Beruflich Dokumente
Kultur Dokumente
SERVICIO PARTICULAR
LOTES
40
CALIFICACION
ELECTRICA (kW)
POTENCIA INSTALADA
(KW)
0.2
8
Sector de Distribucin Tpico 5 - Rural
F.S
MAX. DEMANDA
(KW)
0.83
6.64
CARGAS ESPECIALES
CANTIDAD
CALIFICACION
ELECTRICA (kW)
POTENCIA
INSTALADA (KW)
F.S
MAX. DEMANDA
(KW)
0.4
0.4
0.4
0.7
0.7
0.7
1.2
1.2
1.2
0.25
0.35
0.35
0.5
0.5
0.5
3.15
PUNTOS DE ILUMINACION
CMAP
KALP
N.U
P.L
283.5
6.3
40
60
CMAP
283.5
N HORAS
360
KWh
(KWh/usuario*mes)
Lotes
(w)
P.N.L
60
KALP(SDT-5)
6.3
N.U
40
PUNTOS DE ILUMINACION
CE
5
13.13
ALUMBRADO PUBLICO
# DE LAMPARA
14
F.S
1
M.DEMANDA KW
RESUMEN DE CARGAS
MAX. DEMANDA
(KW)
FACTOR DE
POTENCIA
MAX.
DEMANDA
(KVA)
SERVICIO PARTICULAR
CARGAS ESPECIALES
ALUMBRADO PUBLICO
6.64
3.15
0.84
1
1
0.9
6.64
3.15
0.933
P . LAMPARA
0.06
P.TOT
0.84
0.84
TOTAL
10.63
CON FACTOR DE RESERVA
10.72
13.94
14
MXIMA DEMANDA
13.94
KVA
RESUMEN
UND. KV
UND.KVA
9.79
9.79
ALUMBRADO PBLICO
0.84
0.933
GE
FAC
FORMACIN
1
2
3
4
5
6
7
8
9
10
11
3x35+16/25
3x25+16/25
3x16+16/25
3x35/25
3x25/25
3x16/25
2x35+16/25
2x25+16/25
2x16+16/25
2x16/25
1x16/25
RESISTENCIA DEL
CONDUCTOR DE FASE
A 20 C
A 40 C
0.868
0.929
1.200
1.285
1.910
2.045
0.868
0.929
1.200
1.285
1.910
2.045
0.868
0.929
1.200
1.285
1.910
2.045
1.910
2.045
1.910
2.045
RESISTENCIA DEL
CONDUCTOR DE
A 20 C
A 40 C
1.910
2.045
1.910
2.045
1.910
2.045
1.910
2.045
1.910
2.045
1.910
2.045
-
FACTORES DE CABLES
RESISTENCIA DEL
CONDUCTOR NEUTRO
A 20 C
A 40 C
1.38
1.478
1.38
1.478
1.38
1.478
1.38
1.478
1.38
1.478
1.38
1.478
1.38
1.478
1.38
1.478
1.38
1.478
1.38
1.478
1.38
1.478
REACTANCIA INDUCTIVA
(0/Km)
XL(30)
XL(10)
0.094
0.123
0.100
0.116
0.110
0.110
0.091
0.095
0.103
0.086
0.114
0.093
0.109
0.096
0.096
0.096
0.094
3.538
K(440-220 V)
3.78
3.776
3.765
3.765
K(220 VAP)
3.272
3.272
3.272
3.272
3.272
3.272
3.272
3.272
3.272
CAPACIDAD DE CORRIENTE
A 40 C (A)
Cond. Fase Cond. A.P.
64
102
64
83
64
64
102
83
64
64
102
64
83
64
64
64
-
CIRCUITO I
N de Lotes
Cargas Especiales
Potencia (kW)
0
1
2
2.1
3
4
5
5.1
6
7
7.1
8
8.1
9
9.1
10
A
0
4
0
4
2
0
0
4
5
2
3
3
3
0
4
2
4
0
0
0
0
1
2
0
0
0
0
0
0.664
0
0.664
0.682
1.7
0
0.664
0.83
0.332
0.498
0.498
0.498
0
0.664
0.332
1.764
Lotes totales
0
0
0
0
2
40
3.538
3.538
3.538
3.538
3.538
3.538
3.538
3.538
3.538
3.538
3.538
3.538
3.538
3.538
3.538
3.538
3.538
3
14.37
17.65
28.09
28.76
37.91
5.23
24.83
22.87
24.18
43.12
18.95
39.53
13.07
18.95
60.78
33.32
S CORRIENTE (A)
22.25
18.241
16.732
1.509
15.223
13.673
9.809
1.509
8.3
6.414
1.132
4.527
1.132
2.264
1.509
0.755
4.009
440/220 V
Voltaje (V)
S Voltaje (V)
% DV
0.2362
0.9274
1.0448
0.15
1.549
1.8339
0.1815
0.1326
0.6716
0.5487
0.1727
0.3035
0.1583
0.1047
0.1012
0.1624
0.4726
0.2362
1.1636
2.2084
2.3584
3.7574
5.5913
5.7728
5.9054
6.4444
6.9931
7.1658
7.2966
7.4549
7.4013
7.5025
7.5637
0.7088
0.11%
0.53%
1.00%
1.07%
1.71%
2.54%
2.62%
2.68%
2.93%
3.18%
3.26%
3.32%
3.39%
3.36%
3.41%
3.44%
0.32%
Max. Cada
3.44%
Luminarias totales
CADA DE TENSIN EN
LAMPARA 50 W
LAMPARA 70 W
LAMPARA 150 W
Potencia (kW)
1
0
1
1
1
1
0
1
1
1
1
1
1
0
1
1
1
0.06
0
0.06
0.06
0.06
0.06
0
0.06
0.06
0.06
0.06
0.06
0.06
0
0.06
0.06
0.06
14
Factor de Caida k
Longitud (m)
0.78
0.66
0.66
0.06
0.54
0.48
0.42
0.06
0.36
0.3
0.06
0.24
0.06
0.12
0.06
0.06
0.06
2x16+16/25
2x16+16/25
2x16+16/25
2x16+16/25
2x16+16/25
2x16+16/25
2x16+16/25
2x16+16/25
2x16+16/25
2x16+16/25
2x16+16/25
2x16+16/25
2x16+16/25
2x16+16/25
2x16+16/25
2x16+16/25
2x16+16/25
3.272
3.272
3.272
3.272
3.272
3.272
3.272
3.272
3.272
3.272
3.272
3.272
3.272
3.272
3.272
3.272
3.272
3
14.37
17.65
28.09
28.76
37.91
5.23
24.83
22.87
24.18
43.12
18.95
39.53
13.07
18.95
60.78
33.32
Corriente (A)
Voltaje (V)
S Voltaje (V)
% DV
3.545
3
3
0.273
2.455
2.182
1.909
0.273
1.636
1.364
0.273
1.091
0.273
0.545
0.273
0.273
0.273
0.0348
0.1411
0.1733
0.0251
0.231
0.2707
0.0327
0.0222
0.1224
0.1079
0.0385
0.0676
0.0353
0.0233
0.0169
0.0543
0.0298
0.0348
0.1759
0.3492
0.3743
0.5802
0.8509
0.8836
0.9058
1.006
1.1139
1.1524
1.1815
1.2168
1.2048
1.2217
1.4778
0.0646
0.02%
0.08%
0.16%
0.17%
0.26%
0.39%
0.40%
0.41%
0.46%
0.51%
0.52%
0.54%
0.55%
0.55%
0.56%
0.67%
0.03%
Max. Cada
0.67%