MACH-Global

Controller
Quick Start Guide

Ideal for high-point


applications where unrestricted
programming and full data
acquisition are
required.
Seven standard communication
ports: Local PC port, 2ND Local PC
or Modem port, Subnetwork A port,
Subnetwork B port, Main network
port and two Auxiliary ports.

The MACH-Global
building controller is a
powerful, central-point,
programmable DDC
controller designed
to meet the needs of
large systems where
maximum accessibility
and network capability
are required.

SMART-Sensor support for up to


16 units; Ethernet Port for IP and
BACnet communication at 10
Mbaud.
Accommodates up to eight I/O
cards for a maximum of 128
monitor/control points.

...people and technology

you can rely onTM

2002 Reliable Controls Corporation

MACH-Global Controller

Document Conventions
Reliable ControlsTM Quick Start Guides use several
conventions to aid in your understanding of the material and
to make information more readily accessible. These
conventions are outlined below.
Software menu items will appear in bold faced type and follow
the form:
Start>Programs>Reliable ControlsTM>RC-StudioTM
Two symbols are used to draw your attention to items
warranting special attention:

The Attention Symbol is used to


draw your attention to concepts
and particular items that require
caution or thought before
implementation.

The Light Bulb is used to draw your


attention to information and
practices that will make your life
easier.

ii

2002 Reliable Controls Corporation

MACH-Global Controller

2002 Reliable Controls Corporation


All rights Reserved
Printed in Canada
This manual is for information purposes only. The contents and products
described are subject to change without notice. Reliable Controls
Corporation makes no representation with respect to this manual. In no
event shall Reliable Controls Corporation be liable for damages, direct or
incidental, arising out of or related to the use of this manual. No part of this
document may be reproduced or transmitted in any form or by any
means, without the express written permission of Reliable Controls
Corporation.
Reliable Controls Corporation
207-3375 Whittier Avenue
Victoria, BC, Canada V8Z 3R1
Tel: 250-475-2036
Fax: 250-475-2096
Toll Free: 1-877-457-9301
www.reliable-controls.com
BACnet is a registered trade mark of the American Society of Heating,
Refrigeration, Air Conditioning Engineers (ASHRAE).
MACH-Global, SMART-Sensor, SMART-Net, RC-Studio, and RCToolkit are trademarks of Reliable Controls Corporation.

iii

MACH-Global Controller

iv

2002 Reliable Controls Corporation

MACH-Global Controller

Contents
Package Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Getting Started. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . 3
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Physical Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Status LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Communication Ports . . . . . . . . . . . . . . . . . . . . . . . .
Port A. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Port B - 2nd Local PC/Modem . . . . . . . . . . . . . .
SMART-Net Port . . . . . . . . . . . . . . . . . . . . . . . .
AUX EIA-232 Port . . . . . . . . . . . . . . . . . . . . . . . .
MAIN~MS/TP 1. . . . . . . . . . . . . . . . . . . . . . . . . .
SUB-A~MS/TP 2. . . . . . . . . . . . . . . . . . . . . . . . .
SUB-B~MS/TP 3. . . . . . . . . . . . . . . . . . . . . . . . .
AUX EIA-485/EIA-422 . . . . . . . . . . . . . . . . . . . . .

11
13
15
16
16
16
17
17
17

MSet Configuration . . . . . . . . . . . . . . . . . . . . . . . . . .
Basic Configuration. . . . . . . . . . . . . . . . . . . . . . .
Ethernet Configuration . . . . . . . . . . . . . . . . . . . .
BACnet Setup . . . . . . . . . . . . . . . . . . . . . . . . . .

18
18
23
26

Expansion Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Input Expansion Cards . . . . . . . . . . . . . . . . . . . . 28
Output Expansion Cards . . . . . . . . . . . . . . . . . . 30

iv

2002 Reliable Controls Corporation

MACH-Global Controller

SMART-Sensor Connection . . . . . . . . . . . . . . . . . . 33
Networking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Network Connections . . . . . . . . . . . . . . . . . . . . . 34
End-of-Line Termination . . . . . . . . . . . . . . . . . . . 35
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . 37

2002 Reliable Controls Corporation

MACH-Global Controller

vi

2002 Reliable Controls Corporation

MACH-Global Controller

vi

2002 Reliable Controls Corporation

MACH-Global Controller

Package Contents

Package Contents
Your new MACH-Global package should include:
1. The MACH-Global controller.
2. A package containing four mounting screws.

2002 Reliable Controls Corporation

MACH-Global Controller

Getting Started

Getting Started
This guide identifies the physical installation procedure and
connection of the MACH-Global controller within a Reliable
Controls MACH-System.
There are many important concepts and practices that
accompany the use of the MACH-Global controller. This
document is intended to provide installation and setup
procedures for first time users. The most important concepts
that are crucial to the reliable operation of the MACH-Global
are introduced.
Ethernet Port
Fuse
Ethernet

Status

MAIN~MS/TP 1 Port

AB+
GND
AB+
EOL
EOL

ON

OFF

485

422

Power
Off
24VAC 60Hz 75VA

MAIN ~ MS/TP 1

TX

Link

Status

GND

NET
NET

SUB-A~MS/TP 2 Port

Status

EOL
EOL

SUB-B~MS/TP 3 Port

Port A

Status

ON

AB+

SUB-A ~ MS/TP 2

AB+

SUB-B ~ MS/TP 3

Port B
Status

ON

Power Connection
Port A - Workstation

PC ~ PTP

OFF

Status

EOL
EOL

On

Port B - Workstation/Modem

PC/Modem ~ PTP

OFF

SMART-Net

TM
SMART-Net Port

Status

AUX EIA-485/EIA-422 Port

AB+
GND
AB+
EOL
EOL

OUT

IN

485

422

AUX EIA-232 Port

AUX EIA-485/EIA-422

Status

AUX EIA-232

BUILDING CONTROLLER

NET
NET

Made in Canada www.reliable-controls.com 2002 Reliable Controls Corporation

IN 1-16
OUT 113-128

IN 33-48
OUT 81-96

IN 65-80
OUT 49-64

IN 97-112
OUT 17-32

IN 17-32
OUT 97-112

IN 49-64
OUT 65-80

IN 81-96
OUT 33-48

IN 113-128
OUT 1-16

Input/Output Expansion Card Ports

2002 Reliable Controls Corporation

MACH-Global Controller

Getting Started
Product Overview
The MACH-Global controller features:
!

Nine standard communication ports allowing for communication


with either BACnet or Reliable protocol.
" Port A - Local workstation port or BACnet PTP-A (EIA-232).
" Port B - Second local workstation/modem port or BACnet
PTP-B (EIA-232).
" SMART-NetTM - SMART-Sensor port.
" AUX EIA-232 - Auxiliary port.
" Ethernet - Ethernet port (10BaseT) using BACnet and/or
Reliable protocols.
" MAIN~MS/TP 1- Main network or BACnet MS/TP 1
network (EIA-485).
" SUB -A~MS/TP 2 - Subnetwork A or BACnet MS/TP 2
network (EIA-485).
" SUB-B~MS/TP 3 - Subnetwork B or BACnet MS/TP 3
network (EIA-485).
" AUX EIA-485/EIA-422 - Auxiliary port.

Eight expansion ports for Input/Output cards allowing up to 128


points of control.

HOA switches on output expansion cards with position feedback


to RC-Studio software.

Remote communications using Ethernet/Internet.

128 Control-BASIC programs, each with 2500 bytes.

256 Variables with standard and custom ranges available.

2002 Reliable Controls Corporation

MACH-Global Controller

Getting Started
!

64 PID controllers for closed loop control.

96 Trend Logs that can be used as the basis for long term data
storage.

128 Runtime Logs for tracking the on/off times of a digital point.

64 System Groups of up to 160 points per group display.

32 Weekly schedules, 8 Annual schedules

48 Variable arrays.

128 user passwords.

20 custom tables for creating custom input ranges.

16 custom units - 8 digital and 8 analogue engineering units.

2002 Reliable Controls Corporation

MACH-Global Controller

Installation

Installation
The MACH-Global controller is screw mounted vertically in
an enclosure.

Ground yourself before touching


the controller to avoid damaging
the electronics. Touch a grounded
metal surface to discharge static
electricity.

This controller is intended to be


installed in accordance with the
National Electric Code or the
Canadian Electric Code, Part 1,
and in a manner acceptable to the
local authority having jurisdiction.

1. Position the MACH-Global


controller in the enclosure,
leaving ample space for access to
the Ports.
2. Pre-drill four mounting screw
holes.
3. Mount the controller in the
enclosure. Physical dimensions
are shown on the following page.
4. Mount the Expansion Cards
vertically in the same enclosure.
Using the same enclosure is
necessary to minimize the
possibility of induced noise in the
cables.

5. Connect the Expansion Cards to the MACH-Global controller using


20-conductor ribbon cable with a maximum allowable cable length of
1 meter.
6. Mount all peripheral devices in a separate enclosure.

2002 Reliable Controls Corporation

MACH-Global Controller

Physical Dimensions

Physical Dimensions

2002 Reliable Controls Corporation

MACH-Global Controller

Power Wiring

Power Wiring
The MACH-Global controller is powered with a non-isolated
Class 2, 24 VAC or 24 VDC, 75VA power supply.
One or more controllers can be
powered from the same
source. Ensure that polarity is
Do not connect any peripheral
devices to the same power source the same when multiple
controllers share the same
as the MACH-Global controller.
power source. Networking
components may be damaged
if polarity is crossed.
Use only a Class 2 transformer.
Refer to the technical
specifications at the back of this
document.

1. Connect the hot wire to the


24 VAC connection at the top
right side of the controller.
2. Connect the neutral wire to the
GND connection at the top right
side of the controller.

Ground one side of the transformer


secondary for use as the Earth
ground.

3. Connect a wire from the second


GND connection to the earth
ground.

2002 Reliable Controls Corporation

MACH-Global Controller

Power Wiring

MACH-Global Power Wiring

2002 Reliable Controls Corporation

MACH-Global Controller

Status LEDs

Status LEDs
The MACH-Global controller has ten different status LEDs.
There is one general power status LED located at the top right
of the controller, and nine network status LEDs.
Ethernet Status
TX

Link

Main Network Status


Power Status
Subnetwork A Status

Port A Status

Subnetwork B Status

Port B Status

Auxilliary Network Status


AUX EIA-232 Status

2002 Reliable Controls Corporation

MACH-Global Controller

Status LEDs
MACH-Global Controller Status LED Indications
LED
Power
Status

Indication

Description

On steady

Power up indication.

Flickers

Normal operation; frequency changes


with scan rate.

On 1 second then off for


1 second

Memory check failure. Controller


requires operating system.

EIA-232
Ports

Off steady

Indicates no activity.

Blinking

Communication activity.

EIA-485
Ports

Off steady

Indicates no network activity, the


panel is awaiting communication.

On Steady

Port possesses token and is


transmitting on the network.

Blinking

Indicates networking with other


controllers on the network.

Ethernet TX

Flashes

Transmitting on Ethernet.

Ethernet
Link

On

Good connection to Ethernet Hub.

A binary counting pattern on EIA-485 LEDs indicates


that a clear panel operation is in progress. This
happens on power up if the controller determines that
its memory is corrupt, or when the Clear Panel
command in RC-Studio is executed.

10

2002 Reliable Controls Corporation

MACH-Global Controller

Communication Ports

Communication Ports
The MACH-Global controller provides a sophisticated
communication management system with nine independent
communication ports. These ports are all baud-rate
independent and can communicate up to 76.8 kbps on the
EIA-485 network and up to 57.6 kbps when connected to a
workstation.
MACH-Global Controller Communication Ports
Ethernet

MAIN~MS/TP 1

SUB-A~MS/TP 2
SUB-B~MS/TP 3

A /PTP 1- Workstation
B/PTP 2 - Workstation/Modem
SMART-NetTM

AUX EIA-485/EIA-422

2002 Reliable Controls Corporation

AUX EIA-232

11

MACH-Global Controller

Communication Ports
MACH-GlobalTM Controller Communication Ports
Port

Description

Port A

EIA-232 port for local PC communication. Can also be


configured as BACnet PTP A communication port.

Port B

EIA-232 port for either a second local PC or a modem, but


not both simultaneously. Can also be configured as
BACnet PTP B communication port

SMART-Net

SMART-Net port for connection of up to 16


SMART-Sensors.

AUX EIA-232

Auxiliary EIA-232 port for future expansion.

MAIN~MS/TP 1

EIA-485 main network port capable of directly networking


up to 32 main network controllers. Can be configured to
communicate with either Reliable Controls protocol or
BACnet MS/TP protocol.

SUB-A~MS/TP 2

EIA-485 subnetwork port capable of networking up to 124


controllers. Can be configured to communicate with either
Reliable Controls protocol or BACnet MS/TP protocol.

SUB-B~MS/TP 3

EIA-485 subnetwork port capable of networking up to 124


controllers. Can be configured to communicate with either
Reliable Controls protocol or BACnet MS/TP protocol.

AUX EIA-485/EIA422

Auxiliary EIA-485/EIA-422 port for future expansion.

Ethernet

10BaseT port for Ethernet/IP connection. Up to 125


controllers and operators may communicate on the
Ethernet connection. This port simultaneously supports
Reliable Controls protocol over IP, BACnet 8802-3, and
BACnet/IP.

12

2002 Reliable Controls Corporation

MACH-Global Controller

Communication Ports
Port A
Port A is an EIA-232 port used for local workstation
connection.
!

Can also be used for BACnet Point-To-Point communication.

Port must be configured using the MSet application found in


RC-Toolkit.

Features automatic switching between Reliable Controls


protocol and BACnet protocol requiring minimal setup.
" If the port is set as a BACnet port then the port will attempt
to initiate a BACnet connection. If successful the
communication will proceed as indicated by the LED
flashing at least every 15 seconds.
" If the attempt to initiate a BACnet connection is
unsuccessful this port will revert to a Reliable Controls
protocol port.
" Whether or not the port is set as a BACnet port, if a
connected device attempts to initiate a BACnet connection
the port will respond appropriately by establishing the
BACnet connection.
" Upon the termination of BACnet communications the port
reverts back to Reliable Controls protocol.

2002 Reliable Controls Corporation

13

MACH-Global Controller

Communication Ports
Use the CC-C1-B/C computer cable to connect a
workstation serial port to local port A or local port B on the
MACH-Global controller.
CC-C1-B/C Cable

Operator Workstation

The EIA-232 status LED flashes to


indicate activity between the
workstation and the
MACH-Global controller.

CC-C1-B/C Computer Cable


( closeup )

14

2002 Reliable Controls Corporation

MACH-Global Controller

Communication Ports
Port B - 2nd Local PC/Modem
Port B is an EIA-232 port used for either local workstation
connection or modem connection. This port features
automatic switching between Reliable Controls protocol
and BACnet protocol as described in the previous section
(Port A).
Use the CC-M1-B/C modem cable to connect the
MACH-Global controller to a modem

The EIA-232 status light flashes to


indicate activity between the
modem and the MACH-Global
controller.
Modems must be purchased from
Reliable Controls to ensure
proper operation.

Do not connect a modem and a


second workstation to the
MACH-Global controller
simultaneously

2002 Reliable Controls Corporation

Modem
CC-M1-B/C Cable

CC-M1-B/C Modem Cable


( closeup )

15

MACH-Global Controller

Communication Ports
SMART-Net Port
The SMART-Net port is capable of networking up to 16
SMART-Sensors.
AUX EIA-232 Port
The Auxiliary EIA-232 port has been included for future
expansion
MAIN~MS/TP 1
MAIN~MS/TP 1 is an EIA-485 main network port capable of
networking directly to 32 main network controllers.
Alternatively, this port can be configured to communicate with
BACnet devices. Use the MSet tool in RC-Toolkit to
configure the port to use BACnet MS/TP 1.
MAIN~MS/TP 1 can also be configured as an EIA-422 port.
To configure MAIN~MS/TP 1 as an EIA-422 port, the DIP
switches beside the port (Net) must be toggled down on the
left side.
For details on EIA-485 configuration, please refer to the
Network Connection section of this document.

16

2002 Reliable Controls Corporation

MACH-Global Controller

Communication Ports
SUB-A~MS/TP 2
SUB-A~MS/TP 2 is an EIA-485 port capable of hosting up to
124 subnetwork controllers.
Alternatively, this port can be configured to communicate
with BACnet devices. Use the MSet tool in RC-Toolkit to
configure the port to use BACnet MS/TP 2.
SUB-B~MS/TP 3
SUB-B~MS/TP 3 is an EIA-485 port capable of hosting up to
124 subnetwork controllers.
Alternatively, this port can be configured to communicate
with BACnet devices. Use the MSet tool in RC-Toolkit to
configure the port to use BACnet MS/TP 3.
AUX EIA-485/EIA-422
AUX EIA-485/EIA-422 is an auxiliary port capable of
communicating with either EIA-485 or EIA-422. DIP switches
(Net) beside the port are used to determine the port
configuration (down on the left for EIA-422, down on the right
for EIA-485).

2002 Reliable Controls Corporation

17

MACH-Global Controller

MSet Configuration

MSet Configuration
The RC-Toolkit software MSet application is used to
prepare every controller for network communication. When
the installation and work station connection are completed
(as previously described), perform the following steps to
establish a network identity for the controller.
Basic Configuration
1. Launch the RC-Toolkit application and enter the password (June) to
reach the following screen.

18

2002 Reliable Controls Corporation

MACH-Global Controller

MSet Configuration
2. Under PC Configuration, on the bottom left, choose the appropriate
connection method.
!

For Direct connection choose the Com Port used on the work
station.

For TCP/IP connection enter the IP address of the controller (see


Ethernet Configuration).

For Modem connection the screen will appear as seen below.


You will need to provide the phone number to dial. The three
default modem strings shown below can be changed if required.

2002 Reliable Controls Corporation

19

MACH-Global Controller

MSet Configuration
3. Double click the MSet icon to reach the screen shown below.

20

2002 Reliable Controls Corporation

MACH-Global Controller

MSet Configuration
4. Under Network Setup enter the
Network Address of the
controller being configured and
tell the software whether this is
the Last Panel on the
network.The Last Panel is the
highest numbered panel on an
EIA-485 network segment
5. Under Expansion choose the
number of In cards and Out
cards when there are one or
more I/O Expansion Cards
attached to the controller. Use the
arrows to set the number of
Expansion Cards being
configured on the MACHGlobal controller.
6. Under Port Setup choose the
controllers baud rates and port
configurations.
" Port A can be configured to
connect to a workstation or
communicate with BACnet
devices.

2002 Reliable Controls Corporation

The MACH-Global controller is


designed to reside on a main
network. The MACH-Global
controller cannot reside on a
subnetwork.

If the MACH-Global controller is


being added to an existing 10
Mbps, ISO 8802.3, IP network you
will need to obtain the Host IP
Addresses from the network
administrator.

Network Addresses need to be


unique to each panel on the
network. Duplications will cause
erratic network performance.

21

MACH-Global Controller

MSet Configuration
" Port B can be configured to
connect to a second
workstation, a modem, or to
communicate with BACnet
devices.The Modem button
opens the Modem
Configuration screen
allowing you to ensure the
parameters are correct. The
Dial-out settings are
typically used when calling
Alphanumeric pagers, where 7 Data bits, Even parity, and 1 Stop
bit must be set
" The Main, Sub-A, and Sub-B ports can be configured to
communicate with either Reliable Controls protocol or
BACnet MS/TP.
7. The IP Addresses button is used to specify the IP addresses for the
network. Please refer to the next section of this document.
8. Where BACnet devices are involved, use the BACnet Setup as
described below.
9. Note the Panel Time/Date are displayed on the upper right. Use the
Setup>Set Time/Date menu item to modify the time and date as
required.
10.Choose Send to transmit the changes to the controller. Choose Load
to check the accuracy of the changes.
11.Choose Done to exit the MSet application.

22

2002 Reliable Controls Corporation

MACH-Global Controller

MSet Configuration
Ethernet Configuration
To configure the MACH-Global controller for Ethernet
operation select the IP Addresses button after connecting to
the controller as described in the previous section. The
following screen will be displayed.

The screen is organised in the areas discussed below:


!

The Address Table is the collection of IP addresses necessary


for this panel to network. The table has a column for the IP
address of each panel on the network and a column that will
display the MAC Address of each device on the network.

2002 Reliable Controls Corporation

23

MACH-Global Controller

MSet Configuration
" IP Addresses are 32 bit
numbers that are most
commonly represented in
dotted decimal notation
All panels that reside on a
(XXX.XXX.XXX.XXX). Each
main EIA-485 network must
decimal number represents
be assigned the same IP
eight bits of binary data and
address as the Ethernet
can have a decimal value of 0 - enabled panel they are
255. There are two situations
connected to.
with the Reliable Controls
MACH-System; either the
network will exist by itself (dedicated) or will be joined to an
existing network. In the case where the network is dedicated
the numbers can be anything so long as each panel on the
network is assigned a unique number, and the first of the
four numbers are not 0. The Reliable Controls convention,
for dedicated networks, is to assign the first three numbers
to 192.168.1 and the fourth number would be the assigned
panel number. When the network will be added to an existing
network you will need to obtain the IP addresses from the
Network Administrator. To remove an address from the table
change it to 0.0.0.0.
" The MAC Address column is a read only column that
identifies each device that is part of the network. The first
three groups of numbers in this address are assigned by
IEEE, and are Organizationally Unique Identifiers (OUI) for
each manufacturer. The numbers 00-02-D9 identify devices
manufactured by Reliable Controls. The fourth group
identifies the individual product and the remaining groups
detail the serial number of the product.
" Where a router is involved in the network you will need to
enter the IP address of the router in the Router row. The IP
address will be obtained from the Network Administrator.

24

2002 Reliable Controls Corporation

MACH-Global Controller

MSet Configuration
" The address of the panel being setup must be entered in the
Self row.
!

Under TCP/IP Setup the Subnet Mask, and MTU (Maximum


Transmission Unit) are typically obtained from the Network
Administrator. If this is a dedicated network for the Reliable
Controls MACH-System the subnet mask should be set to
0.0.0.0 and the MTU set to 1500.
" The Subnet Mask is used to identify panels that must be
accessed via a router.
" The MTU (Maximum Transmission Unit) is used to determine
the maximum packet size when sending data.

Use the file management buttons on the lower right. Choose


Send to send the changes to the panel you are connected to.
Use Load to verify the changes were sent correctly.

Once the IP Addresses for all panels on the network have


been entered use File Save to save the table for use with
other Ethernet enabled panels (ETHER-Link,
MACH-Global, MACH-Net, and MODBUS-Link). Each of
these panels has a table containing the IP addresses of all the
other panels on the network. These tables must be
configured in each panel.

After configuring the first panel and


saving the table, MSet the next
panel and use the Get File
command to import the table.

Panels that are connected directly


to the Ethernet require individually
different (unique) IP addresses.

2002 Reliable Controls Corporation

25

MACH-Global Controller

MSet Configuration
BACnet Setup
The BACnet Setup is used when this panel will be
communicating with BACnet devices. Press the BACnet
Configuration button to reach the screen shown below:

The Device Number, Ethernet Network #, B/IP Network #,


and MS/TP 1 Network # will default to the numbers derived
from the Network Address for the MACH-Global controller. The
numbers are required by other BACnet devices to initiate
services on data within the MACH-Global controller.

The Port A PTP Password is optional and is used to validate


handshaking between the MACH-Global controller and other
BACnet devices using PTP.

The Port B PTP Password is optional and is used to validate


handshaking between the MACH-Global controller and other
BACnet devices using PTP.

26

2002 Reliable Controls Corporation

MACH-Global Controller

MSet Configuration
!

Use the BACset tool in RCToolkitTM to map services on


data residing in external
BACnet devices.

2002 Reliable Controls Corporation

Controllers that are connected to


the MACH-Global controller via
EIA-485 need the same IP
address as the MACH-Global
controller.

27

MACH-Global Controller

Expansion Cards

Expansion Cards
A maximum of eight expansion cards can be attached to the
MACH-Global using the expansion card ports located at the
bottom of the controller. Each expansion card
accommodates 16 universal points that allow a maximum of
128 points of measurement and control directly onboard.
Any expansion card arrangement is permissible provided the
quantity and type of card are specified correctly in the MSet
configuration procedure described previously.
Input Expansion Cards
The MACH-Global input expansion card is a general
purpose universal input card that is designed for use with the
MACH-Global controller.
!

The number of expansion cards is configured using the MSet


tool in RC-Toolkil.

Each input can be configured as either digital (binary) or


analogue (modulating) or as a pulse counter.

Each input can be connected to a two-wire input device.

Each input can accept 0-5 VDC, dry contact with a 10 k pullup, or 4-20 mA.

Each input has two DIP switches for configuring what type
(0-5 VDC, thermistor/dry contact, or 4-20 mA) each input will
accept.

A maximum of eight input expansion cards can be connected to


one MACH-Global controller.

28

2002 Reliable Controls Corporation

MACH-Global Controller

Expansion Cards
!

Each input has an LED indicator that displays a brightness


proportional to the input signal level.

Input expansion cards are connected to the controller from Left


to Right, with inputs 1 to 16 in port 1 and inputs 17 to 32 in port
2 etc.

Power for the input expansion cards is supplied by the


MACH-Global controller via the ribbon cables used for
connection.

Wire the input signal to the


positive terminal (+), and the
input common to the
corresponding negative
terminal (-).

Mount all input expansion cards in


the same enclosure as the MACHGlobal Controller.

The maximum voltage resolved by


an input is 5 VDC.

MGX-RC-B/C
Ribbon Cable

2002 Reliable Controls Corporation

29

MACH-Global Controller

Expansion Cards
Output Expansion Cards
The MACH-Global output expansion card is a general
purpose universal output card that is designed for use with
the MACH-Global controller.
!

MACH-Global expansion cards are powered with a 24 VAC


50 VA power supply. (Requires 30 VA nominal for 16 outputs @
20 mA each).

The number of expansion cards is configured using the MSet


tool in RC-Toolkit.

Universal outputs can be configured as either digital (binary) or


analogue (modulating). (0-12 VDC, 75 mA each)

Each output can be connected to a two-wire output device (relay,


actuator).

Every output features a Hand/Off/Auto switch for convenient


override in the field. The position of the HOA switch is fed back to
RC-Studio for viewing.

A maximum of eight output expansion cards can be connected


to one MACH-Global controller.

Output expansion cards are connected to the controller from


Right to Left, with outputs 1 to 16 in port 8 and output 17 to 32 in
port 7 etc.

Each output expansion card features an onboard power switch.

30

2002 Reliable Controls Corporation

MACH-Global Controller

Expansion Cards

Mount all output expansion cards in


the same enclosure as the
MACH-Global controller.

Wire the input signal to the


positive terminal (+), and the
input common to the
corresponding negative
terminal (-).

Keep ribbon cables as short as


possible to reduce interference.

The maximum voltage provided


by an output is 12 VDC. The
maximum current sourced by an
output is 75 mA.

Only consider relays approved by


Reliable Controls when selecting
relays for output connection.

2002 Reliable Controls Corporation

31

MACH-Global Controller

Expansion Cards
MACH-Global Output Expansion Card Wiring

32

2002 Reliable Controls Corporation

MACH-Global Controller

SMART-Sensor Connection

SMART-Sensor Connection
The MACH-Global controller supports up to 16
SMART-Sensors. The SMART-Sensors are ideal for
measuring space/zone temperatures and providing user level
adjustments to temperature set points.
See the SMART-Sensor Quick Start Guide for installation
details.

SMART-Sensors
SS-DP
All cables to the first
SMART-Sensors are
to be voice cables

Ensure that the SMART-Sensor


voice cable is connected to the
SMART-Net port and not the
PC/Modem port.

All cables to the secondary SMART-Sensors are to be data cables

SSX

Voice Cable

Voice Cable

SMART-Sensors need to be
properly addressed using the
configurable internal jumpers.
MACH-Global

2002 Reliable Controls Corporation

33

MACH-Global Controller

Networking

Networking
The Reliable Controls MACH-System can be networked in a
variety of ways, which are discussed in the Networking the
Reliable Controls MACH-System document.
When employing EIA-485 and EIA-422 networks with the
MACH-Global controller the next two sections are relevant.
Network Connections
The MACH-Global controller has four EIA-485 network
ports. Two of the ports (Main and AUX~EIA-485) can be
converted to EIA-422 operation.
EIA-485 Connection
To make an EIA-485 connection:
!

Connect one conductor to the A terminal (also known as


negative) and the other to the B terminal (also known as
positive). Maintain the same polarity for the whole network
segment.

When shielded cable is used, ground the shielding in one place


only and join the shields together using a wire nut (marrette)
where appropriate.

EIA-422 Connection
To make an EIA-422 connection (MAIN~MS/TP 1 and AUX
EIA-485/EIA-422):
!

34

MAIN~MS/TP 1 - toggle the Net DIP switches down on the left


side.

2002 Reliable Controls Corporation

MACH-Global Controller

Networking
!

AUX~EIA-485/EIA-422 - toggle the Net DIP switches down on


the left side.

Both MAIN~MS/TP 1 and AUX EIA485/EIA-422 ports have five


terminals. Upper A and B are receiver inputs and lower A and B
are transmitter outputs.

Try to Daisy-Chain the network cable as shown below. Avoid


Star and Stub connections.
Controller #2

\//\/\

\//\/\/\/\/\/\
/\

OFF

EOL
EOL

485 422

ON

OFF

485 422

NET
NET

NET
NET

AB+
MAIN ~
GND
MS/TP 1
AB+

/\/\/\/\/\/\/\/\/\/\
\//\/\
/\

/\/\/\/\/\
\//\/\

ON

AB+
MAIN ~
GND
MS/TP 1
AB+

/\/\/\/\/\
\//\/\ /\/\

/\/\/\/\
\//\/\/\

EOL
EOL

/\/\/\/\/\/\
\//\/\

\//\/\

AB+
MAIN ~
GND
MS/TP 1
AB+

Controller #3

\//\/\

Controller #1

GND

Shield
Grounded

EOL
EOL

ON

OFF

485 422
NET
NET

Network
Shields Connected
with Marrette

EIA-485 Connection
End-of-Line Termination
On all EIA-485 networks it is necessary to add end-of-line
(EOL) terminators to prevent reflected noise returning into the
network. The EOL terminators must be installed on the
controllers at the extremities of the network. To determine the
network extremities, calculate the maximum length between
any two controllers. The controllers at the extremities must be
terminated.

2002 Reliable Controls Corporation

35

MACH-Global Controller

Networking

Daisy-chain the network wiring to


avoid network splits.

On all EIA-485 ports of the


MACH-Global controller
there are two EOL DIP switches
located to the right of the
network terminals. Toggle the
DIP switches down on the right
side to enable the EOL
terminating resistance.

Main EOL DIP Switch

SUB-A EOL DIP Switch


SUB-B EOL DIP Switch

AUX EOL DIP Switch

36

2002 Reliable Controls Corporation

MACH-Global Controller

Technical Specifications

Technical Specifications
Specifications
Processor

16-bit embedded microprocessor

Memory

2 MB non-volatile RAM

Firmware

1 MB Flash EEPROM

Software

RC-Studio

Time

Real-time clock (48 hr. backup)


Power

Supply Voltage

Class 2, 24 VAC 75 VA

Connector

2 pole, 12 AWG maximum

Indication

One LED, Green, Main Status


Communications

2 EIA-485/422 Serial

76.8 kbps maximum

3 EIA-232 Serial

57.6 kbps maximum

2 EIA-485

76.8 kbps maximum

1 IEEE 802.3

10 Mbps

SMART-Net

RJ-11 connector, 6 pin

Connectors

5 pin removable, 3 pin removable,


2 pin removable, RJ-45, RJ-11

2002 Reliable Controls Corporation

37

MACH-Global Controller

Technical Specifications

Ambient Limits
Operating Temperature

-18C to 49C (0F to 120F)

Shipping Temperature

-40C to 60C (-20F to 140F)

Humidity

10% to 90% RH non-condensing


Physical Specifications

Dimensions

31.4 cm L x 19.90 cm W x 3.8 cm D


(12.38 L x 7.8 W x 1.25 D)

Weight

0.6 kg (1.5 lb)

Cover

Cold-rolled steel, powder coated

Mounting

Screw mounted with #6 holes


30.0 cm L x 18.5 cm W (11.8 L x
7.25 W)

38

2002 Reliable Controls Corporation

MACH-Global Controller

Technical Specifications

Inputs
Quantity

Eight possible ports, each addressing


16 points

Converter

12-bit A-D

Analogue Input

0-5 VDC, 4-20 mA, 10 k pull-up

Digital Input

Dry contact

Input Impedance

0-5VDC @ 15 k, 4-20 mA @ 250 ,


Thermistor @ 10 k

Connectors

Two 16-pole removable connectors for


inputs, one 20-pole ribbon cable
header

Overload protection

24 VAC over-voltage protection

Led Indication

1 LED indicator for each input

2002 Reliable Controls Corporation

39

MACH-Global Controller

Technical Specifications

Outputs
Quantity

Eight possible ports each addressing


16 points

Converter

12-bit D-A

Analogue Output

0-12 VDC

Digital Output

0-12 VDC

Output Power

75 mA (maximum)

Overload Protection

24 VAC over-voltage and short


protection

Connectors

Two 16-pole removable connector for


outputs, one 20-pole ribbon cable
header, 2 pole power connector

Power Supply

24 VAC 50 VA Class 2

40

2002 Reliable Controls Corporation

MACH-Global Controller

Notes

2002 Reliable Controls Corporation

41

MACH-Global Controller

MACH-Global Rev 1.3 PLC 10/02

207-3375 Whittier Ave., Victoria, BC, Canada, V8Z 3R1