Quick Start Guide
The MACH-Global
building controller is a
powerful, central-point,
programmable DDC
controller designed
to meet the needs of
large systems where
maximum accessibility
and network capability
are required.
MACH-Global Controller
Document Conventions
Reliable ControlsTM Quick Start Guides use several
conventions to aid in your understanding of the material and
to make information more readily accessible. These
conventions are outlined below.
Software menu items will appear in bold faced type and follow
the form:
Start>Programs>Reliable ControlsTM>RC-StudioTM
Two symbols are used to draw your attention to items
warranting special attention:
ii
MACH-Global Controller
iii
MACH-Global Controller
iv
MACH-Global Controller
Contents
Package Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Getting Started. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . 3
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Physical Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Status LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Communication Ports . . . . . . . . . . . . . . . . . . . . . . . .
Port A. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Port B - 2nd Local PC/Modem . . . . . . . . . . . . . .
SMART-Net Port . . . . . . . . . . . . . . . . . . . . . . . .
AUX EIA-232 Port . . . . . . . . . . . . . . . . . . . . . . . .
MAIN~MS/TP 1. . . . . . . . . . . . . . . . . . . . . . . . . .
SUB-A~MS/TP 2. . . . . . . . . . . . . . . . . . . . . . . . .
SUB-B~MS/TP 3. . . . . . . . . . . . . . . . . . . . . . . . .
AUX EIA-485/EIA-422 . . . . . . . . . . . . . . . . . . . . .
11
13
15
16
16
16
17
17
17
MSet Configuration . . . . . . . . . . . . . . . . . . . . . . . . . .
Basic Configuration. . . . . . . . . . . . . . . . . . . . . . .
Ethernet Configuration . . . . . . . . . . . . . . . . . . . .
BACnet Setup . . . . . . . . . . . . . . . . . . . . . . . . . .
18
18
23
26
Expansion Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Input Expansion Cards . . . . . . . . . . . . . . . . . . . . 28
Output Expansion Cards . . . . . . . . . . . . . . . . . . 30
iv
MACH-Global Controller
SMART-Sensor Connection . . . . . . . . . . . . . . . . . . 33
Networking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Network Connections . . . . . . . . . . . . . . . . . . . . . 34
End-of-Line Termination . . . . . . . . . . . . . . . . . . . 35
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . 37
MACH-Global Controller
vi
MACH-Global Controller
vi
MACH-Global Controller
Package Contents
Package Contents
Your new MACH-Global package should include:
1. The MACH-Global controller.
2. A package containing four mounting screws.
MACH-Global Controller
Getting Started
Getting Started
This guide identifies the physical installation procedure and
connection of the MACH-Global controller within a Reliable
Controls MACH-System.
There are many important concepts and practices that
accompany the use of the MACH-Global controller. This
document is intended to provide installation and setup
procedures for first time users. The most important concepts
that are crucial to the reliable operation of the MACH-Global
are introduced.
Ethernet Port
Fuse
Ethernet
Status
MAIN~MS/TP 1 Port
AB+
GND
AB+
EOL
EOL
ON
OFF
485
422
Power
Off
24VAC 60Hz 75VA
MAIN ~ MS/TP 1
TX
Link
Status
GND
NET
NET
SUB-A~MS/TP 2 Port
Status
EOL
EOL
SUB-B~MS/TP 3 Port
Port A
Status
ON
AB+
SUB-A ~ MS/TP 2
AB+
SUB-B ~ MS/TP 3
Port B
Status
ON
Power Connection
Port A - Workstation
PC ~ PTP
OFF
Status
EOL
EOL
On
Port B - Workstation/Modem
PC/Modem ~ PTP
OFF
SMART-Net
TM
SMART-Net Port
Status
AB+
GND
AB+
EOL
EOL
OUT
IN
485
422
AUX EIA-485/EIA-422
Status
AUX EIA-232
BUILDING CONTROLLER
NET
NET
IN 1-16
OUT 113-128
IN 33-48
OUT 81-96
IN 65-80
OUT 49-64
IN 97-112
OUT 17-32
IN 17-32
OUT 97-112
IN 49-64
OUT 65-80
IN 81-96
OUT 33-48
IN 113-128
OUT 1-16
MACH-Global Controller
Getting Started
Product Overview
The MACH-Global controller features:
!
MACH-Global Controller
Getting Started
!
96 Trend Logs that can be used as the basis for long term data
storage.
128 Runtime Logs for tracking the on/off times of a digital point.
48 Variable arrays.
MACH-Global Controller
Installation
Installation
The MACH-Global controller is screw mounted vertically in
an enclosure.
MACH-Global Controller
Physical Dimensions
Physical Dimensions
MACH-Global Controller
Power Wiring
Power Wiring
The MACH-Global controller is powered with a non-isolated
Class 2, 24 VAC or 24 VDC, 75VA power supply.
One or more controllers can be
powered from the same
source. Ensure that polarity is
Do not connect any peripheral
devices to the same power source the same when multiple
controllers share the same
as the MACH-Global controller.
power source. Networking
components may be damaged
if polarity is crossed.
Use only a Class 2 transformer.
Refer to the technical
specifications at the back of this
document.
MACH-Global Controller
Power Wiring
MACH-Global Controller
Status LEDs
Status LEDs
The MACH-Global controller has ten different status LEDs.
There is one general power status LED located at the top right
of the controller, and nine network status LEDs.
Ethernet Status
TX
Link
Port A Status
Subnetwork B Status
Port B Status
MACH-Global Controller
Status LEDs
MACH-Global Controller Status LED Indications
LED
Power
Status
Indication
Description
On steady
Power up indication.
Flickers
EIA-232
Ports
Off steady
Indicates no activity.
Blinking
Communication activity.
EIA-485
Ports
Off steady
On Steady
Blinking
Ethernet TX
Flashes
Transmitting on Ethernet.
Ethernet
Link
On
10
MACH-Global Controller
Communication Ports
Communication Ports
The MACH-Global controller provides a sophisticated
communication management system with nine independent
communication ports. These ports are all baud-rate
independent and can communicate up to 76.8 kbps on the
EIA-485 network and up to 57.6 kbps when connected to a
workstation.
MACH-Global Controller Communication Ports
Ethernet
MAIN~MS/TP 1
SUB-A~MS/TP 2
SUB-B~MS/TP 3
A /PTP 1- Workstation
B/PTP 2 - Workstation/Modem
SMART-NetTM
AUX EIA-485/EIA-422
AUX EIA-232
11
MACH-Global Controller
Communication Ports
MACH-GlobalTM Controller Communication Ports
Port
Description
Port A
Port B
SMART-Net
AUX EIA-232
MAIN~MS/TP 1
SUB-A~MS/TP 2
SUB-B~MS/TP 3
AUX EIA-485/EIA422
Ethernet
12
MACH-Global Controller
Communication Ports
Port A
Port A is an EIA-232 port used for local workstation
connection.
!
13
MACH-Global Controller
Communication Ports
Use the CC-C1-B/C computer cable to connect a
workstation serial port to local port A or local port B on the
MACH-Global controller.
CC-C1-B/C Cable
Operator Workstation
14
MACH-Global Controller
Communication Ports
Port B - 2nd Local PC/Modem
Port B is an EIA-232 port used for either local workstation
connection or modem connection. This port features
automatic switching between Reliable Controls protocol
and BACnet protocol as described in the previous section
(Port A).
Use the CC-M1-B/C modem cable to connect the
MACH-Global controller to a modem
Modem
CC-M1-B/C Cable
15
MACH-Global Controller
Communication Ports
SMART-Net Port
The SMART-Net port is capable of networking up to 16
SMART-Sensors.
AUX EIA-232 Port
The Auxiliary EIA-232 port has been included for future
expansion
MAIN~MS/TP 1
MAIN~MS/TP 1 is an EIA-485 main network port capable of
networking directly to 32 main network controllers.
Alternatively, this port can be configured to communicate with
BACnet devices. Use the MSet tool in RC-Toolkit to
configure the port to use BACnet MS/TP 1.
MAIN~MS/TP 1 can also be configured as an EIA-422 port.
To configure MAIN~MS/TP 1 as an EIA-422 port, the DIP
switches beside the port (Net) must be toggled down on the
left side.
For details on EIA-485 configuration, please refer to the
Network Connection section of this document.
16
MACH-Global Controller
Communication Ports
SUB-A~MS/TP 2
SUB-A~MS/TP 2 is an EIA-485 port capable of hosting up to
124 subnetwork controllers.
Alternatively, this port can be configured to communicate
with BACnet devices. Use the MSet tool in RC-Toolkit to
configure the port to use BACnet MS/TP 2.
SUB-B~MS/TP 3
SUB-B~MS/TP 3 is an EIA-485 port capable of hosting up to
124 subnetwork controllers.
Alternatively, this port can be configured to communicate
with BACnet devices. Use the MSet tool in RC-Toolkit to
configure the port to use BACnet MS/TP 3.
AUX EIA-485/EIA-422
AUX EIA-485/EIA-422 is an auxiliary port capable of
communicating with either EIA-485 or EIA-422. DIP switches
(Net) beside the port are used to determine the port
configuration (down on the left for EIA-422, down on the right
for EIA-485).
17
MACH-Global Controller
MSet Configuration
MSet Configuration
The RC-Toolkit software MSet application is used to
prepare every controller for network communication. When
the installation and work station connection are completed
(as previously described), perform the following steps to
establish a network identity for the controller.
Basic Configuration
1. Launch the RC-Toolkit application and enter the password (June) to
reach the following screen.
18
MACH-Global Controller
MSet Configuration
2. Under PC Configuration, on the bottom left, choose the appropriate
connection method.
!
For Direct connection choose the Com Port used on the work
station.
19
MACH-Global Controller
MSet Configuration
3. Double click the MSet icon to reach the screen shown below.
20
MACH-Global Controller
MSet Configuration
4. Under Network Setup enter the
Network Address of the
controller being configured and
tell the software whether this is
the Last Panel on the
network.The Last Panel is the
highest numbered panel on an
EIA-485 network segment
5. Under Expansion choose the
number of In cards and Out
cards when there are one or
more I/O Expansion Cards
attached to the controller. Use the
arrows to set the number of
Expansion Cards being
configured on the MACHGlobal controller.
6. Under Port Setup choose the
controllers baud rates and port
configurations.
" Port A can be configured to
connect to a workstation or
communicate with BACnet
devices.
21
MACH-Global Controller
MSet Configuration
" Port B can be configured to
connect to a second
workstation, a modem, or to
communicate with BACnet
devices.The Modem button
opens the Modem
Configuration screen
allowing you to ensure the
parameters are correct. The
Dial-out settings are
typically used when calling
Alphanumeric pagers, where 7 Data bits, Even parity, and 1 Stop
bit must be set
" The Main, Sub-A, and Sub-B ports can be configured to
communicate with either Reliable Controls protocol or
BACnet MS/TP.
7. The IP Addresses button is used to specify the IP addresses for the
network. Please refer to the next section of this document.
8. Where BACnet devices are involved, use the BACnet Setup as
described below.
9. Note the Panel Time/Date are displayed on the upper right. Use the
Setup>Set Time/Date menu item to modify the time and date as
required.
10.Choose Send to transmit the changes to the controller. Choose Load
to check the accuracy of the changes.
11.Choose Done to exit the MSet application.
22
MACH-Global Controller
MSet Configuration
Ethernet Configuration
To configure the MACH-Global controller for Ethernet
operation select the IP Addresses button after connecting to
the controller as described in the previous section. The
following screen will be displayed.
23
MACH-Global Controller
MSet Configuration
" IP Addresses are 32 bit
numbers that are most
commonly represented in
dotted decimal notation
All panels that reside on a
(XXX.XXX.XXX.XXX). Each
main EIA-485 network must
decimal number represents
be assigned the same IP
eight bits of binary data and
address as the Ethernet
can have a decimal value of 0 - enabled panel they are
255. There are two situations
connected to.
with the Reliable Controls
MACH-System; either the
network will exist by itself (dedicated) or will be joined to an
existing network. In the case where the network is dedicated
the numbers can be anything so long as each panel on the
network is assigned a unique number, and the first of the
four numbers are not 0. The Reliable Controls convention,
for dedicated networks, is to assign the first three numbers
to 192.168.1 and the fourth number would be the assigned
panel number. When the network will be added to an existing
network you will need to obtain the IP addresses from the
Network Administrator. To remove an address from the table
change it to 0.0.0.0.
" The MAC Address column is a read only column that
identifies each device that is part of the network. The first
three groups of numbers in this address are assigned by
IEEE, and are Organizationally Unique Identifiers (OUI) for
each manufacturer. The numbers 00-02-D9 identify devices
manufactured by Reliable Controls. The fourth group
identifies the individual product and the remaining groups
detail the serial number of the product.
" Where a router is involved in the network you will need to
enter the IP address of the router in the Router row. The IP
address will be obtained from the Network Administrator.
24
MACH-Global Controller
MSet Configuration
" The address of the panel being setup must be entered in the
Self row.
!
25
MACH-Global Controller
MSet Configuration
BACnet Setup
The BACnet Setup is used when this panel will be
communicating with BACnet devices. Press the BACnet
Configuration button to reach the screen shown below:
26
MACH-Global Controller
MSet Configuration
!
27
MACH-Global Controller
Expansion Cards
Expansion Cards
A maximum of eight expansion cards can be attached to the
MACH-Global using the expansion card ports located at the
bottom of the controller. Each expansion card
accommodates 16 universal points that allow a maximum of
128 points of measurement and control directly onboard.
Any expansion card arrangement is permissible provided the
quantity and type of card are specified correctly in the MSet
configuration procedure described previously.
Input Expansion Cards
The MACH-Global input expansion card is a general
purpose universal input card that is designed for use with the
MACH-Global controller.
!
Each input can accept 0-5 VDC, dry contact with a 10 k pullup, or 4-20 mA.
Each input has two DIP switches for configuring what type
(0-5 VDC, thermistor/dry contact, or 4-20 mA) each input will
accept.
28
MACH-Global Controller
Expansion Cards
!
MGX-RC-B/C
Ribbon Cable
29
MACH-Global Controller
Expansion Cards
Output Expansion Cards
The MACH-Global output expansion card is a general
purpose universal output card that is designed for use with
the MACH-Global controller.
!
30
MACH-Global Controller
Expansion Cards
31
MACH-Global Controller
Expansion Cards
MACH-Global Output Expansion Card Wiring
32
MACH-Global Controller
SMART-Sensor Connection
SMART-Sensor Connection
The MACH-Global controller supports up to 16
SMART-Sensors. The SMART-Sensors are ideal for
measuring space/zone temperatures and providing user level
adjustments to temperature set points.
See the SMART-Sensor Quick Start Guide for installation
details.
SMART-Sensors
SS-DP
All cables to the first
SMART-Sensors are
to be voice cables
SSX
Voice Cable
Voice Cable
SMART-Sensors need to be
properly addressed using the
configurable internal jumpers.
MACH-Global
33
MACH-Global Controller
Networking
Networking
The Reliable Controls MACH-System can be networked in a
variety of ways, which are discussed in the Networking the
Reliable Controls MACH-System document.
When employing EIA-485 and EIA-422 networks with the
MACH-Global controller the next two sections are relevant.
Network Connections
The MACH-Global controller has four EIA-485 network
ports. Two of the ports (Main and AUX~EIA-485) can be
converted to EIA-422 operation.
EIA-485 Connection
To make an EIA-485 connection:
!
EIA-422 Connection
To make an EIA-422 connection (MAIN~MS/TP 1 and AUX
EIA-485/EIA-422):
!
34
MACH-Global Controller
Networking
!
\//\/\
\//\/\/\/\/\/\
/\
OFF
EOL
EOL
485 422
ON
OFF
485 422
NET
NET
NET
NET
AB+
MAIN ~
GND
MS/TP 1
AB+
/\/\/\/\/\/\/\/\/\/\
\//\/\
/\
/\/\/\/\/\
\//\/\
ON
AB+
MAIN ~
GND
MS/TP 1
AB+
/\/\/\/\/\
\//\/\ /\/\
/\/\/\/\
\//\/\/\
EOL
EOL
/\/\/\/\/\/\
\//\/\
\//\/\
AB+
MAIN ~
GND
MS/TP 1
AB+
Controller #3
\//\/\
Controller #1
GND
Shield
Grounded
EOL
EOL
ON
OFF
485 422
NET
NET
Network
Shields Connected
with Marrette
EIA-485 Connection
End-of-Line Termination
On all EIA-485 networks it is necessary to add end-of-line
(EOL) terminators to prevent reflected noise returning into the
network. The EOL terminators must be installed on the
controllers at the extremities of the network. To determine the
network extremities, calculate the maximum length between
any two controllers. The controllers at the extremities must be
terminated.
35
MACH-Global Controller
Networking
36
MACH-Global Controller
Technical Specifications
Technical Specifications
Specifications
Processor
Memory
2 MB non-volatile RAM
Firmware
1 MB Flash EEPROM
Software
RC-Studio
Time
Supply Voltage
Class 2, 24 VAC 75 VA
Connector
Indication
2 EIA-485/422 Serial
3 EIA-232 Serial
2 EIA-485
1 IEEE 802.3
10 Mbps
SMART-Net
Connectors
37
MACH-Global Controller
Technical Specifications
Ambient Limits
Operating Temperature
Shipping Temperature
Humidity
Dimensions
Weight
Cover
Mounting
38
MACH-Global Controller
Technical Specifications
Inputs
Quantity
Converter
12-bit A-D
Analogue Input
Digital Input
Dry contact
Input Impedance
Connectors
Overload protection
Led Indication
39
MACH-Global Controller
Technical Specifications
Outputs
Quantity
Converter
12-bit D-A
Analogue Output
0-12 VDC
Digital Output
0-12 VDC
Output Power
75 mA (maximum)
Overload Protection
Connectors
Power Supply
24 VAC 50 VA Class 2
40
MACH-Global Controller
Notes
41