Beruflich Dokumente
Kultur Dokumente
ABSTRACT
Internal partial discharge of large power transformers,
whether detected during acceptance testing, by dissolved gas analysis (DGA), or by field measurements,
often indicate incipient or ongoing degradation of the
insulation system.
The internal structure of large power transformers is
very complex. Opening a transformer for diagnostic
measurements is time consuming and very costly. Thus,
typically, diagnostic measurements are limited to the
accessible terminals and the tank wall. Time constraints
and cost considerations further reduce the applicable
techniques.
Strategies and their limitations to identify the location
of partial discharge using the analysis of shape and
phase position of partial discharge pattern under different excitation configurations are discussed. Using an
eight-channel partial discharge detector with parallel
acquisition on all channels minimizes the efforts to
compare the results derived from different taps. Further,
analyzing the electrical signals in frequency as well as
in time domain offers additional indications concerning
the location.
Finally, acoustic signals captured at the tank wall narrow down the area of partial discharge activity. Especially for low level discharge activity acquiring the
phase resolved pattern of the acoustically acquired signal as well as using averaging techniques in time do main simplifies finding the location within the transformer.
PARTIAL DISCHARGE IN LARGE POWER
TRANS FORMERS
The oil-paper insulation system used in large power
transformers does tolerate partial discharge activity to
some extend, other than polymeric insulation systems, such as Polyethylene, for instance. However,
despite some self-healing effects under partial discharge activity, ongoing partial discharge deteriorates
the insulation system and, thus, shall be avoided for
normal operation conditions.
Generally, large power transformers offer the highest
complexity if compared with other high voltage substation equipment. Especially, if equipped with tert iary windings and load tap changers (LTC), the high
internal complexity of the winding and the required
connections and cable assemblies must be considered.
Here, the differential electrical field between con-
In case the agreed acceptance level of partial discharge activity is exceeded, the source, nature, and
location of the partial discharge activity must be
evaluated.
The very first measure to learn about the location is
to compare the ratio of the levels detected at the different taps against the ratio found during the calibration and as recorded with the cross-coupling matrix
[2]. If the ratio compares well with the calibration
ratio, the location of the partial discharge activity
will be close to this tap.
Simply comparing the magnitudes and ratio, while
considering the transformer's winding scheme, will
also give early indications in case of discharge between high voltage and low voltage windings, such as
found at or within barriers, for instance.
ANALYSIS IN PHASE DOMAIN
However, besides simply comparing levels and ratio,
the analysis of the amplitude-phase-height distrib ution or -q-n pattern provides additionally an unde rstanding of the interfaces being involved with the
partial discharge activity. Furthermore, analyzing this
-q-n pattern offers information concerning the geometry of the area that produces the partial discharge
activity. Extensive research on the interpretation of
such partial discharge pattern was made since the
required instruments firstly became commercially
available in the early 90ies [4].
As an example, Fig. 3 shows partial discharge activity of several gas inclusions in epoxy resin, as it can
happen in case air bubbles are trapped in epoxy glue.
Similar pattern can be observed in case vacuum is not
correctly pulled and the transformer is not suff iciently processed when filling the tank with oil.
In case a partial discharge pattern is symmetrically in
its phase distribution for the positive and the negative
half cycle, as with Fig. 3, the partial discharge source
is also symmetrically within the insulation system.
Here, the discharge process is independent of the po larity and, hence, the pattern reflects this polarity
independence.
Partial discharge signals traveling large power transformer face reflection and attenuation. Further, since
a power transformer is a large object if comparing the
available signal bandwidth and the signal speed, the
influence of the travel time can observed and used for
analysis.
Signals being generated close to the bushing tap produce an impulse with a short rise time and not much
ringing. Likewise, pulses travel a cleat-bar cable
having no impedance change along the way to the tap
will show such clear behavior. Using a digital oscilloscope connected to selected taps, as identified during phase-resolved testing, allows analyzing this
effect.
Triangulation
For locating acoustic impulse signals in a confined
space the so-called triangulation is a common pra ctice. The basic principle is to have for instance three
sensors mounted on three neighboring faces of a cubical tank. Based on the different arrival of the signals the location is determined.
However, in order to function smoothly, this princ iple requires two main conditions being met:
1.
2.
Regrettably, both conditions are not met with realworld large power transformers [7]. Internally, surely
not being homogeneous, the structures of a power
transformer offer strongly varying attenuation and
travel speed. Likewise, instead of being membranes,
the tank walls are made of thick steel allowing the
acoustic emission to travel along the wall and thus
producing misleading results concerning the direction
and location of the source. Further, the tank walls are
often reinforced in their structure, which produces
additional reflections.
~0.65ms
Generally, the oil-paper insulation of a power transformer is a 'forgiving' insulation system, i.e. it can
tolerate partial discharge for a while. Partial discharge activity, on the other hand is an indicator for
on-going degradation of the overall insulation system. Thus, partial discharge monitoring is one option
to choose of, if it come to transformer monitoring.
Typically, bushing coupler units suited for permanent
installation are mounted to the test tap of the con-
Site 1
SUMMARY
Large power transformers are having a complex internal
life that is mostly hidden by the tank. Thus, analyzing
and locating internal partial discharge activity is a demanding task. Combining traditional methods with
modern measurement technique offers collecting the
results and information needed to support the required
decisions. However, in-depth knowledge of the internal
life of a transformer as well as of the high frequency
properties and the acoustic behavior of the components
is essential for the adequate interpretation of the results
Using modern signal processing techniques has
greatly improved traditional testing methods for accessing the health of large power transformers.
References
[1] IEEE C57.113-1991 "IEEE Recommended Practice for Partial Discharge Measurement in LiquidFilled Power Transformers and Shunt Reactors".
[2] Gross, D., Soeller, M. "Partial Discharge Diagnosis on large Power Transformers," ISEI 2004
Conference, Indianapolis, IN, September 19-22,
2004, 04CH37561C, pp. 186-191.
[3] Gross, D., Soeller, M., "Partial Discharge Acceptance Testing and Monitoring on Power
Transformers," ETG Fachtagung, Diagnostik el.
Betriebsmittel, Berlin, Germany, February 26-27,
2002, ISBN 3-8007-2671-8, pp. 213-216.
[4] Fruth, B., Gross, D. "Phase Resolving Partial
Discharge Pattern Acquisition and Spectrum
Analysis", Proc. of the ICPDAM, July 1994, Brisbane NSW, Australia, 94CH3311-8, pp. 578-581.
[5] Brunlich, R., Hssig, M., Fuhr, J., and Aschwanden, T. "Assessment of Insulation Condition of
Large Power Transformers by On-Site Electrical
Diagnostic Methods", ISEI International Symposium on Electrical Insulation, Anaheim, CA,
U.S.A., April 2-5, 2000.
[6] Carlson, ., Fuhr, J., Schemel, G., and Wegscheider, F. Testing Power Transformers. ABB
Business Area Power Transformers, 2003, ISBN
3-00-010400-3.
[7] Bengtsson, T, Kols, H., Jnsson, B., "Transformer
PD Diagnosis using Acoustic Emission Technique," Conf. Proc. of ISH, August 25-29, 1997,
Montral, Canada, Vol 4, pp. 115-119.
[8] IEC60270, High-voltage test techniques - Partial
discharge measurements, CEI/IEC 60270:2000.
Site 2
TCP/IP Intranet
Monitoring Center
ICMpilot S/W
Redundant Storage
FTP File Sharing
Contact information:
Power Diagnostix Systems GmbH
Brsseler Ring 95a, 52074 Aachen
Tel.: +49 241 74927, Fax: +49 241 79521
Web Site: www.pdix.com