Beruflich Dokumente
Kultur Dokumente
a r t i c l e
i n f o
Article history:
Received 22 March 2012
Revised 2 November 2012
Accepted 4 November 2012
Available online 19 December 2012
Keywords:
Hybrid system
Direct evaporative cooling
Payback period
Life cycle cost
Net present value
a b s t r a c t
Results of a preliminary analysis to study the nancial feasibility of a hybrid mode operation of a direct evaporative
cooler (DEC) with an air conditioning (AC) unit to reduce the annual expenditure on electricity usage (as against a
standalone AC unit to provide almost similar level of comfort) are presented. Four different building applications
located in four different cities of India have been considered in the study. The hybrid mode operation is found
nancially attractive for movie theater and waiting hall building applications for all the climatic conditions considered in the present study.
2012 International Energy Initiative. Published by Elsevier Inc. All rights reserved.
Introduction
The need and use of air-conditioning are rapidly increasing in
urban India and normally vapor compression systems are being
used for this purpose. As a consequence the electrical consumption
for air-conditioning is also increasing at a rapid rate. It is therefore
imperative to develop and implement practically feasible alternative
options that can provide acceptable levels of comfort with relatively
lower electricity consumption. For commercial buildings, use of direct
evaporative cooling based systems in a hybrid mode with conventional vapor compression based air-conditioning systems during hot
and dry months of the year is one such possibility. Besides the operational issues of a hybrid system, the primary consideration in making
a choice for the hybrid system as against a standard vapor compression based air-conditioning system would concern the nancial
viability of increased capital investment (higher cost of a hybrid system consisting of both the vapor compression air-conditioning (AC)
system as well the direct evaporative cooler (DEC) as against its
lower overall cost of operation due to lower electricity consumption
of the hybrid system as against that of a standalone AC unit for
satisfaction of the same demand). The approach and the results of
an attempt to study the nancial feasibility of an investment in a
hybrid (AC + DEC) system as compared to a standalone AC system
are presented in this paper for four Indian cities.
Four cities in India namely Akola (hot and dry climate), Bangalore 1
(temperate climate), Delhi (composite climate) and Indore (composite
Corresponding author. Tel.: +91 11 26591262.
E-mail address: tarak@ces.iitd.ac.in (T.C. Kandpal).
1
New name for city of Bangalore is Bengaluru.
climate) were considered for the study. Though the sites of Delhi and
Indore are in the same climatic zone, but being in different regions
their ambient conditions differ considerably and hence also the room
conditions (Hindoliya, 2005). Building application congurations considered include (i) high density ofce (with high internal loads due to
occupancy, lights, computers etc.), (ii) low density ofce, (iii) movie
theater and (iv) waiting hall. The external and internal input parameters to TRNSYS (2005) for these buildings are presented in Table A1 of
the Appendix (Jain, 2010). In the case of the standalone AC unit the
room temperature is set at 26 C and RH 70%. Since with the use of a
direct evaporative cooler (DEC) the attained room conditions change
with ambient conditions, a range of room temperatures and relative
humidity values are considered as set points (27.1 C, 70%; 27.6 C,
60%; and 28.1 C, 50%) (Jain, 2010). A systematic procedure (Fig. 1)
was followed for estimating the electricity requirement for maintaining
the desired comfort level in the chosen building congurations at the
four selected locations. TRNSYS (2005) was used to simulate the
rooms/buildings. The fractions of time during the year when cooling is
needed and a DEC can provide the acceptable comfort were estimated.
The results obtained are summarized in Table 1.
Analysis
The hybrid system considered in the system consists of a DEC unit
along with the AC unit arranged in a manner that whenever the
required comfort is not achieved with the DEC unit, the AC unit is
switched on and DEC unit is switched off. The AC unit considered in
the study is a split air cooled system with indoor and outdoor units
interconnected with refrigerant piping and its cost includes the cost of
refrigerant piping, cost of air distribution system and standard control
0973-0826/$ see front matter 2012 International Energy Initiative. Published by Elsevier Inc. All rights reserved.
http://dx.doi.org/10.1016/j.esd.2012.11.002
48
consumption (in kWh) for standalone AC unit (AECac) and the unit
price of electricity (Upe) for the user during the rst year. If the unit
cost of electricity is expected to escalate at annual rate (in fraction)
resc, the annual operating cost of the AC unit (AOC-ACj) in jth year
of its useful life can be estimated as
j1
AOCACj AECac Upe 1 resc :
PVLCCac
AEC ac U pe
1 r esc n
1
dresc
1d
PVLCChybrid
AEC hyb U pe
1 r esc n
1
dr esc
1d
Fig. 1. Schematic diagram of the procedure for estimation of energy savings with the
use of hybrid system.
PVCOMhybrid
AMC hyb
1 jesc n
1
:
djesc
1d
Table 1
Potential of using direct evaporative cooler unit and corresponding annual electricity savings.
Building Application
Annual amount of electricity saved with the use of hybrid system (kWh)
Akola
Bangalore
Delhi
Indore
Akola
Bangalore
Delhi
Indore
0.56
0.57
0.53
0.43
0.88
0.83
0.79
0.55
0.37
0.37
0.35
0.31
0.65
0.65
0.61
0.55
5600
3000
13,600
11,700
6100
4000
7100
6700
1900
1300
3800
3700
4500
3100
8800
8500
Notes: (i) hours of operations of AC unit and DEC unit in a hybrid system are presented in Table A2 of the Appendix.
(ii) Capacities of AC unit and DEC unit are indicated in Table A3 of the Appendix.
Table 3
Costs of split air cooled AC units.
Air ow rate
(in cubic feet per minute)
Air ow rate
(in cubic meter per minute)
1000
2000
3000
5000
28
57
85
142
27,050
44,400
58,550
81,450
a
Values of various costs quoted in the paper pertain to year 2010 (US $1 = Rs 45.50
in October, 2010).
3.0
5.5
8.5
11.0
17.0
22.0
48,000
78,000
110,000
145,000
210,000
280,000
Discount rate
A discount rate of 12% is used in the study.
Cost of variable frequency drive (VFD) and controls
Based on the inputs received from the manufacturers the cost of
VFD and cost of controls is assumed to be Rs. 25,000 each.
Useful life
The expected useful life of the AC unit as well as that of the
DEC unit is assumed to be 15 years with the provision of an annual
maintenance contract.
Cost of annual maintenance contract for AC and DEC units
Based on detailed discussions with the manufacturers and suppliers
of both the AC and DEC units in the country, the cost of AMC is estimated
at 10% of the total capital cost with an annual increase of 5% from the
base year value.
Cost of air distribution system
Air distribution system includes sheet metal duct, exible connection, volume control dampers, supply/return air diffusers, exhaust air
grilles etc. Using the cost estimates received from the manufacturers
and suppliers (Table 2) the following cost function is obtained for the
cost of air distribution system (Cads) in Indian Rupees as a function of
the air ow rate (AFR) in cubic meter per minute.
0:6861
Cads 2752:6AFR
49
Table 4
Capital cost of direct evaporative cooler (DEC) units (air washer type).
Capacity of DEC unit
(cubic feet per minute)
2500
3000
5000
10,000
15,000
20,000
25,000
30,000
71
85
142
283
425
567
708
850
30,000
36,000
60,000
120,000
172,500
230,000
287,500
345,000
50
Table 5
Measures of nancial attractiveness for all the four building applications in Akola, Bangalore, Delhi and Indore.
Unit
Akola
Bangalore
AC system
Hybrid system
AC system
1000 Rs
1000 Rs
Years
1165
171
1002
147
3.6
750
110
1000 Rs
163
1000 Rs
1000 Rs
Years
680
100
710
104
14.5
1000 Rs
30
1000 Rs
1000 Rs
Years
3012
442
2329
342
1.1
1107
162
1000 Rs
1000 Rs
1000 Rs
Years
3180
467
1000 Rs
684
2519
370
0.6
661
Delhi
Indore
AC system
Hybrid system
AC system
543
80
3.3
739
108
823
121
42
746
110
207
84
551
81
489
72
6.1
535
79
658
97
Not feasible
547
80
123
18
906
133
4
1979
291
1967
289
8.7
1625
239
1321
194
2.9
201
12
2011
295
1923
282
4.1
1752
257
89
1384
203
Fig. 2. Sensitivity of the net present value of hybrid system (DEC + AC) in high density
ofce to the values of (a) discount rate, (b) useful life, and (c) unit price of electricity.
Hybrid system
62
1124
165
2.5
260
Hybrid system
674
99
6
73
565
83
12.2
304
1371
201
1.7
354
Fig. 3. Sensitivity of net present value of hybrid system (DEC + AC) in low density
ofce to the values of (a) discount rate, (b) useful life, and (c) unit price of electricity.
51
Fig. 4. Sensitivity of net present value of hybrid system (DEC + AC) in movie theater to
the values of (a) discount rate, (b) useful life, and (c) unit price of electricity.
Fig. 5. Sensitivity of net present value of hybrid system (DEC + AC) in waiting hall to
the values of (a) discount rate, (b) useful life, and (c) unit price of electricity.
Fig. 3. Results for the cases of movie theater and waiting hall are
presented in Figs. 4 and 5 respectively for all the four locations considered in the study. It may be noted that except the low density ofce, all
the other three building applications in Indore and Akola can benet
from the use of a hybrid system with monetary gains for the investor.
In Delhi, only the movie theater and the waiting hall building can
benet from the use of a hybrid system. This is different from the
results obtained for Indore, although the city of Delhi is grouped in
the same climatic zone i.e. composite zone as per the National Building Code. In Bangalore, all the four building applications can benet
from the hybrid system. A summary of the feasibility of using hybrid
Table 6
Feasibility of using hybrid system as against standalone vapor compression AC system
{feasible: []; not feasible: [X]}.
S. no.
High density
ofce
Low density
ofce
Movie
theater
Waiting
hall
2
3
4
52
The building applications considered are of multi-storied and with multi-zone, however, for the purpose of study, part unit size of 10 m 5 m
is considered from a building oriented along east-west (facing northsouth direction). Same area modular unit* considered in all the building
application for the purpose of comparison.
Table A1
External and internal input parameters for different building applications (Jain, 2010).
Sl. no.
Description
Movie theater
Waiting hall
Remarks
Area (m2)
Height (m)
3
5
6
Volume (m3)
Occupancy (numbers)
Fresh air in cubic meter per minute
(CMM)
Air changes per hour (ac/h)
North wall area (m2)
South wall area (m2)
Ceiling
North window (m2)
175 m3
8
4.8
175 m3
4
2.4
300 m3
75
36
175 m3
50
24
1.65
35
35
Internal partition
14
0.82
35
35
Internal partition
14
7.2
60
60
Internal partition
0
8.23
35
35
Internal partition
14
14
24 W/m2
14
11.8 W/m2
0
12.9 W/m2
14
10.8 W/m2
0.39
0.75
2.83
0.39
0.75
2.83
0.39
0.39
0.75
2.83
7
8
9
10
11
12
13
14
15
16
Notes:
Table A2
Hours of operation of AC unit and DEC unit is a hybrid system for comfort conditions of 26 TSI (Jain, 2010).
Building application
Operating hours of AC and DEC in a hybrid system for comfort conditions of 26 TSI
Akola
Bangalore
Delhi
Indore
AC
DEC
AC
DEC
AC
DEC
AC
DEC
3868
3623
3956
4854
4887
4881
4385
3702
1028
1420
1774
3842
7732
7090
6511
4782
3691
3605
3711
3998
2187
2146
1955
1793
2542
2461
2643
3141
4727
4510
4175
3908
Table A3
Selected DEC unit capacity in m3/h for different building application and AC unit capacity for different building applications as well as for different cities (Jain, 2010).
Building applications
Capacity of selected AC unit (in tons of refrigeration (TR) and ow rate in m3/min).
Akola
87.5
87.5
150
87.5
Bangalore
Delhi
Indore
TR
m3/min
TR
m3/min
TR
m3/min
TR
m3/min
5.5
3
17
17
62
34
193
193
3
3
5.5
5.5
34
34
62
62
3
3
11
11
34
34
125
125
3
3
8.5
8.5
34
34
96
96
a
DEC unit capacity is calculated with volume of the room and air change rate. In our case, volume (10 m 5 m 3.5 m) and air change rate (30 ac/h) is same for all the type of
buildings except in movie theater where volume is different as height is 6.0 m (air change rate is same as 30 ac/h).
References
Hindoliya DA. Evaporative Cooling for Thermal comfort in Buildings, Ph. D. Thesis.
Delhi: Indian Institute of Technology Delhi, 2005.
Jain Varun. Energy Conservation In Space Conditioning in India through Direct
53
Evaporative Cooling, Ph. D. Thesis. Centre for Energy Studies, Indian Institute of
Technology Delhi, 2010.
TRNSYS, 16. A transient system simulation program. Solar Energy Laboratory, University
of Wisconsin-Madison, 1500 Engineering Drive, 1303 Engineering Research Building,
Madison, WI 53706 USA; 2005.