GENERAL REPORT
Country
Customer Name
INDONESIA TOTAL E&P
PD
Customer
Package
Number
Tag
S/N
70231
CG01823
TEG 9610
70232
TEG 9620
CG01824
FIELD REP
Andika Pratama
Yusup Armansyah
Site Name
NPU Site
Engine
Package
S/N
Starts
Report Dates
November, 2014
CSA Numbers
Package
Hours
Engine
Hours
Service Order
No.
1072H
PT. Indoturbine
1/11
FSR NAME
Andika Pratama
Yusup Armansyah
I. Purpose of visit
The purpose of visit is Technical Services for HMI Upgrade Centaur 50 (TEG 9610 & 9620) at NPU Total E&P Indonesie
II. Engine Specification:
PT.Indoturbine
2/11
FSR NAME
Andika Pratama
Yusup Armansyah
4 November, 2014
5 November, 2014
6 November, 2014
7 November, 2014
Pre Job Meeting with Project Engineer and Control System Total E&P
Programming additional rung PLC 5 as per mandatory for Upgrade new HMI
Start to SAT Check functional test for communication throught existing PLC program for TEG 9610
8 November, 2014
Pre Job Meeting with Project Engineer and Control System Total E&P
Continue Commisioning Functional Test with Instrument Team
Commisioning done, continue with Start Engine as per sequence
9 November, 2014
Pre Job Meeting with Project Engineer and Control System Total E&P
Give a short training for new navigation HMI TT4000 ver 5 as per Customer request
Completed Handover Document and Dosier
10 November, 2014
PT.Indoturbine
3/11
FSR NAME
Andika Pratama
Yusup Armansyah
PT. Indoturbine
Distributor of Solar Turbines
PT.Indoturbine
4/11
FSR NAME
Andika Pratama
Yusup Armansyah
Check all existing parts working prperly before HMI system installed on panel
PT.Indoturbine
5/11
FSR NAME
Andika Pratama
Yusup Armansyah
Perform Commissioning as per procedure. Give a short training for operating new HMI with TT4000 ver 5
procedure
New wire configuration on TCP TEG 9610 for new HMI display with TT4000 ver 5
6/11
FSR NAME
Andika Pratama
Yusup Armansyah
Found new program on HMI TT4000 ver 5 start crank button fuction visibilty was disable. Change with
new configuration to perform proper function due to PLC5 program.
Found new program on HMI TT4000 ver 5 stop crank button fuction visibilty was disable. Change with
new configuration to perform proper function due to PLC5 program.
PT.Indoturbine
7/11
FSR NAME
Andika Pratama
Yusup Armansyah
PT.Indoturbine
8/11
FSR NAME
Andika Pratama
Yusup Armansyah
PT.Indoturbine
9/11
FSR NAME
Andika Pratama
Yusup Armansyah
Added Logix and make new rung on ladder 11 rung 26 and change addres
PT.Indoturbine
10/11
FSR NAME
Andika Pratama
Yusup Armansyah
PT.Indoturbine
11/11