . . . . . . . . . . . . . . 15-32
electromagnetic compatibility,
tecnical data . . . . . . . . . . . . . . . . . . . . 15-33
shock and vibration,tecnical data . . . . 15-32
technical data . . . . . . . . . . . . . . . . . . . 15-32
ePC
components . . . . . . . . . . . . . . . . . . . . . . 2-14
connecting CPC 100 to a PC (network) 11-1
interfaces to ext. PC . . . . . . . . . . . . . . . . 2-4
Ethernet connector . . . . . . . . . . . . . . . . . . 15-29
explorer. Refer to CPC Explorer
ext. booster
galvanic connection to mains! . . . . . . . . . 1-7
techical data . . . . . . . . . . . . . . . . . . . . . 16-5
1000A mode . . . . . . . . . . . . . . . . . . . 16-7
2000A mode . . . . . . . . . . . . . . . . . . . 16-6
where to connect . . . . . . . . . . . . . . . . . . 2-12
ext. transformer. Refer to ext. booster
external functions
connector for external safety functions 15-31
18 - 3
file
glossary
symbols . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
18 - 4
H
handwheel . . . . . . . . . . . . . . . . . . . . . . . . . 2-15
hide CPC on the network . . . . . . . . . . . . . . 2-37
hotline . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17-21
humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-10
I
I AC input
synchronizing Amplifier test card . . . . . 8-29
I out
setting in Quick . . . . . . . . . . . . . . . . . . . . 3-3
IEEE Std 80-2000 . . . . . . . . . . . . . . . . . . . 7-14
IEEE Std 81-1983 . . . . . . . . . . . . . . . . . . . 7-14
impedance
ground . . . . . . . . . . . . . . . . . . . . . . . . . . 7-14
INPUT
functional group, description . . . . . . . . . . 2-9
input
binary . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
synchronization inputs for Amplifier . . . 8-29
Insert Card . . . . . . . . . . . . . . . . . . . . . . . . . 2-23
Inserting . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-6
installation
CPC Editor . . . . . . . . . . . . . . . . . . . . . . 13-3
CPC Explorer . . . . . . . . . . . . . . . . . . . . 12-3
interface
to ext. PC . . . . . . . . . . . . . . . . . . . . . . . . 2-4
technical data . . . . . . . . . . . . . . . . . 15-29
IP
Auto-IP . . . . . . . . . . . . . . . . . . . . . . . . . 11-3
definition in glossary . . . . . . . . . . . . . . . . 1-3
specify IP address in CPC Explorer . . . 12-6
Index
J
jog dial handwheel . . . . . . . . . . . . . . . . . . 2-15
K
key lock . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
keyboard. Refer to ePC components
L
language
of CPC Explorer interface . . . . . . . . . 12-15
lastmeas.xml. Refer to Auto Save
LCD
definition in glossary . . . . . . . . . . . . . . . 1-3
monitor . . . . . . . . . . . . . . . . . . . . . . . . . 2-15
LED
AC output selected . . . . . . . . . . . . . . . . 2-6
DC output selected . . . . . . . . . . . . . . . . 2-8
license file
upgrading with CPC Explorer . . . . . . 12-13
viewing in CPC Explorer . . . . . . . . . . 12-11
licensed test cards . . . . . . . . . . . . . . . . . . 2-24
lights I/O . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
log file
clearing the log file . . . . . . . . . . . . . . . . 2-40
defining log file entries . . . . . . . . . . . . . 2-40
viewing in CPC Explorer . . . . . . . . . . 12-11
whats a log file? . . . . . . . . . . . . . . . . . 2-39
low level AC voltage input
synchronizing Amplifier test card . . . . . 8-29
low power current transformer . . . . . . . . . 4-43
M
Main Power Supply
technical data . . . . . . . . . . . . . . . . . . . . 15-4
manufacturer address . . . . . . . . . . . . . . . 17-21
max. values
at AC OUTPUT . . . . . . . . . . . . . . . . . . . . 2-6
at DC OUTPUT . . . . . . . . . . . . . . . . . . . . 2-8
measured quantity
setting in Quick . . . . . . . . . . . . . . . . . . . . 3-3
measurement
frequency-selective measurement . . . . . 3-6
measuring
in Quick . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
measuring inputs . . . . . . . . . . . . . . . . . . . 2-9
measuring state
in Quick . . . . . . . . . . . . . . . . . . . . . . . 3-2
menu
context-dependent menu keys . . . . . . . 2-16
Edit menu . . . . . . . . . . . . . . . . . . . . . . . . 9-3
File menu . . . . . . . . . . . . . . . . . . . . . . . . 9-3
File Operations . . . . . . . . . . . . . . . . . . . . 9-2
minimum
state duration in Sequencer . . . . . . . . . . 8-7
minimum computer requirements
for CPC Editor . . . . . . . . . . . . . . . . . . . . 13-2
for CPC Explorer . . . . . . . . . . . . . . . . . . 12-2
monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-15
N
navigation
handwheel . . . . . . . . . . . . . . . . . . . . . . . 2-15
navig. elements front panel control . . . . 2-14
network
10BaseT connecting cables . . . 11-3, 15-29
communication parameters . . . . . . . . . . 11-3
CPC 100 in a network . . . . . . . . . . . . . . 11-1
hide CPC on the network . . . . . . . . . . . 2-37
tab Options | Network . . . . . . . . . . . . . . 2-37
new folder
create folder with CPC Explorer . . . . . . 12-7
18 - 5
Q
qualification of operating personnel . . . . . . . 1-6
18 - 6
Index
Quick
do not use for meas. winding resistance 1-7
introduction . . . . . . . . . . . . . . . . . . . . . . 3-1
R
Ramping . . . . . . . . . . . . . . . . . . . . . . . . . . 8-18
rd (reading) . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Reference Manual
ordering information . . . . . . . . . . . . . . 16-15
Registry
saving settings to R. . . . . . . . . . . . . . . 2-33
report
what is a report? . . . . . . . . . . . . . . . . . 2-18
reset
Restore Factory Defaults . . . . . . . . . . . 2-36
Resistance
do not use for meas. winding resistance 1-7
resistance
earth resistance (RGround) . . . . . . . . . 7-14
uOhm measurement . . . . . . . . . . . . . . . 7-3
voltage withstand . . . . . . . . . . . . . . . . . 7-22
winding resistance . . . . . . . . . . . . . . . . . 7-9
Restore Factory Defaults . . . . . . . . . . . . . 2-36
RGround
earth resistance test . . . . . . . . . . . . . . 7-14
RJ-45 Ethernet connector . . . . . . . . . . . . 15-29
Rogowski coil
CTRogowski (ratio) . . . . . . . . . . . . . . . 4-38
RS232 ePC interface . . . . . . . . . . . . . . . 15-30
S
safety
ambient conditions . . . . . . . . . . . . . . . . 1-10
Emergency Stop . . . . . . . . . . . . . . . . . 2-11
front panel input/output sockets . . . . . . . 1-9
instructions . . . . . . . . . . . . . . . . . . . . . . . 1-5
key lock . . . . . . . . . . . . . . . . . . . . . . . . 2-10
qualification of operating personnel . . . . 1-6
side panel output sockets . . . . . . . . . . . 1-9
18 - 7
T
tap changer
counting order tap numbers . . . . . . 6-8, 6-21
example w/ TRTapCheck . . . . . . . . . . 6-23
setting tab no.
after a TRRatio test . . . . . . . . . . . . . 6-12
after a TRTapCheck test . . . . . . . . . 6-23
during a TRRatio test . . . . . . . . . . . 6-11
during a TRTapCheck test . . . . . . . 6-22
prior to a TRRatio test . . . . . . . . . . . . 6-8
prior to a TRTapCheck test . . . . . . . 6-20
technical data
0...3V AC input . . . . . . . . . . . . . . . . . . 15-25
18 - 8
Index
CT . . . . . . . . . . . . . . . . . . . . . . . . . . 4-20
Resistance . . . . . . . . . . . . . . . . . . . . . 7-9
Transformer . . . . . . . . . . . . . . . . . . . 6-13
test assessment . . . . . . . . . . . . . . . . . . . . . 10-2
test card
how to set up . . . . . . . . . . . . . . . . . . . . . 2-25
inserting test cards to a test procedure . 2-23
what is a test card? . . . . . . . . . . . . . . . . 2-17
test card default
how to define . . . . . . . . . . . . . . . . . . . . . 2-42
what is a test card default? . . . . . . . . . . 2-17
Test Card View . . . . . . . . . . . . . . . . . . . . . . 2-22
test object
preparation prior to test . . . . . . . . . . . . . 2-46
test procedure
what is a test procedure? . . . . . . . . . . . 2-18
test procedure default
how to define . . . . . . . . . . . . . . . . . . . . . 2-43
on start-up . . . . . . . . . . . . . . . . . . 2-20, 2-43
what is test proc. default? . . . . . . . . . . . 2-18
test procedure template
how to define . . . . . . . . . . . . . . . . . . . . . 2-45
what is a test proc. template? . . . . . . . . 2-18
test report
saving to PDF . . . . . . . . . . . . . . . . . . . 12-16
test start / stop . . . . . . . . . . . . . . . . . 2-16, 8-30
text editor (Comment card) . . . . . . . . . . . . 8-33
threshold value trigger (Quick) . . . . . . . . . . 3-12
time
state duration in Sequencer . . . . . . . . . . 8-7
transformer
current.Refer to CT
non-conventional
el.voltage transformers . . . . . . . . . . 5-21
low powerCT . . . . . . . . . . . . . . . . . . 4-43
Rogowski . . . . . . . . . . . . . . . . . . . . . 4-38
ratio & tap changer . . . . . . . . . . . . . . . . . 6-3
tap changer & winding resistance . . . . . 6-18
TRTapCheck . . . . . . . . . . . . . . . . . . . . . 6-18
voltage withstand . . . . . . . . . . . . . . . . . 6-25
winding resistance . . . . . . . . . . . . . . . . . 6-13
trigger
definition in glossary . . . . . . . . . . . . . . . . 1-4
input BIN IN . . . . . . . . . . . . . . . . . . . . . . 2-10
settings in Quick . . . . . . . . . . . . . . . . . . 3-11
18 - 9
Transformer . . . . . . . . . . . . . . . . . . . . . . 6-25
VT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-13
VT
burden . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8
electronic voltage transformers . . . . . . . 5-21
polarity check . . . . . . . . . . . . . . . . . . . . 5-16
ratio and polarity . . . . . . . . . . . . . . . . . . . 5-3
voltage withstand . . . . . . . . . . . . . . . . . 5-13
U
Up / Down keys . . . . . . . . . . . . . . . . . . . . . 2-15
upgrade CPC 100 software . . . . . . . . . . . 12-13
uploading files with CPCExplorer . . . . . . 12-12
user interface
definition in glossary . . . . . . . . . . . . . . . 1-4
See also software user interface
User Manual. Refer to Reference Manual
V
V out
setting in Quick . . . . . . . . . . . . . . . . . . . 3-3
V1 AC
synchronizing outputs with V1 AC
Quick test card . . . . . . . . . . . . . . . . 3-10
Sequencer test card . . . . . . . . . . . . . 8-4
V1 AC input
synchronizing Amplifier test card . . . . . 8-29
V2 AC input
synchronizing Amplifier test card . . . . . 8-29
values
how to enter in software . . . . . . . . . . . . 2-25
VDE 0101 . . . . . . . . . . . . . . . . . . . . . . . . . 7-14
version
CPC 100 software . . . . . . . . . . . . . 1-2, 2-17
CPC Editor . . . . . . . . . . . . . . . . . . . . . . 13-1
view
view selector . . . . . . . . . . . . . . . . 2-15, 2-21
voltage
max. voltage at AC OUTPUT . . . . . . . . . 2-6
voltage withstand
CT . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-25
Resistance . . . . . . . . . . . . . . . . . . . . . . 7-22
18 - 10
W
warning lights I/O . . . . . . . . . . . . . . . . . . . . 2-11
weight
CP CB2 . . . . . . . . . . . . . . . . . . . . . . . . . 16-5
CPC . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-34
winding resistance
CT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-20
do not use Quick or Resistance . . . . . . . 1-7
of tap changer, with TRTapCheck . . . . . 6-22
Resistance . . . . . . . . . . . . . . . . . . . . . . . 7-9
Transformer . . . . . . . . . . . . . . . . . . . . . . 6-13
Windows Registry
saving settings to W. R. . . . . . . . . . . . . 2-33
X
xml
Auto Save . . . . . . . . . . . . . . . . . . . . . . . 2-35
xml, file name extension . . . . . . . . . . . . . . . . 9-1
xmt, file name extension . . . . . . . . . . . . . . . 9-1