Fan Coil Units

Technical Data

ECDEN10-400

FWV-DT/DF

Fan Coil Units

Technical Data

ECDEN10-400

FWV-DT/DF

Indoor Unit Fan Coil Units FWV-DT/DF

TABLE OF CONTENTS
FWV-DT/DF

Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Technical Specifications - (2 pipe) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Specifications - (4 pipe) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Specifications - (2 pipe, 4 pipe) . . . . . . . . . . . . . . . . . . . . . . . . . . . .

............................................................... 6

Control systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Control Systems

Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Options

..................................................... 7

Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Cooling Capacity Tables - 2 pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Cooling Capacity Tables - 4 pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Capacity Correction Factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Heating Capacity Tables - 2 pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Heating Capacity Tables - 4 pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Power consumption - 2 pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Power consumption - 4 pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dimensional Drawings

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring Diagrams - Single Phase

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
34

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operation Range

11

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation Method

10

31

Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Sound Level Data - 2 pipe
Sound Level Data - 4 pipe

30

36

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

Hydraulic performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Water Pressure Drop Curve Evaporator - Cooling 2 pipe . . . . . . . . . . .
Water Pressure Drop Curve Evaporator - Heating 2 pipe . . . . . . . . . .
Water Pressure Drop Curve Evaporator - Heating 4 pipe . . . . . . . . . .

Fan coil Indoor Unit

37
38
39

Indoor Unit Fan Coil Units FWV-DT/DF

1
n t U i n l UF iD /o r TCco D o - nd V naW FI

Features
Quick fixing system for wall mounted installation

Valve packages contain balancing valves and sensor pocket

Pre-assembled 3-way/4-port on/off valves are available

Fast-on connections for electrical options: no tools needed

Valve packages are insulated, no extra drain pan required

The air filter can easily be removed for cleaning

Fan coil Indoor Unit

Indoor Unit Fan Coil Units FWV-DT/DF

Specifications
FWV01DATN
6V3/TV6V3

2-1 Technical Specifications - (2 pipe)


Cooling capacity

Total capacity

Sensible capacity

Heating capacity

Power input

Dimensions

Weight
Casing

2 pipe

FWV02DATN
6V3/TV6V3

FWV03DATN
6V3/TV6V3

Fan

kW

1.54 (1)

2.09 (1)

2.93 (1)

4.33 (1)

4.77 (1)

6.71 (1)

8.02 (1)

kW

1.24 (1)

1.81 (1)

2.38 (1)

3.27 (1)

3.87 (1)

5.27 (1)

6.24 (1)
4.11 (1)

Low

kW

1.04 (1)

1.45 (1)

1.76 (1)

2.51 (1)

3.17 (1)

3.97 (1)

High

kW

1.20 (1)

1.51 (1)

2.11 (1)

3.15 (1)

3.65 (1)

4.91 (1)

5.96 (1)

Nom.

kW

0.97 (1)

1.31 (1)

1.70 (1)

2.45 (1)

2.92 (1)

3.83 (1)

4.63 (1)

Low

kW

0.79 (1)

1.05 (1)

1.26 (1)

1.80 (1)

2.32 (1)

2.84 (1)

3.05 (1)

High

kW

2.14 (2)

2.57 (2)

3.81 (2)

5.63 (2)

6.36 (2)

7.83 (2)

10.03 (2)

Medium

kW

1.73 (2)

2.18 (2)

3.08 (2)

4.30 (2)

5.21 (2)

6.23 (2)

7.80 (2)

Low

kW

1.43 (2)

1.79 (2)

2.28 (2)

3.29 (2)

4.24 (2)

4.77 (2)

5.24 (2)

High

37

53

56

137

175

28

36

43

61

68

104

130

Low

21

24

29

38

47

76

90

Unit

Height

98

mm

Width

mm

Depth

mm

Unit

kg

Operation weight

kg

564
774

984

1,194

Water pressure drop

1,404

226
19

20

251

25

30

31

41

1.6

2.1

Colour

Plastic and metal RAL9010


Plastic + sheet metal

Rows

Quantity

Stages

Quantity

3
10

Fin pitch

mm

Face area

Water volume

1.8

12

1.6
0.086

0.5

0.7

Type

1.8
0.138

0.191

0.292

1.4

2.1

Centrifugal multi-blade, double suction


1

High

m/h

319

344

442

706

785

1,011

1,393

Medium

m/h

233

271

341

497

605

771

1,022

Low

m/h

178

211

241

361

470

570

642

Available pressure

High

Pa

Speed

Steps

3 (high, medium, low)

Model

Water flow

FWV10DATN
6V3/TV6V3

Nom.

Air flow rate

Sound power level

FWV08DATN
6V3/TV6V3

High

Quantity

Fan motor

FWV06DATN
6V3/TV6V3

Nom.

Material
Heat exchanger

FWV04DATN
6V3/TV6V3

Closed induction, B class insulation, winding thermal cut-out

High

dBA

45

50

47

52

56

58

64

Nom.

dBA

39

44

41

43

49

51

57

Low

dBA

33

38

33

35

43

44

48

Cooling

l/h

265

359

504

745

820

1,154

1,343

Heating

l/h

265

359

504

745

820

1,154

1,343

Cooling

kPa

11

12

14

12

19

Heating

kPa

10

16

13
9

11

Air filter

Plastic

Insulation material

Class 1 self-extinguishing

Vibration insulation

Rubber ring for fan motor

Water connections

Std. heat exchanger

Piping connections

Drain

inch
OD

mm

Notes

1/2

3/4
16

(1) Cooling: 2 pipe: air 27CDB, 19CWB; entering water 7C; leaving water 12C
(2) Heating: 2 pipe: air 20CDB; entering water 50C; water flow rate as during cooling
(3) Air flow at 0Pa ESP

Fan coil Indoor Unit

Indoor Unit Fan Coil Units FWV-DT/DF

Specifications
FWV01DAFN
6V3/FV6V3

2-2 Technical Specifications - (4 pipe)


Cooling capacity

Total capacity

Sensible capacity

Heating capacity

Power input

4 pipe

Weight
Casing

FWV03DAFN
6V3/FV6V3

FWV04DAFN
6V3/FV6V3

Additional heat
exchanger

kW

1.46 (1)

1.90 (1)

2.87 (1)

4.33 (1)

4.67 (1)

6.64 (1)

7.88 (1)

1.24 (1)

1.62 (1)

2.33 (1)

3.27 (1)

3.81 (1)

5.23 (1)

6.16 (1)

Low

kW

0.99 (1)

1.35 (1)

1.73 (1)

2.48 (1)

3.11 (1)

3.93 (1)

4.07 (1)

High

kW

1.14 (1)

1.51 (1)

2.07 (1)

3.15 (1)

3.57 (1)

4.85 (1)

5.85 (1)

Nom.

kW

0.97 (1)

1.25 (1)

1.66 (1)

2.45 (1)

2.87 (1)

3.80 (1)

4.57 (1)

Low

kW

0.75 (1)

1.10 (1)

1.24 (1)

1.78 (1)

2.28 (1)

2.82 (1)

3.02 (1)

High

kW

1.90 (2)

2.10 (2)

3.08 (2)

5.05 (2)

5.30 (2)

7.91 (2)

9.30 (2)

Medium

kW

1.70 (2)

1.78 (2)

2.68 (2)

4.25 (2)

4.65 (2)

6.83 (2)

7.95 (2)

Low

3.60 (2)

4.04 (2)

5.69 (2)

6.12 (2)

kW

1.50 (2)

1.56 (2)

2.18 (2)

37

53

56

Nom.

28

36

43

21

24

29

Height

mm

Width

mm

Depth

mm

Unit

kg

Operation weight

kg

98

774
20

Water pressure drop

104

130

38

47

76

90

984
21

1,194

1,404
251

26

32

33

44

1.6

2.1

Plastic + sheet metal

Rows

Quantity

Stages

Quantity

Fin pitch

mm

Face area

Water volume

Rows

Quantity

Stages

Quantity

3
10

1.8

12

1.6
0.086

0.5

0.7

1.8
0.138

0.191

0.292

1.4

2.1

1
8

10

mm

Face area

Water volume

1.6
0.068

0.11

0.152

0.243

0.2

0.3

0.4

0.6

Type

Centrifugal multi-blade, double suction


1

High

m/h

307

327

431

690

763

998

1,362

Medium

m/h

225

261

332

490

593

765

1,007

174

205

238

356

460

565

636

Low

m/h

Available pressure

High

Pa

Speed

Steps

3 (high, medium, low)

Model

Water flow

68

Plastic and metal RAL9010

Air flow rate

Sound power level

175

61

226

Quantity

Fan motor

137

564

Colour

Fin pitch

Fan

FWV10DAFN
6V3/FV6V3

kW

Material
Heat exchanger

FWV08DAFN
6V3/FV6V3

High

High

Unit

FWV06DAFN
6V3/FV6V3

Nom.

Low
Dimensions

FWV02DAFN
6V3/FV6V3

Closed induction, B class insulation, winding thermal cut-out

High

dBA

45

50

47

52

56

58

64

Nom.

dBA

39

44

41

43

49

51

57

Low

dBA

33

38

33

35

43

44

48

Cooling

l/h

251

327

494

745

803

1,142

1,355

Heating

l/h

196

182

286

396

465

694

816

Cooling

kPa

11

12

14

12

19

Heating

kPa

13
7

Air filter

10
Plastic

Insulation material

Class 1 self-extinguishing

Vibration insulation

Rubber ring for fan motor

Water connections

Std. heat exchanger

Piping connections

Drain

inch
OD

mm

Notes

1/2

3/4
16

(1) Cooling: 4 pipe: air 27CDB, 19CWB; entering water 7C; leaving water 12C
(2) Heating: 4 pipe: air 20CDB; entering water 70C; leaving water 60C
(3) Air flow at 0Pa ESP

Fan coil Indoor Unit

Indoor Unit Fan Coil Units FWV-DT/DF

Specifications
FWV01DATN
6V3/TV6V3

2-3 Electrical Specifications - (2 pipe, 4 pipe)


Power supply

Required wire section

FWV03DATN
6V3/TV6V3

Phase

FWV04DATN
6V3/TV6V3

FWV06DATN
6V3/TV6V3

FWV08DATN
6V3/TV6V3

FWV10DATN
6V3/TV6V3

Frequency

Hz

Voltage

Required fuses
Current input

FWV02DATN
6V3/TV6V3

50
230

High

0.17

0.24

0.25

0.44

0.43

0.60

0.76

Medium

0.13

0.16

0.20

0.29

0.31

0.46

0.58

Low

0.10

0.11

0.14

0.19

0.22

0.34

0.41

mm

Note

0.5

1
(4) The power consumption for the valve motor is 5W (peak) only during opening.

Fan coil Indoor Unit

Indoor Unit Fan Coil Units FWV-DT/DF

Options

3-1

Options

):9):/):0
'HVFULSWLRQ

'DLNLQ

)

)

)

)

)

)

)

)&8XQLW

):9):/
):0



$GGLWLRQDOVLQJOHURZKHDWH[FKDQJHU

(65+$

(65+$

(OHFWULFKHDWHU

((+$

((+$ ((+$ ((+$

(09$

(09$

(09$

(09$

(09$

SLSH212))ZD\PRWRUGULYHQYDOYH
FRPSOHWHZLWKPRXQWLQJNLW
SLSH212))ZD\PRWRUGULYHQYDOYH
FRPSOHWHZLWKPRXQWLQJNLW
)DQVWRSWKHUPRVWDW
$LULQWDNH GLVFKDUJHJULOOIURQW)LOWHU[LQJ
NLWIRUFRQFHLOHGPRGHOV
6XSSRUWLQJIHHWIHHW VXSSRUWLQJEUDFNHWV
FRYHUV
6XSSRUWLQJIHHWJULOO

(65+$ (65+$

<)67$
($,')$

(65+$

((+$

((+$

(09$

(09$

(09$

<)67$
($,'
($,')$
)$

($,')$

(6)9$

($,')$

(6)9$

(6)9*$

(6)9$

(6)9
(6)9*$ (6)9*$
*$
()$$
()$$
()$$
(539$ (539$ (539$
(&):0%

(6)9*$

)UHVKDLULQWDNHORXYHUV PDQXDO
()$$
5HDUSDQHOIRU9HUWLFDOPRXQWHGPRGHOV
(539$
&RQWUROOHU(OHFWURPHFKDQLFDOEXLOWLQ
(&):0%
3RZHULQWHUIDFHIRUFRQQHFWLRQRIXSWR)&8
(3,06%
WRDVLQJOHFRQWUROSDQHO
9HUWLFDO'UDLQ3DQ
('39$
+RUL]RQWDO'UDLQ3DQ
('3+$
)FX&RQWUROOHU6WDQGDUGYHUVLRQ
):(&$
)FX&RQWUROOHU$GYDQFHGYHUVLRQ
):(&$
)FX&RQWUROOHU$GYDQFHGSOXVYHUVLRQ
):(&$
)FXWHPSHUDWXUHVHQVRUNLW
):76.$
)FXUHODWLYHKXPLGLW\VHQVRUNLW
):+6.$
2QERDUGIFX&RQWUROOHULQVWDOODWLRQNLW
):(&.$

()$$
(539$

):9 ):/ ):0 1RWHVUHPDUNV

&DQQRWEHXVHGLQFRPELQDWLRQZLWK
HOHFWULFKHDWHU
&DQQRWEHXVHGLQFRPELQDWLRQZLWKDG
GLWLRQDO+(UHTXLUHVHOHFWURQLF&RQWUROOHU
UHTXLUHVHOHFWURQLF&RQWUROOHURUHOHFWUR
PHFKDQLFDO&RQWURO
UHTXLUHVHOHFWURQLF&RQWUROOHU

;
;

&RYHUVFDQQRWEHXVHGIRU):0

;
;
;
;

;
;

(3,06%

('39$
('3+$
):(&$
):(&$
):(&$
):76.$
):+6.$
):(&.$

;
;
;
;
;
;
;
;

;
;
;
;
;
;
;

;
;
;
;
;
;

2QO\IRUYHUWLFDOPRXQWHGXQLWV

ZDWHUSUREHLQFOXGHG
ZDWHUSUREHLQFOXGHG
ZDWHUSUREHLQFOXGHG

7:%  

):9):/):0

)FX&RQWUROOHU$GYDQFHG
SOXVYHUVLRQ

)FXWHPSHUDWXUHVHQVRUNLW

)FXUHODWLYHKXPLGLW\
VHQVRUNLW

2QERDUGIFX&RQWUROOHU
LQVWDOODWLRQNLW

):(&$

):(&$

):(&$

):76.$

):+6.$

):(&.$

)FX&RQWUROOHU$GYDQFHG
YHUVLRQ

(539$

('3+$

()$$

)FX&RQWUROOHU6WDQGDUG
YHUVLRQ

5HDUSDQHOIRU9HUWLFDO
PRXQWHGPRGHOV

(6)9*$

('39$

)UHVKDLULQWDNHORXYHUV
PDQXDO

(6)9$

($,')$

+RUL]RQWDO'UDLQ3DQ

6XSSRUWLQJIHHWJULOO

($,')$

;
;

;
;

9HUWLFDO'UDLQ3DQ

6XSSRUWLQJIHHWIHHW
VXSSRUWLQJEUDFNHWV
FRYHUV

<)67$

;
;

<)67$

3RZHULQWHUIDFHIRU
FRQQHFWLRQRIXSWR)&8WR (3,06%
DVLQJOHFRQWUROSDQHO

$LULQWDNH GLVFKDUJHJULOO
IURQW)LOWHU[LQJNLWIRU
FRQFHLOHGPRGHOV

;
;

&RQWUROOHU(OHFWURPHFKDQLFDO
(&):0%
EXLOWLQ

)DQVWRSWKHUPRVWDW

;
;

;
;

(09$
(09$

SLSH212))ZD\PRWRU
(09$
GULYHQYDOYHFRPSOHWHZLWK
PRXQWLQJNLW

((+$

(65+$
((+$

SLSH212))ZD\PRWRU
(09$
GULYHQYDOYHFRPSOHWHZLWK
PRXQWLQJNLW

(OHFWULFKHDWHU

(65+$

$GGLWLRQDOVLQJOHURZKHDWH[FKDQJHU
(OHFWULFKHDWHU
SLSH212))ZD\PRWRUGULYHQ
YDOYHFRPSOHWHZLWKPRXQWLQJNLW
SLSH212))ZD\PRWRUGULYHQ
YDOYHFRPSOHWHZLWKPRXQWLQJNLW
)DQVWRSWKHUPRVWDW
$LULQWDNH GLVFKDUJHJULOOIURQW)LOWHU
[LQJNLWIRUFRQFHLOHGPRGHOV
6XSSRUWLQJIHHWIHHW VXSSRUWLQJ
EUDFNHWVFRYHUV
6XSSRUWLQJIHHWJULOO
)UHVKDLULQWDNHORXYHUV PDQXDO
5HDUSDQHOIRU9HUWLFDOPRXQWHGPRGHOV
&RQWUROOHU(OHFWURPHFKDQLFDOEXLOWLQ
3RZHULQWHUIDFHIRUFRQQHFWLRQRIXSWR
)&8WRDVLQJOHFRQWUROSDQHO
9HUWLFDO'UDLQ3DQ
+RUL]RQWDO'UDLQ3DQ
)FX&RQWUROOHU6WDQGDUGYHUVLRQ
)FX&RQWUROOHU$GYDQFHGYHUVLRQ
)FX&RQWUROOHU$GYDQFHGSOXVYHUVLRQ
)FXWHPSHUDWXUHVHQVRUNLW
)FXUHODWLYHKXPLGLW\VHQVRUNLW
2QERDUGIFX&RQWUROOHULQVWDOODWLRQNLW

$GGLWLRQDOVLQJOHURZKHDW
H[FKDQJHU

'HVFULSWLRQ

;
;

;
;

;
;

;
;

;
;

;
;

;
;

;
;

;
;

(6)9$

(6)9*$
()$$
(539$
(&):0%

;
;
;

;
;
;

;
;
;
;

;
;
;

;
;
;
;

;
;

;
;
;

;
;
;
;

;
;
;
;

;
;
;
;

;
;
;

;
;
;

;
;
;

;
;
;

;
;
;

;
;
;

(3,06%

('39$
('3+$
):(&$
):(&$
):(&$
):76.$
):+6.$
):(&.$

;
;
;
;
;
;
;
;

;
;
;
;
;
;
;
;

;
;
;
;
;
;
;
;

;
;
;
;
;
;
;
;

;
;
;

;
;
;

;
;

;
;

;
;
;
;
;
;
;

;
;
;
;
;
;
;
;

;
;
;
;
;
;
;
;

;
;
;
;
;
;
;
;

;
;
;
;
;
;
;
;

;
;

;
;
;
;
;
;
;
;

;
;
;
;
;
;

;
;
;
;
;
;

;
;

;
;

;
;

;
;
;
;
;

;
;

;
;
;
;
;
;
;

;
;

;
;
;

;
;
;

;
;

;
;
;
;

7:%  

Fan coil Indoor Unit

Indoor Unit Fan Coil Units FWV-DT/DF

Control systems

4-1

Control Systems
Cool/heat changeover

Options

Basic control functions

Control features

2-pipe

4-pipe

Manual cool/heat changeover.


Automatic cool/heat changeover based on water temperature.
Automatic cool/heat changeover based on air temperature.
Control of the 3-way/4pipe ON/OFF valve. The water valve shut-off once the desired temperature is reached.
The controller controls the electric heater as integration or replacement of the hot water heating system. When the operating mode
selector witch is turned on electric heater and the electric heater is turned on, the fan runs continuously at medium speed.
The fan speed can be set at one of the 3 speeds (low, medium or maximum) by turning the operation mode selector.

The fan speed is switched automatically based on the difference between the temperature set on the thermostat and the room
temperature.
Optimised comfort cooling. When the fan coil has reached the desired setpoint, the fan will operate at medium speed and at
regular intervals to ensure constant room temperature and lower sound.
The controller prevents the fan coil unit from operating in one mode, if the required water temperature is not achieved to operate
in the selected mode.
The dead zone is a temperature interval close to the set temperature. When the air is warmer/cooler than the top/lower limit of the
neutral zone, the cooling/heating mode is selected.

Fan coil Indoor Unit

Fan coil Indoor Unit

Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.

Total cooling capacity


W
880
720
640
1290
1120
910
1730
1450
1240
2480
1990
1750
2820
2150
1960
3850
3140
2730
4790
3380
2770

6 - 11
Sensible cooling capacity
Water flow
W
!/h
840
152
720
124
570
110
1070
221
930
192
750
157
1470
296
1200
249
960
213
2170
425
1740
341
1360
300
2570
484
1990
369
1650
336
3380
661
2680
539
2130
469
4200
822
3120
579
2270
474
Water pressure drop
kPa
5
4
3
6
5
3
5
3
3
5
3
3
6
4
3
5
3
3
8
4
3

Total cooling capacity


W
820
660
580
1090
880
780
1480
1260
1090
2140
1720
1520
2390
1980
1700
3290
2720
2380
4000
3130
2400

7 - 12
Sensible cooling capacity
Water flow
W
!/h
820
140
660
114
580
100
1090
187
830
151
700
133
1480
255
1120
216
890
186
2140
368
1630
295
1270
261
2390
410
1980
340
1550
292
3290
565
2510
467
1990
409
4000
687
3130
538
2120
412
Water pressure drop
kPa
4
3
2
4
3
2
3
3
2
4
2
2
4
3
2
4
3
2
6
4
2

Total cooling capacity


W
730
610
540
980
860
730
1370
1180
920
1970
1620
1290
2120
1830
1590
3040
2570
2010
3550
2890
2170

22 - 16
8 - 13
Sensible cooling capacity
Water flow
W
!/h
730
125
610
104
540
92
980
169
860
148
730
125
1370
235
1180
203
820
158
1970
339
1620
279
1170
221
2120
363
1830
314
1590
272
3040
522
2570
441
1840
346
3550
610
2890
496
2170
373
Water pressure drop
kPa
4
3
2
4
3
2
3
2
1
3
2
1
3
3
2
3
2
1
5
3
2

Total cooling capacity


W
650
550
490
880
790
670
1260
1080
860
1810
1490
1230
1930
1670
1460
2780
2360
1940
3120
2650
1990

Water pressure drop


kPa
3
2
2
3
2
2
3
2
1
3
2
1
3
2
2
3
2
1
4
3
2

Capacity tables

5-1
Cooling Capacity Tables - 2 pipe

4TW60012-1A (Sheet 1/13)

9 - 14
Sensible cooling capacity
Water flow
W
!/h
650
111
550
95
490
84
880
151
790
135
670
114
1260
216
1080
186
860
149
1810
310
1490
256
1230
212
1930
331
1670
287
1460
250
2780
478
2360
405
1940
333
3120
536
2650
455
1990
342

FW 10 TN/TV

FW 08 TN/TV

FW 06 TN/TV

FW 04 TN/TV

FW 03 TN/TV

FW 02 TN/TV

FW 01 TN/TV

Air temperature (C DB - C WB)


Water temperature (Entering C - leaving C)
Model

Indoor Unit Fan Coil Units FWV-DT/DF

Fan coil Indoor Unit

Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.

Total cooling capacity


W
1480
1190
1000
2020
1750
1400
2820
2290
1690
4170
3140
2390
4600
3720
3040
6470
5060
3780
7730
6000
3920

6 - 11
Sensible cooling capacity
Water flow
W
!/h
1110
254
900
205
740
172
1410
346
1230
300
980
240
1970
484
1590
393
1180
290
2940
715
2280
538
1670
410
3400
788
2720
639
2160
522
4590
1109
3580
868
2640
649
5560
1325
4320
1030
2830
672
Water pressure drop
kPa
13
9
6
13
10
7
11
7
4
12
7
4
14
9
7
11
7
4
19
12
6

Total cooling capacity


W
1260
1010
850
1750
1520
1210
2440
1970
1460
3590
2670
2060
3970
3200
2580
5590
4320
3230
6690
5150
3270

7 - 12
Sensible cooling capacity
Water flow
W
!/h
1030
217
830
174
670
145
1300
300
1130
260
910
208
1820
419
1460
338
1080
251
2710
617
2090
458
1540
354
3150
682
2510
549
1970
444
4230
960
3270
741
2410
554
5150
1148
3980
885
2570
561
Water pressure drop
kPa
9
6
5
10
8
5
8
6
3
9
5
3
10
7
5
9
6
3
15
9
4

Total cooling capacity


W
1020
810
680
1450
1260
1000
2010
1590
1300
2940
2080
1830
3280
2580
2050
4590
3360
2870
5540
4160
2900

25 - 18
8 - 13
Sensible cooling capacity
Water flow
W
!/h
940
175
750
139
610
117
1190
250
1030
217
820
172
1640
345
1310
273
1020
224
2450
504
1860
357
1440
315
2880
562
2270
443
1760
352
3830
788
2890
578
2270
492
4700
951
3590
714
2420
498
Water pressure drop
kPa
6
4
3
7
6
4
6
4
3
6
3
3
7
5
3
6
4
3
10
6
3

Total cooling capacity


W
920
740
620
1120
970
820
1660
1320
1140
2440
1880
1600
2690
2160
1780
3730
2850
2500
4520
3460
2520

Water pressure drop


kPa
5
4
3
4
3
3
4
3
2
4
3
2
5
4
3
4
3
2
7
5
3

Capacity tables

5-1
Cooling Capacity Tables - 2 pipe

4TW60012-1A (Sheet 3/13)

9 - 14
Sensible cooling capacity
Water flow
W
!/h
920
158
740
126
620
107
1060
193
920
167
750
141
1660
284
1200
226
950
196
2440
418
1880
322
1350
274
2690
463
2160
371
1660
306
3730
640
2690
489
2120
429
4520
776
3460
595
2280
433

FW 10 TN/TV

FW 08 TN/TV

FW 06 TN/TV

FW 04 TN/TV

FW 03 TN/TV

FW 02 TN/TV

FW 01 TN/TV

Air temperature (C DB - C WB)


Water temperature (Entering C - leaving C)
Model

Indoor Unit Fan Coil Units FWV-DT/DF

10

Fan coil Indoor Unit

Max
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.

Total cooling capacity


W
1750
1410
1180
2350
2030
1630
3290
2670
1990
4870
3690
2850
5360
4350
3570
7520
5930
4510
9000
7020
4690

6 - 11
Sensible cooling capacity
Water flow
W
!/h
1280
301
1040
242
850
203
1610
403
1400
348
1120
279
2260
564
1820
459
1360
341
3370
835
2620
632
1950
489
3890
919
3120
747
2490
613
5250
1289
4110
1016
3070
774
6350
1544
4950
1204
3290
804
Water pressure drop
kPa
17
12
9
16
13
9
14
10
6
15
9
6
18
12
9
15
10
6
25
16
8

Total cooling capacity


W
1540
1240
1040
2090
1810
1450
2930
2380
1760
4330
3270
2510
4770
3870
3170
6710
5270
3970
8020
6240
4110

7 - 12
Sensible cooling capacity
Water flow
W
!/h
1200
264
970
213
790
179
1510
359
1310
311
1050
249
2110
503
1700
408
1260
302
3150
743
2450
561
1800
431
3650
818
2920
664
2320
544
4910
1152
3830
904
2840
681
5960
1376
4630
1071
3050
706
Water pressure drop
kPa
13
9
7
13
10
7
11
8
5
12
8
5
14
10
7
12
8
5
20
13
6

Total cooling capacity


W
1310
1060
890
1810
1570
1260
2540
2060
1500
3750
2800
2100
4140
3340
2710
5830
4530
3310
6960
5390
3430

27 - 19
8 - 13
Sensible cooling capacity
Water flow
W
!/h
1120
226
900
181
730
152
1400
311
1220
270
970
216
1950
436
1570
353
1150
258
2920
643
2260
481
1640
361
3400
710
2710
574
2140
466
4560
1001
3530
778
2570
569
5560
1196
4300
924
2780
588
Water pressure drop
kPa
10
7
5
10
8
5
9
6
4
10
6
3
11
8
5
9
6
4
16
10
5

Total cooling capacity


W
1090
880
710
1510
1320
1050
2110
1680
1320
3090
2230
1860
3430
2730
2150
4830
3630
2910
5800
4400
2940

Water pressure drop


kPa
7
5
3
8
6
4
6
4
3
7
4
3
8
5
4
7
4
3
11
7
3

Capacity tables

5-1
Cooling Capacity Tables - 2 pipe

4TW60012-1A (Sheet 5/13)

9 - 14
Sensible cooling capacity
Water flow
W
!/h
1090
188
880
151
670
122
1290
260
1120
226
890
180
1790
362
1420
289
1080
227
2670
530
2050
383
1540
319
3140
589
2480
469
1920
370
4170
829
3190
624
2420
500
5120
995
3930
756
2600
505

FW 10 TN/TV

FW 08 TN/TV

FW 06 TN/TV

FW 04 TN/TV

FW 03 TN/TV

FW 02 TN/TV

FW 01 TN/TV

Air temperature (C DB - C WB)


Water temperature (Entering C - leaving C)
Model

Indoor Unit Fan Coil Units FWV-DT/DF

Fan coil Indoor Unit

Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.

Total cooling capacity


W
2640
2120
1770
3430
2940
2360
4770
3880
2890
7110
5400
4190
7810
6350
5220
10880
8610
6630
13100
10270
6950

6 - 11
Sensible cooling capacity
Water flow
W
!/h
1520
453
1230
364
1020
304
1920
589
1660
505
1340
404
2690
818
2180
665
1630
495
4000
1220
3120
926
2350
719
4570
1340
3690
1090
2970
895
6210
1867
4890
1478
3710
1137
7470
2246
5860
1762
3950
1193
Water pressure drop
kPa
35
24
17
32
25
17
27
19
11
30
18
12
34
24
17
29
19
12
48
31
16

Total cooling capacity


W
2440
1960
1640
3190
2740
2200
4450
3620
2700
6630
5030
3910
7280
5920
4870
10160
8040
6190
12230
9570
6480

7 - 12
Sensible cooling capacity
Water flow
W
!/h
1450
419
1170
337
960
282
1820
548
1580
471
1270
377
2550
764
2070
621
1550
463
3800
1137
2960
864
2230
671
4350
1249
3510
1016
2820
836
5900
1743
4650
1381
3520
1062
7120
2098
5580
1642
3750
1112
Water pressure drop
kPa
30
21
15
28
22
15
24
16
10
26
16
10
30
21
15
25
17
11
42
27
14

Total cooling capacity


W
2240
1800
1510
2940
2530
2030
4110
3350
2500
6120
4650
3620
6720
5470
4500
9400
7440
5730
11280
8840
5980

30 - 22
8 - 13
Sensible cooling capacity
Water flow
W
!/h
1370
384
1110
309
910
259
1730
505
1500
435
1200
349
2410
706
1960
575
1460
429
3600
1050
2810
798
2110
621
4130
1153
3330
939
2670
773
5600
1613
4400
1278
3320
983
6760
1937
5290
1517
3550
1026
Water pressure drop
kPa
26
18
13
24
19
13
20
14
9
22
14
9
26
18
13
22
15
9
36
24
12

Total cooling capacity


W
2020
1630
1360
2680
2310
1860
3760
3060
2290
5580
4240
3300
6130
4990
4110
8600
6810
5230
11110
8680
5850

Water pressure drop


kPa
21
15
11
20
16
11
17
12
7
19
12
8
22
15
11
19
12
8
29
19
9

Capacity tables

5-1
Cooling Capacity Tables - 2 pipe

4TW60012-1A (Sheet 7/13)

9 - 14
Sensible cooling capacity
Water flow
W
!/h
1290
347
1050
279
860
234
1630
460
1410
397
1130
319
2280
645
1840
526
1370
393
3400
958
2650
729
1980
567
3910
1053
3140
857
2520
706
5280
1476
4150
1169
3120
898
6840
1909
5320
1491
3540
1004

FW 10 TN/TV

FW 08 TN/TV

FW 06 TN/TV

FW 04 TN/TV

FW 03 TN/TV

FW 02 TN/TV

FW 01 TN/TV

Air temperature (C DB - C WB)


Water temperature (Entering C - leaving C)
Model

Indoor Unit Fan Coil Units FWV-DT/DF

11

12

Fan coil Indoor Unit

Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.

Total cooling capacity


W
850
670
620
1160
980
870
1680
1440
1230
2420
1980
1740
2750
2140
1940
3790
3130
2720
4690
3360
2750

6 - 11
Sensible cooling capacity
Water flow
W
!/h
850
146
640
116
550
107
1080
199
890
167
740
149
1430
289
1180
246
950
211
2120
415
1720
339
1350
298
2500
471
1960
367
1630
334
3330
650
2660
537
2120
467
4120
803
3090
576
2260
472
Water pressure drop
kPa
5
3
3
6
5
4
4
3
3
4
3
3
5
4
3
5
3
3
7
4
3

Total cooling capacity


W
770
620
560
990
860
740
1460
1250
1080
2110
1710
1510
2330
1960
1690
3270
2710
2370
3930
3110
2390

7 - 12
Sensible cooling capacity
Water flow
W
!/h
770
132
620
107
560
96
990
170
860
148
690
127
1460
251
1100
214
880
185
2110
363
1610
294
1260
260
2330
400
1960
336
1520
289
3270
561
2490
465
1970
407
3930
674
3110
533
2110
410
Water pressure drop
kPa
4
3
2
5
4
3
3
3
2
4
2
2
4
3
2
3
2
2
5
3
2

Total cooling capacity


W
690
570
520
900
790
690
1350
1160
910
1950
1610
1280
2070
1810
1570
3020
2560
2010
3480
2870
2160

22 - 16
8 - 13
Sensible cooling capacity
Water flow
W
!/h
690
118
570
98
520
89
900
154
790
136
690
118
1350
232
1160
199
810
157
1950
335
1610
276
1160
220
2070
356
1810
310
1570
269
3020
518
2560
439
1820
344
3480
597
2870
492
2160
370
Water pressure drop
kPa
3
2
2
4
3
2
3
2
1
3
2
1
3
3
2
3
2
1
4
3
2

Total cooling capacity


W
620
520
470
810
720
630
1240
1070
850
1790
1480
1220
1900
1660
1440
2760
2350
1930
3090
2630
1980

Water pressure drop


kPa
3
2
2
3
3
2
2
2
1
3
2
1
3
2
2
3
2
1
3
2
1

Capacity tables

5-2
Cooling Capacity Tables - 4 pipe

4TW60012-1A (Sheet 2/13)

9 - 14
Sensible cooling capacity
Water flow
W
!/h
620
107
520
90
470
81
810
140
720
124
630
108
1240
213
1070
183
850
147
1790
307
1480
254
1220
210
1900
326
1660
284
1440
247
2760
475
2350
403
1930
331
3090
530
2630
451
1980
340

FW 10 TN/TV

FW 08 FN/FV

FW 06 FN/FV

FW 04 FN/FV

FW 03 FN/FV

FW 02 FN/FV

FW 01 FN/FV

Air temperature (C DB - C WB)


Water temperature (Entering C - leaving C)
Model

Indoor Unit Fan Coil Units FWV-DT/DF

Fan coil Indoor Unit

Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.

Total cooling capacity


W
1400
1100
950
1830
1560
1300
2770
2240
1660
4100
3100
2360
4500
3660
2990
6390
5020
3740
7590
5930
3880

6 - 11
Sensible cooling capacity
Water flow
W
!/h
1060
241
840
188
700
163
1400
315
1160
268
950
223
1930
474
1560
384
1160
285
2890
703
2250
532
1650
405
3320
772
2670
628
2120
513
4540
1097
3550
862
2620
642
5460
1301
4260
1016
2800
665
Water pressure drop
kPa
11
7
6
14
10
8
10
7
4
11
7
4
13
9
6
11
7
4
15
10
5

Total cooling capacity


W
1190
930
800
1590
1350
1120
2390
1930
1450
3530
2630
2050
3890
3150
2530
5530
4290
3210
6570
5090
3260

7 - 12
Sensible cooling capacity
Water flow
W
!/h
980
205
770
159
640
138
1300
272
1080
231
870
192
1780
410
1420
330
1070
249
2660
606
2060
452
1520
351
3080
668
2460
540
1940
435
4180
949
3240
735
2390
551
5050
1128
3930
873
2550
559
Water pressure drop
kPa
9
6
4
11
8
6
8
5
3
9
5
3
10
7
5
9
6
3
12
7
3

Total cooling capacity


W
960
740
660
1310
1110
920
1970
1550
1290
2880
2070
1820
3200
2530
2040
4530
3330
2860
5430
4090
2890

25 - 18
8 - 13
Sensible cooling capacity
Water flow
W
!/h
890
165
700
127
590
113
1200
226
990
191
790
158
1610
337
1270
266
1000
222
2410
494
1840
355
1430
313
2810
550
2220
435
1740
350
3780
778
2860
571
2250
490
4610
932
3540
702
2410
496
Water pressure drop
kPa
6
4
3
8
6
4
6
4
3
6
3
3
7
5
3
6
4
3
8
5
3

Total cooling capacity


W
870
680
600
1110
940
780
1620
1300
1130
2390
1860
1590
2640
2120
1770
3680
2840
2490
4430
3420
2510

Water pressure drop


kPa
5
3
3
6
4
3
4
3
2
4
3
2
5
3
3
4
3
2
6
4
2

Capacity tables

5-2
Cooling Capacity Tables - 4 pipe

4TW60012-1A (Sheet 4/13)

9 - 14
Sensible cooling capacity
Water flow
W
!/h
870
149
680
116
600
103
1110
190
940
161
740
134
1620
278
1180
224
940
194
2390
411
1860
320
1340
273
2640
453
2120
365
1640
303
3680
633
2680
487
2110
427
4430
761
3420
587
2260
431

FW 10 TN/TV

FW 08 FN/FV

FW 06 FN/FV

FW 04 FN/FV

FW 03 FN/FV

FW 02 FN/FV

FW 01 FN/FV

Air temperature (C DB - C WB)


Water temperature (Entering C - leaving C)
Model

Indoor Unit Fan Coil Units FWV-DT/DF

13

14

Fan coil Indoor Unit

Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.

Total cooling capacity


W
1660
1300
1130
2140
1820
1510
3220
2610
1960
4780
3640
2820
5250
4280
3510
7430
5880
4470
8840
6930
4650

6 - 11
Sensible cooling capacity
Water flow
W
!/h
1220
285
970
223
810
193
1600
367
1330
312
1080
260
2210
552
1780
449
1340
336
3310
821
2590
625
1920
483
3800
900
3060
735
2440
603
5190
1275
4080
1010
3050
767
6240
1516
4890
1190
3260
797
Water pressure drop
kPa
15
10
8
18
14
10
13
9
6
15
9
6
17
12
8
15
10
6
20
13
6

Total cooling capacity


W
1460
1140
990
1900
1620
1350
2870
2330
1730
4260
3230
2480
4670
3810
3110
6640
5230
3930
7880
6160
4070

7 - 12
Sensible cooling capacity
Water flow
W
!/h
1140
250
900
196
750
169
1510
326
1250
278
1010
231
2070
493
1660
400
1240
297
3090
730
2420
554
1780
425
3570
802
2870
653
2280
534
4850
1138
3800
898
2820
675
5850
1352
4570
1057
3020
699
Water pressure drop
kPa
12
8
6
15
11
8
11
8
5
12
7
5
14
10
7
12
8
5
16
10
5

Total cooling capacity


W
1240
970
840
1650
1400
1170
2490
2010
1470
3680
2760
2080
4050
3290
2660
5760
4500
3270
6840
5320
3390

27 - 19
8 - 13
Sensible cooling capacity
Water flow
W
!/h
1060
213
840
166
700
144
1410
283
1160
240
940
200
1910
427
1530
345
1130
253
2870
632
2230
474
1620
357
3320
696
2660
564
2100
457
4500
990
3510
772
2550
562
5450
1173
4240
912
2750
581
Water pressure drop
kPa
9
6
5
11
9
6
8
6
3
9
6
3
11
7
5
9
6
3
12
8
4

Total cooling capacity


W
1040
810
670
1300
1160
960
2060
1640
1310
3030
2200
1850
3360
2680
2100
4770
3600
2900
5690
4340
2930

Water pressure drop


kPa
7
4
3
7
6
4
6
4
3
7
4
3
8
5
3
7
4
3
9
6
3

Capacity tables

5-2
Cooling Capacity Tables - 4 pipe

4TW60012-1A (Sheet 6/13)

9 - 14
Sensible cooling capacity
Water flow
W
!/h
1040
178
810
139
640
115
1300
224
1070
199
860
165
1750
354
1390
282
1070
225
2620
520
2010
377
1530
317
3060
577
2430
461
1880
361
4120
819
3160
618
2400
497
5020
977
3880
745
2580
503

FW 10 TN/TV

FW 08 FN/FV

FW 06 FN/FV

FW 04 FN/FV

FW 03 FN/FV

FW 02 FN/FV

FW 01 FN/FV

Air temperature (C DB - C WB)


Water temperature (Entering C - leaving C)
Model

Indoor Unit Fan Coil Units FWV-DT/DF

Fan coil Indoor Unit

Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.

Total cooling capacity


W
2510
1970
1690
3150
2660
2210
4670
3790
2840
6990
5330
4140
7650
6250
5130
10760
8550
6580
12880
10140
6900

6 - 11
Sensible cooling capacity
Water flow
W
!/h
1440
430
1150
337
970
290
1880
540
1570
457
1280
379
2630
802
2130
650
1600
487
3930
1199
3080
915
2320
710
4470
1312
3630
1073
2920
880
6140
1846
4860
1467
3680
1127
7340
2208
5790
1740
3920
1183
Water pressure drop
kPa
32
21
16
35
27
19
26
18
11
29
18
11
33
23
16
28
19
12
38
25
13

Total cooling capacity


W
2320
1820
1570
2920
2480
2060
4360
3540
2660
6510
4970
3860
7130
5830
4790
10050
7990
6140
12010
9450
6430

7 - 12
Sensible cooling capacity
Water flow
W
!/h
1370
398
1090
312
920
269
1790
502
1490
425
1220
353
2500
748
2020
607
1520
456
3740
1117
2930
853
2200
663
4260
1224
3450
1001
2770
822
5840
1724
4620
1371
3490
1054
7000
2061
5510
1622
3720
1103
Water pressure drop
kPa
27
18
14
31
23
17
23
16
10
25
16
10
29
20
14
25
17
10
34
22
11

Total cooling capacity


W
2120
1670
1440
2690
2280
1900
4030
3280
2460
6010
4590
3570
6580
5380
4430
9290
7390
5680
11090
8730
5930

30 - 22
8 - 13
Sensible cooling capacity
Water flow
W
!/h
1300
364
1030
286
870
246
1700
462
1420
392
1150
326
2370
692
1910
562
1440
422
3540
1032
2770
789
2080
613
4040
1130
3270
925
2620
760
5530
1596
4370
1269
3300
975
6640
1904
5220
1498
3520
1018
Water pressure drop
kPa
23
15
12
27
20
15
20
14
8
22
14
9
25
18
13
21
14
9
29
19
10

Total cooling capacity


W
1910
1500
1300
2450
2080
1730
3680
2990
2250
5480
4190
3260
6000
4920
4040
8500
6760
5180
10110
7960
5400

Water pressure drop


kPa
19
13
10
23
17
12
17
12
7
18
12
7
21
15
11
18
12
8
25
16
8

Capacity tables

5-2
Cooling Capacity Tables - 4 pipe

4TW60012-1A (Sheet 8/13)

9 - 14
Sensible cooling capacity
Water flow
W
!/h
1230
329
980
258
820
223
1610
421
1340
357
1090
297
2230
632
1800
514
1350
387
3340
941
2610
720
1950
560
3820
1031
3090
844
2470
694
5220
1460
4120
1161
3100
891
6280
1737
4930
1367
3310
927

FW 10 TN/TV

FW 08 FN/FV

FW 06 FN/FV

FW 04 FN/FV

FW 03 FN/FV

FW 02 FN/FV

FW 01 FN/FV

Air temperature (C DB - C WB)


Water temperature (Entering C - leaving C)
Model

Indoor Unit Fan Coil Units FWV-DT/DF

15

16

Fan coil Indoor Unit


FW..02
medium
0.87
0.87
0.83
0.89

20

low
0.69
0.70
0.68
0.78

F2
0.8
0.65
0.4
0.78
0.68
0.59
0.81
0.67
0.5
0.89
0.84
0.71
0.89
0.86
0.74
0.92
0.92
0.82
0.93
0.91
0.86

F1
0.56
0.33
0.61
0.45
0.35
0.64
0.47
0.77
0.71
0.52
0.77
0.73
0.56
0.86
0.85
0.71
0.87
0.84
0.76
FW..03
medium
0.81
0.81
0.81
0.87

Air: 27C DB - 19C WB - Water: entering 7C - leaving 12C


Air: 20C Water: entering 50C water flow as for cooling
Air: 20C Water: entering 70C - leaving 60C

low
0.68
0.66
0.66
0.73

F1
0.72
0.56
0.35
0.73
0.63
0.55
0.77
0.64
0.48
0.85
0.81
0.68
0.85
0.82
0.71
0.91
0.9
0.81
0.92
0.9
0.84

low
0.60
0.60
0.59
0.71

30

FW..04
medium
0.76
0.78
0.76
0.83
low
0.58
0.57
0.58
0.69

F1
0.5
0.27
0.51
0.29
0.67
0.59
0.34
0.67
0.61
0.4
0.8
0.79
0.6
0.82
0.78
0.67

40

FW..06
medium
0.81
0.80
0.82
0.88

F2
0.57
0.3
0.56
0.32
0.73
0.64
0.36
0.73
0.66
0.43
0.83
0.81
0.62
0.85
0.81
0.69

F1 = correction factor for air flow


F2 = correction factor for capacities

F2
0.67
0.41
0.67
0.5
0.37
0.69
0.5
0.82
0.75
0.55
0.81
0.77
0.59
0.88
0.87
0.73
0.89
0.86
0.78

Correction factors are based on an average value. This can cause deviation depending on conditions used. The Fan Coil Selection software will provide an accurate
result at all conditions.

Cooling
Heating 2-pipe
Heating 4-pipe

F2
0.91
0.84
0.77
0.89
0.85
0.8
0.91
0.84
0.77
0.95
0.93
0.86
0.95
0.93
0.88
0.96
0.96
0.92
0.97
0.96
0.93

low
0.66
0.64
0.66
0.76

F1
0.4
0.36
0.56
0.46
0.56
0.48
0.23
0.74
0.73
0.49
0.77
0.71
0.57

F2
0.47
0.4
0.63
0.51
0.62
0.53
0.25
0.78
0.76
0.51
0.81
0.75
0.6
FW..08
medium
0.79
0.78
0.79
0.86

50

low
0.59
0.58
0.61
0.72

60

4TW60018-1

low
0.52
0.51
0.52
0.66

F2
0.36
0.21
0.5
0.35
0.47
0.36
0.71
0.69
0.39
0.76
0.68
0.5
FW..10
medium
0.78
0.77
0.78
0.85

F1
0.31
0.18
0.42
0.31
0.41
0.31
0.67
0.65
0.37
0.72
0.64
0.47

Capacity Correction Factor

FW..01
medium
0.81
0.81
0.81
0.85

10

5-3

Conditions

TCC
SCC
HC2P
HC40

F1
0.86
0.78
0.71
0.85
0.82
0.78
0.89
0.82
0.75
0.93
0.91
0.84
0.93
0.92
0.86
0.96
0.95
0.91
0.96
0.95
0.92

Capacity tables

Total cooling capacity


Sensible cooling capacity
Heating capacity - 2 pipe
Heating capacity - 4 pipe

ESP
Fan speed
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.

FW..10

FW..08

FW..06

FW..04

FW..03

FW..02

FW..01

FWV - FWL - FWM

Indoor Unit Fan Coil Units FWV-DT/DF

Indoor Unit Fan Coil Units FWV-DT/DF

Capacity tables

5-3

Capacity Correction Factor

Cooling mode

Glycol percentage in weight

Freezing temperature (C)

Capacity correction factor

Pressure drop correction


factor

1.00

10

-4

0.93

1.09

20

-10

0.84

1.18

30

-16

0.76

1.27

40

-24

0.76

1.36

Glycol percentage in weight

Freezing temperature (C)

Capacity correction factor

Pressure drop correction


factor

Heating mode

1.00

10

-4

0.98

1.08

20

-10

0.97

1.11

30

-16

0.94

1.22

40

-24

0.91

1.33
4TW60228-1B

Correction factors are based on an average value (at rated water flow rate). This can cause deviation depending on
conditions used. The Fan Coil Selection software will provide an accurate result at all conditions.

Fan coil Indoor Unit

17

18

Fan coil Indoor Unit

Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.

Heating capacity
W
1820
1480
1210
2150
1810
1500
3200
2580
1910
4730
3610
2760
5360
4390
3570
6490
5170
3970
8400
6530
4390

45 - 40
Water flow
!/h
317
256
211
373
315
260
556
449
332
823
628
480
932
763
620
1129
898
690
1460
1135
764
Water pressure drop Heating capacity
kPa
W
15
2840
11
2310
8
1900
12
3360
9
2840
6
2350
11
5030
8
4070
5
3020
12
7420
8
5690
5
4360
15
8410
11
6900
7
5630
10
10170
7
8100
4
6230
19
13130
12
10220
6
6890

60 - 50
Water flow
!/h
249
201
166
293
248
206
439
356
264
648
497
381
735
603
491
889
708
544
1147
893
602
Water pressure drop Heating capacity
kPa
W
10
3710
7
2990
5
2470
7
4350
6
3670
4
3040
7
6460
5
5220
3
3860
8
9570
5
7300
3
5590
9
10850
7
8860
5
7200
6
13130
4
10460
3
8060
12
17000
7
13200
4
8910

20
70 - 60
Water flow
!/h
325
263
216
382
322
267
567
458
339
840
641
490
952
778
632
1152
918
707
1492
1158
782
Water pressure drop Heating capacity
kPa
W
15
4940
10
4010
7
3320
11
5830
8
4940
6
4110
11
8760
7
7110
4
5290
12
12890
7
9910
5
7620
14
14620
10
12020
7
9810
9
17650
6
14100
4
10880
18
22760
11
17740
6
12020

Water pressure drop


kPa
7
5
3
5
4
3
5
4
2
6
4
2
7
5
3
4
3
2
8
5
3

Capacity tables

5-4
Heating Capacity Tables - 2 pipe

4TW60012-1A (Sheet 9/13)

90 - 70
Water flow
!/h
218
177
147
257
218
181
386
314
233
569
437
336
645
530
433
779
623
480
1005
783
531

FW 10 TN/TV

FW 08 TN/TV

FW 06 TN/TV

FW 04 TN/TV

FW 03 TN/TV

FW 02 TN/TV

FW 01 TN/TV

Air temperature (C)


Water temperature (Entering C - leaving C)
Model

Indoor Unit Fan Coil Units FWV-DT/DF

Fan coil Indoor Unit

Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.

Heating capacity
W
1650
1330
1100
1950
1640
1360
2900
2340
1730
4290
3280
2500
4860
3980
3240
5890
4680
3590
7610
5920
3980

45 - 40
Water flow
!/h
287
232
191
338
285
236
505
407
302
746
570
436
846
693
562
1024
813
625
1323
1029
692
Water pressure drop Heating capacity
kPa
W
13
2670
9
2160
6
1780
10
3150
7
2660
5
2210
10
4730
7
3820
4
2840
10
6970
6
5340
4
4090
13
7900
9
6490
6
5280
8
9550
6
7600
3
5840
16
12320
10
9600
5
6460

60 - 50
Water flow
!/h
233
189
156
275
233
193
413
334
248
609
466
357
690
567
461
834
664
510
1077
839
565
Water pressure drop Heating capacity
kPa
W
9
3530
6
2850
4
2350
7
4140
5
3500
4
2890
6
6150
4
4970
3
3670
7
9110
4
6960
3
5320
8
10330
6
8440
4
6850
5
12500
4
9960
2
7670
10
16190
7
12570
3
8490

22
70 - 60
Water flow
!/h
310
250
206
363
307
254
540
436
322
799
610
467
906
740
601
1097
874
673
1420
1102
744
Water pressure drop Heating capacity
kPa
W
13
4750
9
3860
7
3190
10
5610
8
4760
6
3950
10
8430
7
6840
4
5090
11
12410
7
9540
4
7330
13
14080
9
11570
6
9450
9
17000
6
13580
4
10460
16
21920
10
17080
5
11570

Water pressure drop


kPa
7
5
3
5
4
3
5
3
2
5
3
2
6
5
3
4
3
2
8
5
3

Capacity tables

5-4
Heating Capacity Tables - 2 pipe

4TW60012-1A (Sheet 10/13)

90 - 70
Water flow
!/h
210
170
141
248
210
174
372
302
225
548
421
324
622
511
417
750
600
462
968
754
511

FW 10 TN/TV

FW 08 TN/TV

FW 06 TN/TV

FW 04 TN/TV

FW 03 TN/TV

FW 02 TN/TV

FW 01 TN/TV

Air temperature (C)


Water temperature (Entering C - leaving C)
Model

Indoor Unit Fan Coil Units FWV-DT/DF

19

Air temperature (C)


Water temperature (Entering C - leaving C)
Model
Air flow
m3/h
FW 01 FN/FV
Max.
Med.
Min.
FW 02 FN/FV
Max.
Med.
Min.
FW 03 FN/FV
Max.
Med.
Min.
FW 04 FN/FV
Max.
Med.
Min.
FW 06 FN/FV
Max.
Med.
Min.
FW 08 FN/FV
Max.
Med.
Min.
FW 10 TN/TV
Max.
Med.
Min.

Heating capacity
W
920
820
720
980
860
750
1470
1260
1030
2460
2070
1750
2580
2260
1970
3890
3360
2800
4560
3910
3010

45 - 40
Water flow
!/h
161
143
126
170
150
131
255
220
179
427
360
304
448
393
343
675
584
486
793
679
523
Water pressure drop Heating capacity
kPa
W
6
1420
5
1270
4
1110
8
1500
6
1330
5
1160
5
2240
4
1930
3
1570
13
3790
9
3200
7
2710
10
3970
8
3490
6
3050
31
6020
24
5210
18
4350
37
7060
28
6050
18
4680

60 - 50
Water flow
!/h
124
111
97
131
116
101
196
169
137
331
280
237
347
305
266
526
456
380
617
529
409

20
Water pressure drop Heating capacity
kPa
W
3
1900
3
1700
2
1500
5
2010
4
1780
3
1560
3
3080
2
2680
2
2180
8
5050
6
4250
4
3600
6
5300
5
4650
4
4040
19
7910
15
6830
11
5690
23
9300
17
7950
11
6120

20
70 - 60
Water flow
!/h
167
149
132
176
156
137
270
235
191
443
373
316
465
408
355
694
600
499
816
698
537
Water pressure drop Heating capacity
kPa
W
6
2470
5
2220
4
1950
7
2600
6
2310
5
2020
5
3960
4
3420
3
2780
12
6580
9
5560
7
4730
10
6890
8
6060
6
5290
30
10410
23
9020
17
7540
36
12210
27
10470
17
8100

Water pressure drop


kPa
3
2
2
3
3
2
2
2
1
6
4
3
5
4
3
14
11
8
17
13
8

5
Capacity tables

5-5
Heating Capacity Tables - 4 pipe

Fan coil Indoor Unit

4TW60012-1A (Sheet 11/13)

90 - 70
Water flow
!/h
109
98
86
115
102
89
175
151
123
290
245
209
304
268
234
460
398
333
539
462
358

Indoor Unit Fan Coil Units FWV-DT/DF

Fan coil Indoor Unit

Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.
Max.
Med.
Min.

Heating capacity
W
830
740
650
870
770
670
1300
1120
910
2210
1860
1570
2320
2040
1770
3510
3040
2530
4120
3530
2720

45 - 40
Water flow
!/h
144
128
113
152
134
117
227
195
158
385
324
273
403
354
308
610
528
440
717
614
473
Water pressure drop Heating capacity
kPa
W
5
1320
4
1180
3
1040
6
1400
5
1230
4
1080
4
2080
3
1790
2
1450
11
3540
8
2990
6
2520
9
3710
7
3260
5
2840
26
5640
20
4890
15
4080
31
6610
24
5670
15
4380

60 - 50
Water flow
!/h
115
103
91
122
108
94
181
156
127
310
261
220
324
285
248
493
427
356
578
495
383
Water pressure drop Heating capacity
kPa
W
3
1810
2
1620
2
1430
4
1910
3
1690
3
1480
3
2930
2
2530
1
2060
7
4800
5
4040
4
3420
6
5040
4
4420
3
3840
17
7530
13
6500
10
5410
20
8850
16
7570
10
5820

22
70 - 60
Water flow
!/h
159
142
125
167
148
130
257
222
181
421
354
300
442
387
337
660
570
475
777
664
511
Water pressure drop Heating capacity
kPa
W
5
2370
4
2130
3
1870
7
2500
6
2220
4
1940
5
3790
4
3270
3
2660
11
6320
8
5340
6
4550
9
6630
7
5830
6
5090
27
10020
21
8680
15
7260
33
11750
25
10080
16
7800

Water pressure drop


kPa
2
2
2
3
3
2
2
2
1
5
4
3
4
3
3
13
10
7
16
12
8

Capacity tables

5-5
Heating Capacity Tables - 4 pipe

4TW60012-1A (Sheet 12/13)

90 - 70
Water flow
!/h
105
94
83
110
98
86
167
144
118
279
236
201
292
257
225
443
383
320
519
445
344

FW 10 TN/TV

FW 08 FN/FV

FW 06 FN/FV

FW 04 FN/FV

FW 03 FN/FV

FW 02 FN/FV

FW 01 FN/FV

Air temperature (C)


Water temperature (Entering C - leaving C)
Model

Indoor Unit Fan Coil Units FWV-DT/DF

21

Indoor Unit Fan Coil Units FWV-DT/DF

Capacity tables

5-6

Power consumption - 2 pipe

FWV-FWL-FWM
FW01
AP
(Pa)
0
10
20
30
45
50

MAX
Power input
(W)
37
37
35
35
34
33

Current
(A)
0.170
0.160
0.150
0.150
0.140
0.140

MED
Power input
(W)
28
26
25
24

Current
(A)
0.130
0.120
0.110
0.110

MIN
Power input
(W)
21
21
20

Current
(A)
0.100
0.090
0.088

4TW60011-2B (1/14)

FWV-FWL-FWM
FW02
AP
(Pa)
0
10
20
30
40

MAX
Power input
(W)
53
52
48
46
46

Current
(A)
0.240
0.235
0.217
0.208
0.208

MED
Power input
(W)
36
32
31
31
30

Current
(A)
0.160
0.142
0.138
0.138
0.133

MIN
Power input
(W)
24
21
21
20

Current
(A)
0.110
0.096
0.096
0.092

4TW60011-2B (2/14)

22

Fan coil Indoor Unit

Indoor Unit Fan Coil Units FWV-DT/DF

Capacity tables

5-6

Power consumption - 2 pipe

FWV-FWL-FWM
FW03
AP
(Pa)
0
10
20
30
40
50

MAX
Power input
(W)
56
55
53
53
52
51

Current
(A)
0.252
0.248
0.239
0.239
0.234
0.230

MED
Power input
(W)
43
42
41
41
40

Current
(A)
0.200
0.195
0.191
0.191
0.186

MIN
Power input
(W)
29
29
29
28

Current
(A)
0.138
0.134
0.131
0.130

4TW60011-2B (3/14)

FWV-FWL-FWM
FW04
AP
(Pa)
0
10
20
30
40
50
60
70
75

MAX
Power input
(W)
98
94
92
90
88
85
81
76
74

Current
(A)
0.440
0.422
0.413
0.404
0.395
0.382
0.364
0.341
0.332

MED
Power input
(W)
61
59
57
55
53
50
45

Current
(A)
0.287
0.276
0.259
0.254
0.242
0.228
0.211

MIN
Power input
(W)
38
37
36
34
31

Current
(A)
0.192
0.187
0.182
0.172
0.157

4TW60011-2B (4/14)

Fan coil Indoor Unit

23

Indoor Unit Fan Coil Units FWV-DT/DF

Capacity tables

5-6

Power consumption - 2 pipe

FWV-FWL-FWM
FW06
AP
(Pa)
0
10
20
30
40
50
60
70

MAX
Power input
(W)
98
96
94
91
90
89
86
82

Current
(A)
0.430
0.421
0.412
0.399
0.395
0.391
0.377
0.360

MED
Power input
(W)
68
67
64
62
61
59
56

Current
(A)
0.310
0.305
0.292
0.283
0.278
0.269
0.255

MIN
Power input
(W)
47
45
44
43
42

Current
(A)
0.220
0.211
0.206
0.201
0.197

4TW60011-2B (5/14)

FWV-FWL-FWM
FW08
AP
(Pa)
0
10
20
30
40
50
60
70
80
90
100

MAX
Power input
(W)
137
133
129
126
122
117
113
108
103
96
88

Current
(A)
0.600
0.585
0.569
0.550
0.531
0.511
0.491
0.471
0.450
0.418
0.385

MED
Power input
(W)
104
103
102
98
95
92
88
83

Current
(A)
0.457
0.452
0.446
0.430
0.414
0.400
0.386
0.364

MIN
Power input
(W)
76
75
73
72
70
67

Current
(A)
0.338
0.333
0.328
0.319
0.310
0.297

4TW60011-2B (6/14)

24

Fan coil Indoor Unit

Indoor Unit Fan Coil Units FWV-DT/DF

Capacity tables

5-6

Power consumption - 2 pipe

FWV-FWL-FWM
FW10
AP
(Pa)
0
10
20
30
40
50
60
70
80
90
100

MAX
Power input
(W)
175
170
165
161
156
150
144
139
133
127
120

Current
(A)
0.764
0.742
0.720
0.701
0.681
0.655
0.629
0.605
0.581
0.552
0.524

MED
Power input
(W)
130
128
125
121
116
112
107
102
96
92

Current
(A)
0.578
0.567
0.556
0.536
0.516
0.496
0.476
0.451

MIN
Power input
(W)
90
88
86
84
82
79

Current
(A)
0.414
0.405
0.396
0.386
0.377
0.363

4TW60011-2B (7/14)

Fan coil Indoor Unit

25

Indoor Unit Fan Coil Units FWV-DT/DF

Capacity tables

5-7

Power consumption - 4 pipe

FWV-FWL-FWM
FW01
AP
(Pa)
0
10
20
30
45
50

MAX
Power input
(W)
37
37
35
35
34
33

Current
(A)
0.170
0.160
0.150
0.150
0.140
0.140

MED
Power input
(W)
28
26
25
24

Current
(A)
0.130
0.120
0.110
0.110

MIN
Power input
(W)
21
21
20

Current
(A)
0.100
0.090
0.088

4TW60011-2B (8/14)

FWV-FWL-FWM
FW02
AP
(Pa)
0
10
20
30
40

MAX
Power input
(W)
53
52
48
46
46

Current
(A)
0.240
0.235
0.217
0.208
0.208

MED
Power input
(W)
36
32
31
31
30

Current
(A)
0.160
0.142
0.138
0.138
0.133

MIN
Power input
(W)
24
21
21
20

Current
(A)
0.110
0.096
0.096
0.092

4TW60011-2B (9/14)

26

Fan coil Indoor Unit

Indoor Unit Fan Coil Units FWV-DT/DF

Capacity tables

5-7

Power consumption - 4 pipe

FWV-FWL-FWM
FW03
AP
(Pa)
0
10
20
30
40
50

MAX
Power input
(W)
56
55
53
53
52
51

Current
(A)
0.252
0.248
0.239
0.239
0.234
0.230

MED
Power input
(W)
43
42
41
41
40

Current
(A)
0.200
0.195
0.191
0.191
0.186

MIN
Power input
(W)
29
29
29
28

Current
(A)
0.138
0.134
0.131
0.130

4TW60011-2B (10/14)

FWV-FWL-FWM
FW04
AP
(Pa)
0
10
20
30
40
50
60
70
75

MAX
Power input
(W)
98
94
92
90
88
85
81
76
74

Current
(A)
0.440
0.422
0.413
0.404
0.395
0.382
0.364
0.341
0.332

MED
Power input
(W)
61
59
57
55
53
50
45

Current
(A)
0.287
0.276
0.259
0.254
0.242
0.228
0.211

MIN
Power input
(W)
38
37
36
34
31

Current
(A)
0.192
0.187
0.182
0.172
0.157

4TW60011-2B (11/14)

Fan coil Indoor Unit

27

Indoor Unit Fan Coil Units FWV-DT/DF

Capacity tables

5-7

Power consumption - 4 pipe

FWV-FWL-FWM
FW06
AP
(Pa)
0
10
20
30
40
50
60
70

MAX
Power input
(W)
98
96
94
91
90
89
86
82

Current
(A)
0.430
0.421
0.412
0.399
0.395
0.391
0.377
0.360

MED
Power input
(W)
68
67
64
62
61
59
56

Current
(A)
0.310
0.305
0.292
0.283
0.278
0.269
0.255

MIN
Power input
(W)
47
45
44
43
42

Current
(A)
0.220
0.211
0.206
0.201
0.197

4TW60011-2B (12/14)

FWV-FWL-FWM
FW08
AP
(Pa)
0
10
20
30
40
50
60
70
80
90
100

MAX
Power input
(W)
137
133
129
126
122
117
113
108
103
96
88

Current
(A)
0.600
0.585
0.569
0.550
0.531
0.511
0.491
0.471
0.450
0.418
0.385

MED
Power input
(W)
104
103
102
98
95
92
88
83

Current
(A)
0.457
0.452
0.446
0.430
0.414
0.400
0.386
0.364

MIN
Power input
(W)
76
75
73
72
70
67

Current
(A)
0.338
0.333
0.328
0.319
0.310
0.297

4TW60011-2B (13/14)

28

Fan coil Indoor Unit

Indoor Unit Fan Coil Units FWV-DT/DF

Capacity tables

5-7

Power consumption - 4 pipe

FWV-FWL-FWM
FW10
AP
(Pa)
0
10
20
30
40
50
60
70
80
90
100

MAX
Power input
(W)
175
170
165
161
156
150
144
139
133
127
120

Current
(A)
0.764
0.742
0.720
0.701
0.681
0.655
0.629
0.605
0.581
0.552
0.524

MED
Power input
(W)
130
128
125
121
116
112
107
102
96
92

Current
(A)
0.578
0.567
0.556
0.536
0.516
0.496
0.476
0.451

MIN
Power input
(W)
90
88
86
84
82
79

Current
(A)
0.414
0.405
0.396
0.386
0.377
0.363

4TW60011-2B (14/14)

Fan coil Indoor Unit

29

Indoor Unit Fan Coil Units FWV-DT/DF

Dimensional drawings

6-1

Dimensional Drawings

FWV - FWL

FWV+FWL 01+02
FWV+FWL 03
FWV+FWL 04+06
FWV+FWL 08+10
Legend

774
984
1194
1404

226
226
226
251

498
708
918
1128

51
51
51
48

458
458
458
497

163
163
163
185

263
263
263
259

149
149
149
155

198
198
198
220

187
187
187
195

335
335
335
348

99
99
99
120

486
486
486
478

208
208
208
234

198
198
198
208

246
246
246
271

Hydraulic connections

1 Clear space for hydraulic connections (*)


Standard heat exchanger: connection female
2 Slots for wall / ceiling mounting 9x20mm
3 Clear space for electric connections (*)
FW01
FW02
FW03
FW04
FW06
FW08
4 Hydraulic connections (4DF = 4 pipe system)
1/2
1/2
1/2
1/2
1/2
3/4
5 Condensate drainage for vertical installation
Additional heat exchanger: connection female
6 Air outlet for concealed models
7 Air suction for concealed models
FW01
FW02
FW03
FW04
FW06
FW08
8 Condensate drainage for horizontal installation
1/2
1/2
1/2
1/2
1/2
1/2
9 Air outlet
10 Air inlet
(*) Indications applicable to fan coils with hydraulic connections on the left side; in case of right side connections the indications for clear space are reversed.

FW10
3/4

FW10
1/2

4TW60014-1A (Sheet 1/2)

30

Fan coil Indoor Unit

Indoor Unit Fan Coil Units FWV-DT/DF

Wiring diagrams

7-1

Wiring Diagrams - Single Phase

SYMBOLS
BK

Black = maximum speed

BU

Blue = medium speed

GNYE

Yellow/Green = earth connection

RD

Red = minimum speed

WH

White = common

----

Field wiring

Protection fuse (field supply)

IL

Main switch (field supply)

Fan motor

PE

Earth connection

4TW60016-1

Fan coil Indoor Unit

31

Indoor Unit Fan Coil Units FWV-DT/DF

Sound data

8-1

Sound Level Data - 2 pipe

FWV-FWL-FWM

Sound power level and spectrum


Sound power levels dBA
max
med
min

125 Hz
24.8
19.4
13.6

250 Hz
39.1
34.1
29.7

Sound power levels dBA


max
med
min

125 Hz
28.8
22.9
18.0

250 Hz
42.7
37.8
33.1

Sound power levels dBA


max
med
min

125 Hz
27.8
23.0
15.6

250 Hz
40.9
36.0
28.8

Sound power levels dBA


max
med
min

125 Hz
31.7
23.6
17.8

250 Hz
45.4
37.6
31.8

Sound power levels dBA


max
med
min

125 Hz
36.1
28.9
23.7

250 Hz
49.3
43.0
37.4

Sound power levels dBA


max
med
min

125 Hz
37.1
30.6
24.8

250 Hz
51.3
44.9
38.8

Sound power levels dBA


max
med
min

125 Hz
42.6
36.6
27.8

250 Hz
56.0
49.6
42.3

FW01 TN/TV
500 Hz
1000 Hz
41.7
38.4
35.9
30.3
29.0
22.0
FW02 TN/TV
500 Hz
1000 Hz
45.8
43.6
40.7
36.2
35.4
29.1
FW03 TN/TV
500 Hz
1000 Hz
43.5
40.4
37.9
33.0
28.8
22.0
FW04 TN/TV
500 Hz
1000 Hz
47.7
45.4
39.8
34.2
31.5
24.4
FW06 TN/TV
500 Hz
1000 Hz
51.4
50.6
45.2
42.3
39.8
34.4
FW08 TN/TV
500 Hz
1000 Hz
52.8
51.6
46.4
44.7
39.1
37.4
FW10 TN/TV
500 Hz
1000 Hz
58.2
58.4
52.9
51.6
43.8
41.7

2000 Hz
33.7
24.3
16.2

4000 Hz
21.6
15.8
15.2

8000 Hz
15.6
15.4
15.2

Global Lw
45
39
33

2000 Hz
39.3
30.3
22.7

4000 Hz
29.9
19.6
15.5

8000 Hz
17.2
15.4
15.3

Global Lw
50
44
38

2000 Hz
34.0
25.7
17.2

4000 Hz
23.4
18.4
16.0

8000 Hz
18.0
16.6
15.6

Global Lw
47
41
33

2000 Hz
41.7
28.7
17.2

4000 Hz
32.0
21.6
16.5

8000 Hz
19.2
16.5
15.4

Global Lw
52
43
35

2000 Hz
47.4
36.1
28.6

4000 Hz
39.1
28.1
21.9

8000 Hz
24.7
17.9
16.8

Global Lw
56
49
43

2000 Hz
49.8
42.1
32.6

4000 Hz
43.5
33.2
22.8

8000 Hz
32.3
20.9
18.2

Global Lw
58
51
44

2000 Hz
56.5
49.5
38.3

4000 Hz
51.7
43.2
28.6

8000 Hz
44.4
32.7
20.7

Global Lw
64
57
48

NOTES

To calculate the sound pressure you must dene some conditions and use this formula

Lp

Lw10 uLog10

Where: Q

d =
Lp =
Lw =

4Sud
Q

direction factor: is Q=4 if the FCU is installed near 2 walls (vertical or oor-ceiling). Q=2 if the FCU is installed near 1 wall (at oor or
ceiling but faraway the 2 wall)
distance (mt) from the sound source and the measure point
sound pressure (dBA)
sound power (dBA)

Conditions of measurements:
ISO3741 : In case of (M) models, the sound power is calculated WITHOUT any additional inlet or outlet grill or plenum!

4TW60017-1B (1/2)

32

Fan coil Indoor Unit

Indoor Unit Fan Coil Units FWV-DT/DF

Sound data

8-2

Sound Level Data - 4 pipe

):9):/):0

6RXQGSRZHUOHYHODQGVSHFWUXP
6RXQGSRZHUOHYHOVG%$
PD[
PHG
PLQ

+]




+]




6RXQGSRZHUOHYHOVG%$
PD[
PHG
PLQ

+]




+]




6RXQGSRZHUOHYHOVG%$
PD[
PHG
PLQ

+]




+]




6RXQGSRZHUOHYHOVG%$
PD[
PHG
PLQ

+]




+]




6RXQGSRZHUOHYHOVG%$
PD[
PHG
PLQ

+]




+]




6RXQGSRZHUOHYHOVG%$
PD[
PHG
PLQ

+]




+]




6RXQGSRZHUOHYHOVG%$
PD[
PHG
PLQ

+]




+]




):)1)9
+]
+]






):)1)9
+]
+]






):)1)9
+]
+]






):)1)9
+]
+]






):)1)9
+]
+]






):)1)9
+]
+]






):)1)9
+]
+]







+]




+]




+]




*OREDO/Z




+]




+]




+]




*OREDO/Z




+]




+]




+]




*OREDO/Z




+]




+]




+]




*OREDO/Z




+]




+]




+]




*OREDO/Z




+]




+]




+]




*OREDO/Z




+]




+]




+]




*OREDO/Z




127(6

7RFDOFXODWHWKHVRXQGSUHVVXUH\RXPXVWGHQHVRPHFRQGLWLRQVDQGXVHWKLVIRUPXOD

/S /Zu/RJ SuG


4


:KHUH 4

 GLUHFWLRQIDFWRULV4 LIWKH)&8LVLQVWDOOHGQHDUZDOOV YHUWLFDORURRUFHLOLQJ 4 LIWKH)&8LVLQVWDOOHGQHDUZDOO DWRRURUFHLO


LQJEXWIDUDZD\WKHZDOO
G  GLVWDQFH PW IURPWKHVRXQGVRXUFHDQGWKHPHDVXUHSRLQW
/S  VRXQGSUHVVXUH G%$
/Z  VRXQGSRZHU G%$

&RQGLWLRQVRIPHDVXUHPHQWV
,62,QFDVHRI 0 PRGHOVWKHVRXQGSRZHULVFDOFXODWHG:,7+287DQ\DGGLWLRQDOLQOHWRURXWOHWJULOORUSOHQXP

7:% 

Fan coil Indoor Unit

33

Indoor Unit Fan Coil Units FWV-DT/DF

Installation

9-1

Installation Method

Fan coil units should be installed in a position where they heat and cool the room evenly, on walls or ceilings that can bear their weight.
Fit any accessories on the standard unit before installing it. Read the relevant technical sheets for the installation and use of the
accessories. Keep free space around the fan coil to allow proper operation and ordinary and extraordinary maintenance (see the 9.
Dimensional drawings) Provide a panel to reach the unit in case of recessed mounting (Concealed models).
Install the remote control panel, if any, in a position that can easily be reached by the user to set the functions and that is suitable for the
proper detection of the temperature, if provided.
Therefore avoid:
- positions directly exposed to sunlight;
- positions exposed to hot or cold draughts;
- obstacles preventing the proper temperature detection
If the system is shut down during the winter months, drain off the water from the system to prevent damage due to freezing; if antifreeze
solutions are used, check the freezing point using the table shown on technical manual.
Keep at least 100 mm of free space at air inlet for a proper air suction and an easy removal of the filter.
For ducted units the outlet/inlet grill surface must be at least equal to the outlet/inlet surface of the unit to avoid extra noise and strong
performance reduction.
BEFORE THE INSTALLATION
Installation and maintenance should be carried out by technical personnel qualified for this type of machine, in compliance with current
safety regulations.
For installation and use of possible accessories please refer to the pertinent technical sheets.
In choosing where to install the unit, comply with the following points:
- the heating unit should not be placed immediately under a socket
- do not install the unit in rooms where inflammable gases are present
- do not let water is sprayed directly on the unit
- install the unit on ceilings or walls that bear its weight. Leave enough space all around for proper operation and maintenance of the unit.
Keep the unit in its packaging until it is ready to be installed, to prevent dust getting inside it.
INSTALLATION WARNING:
On the fan coil install a switch (IL) and/or all remote controls in a position out of the reach of persons who are in a bathtub
or shower.
In case of ceiling-mounted models, check that the installation height does not exceed the maximum height shown in 7. Dimensional
drawings in order to avoid excessive hot air stratification in the upper part of the room; in case of greater installation heights we suggest to
proceed with the back suction from the lower part of the room. The installation heights shown in the figure refer to the maximum running
speed.
Carry out the hydraulic connections to the heat exchanger and in case of cooling operation, to the water drainage system. We suggest to
provide for the water inlet from the bottom side of the heat exchanger and the outlet on the upper side. Bleed the air from the heat
exchanger operating on the air-vent valves (10 hexagon wrench) located beside the water connections of the heat exchanger. For a better
water drainage lean the drain pipe downwards at least 3 cm/m avoiding loops or narrowing on its way.
INSTALLATION FOR THE CONCEALED CEILING MODEL
The air outlets should not be placed immediately under a socket. For the concealed ceiling model, perform the connection between the fan
coil and the ducts, and place damping material between the duct and the unit. The ducts, in particular the outlet ones, must be insulated. In
order to avoid air back suction on the fan coil, keep a minimum distance between the air outlet and recovered air flow as shown in
installation manual of the unit. The minimum installation height should not be lower than 1.8 metres from floor level. Provide for an
inspection port to the unit.

34

Fan coil Indoor Unit

Indoor Unit Fan Coil Units FWV-DT/DF

Installation

9-1

Installation Method

ELECTRICAL CONNECTIONS
Carry out the electrical wiring after having turned the power off in compliance with the relevant local and national regulations following the
relevant wiring diagram.
Check that the power supply corresponds to the rated power reported on the unit nameplate.
Each fan coil requires a switch (IL) on the feeder line with a distance of at least 3 mm between the opening contacts, and a suitable safety
fuse (F).
USE
To use the fan coil unit, refer to the instructions of the control panel, available as accessory.
Air outlet grids on the cover cabinet (wall mounted and floor/ceiling mounted) can be turned 180 to direct the flow into the room or
towards the wall on which the unit is mounted. The grids and the side doors are snapped into the cabinet. Before removing them in order
to change their position, cut the power off and wear protective gloves.
MAINTENANCE
For safety reasons before carrying out any maintenance or cleaning operation, switch off the unit turning the selection switch to Stop and
the power supply switch on position 0 (OFF).
Be careful during any maintenance operation; you could get injured by some metal parts; use protective work gloves. The fan coils do no
require any particular maintenance operation: only the periodical cleaning of the air filter should be carried out. It is necessary to carry out a
running in period of 100 hours in order to eliminate all mechanical friction. The starting up must be carried out at the maximum speed.
For good operation of the fan coils follow the instructions below:
- keep the air filter clean;
- do not pour liquids into the unit;
- do not introduce metal parts through the air outlet grid;
- keep the air inlet and outlet free at all times.
Each time the machine is turned on after being idle for a long period, ensure there is no air in the heat exchanger. Before using the unit for
air conditions, check that:
- condensate drainage is performed correctly:
- the heat exchanger fins are not obstructed by deposits of dirt.
If necessary clean the fins with low pressure compressed air or steam without damaging them.
CLEANING
For safety reasons before carrying out any maintenance or cleaning operation switch off the unit turning the selection
switch to Stop and the power supply switch on 0 (OFF).
Clean the filter at least once a month and in any case before using the unit (before the heating or the air conditioning season).
For cleaning the air filter proceed as follows (pictures see manual of units):
- Floor models: turn the screws 90, which secure the filter to the cover cabinet, to 1/4 turn and remove the filter;
- Concealed models: reach the fan coil through the inspection panel and remove the filter, turning the locking brackets 90;
- Floor ceiling: remove the air filters that are inside the intake grids located on the front panel of the cover cabinet;
- clean the filter with lukewarm water, or in case of dry dust, with compressed air;
- reassemble the filter after having dried it up
It is recommended to replace the air filter yearly, and to use original spare parts; the fan coil model is reported on the nameplate located on
the internal part of the side panel of the unit.
To clean the unit cabinet proceed as follows
- use a soft cloth;
- do not pour any liquid on the unit, as this could cause electrical shocks or damage the components inside it;
- do not use any aggressive chemical solvents; do not use very hot water to clean the air outlet grid
Note: this is only based text and should be combined with manuals for relative pictures and additional information.

Fan coil Indoor Unit

35

Indoor Unit Fan Coil Units FWV-DT/DF

10

Operation range

10 - 1 Operation Range
Minimum water temperature
Maximum water temperature
Maximum operating pressure
Minimum air inlet temperature
Maximum air inlet temperature
Power supply

+5C
+95C
10 bar
5C
+43C
230V +-10% / 1 / 50Hz
4TW60013-1

36

Fan coil Indoor Unit

Indoor Unit Fan Coil Units FWV-DT/DF

11

Hydraulic performance

11 - 1 Water Pressure Drop Curve Evaporator - Cooling 2 pipe


Water flow l/h

50
100
200
300
400
500
600
800
1000
1500
2000
2500
3000
4000
5000

FW..01
kPa

FW..02
kPa

0.71
2.44
8.25
16.84
27.92
41.33
56.93
94.32
139.51
-

0.41
1.42
4.81
9.81
16.27
24.09
33.19
55.02
81.4
165.77
-

FWV / FWL / FWM


Water pressure drop
FW..03
FW..04
FW..06
kPa
kPa
kPa
0.19
0.66
2.25
4.6
7.63
11.3
15.57
25.82
38.2
77.83
128.9
-

0.11
0.36
1.23
2.51
4.17
6.18
8.51
14.12
20.9
42.61
70.59
104.41
143.74
-

0.1
0.35
1.21
2.46
4.09
6.06
8.35
13.84
20.5
41.8
69.27
102.47
141.09
-

FW..08
kPa

FW..10
kPa

0.05
0.16
0.56
1.14
1.9
2.82
3.89
6.44
9.54
19.46
32.27
47.75
65.76
108.92
161.06

0.05
0.20
0.67
1.37
2.29
3.39
4.68
7.75
11.48
23.42
38.85
57.50
79.22
131.28
194.20
4TW60019-1A (Sheet 1/3)

Fan coil Indoor Unit

37

Indoor Unit Fan Coil Units FWV-DT/DF

11

Hydraulic performance

11 - 2 Water Pressure Drop Curve Evaporator - Heating 2 pipe


Water flow l/h

50
100
200
300
400
500
600
800
1000
1500
2000
2500
3000
4000
5000

FW..01
kPa

FW..02
kPa

0.61
2.02
6.72
13.6
22.45
33.14
45.55
75.27
111.15
-

0.36
1.19
3.94
7.97
13.14
19.39
26.64
44.01
64.97
-

FWV / FWL / FWM


Water pressure drop
FW..03
FW..04
FW..06
kPa
kPa
kPa
0.17
0.56
1.86
3.75
6.18
9.12
12.53
20.69
30.54
62.01
102.52
-

0.09
0.31
1.02
2.07
3.41
5.02
6.89
11.38
16.79
34.06
56.28
83.12
-

0.09
0.31
1.01
2.04
3.36
4.95
6.79
11.2
16.52
33.49
55.34
81.71
112.36
-

FW..08
kPa

FW..10
kPa

0.04
0.14
0.47
0.96
1.57
2.32
3.18
5.24
7.72
15.64
25.84
38.15
52.45
86.7
-

0.04
0.17
0.58
1.16
1.91
2.81
3.86
6.36
9.37
18.96
31.29
46.17
63.45
104.85
154.82
4TW60019-1A (Sheet 2/3)

38

Fan coil Indoor Unit

Indoor Unit Fan Coil Units FWV-DT/DF

11

Hydraulic performance

11 - 3 Water Pressure Drop Curve Evaporator - Heating 4 pipe


Water flow l/h

50
100
200
300
400
500
600
800
1000
1500

FW..01
kPa

FW..02
kPa

0.68
2.27
7.56
15.3
25.27
37.29
51.26
84.72
-

0.68
2.78
9.25
18.74
30.94
45.66
62.76
103.72
-

FWV / FWL / FWM


Water pressure drop
FW..03
FW..04
FW..06
kPa
kPa
kPa
0.26
0.94
3.12
6.32
10.42
15.37
21.12
34.88
51.49
-

0.23
0.93
3.1
6.26
10.32
15.21
20.89
34.47
50.87
103.2

0.21
0.7
2.33
4.7
7.75
11.42
15.67
25.86
38.16
77.4

FW..08
kPa

FW..10
kPa

0.28
1.05
3.46
6.97
11.46
16.86
23.14
38.14
56.23
113.95

0.28
0.95
3.14
6.32
10.39
15.29
20.98
34.56
50.94
103.2
4TW60019-1A (Sheet 3/3)

Fan coil Indoor Unit

39

The present publication is drawn up by way of information only and does not constitute an offer binding
upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this publication to the best of its
knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for
particular purpose of its content and the products and services presented therein. Specifications are subject
to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect
damage, in the broadest sense, arising from or related to the use and/or interpretation of this publication. All
content is copyrighted by Daikin Europe N.V..

Daikin products are distributed by:

Daikin Europe N.V. is participating in the EUROVENT


Certification Programme. Products are as listed in the
EUROVENT Directory of Certified Products.

Naamloze Vennootschap - Zandvoordestraat 300, B-8400 Oostende - Belgium - www.daikin.eu - BE 0412 120 336 - RPR Oostende

ECDEN10-400 CD 08/10 Copyright Daikin


The present publication supersedes ECDEN09-400
Prepared in Belgium by Lannoo (www.lannooprint.be), a company whose concern
for the environment is set in the EMAS and ISO 14001 systems.
Responsible Editor: Daikin Europe N.V., Zandvoordestraat 300, B-8400 Oostende

Daikins unique position as a manufacturer of air


conditioning equipment, compressors and refrigerants
has led to its close involvement in environmental issues.
For several years Daikin has had the intention to become
a leader in the provision of products that have limited
impact on the environment. This challenge demands the
eco design and development of a wide range of products
and an energy management system, resulting in energy
conservation and a reduction of waste.