To ensure a continuous supply of electrical power,


certain installations are connected to two sources:
b a normal source N
b a replacement source R used to supply the
installation when the normal source is unavailable.

PB100840

Interlocking of two Interpact switch-disconnectors


via rotary handles.

A source-changeover system switches the load


between these two sources. It can be automated to
manage transfers according to external conditions. A
source-changeover system includes two or three
circuit breakers or switch-disconnectors.
With Interpact INS, Compact NS and Masterpact NT
and NW, new installation solutions are available to
optimise the size of the switchboard and simplify
installation.

PB100930-68

Complete source-changeover assembly with


two Interpact switch-disconnectors.

PB100842

Interlocking of two Compact NS circuit breakers


on a base plate.

Interlocking of two Masterpact NT and NW circuit breakers


using cables.

312E0100.indd 2

20/10/2008 10:12:30

Source-changeover systems

General content

Presentation

Functions
and characteristics

A-1

Dimensions

B-1

Electrical diagrams

C-1

Catalogue numbers
and order forms

D-1

Livre 1.indb 1

08/10/2008 18:38:11

Presentation

For maximum continuity


of service ...

Manual source-changeover system


PB103937

This is the most simple type. It is controlled manually by an operator and


consequently the time required to switch from the normal to the replacement source
can vary.
A manual source-changeover system is made up of two or three mechanically
interlocked manually-operated circuit breakers or switch-disconnectors.

Remote-operated source-changeover system

PB103936

This is the most commonly employed system for devices with high ratings
(above 400 A). No human intervention is required. Transfer from the normal to
the replacement source is controlled electrically.
A remote-controlled source-changeover system is made up of two or three circuit
breakers or switch-disconnectors linked by an electrical interlocking system that may
have different configurations. In addition, a mechanical interlocking system protects
against electrical malfunctions or incorrect manual operations.

Automatic source-changeover systems

PB103934

Commercial and service sector:


b operating rooms in hospitals
b safety systems for tall buildings
b computer rooms (banks, insurance companies, etc.)
b lighting systems in shopping centres

An automatic controller may be added to a remote-operated source-changeover


system for automatic source control according to programmable operating modes.
This solution ensures optimum energy management:
b transfer to a replacement source according to external requirements
b management of power sources
b regulation
b emergency source replacement, etc.
The automatic controller may be fitted with an option for communication with a
supervisor.

PB103935

Industry:
b assembly lines
b engine rooms on ships
b critical auxiliaries in thermal power stations

Infrastructures:
b port and railway installations
b runway lighting systems
b control systems on military sites

Livre 1.indb 2

08/10/2008 18:38:18

... in a wide range of applications

PB100839

PB100842

Presentation

PB100840

Interlocking of two Interpact switch-disconnectors via rotary


handles.

PB100850

PB100849

Interlocking of two MasterpactNT and NW circuit breakers using cables.

PB100957-62

Complete source-changeover assembly with two Interpact


switch-disconnectors.

Interlocking of two MasterpactNT or NW


circuit breakers using connecting rods.

Interlocking of two Compact NS circuit breakers on a base


plate.

Interlocking of three Masterpact NW circuit


breakers using cables.

PB100851

PB100848

Other source-changeover systems: Telemecanique products

See LC2-D series.

See LC2-F series.

Livre 1.indb 3

08/10/2008 18:38:22

For maximum continuity


of service...

Presentation

DB101543

PB100853

Incoming feeders and main LV switchboards

Currents

From 630 to 6300 A.

PB100852

Power distribution

Currents

From 250 to 3200 A.

PB100854

Loads

Currents

From 40 to 400 A.

Livre 1.indb 4

08/10/2008 18:38:24

... in a wide range of applications




Presentation

QN
0
1
0

QR

QS1

0
0
1

2 normal sources
1 replacement source
DB101540

DB101539

2 sources with coupler on


busbars

DB101538

1 normal source
1 replacement source

QC

QS2

0
0
0
1
0
1
1
1
0
0
1
1
1
0
0 (1)
0
0
1 (1)
(1) possible by forcing
operation.

QN1
0
1
0
1
0

QN2

QR

0
1
0
0
1

0
0
1
0
0

Generator or permanent
source
QN
DB101541

0
1
0

Generator or permanent
source

Typical applications:
b continuous production processes
b operating rooms
b computer rooms...

Generator or permanent
source
DB101544

QN
DB101541

QR
0
0
1

0
1
0

QR
0
0
1

Typical applications:
b large electrical installations (e.g. airports)
b refrigeration units
b special electricity tariffs
b pumping stations...

Livre 1.indb 5

08/10/2008 18:38:24

TOOLS
schneider-electric.com

The technical guide

This international site allows you


to access all the Schneider Electric
products in just  clicks
via comprehensive range datasheets, with direct links to:
p complete library: technical
documents, catalogs, FAQs,
brochures
p selection guides from
the e-catalog.
p product discovery sites and
their Flash animations.
You will also find illustrated
overviews, news to which you
can subscribe, the list of country
contacts

These technical guides help you


comply with installation standards
and rules i.e.: the electrical
installation guide, the protection
guide, the switchboard
implementation guide,
the technical booklets
and the co-ordination tables all form
genuine reference tools
for the design of high performance
electrical installations.
For example, the LV protection
co-ordination guide - discrimination
and cascading - optimises choice
of protection and connection devices
while also increasing markedly
continuity of supply
in the installations.

Livre 1.indb 2

08/10/2008 18:38:26

Source-changeover systems

Functions and characteristics

Presentation

Overview of solutions
Manual source-changeover systems InterpactINS
and Compact NS 40 A to 630 A
Manual source-changeover systems Compact NS
and Masterpact NT/NW 630 A to 6300 A
Remote-operated source-changeover systems
Compact NS100/1600 100 A to 1600 A
Remote-operated source-changeover systems
Masterpact NT/NW 630 A to 6300 A

Manual source-changeover systems


Possible combinations

Remote-operated source-changeover systems


Mechanical interlocking
General characteristics
Mechanical and electrical durability
Connection and insulation accessories for Compact NS and INS y 630 A
Electrical interlocking
Standard configurations

Associated controllers
Controller selection
Controller installation
BA controller
BA controller operating sequences
UA controller
UA controller operating sequences

A-2
A-2
A-3
A-4
A-5

A-6
A-6

A-10
A-10
A-12
A-14
A-15
A-16
A-17

A-18
A-18
A-19
A-20
A-21
A-22
A-23

Operating sequences

A-26

COM communications option

A-28

Dimensions
Electrical diagrams
Catalogue numbers and order forms

B-1
C-1
D-1

A-1

Livre 1.indb 1

08/10/2008 18:38:26

Functions
and characteristics

Overview of solutions

Range

Interpact

Rating (A)
Type of device

INS250 to INS630
INV250 to INV630
100 to 630
Switch-disconnectors

NS100 to NS250
NS400 to NS630
100 to 630
N/H/L circuit breakers
NA switch-disconnectors

DB101548

Compact

INS40 to INS80
INS100 to INS160
40 to 160
Switch-disconnectors with
extended handles

DB101547

Models

Manual source-changeover systems


InterpactINS and Compact NS 40 A
to 630 A

Manual source-changeover systems

DB101545

DB101768

Interlocking via toggles

2 devices side-by-side

3 devices side-by-side

Interlocking via rotary handles


DB101546

DB101769

.4

2 devices side-by-side

ON
I

ON
I
O
OFF

O
OFF

DB101550

DB101549

DB101770

Interlocking via keylocks with captive keys

A number of different devices

DB101551

DB101771

Interlocking on a base plate

2 devices side-by-side

DB101552

DB101772

Complete source-changeover assemblies

2 devices side-by-side

A-2

Livre 1.indb 2

08/10/2008 18:38:30

Functions
and characteristics

Overview of solutions

Range

Compact

Masterpact

NS630b to NS1600
630 to 1600
N/H/L circuit breakers
NA switch-disconnectors

NT06 to NT16
630 to 1600
H1/L1 circuit breakers
HA switch-disconnectors

Models
Rating (A)
Type of device

Manual source-changeover systems


Compact NS and Masterpact NT/NW
630 A to 6300 A
NW08 to NW63
800 to 6300
N1/H1/H2/H3/L1 circuit
breakers
NA/HA/HF switchdisconnectors

Manual source-changeover systems

DB101553

DB101769

Interlocking via extended rotary handles

2 devices side-by-side

I ON

OOFF

push

push

discharged

O OFF

I ON

OOFF

push

push

DB101556

DB101555

DB101554

DB101770

Interlocking via keylocks with captive keys

discharged

O OFF

A number of different devices

sup

degr
ahcs
id

DB101559

NO h

DB101562

hsup

DB101558

FFO

FFO

DB101561

DB101557

DB101773

Mechanical interlocking using connecting rods

FFO

hsup

NO h

sup

FFO

O
degr
ahcs
id

2 devices one above the other


(1)

DB101560

DB101774

Mechanical interlocking using cables

DB101775

2 or 3 devices one above the other

(1)

2 or 3 devices side-by-side

(2)

DB101916

For this case and other cases, please consult us

(1) Implemented with NS630b to NS1600 electrically-operated devices only.


(2) For source-changeover systems using cables, always respect the installation conditions specified on page A-13.

A-3

Livre 1.indb 3

08/10/2008 18:38:36

Functions
and characteristics

Overview of solutions

Range

Compact

Models
Rating (A)
Type of device

Remote-operated source-changeover
systems Compact NS100/1600
100 A to 1600 A
NS100 to NS630
100 to 630
N/H/L circuit breakers
NA switch-disconnectors

NS630b to NS1600
630 to 1600
N/H/L circuit breakers
NA switch-disconnectors

Remote-operated source-changeover system

DB101563

DB101771

Mechanical interlocking on base plate + electrical interlocking

2 electrically-operated devices side-by-side combined


with an electrical interlocking system

DB101557

DB101773

Mechanical interlocking using connecting rods + electrical interlocking

FFO

hsup

NO h

sup

FFO

O
degr
ahcs
id

FFO

hsup

NO h
sup

FFO

O
degr
ahcs
id

2 electrically-operated devices one above


the other combined with an electrical interlocking system

DB101560

DB101777

Mechanical interlocking using cables + electrical interlocking

DB101776

2 electrically-operated devices one above


the other combined with an electrical interlocking system

2 electrically-operated devices side-by-side combined


with an electrical interlocking system
(2)

Automatic source-changeover systems

DB101777

The automatic controller


operates the devices
depending on external
parameters.

DB101564

Remote-operated source-changeover system combined with an automatic-control system

BA: Simple controller that


manages the changeover
function.

UA150: UA controller with a


communication option.

DB101565

UA: Controller that also


manages engine generator
sets.

BA controller

UA and UA150 controller


(2) For source-changeover systems using cables, always respect the installation conditions specified on page A-13.

A-4

Livre 1.indb 4

08/10/2008 18:38:40

Functions
and characteristics

Overview of solutions

Range

Masterpact

Models
Rating (A)
Type of device

Remote-operated source-changeover
systems Masterpact NT/NW
630 A to 6300 A
NT06 to NT16
630 to 1600
H1/L1 circuit breakers
HA switch-disconnectors

NW08 to NW63
800 to 6300
N1/H1/H2/H3/L1 circuit breakers
NA/HA/HF switch-disconnectors

Remote-operated source-changeover system

DB101559

DB101558

DB101773

Mechanical interlocking using connecting rods + electrical interlocking

2 electrically-operated devices side-by-side combined


with an electrical interlocking system

DB101562

DB101774

DB101561

Mechanical interlocking using cables + electrical interlocking

DB101775

2 or 3 electrically-operated devices one above the other


combined with an electrical interlocking system (1)

2 or 3 electrically-operated devices side-by-side combined with


an electrical interlocking system (1)
(2)

Automatic source-changeover systems

DB101564

The automatic controller


operates the devices
depending on external
parameters.
BA: Simple controller that
manages the changeover
function.
UA: Controller that also
manages engine generator
sets.

BA controller

DB101565

DB101776

DB101777

Remote-operated source-changeover system combined with an automatic-control system

UA150: UA controller with a


communication option.

UA and UA150 controller

(1) Three devices with Masterpact NW only.


(2) For source-changeover systems using cables, always respect the installation conditions specified on page A-13.
For other cases, please consult us.

A-5

Livre 1.indb 5

08/10/2008 18:38:45

Manual source-changeover
systems

Functions
and characteristics

Possible combinations
A manual source-changeover system can be installed
on two or three manually-operated and mechanically
interlocked circuit breakers or switch-disconnectors.
Interlocks prevent connection to both sources at the
same time, even momentarily.

All possibilities for manual source-changeover systems


Type of device

Type of interlocking for two devices

Complete
assembly
Interpact switch-disconnectors

Keylock

Direct rotary
handle

Extended
rotary handle

INS40 to INS160
b

INS250-100 to INS630
INV100 to 630

b r

b r

b r

b rr

b
INS/INV630b to 2500
Legend:
r Possible but visible break function disabled.
r 250 A and 630 A ratings can be mixed by using INS320/630 rotary handle interlocking system.

Type of device

Type of interlocking for two devices


Toggle

Keylock

Direct rotary
handle

Extended rotary
handle

On base plate
On base plate
(toggle or direct extended (motor mechanism)
rotary control)

Compact fixed or withdrawable circuit breakers


NS100 to 250

bb

bbp

bb

bb

bbb

bbb

NS400 to NS630

bb

bbp

bb

bb

bbb

bbb

bbp

bbp

bbp

bbbp

bbbp

NS100 to 630

bb
NS630b to 1600 with
bbp
rotary handle
Legend:
b Fixed devices only.
b Fixed or withdrawable devices.
b Devices must be either both fixed or both withdrawable.
p With NS400/630 rotary handle interlocking system.
p Possible with NS400/630 base plate + NS100-250 adaptation kit.
p Devices equipped with rotary handles.

Type of device

bb

Type of interlocking for either all fixed or all withdrawable devices


Keylock

Cable-type,
Cable-type,
Cable-type,
2 devices side-by3 devices side-by2 devices one
side
side
above the other
Compact fixed or withdrawable circuit breakers or swith-disconnectors, with motor mechanism

Cable-type,
3 devices one
above another

b
b
b
NS630b to 1600
Masterpact fixed or withdrawable circuit breakers or swith-disconnectors, manual operation or with motor mechanism
NT06 to 16

NW08 to 63

NT06 to NW63

b
b

Rod-type,
3 devices one
above another

b
b

A-6

Livre 1.indb 6

08/10/2008 18:38:46

Manual source-changeover
systems

Functions
and characteristics

Possible combinations
All possibilities for manual source-changeover systems
DB101571

Complete source-changeover assembly for two switchdisconnectors


These assemblies provide an easy way to implement source changeover functions
with:
b a single 3-position rotary handle that controls the two switch-disconnectors
(Normal source ON, OFF, Replacement source ON)
b a smaller size, taking up less room in the switchboard.
A complete source changeover assembly can be ordered with a single catalogue
number.

Complete source-changeover assembly for two Interpact INS


switch-disconnectors.

Normal N

Replacement R
INS250-100

INS250-100
Ratings 100 A
INS250-160
Ratings 160 A
INS200-200
Ratings 200 A
INS250-250
Ratings 250 A
INS320
Ratings 320 A
INS400
Ratings 400 A
INS500
Ratings 500 A
INS630
Ratings 630 A

INS250-160

INS200-200

INS250-250

INS320

INS400

INS500

INS630

b
b
b
b
b
b
b
b

Possible combinations of Normal and Replacement source circuit breakers

Interlocking of two or three toggle-controlled devices


DB101566

Two devices can be interlocked using this system. Two identical interlocking systems
can be used to interlock three devices installed side by side, in which case one
device is in the ON position and the two others are in the OFF position. Devices must
all have the same configuration, i.e. fixed, plug-in, withdrawable or drawout.
The system is locked using one or two padlocks (shackle diameter 5 to 8 mm).
Two interlocking system models are available for:
b Compact NS100 to 250
b Compact NS400 to 630.

Normal N
Interlocking of two toggle-controlled devices.
NS100
Ratings 16... 100 A
NS160
Ratings 80...160 A
NS250
Ratings 125...250 A
NS400
Ratings 150... 400 A
NS630
Ratings 630 A

Replacement R
NS100

NS160

NS250

NS400

NS630

A-7

Livre 1.indb 7

08/10/2008 18:38:47

Manual source-changeover
systems

Functions
and characteristics

Possible combinations
Combination of Normal and Replacement devices

All Interpact, Compact and Masterpact circuit breakers and switch-disconnectors


from 100 to 6300A with rotary handles or motor mechanisms can be interlocked.

DB101569

Interlocking of a number of devices using keylocks (captive


keys)
Interlocking is based on two identical keylocks with a single key and a keylock
adapter (different for each device). This solution enables interlocking between two
devices that are physically distant or that have very different characteristics, for
example between a low and a medium-voltage device, or between Compact NS
circuit breakers and switch-disconnectors.
A system of wall-mounted captive key boxes makes possible a large number of
combinations between many devices.

Keylock-type interlocking of two circuit breakers with rotary


handles or motor mechanisms.

Possible combinations of Normal and Replacement source circuit breakers

Interlocking of two devices with rotary handles


DB101568

The direct or extended rotary handles are padlocked with the devices in the OFF
position. The mechanism prevents simultaneous closing of the devices, but allows
them to be opened.
ON
I

ON
I
O
OFF

O
OFF

Interlocking of two Compact NS circuit breakers with rotary


handles.

Normal N
Replacement R
NS160
Compact NS100/630 (1) NS100

NS250

NS400

NS630

NS100
Ratings 16... 100 A
b
b
b
v
v
NS160
b
b
b
v
v
Ratings 80...160 A
NS250
b
b
b
v
v
Ratings 125...250 A
NS400
v
v
v
b
b
Ratings 160... 400 A
NS630
Ratings 630 A
v
v
v
b
b
v 250 A and 630 A ratings can be mixed by using NS400/630 rotary handle interlocking system.

Normal N
Replacement R
NS800
Compact NS630/1600 (1) NS630b

NS1000

NS1200

NS1600

NS630b
Ratings 250... 630 A
b
b
b
b
b
NS800
b
b
b
b
b
Ratings 320... 800 A
NS1000
b
b
b
b
b
Ratings 400... 1000 A
NS1200
b
b
b
b
b
Ratings 480... 1200 A
NS1600
b
b
b
b
b
Ratings 640... 1600 A
(1) When mixing NS100/250 and NS400/630 circuit breakers, use the NS400/630 interlocking
system.

A-8

Livre 1.indb 8

08/10/2008 18:38:48

Manual source-changeover
systems

Functions
and characteristics

Possible combinations
Possible combinations of Normal and Replacement source switch-disconnectors

Interlocking of two devices with rotary handles


DB107742

The direct or extended rotary handles are padlocked with the devices in the OFF
position. The mechanism prevents simultaneous closing of the devices, but allows
them to be opened.
Normal N
Interpact INS (1)

Interlocking of two Interpact switch-disconnectors with direct


rotary handles.

Normal N
Interpact INS /INV (2)

Replacement R

INS40
INS63
INS80
INS100
INS40
Ratings 40 A
b
b
b
b
INS63
Ratings 63 A
b
b
b
b
INS80
Ratings 80 A
b
b
b
b
INS100
Ratings 100 A
b
b
b
b
INS125
Ratings 125 A
b
b
b
b
INS160
Ratings 160 A
b
b
b
b
(1) With extended rotary handles only.
(2) Possible with INV, but visible-break function is significantly impaired.

INS125

INS160

Replacement R
INS250-100/
INV100

INS250-160/
INV160

INS250-200/
INV200

INS250-250/
INV250

INS250-100/INV100
b
b
b
b
Ratings 100 A
INS250-160/INV160
Ratings 160 A
b
b
b
b
INS250-200/INV200
Ratings 200 A
b
b
b
b
INS250-250/INV250
Ratings 250 A
b
b
b
b
INS320/INV320
Ratings 320 A
v
v
INS400/INV400
Ratings 400 A
INS500/INV500
Ratings 500 A
INS630/INV630
Ratings 630 A
v
v
v 250 A and 630 A ratings can be mixed by using INS320/630 rotary handle interlocking system.

INS320/
INV320

INS400/
INV400

INS500/
INV500

INS630/
INV630

Possible combinations of Compact Normal and Replacement source circuit breakers

Interlocking of two devices on a base plate


DB101570

A base plate is available for mechanical interlocking of two manually-operated


Compact circuit breakers or switch-disconnectors.
Normal N
Replacement R

push
to
trip

push
to
trip

Interlocking of two manually-operated Compact NS devices on


a base plate.

NS100
Ratings 16... 100 A
NS160
Ratings 80... 160 A
NS250
Ratings 125... 250 A
NS400
Ratings 150... 400 A
NS630
Ratings 630 A

NS100

NS160

NS250

NS400

NS630

DB101903

Combination of Masterpact devices

Interlocking of a number of devices using keylocks


(captive keys)
Interlocking uses two identical keylocks with a single key. This solution enables
interlocking between two devices that are physically distant or that have significantly
different characteristics.

A-9

Livre 1.indb 9

08/10/2008 18:38:50

Functions
and characteristics

Remote-operated
source-changeover systems
Mechanical interlocking

PB100930-67

Electrical interlocking of two or three devices is used to


create a remote-operated source-changeover system.
A basic mechanical interlocking system enhances the
reliability of system operation.

Interlocking of two Compact NS100 to 630 devices using a base


plate
A base plate designed for two Compact circuit breakers can be installed horizontally
or vertically on a mounting rail. Interlocking is carried out on the base plate by a
mechanism located behind the breakers. Access to the circuit breaker controls and
trip units is conserved. Circuit breakers must be fixed or plug-in versions, with or
without earth-leakage protection or measurement modules. The base plate and the
circuit breakers are supplied separately.
b base plate for Compact NS100 to 250 devices
This base plate is intended for two Compact NS100 to 250 devices.
b base plate for Compact NS400 to 630 devices
This base plate is intended for two Compact NS400 to 630 devices. It may also be
used, without any modifications, to interlock a fixed Compact NS100 to 250 with a
Compact NS400 or 630 device.
An adapter kit is required for plug-in versions of the Compact NS100 to 250 devices.
Compact NS100 to 250 devices, in both fixed and plug-in versions, may be equipped
with spreaders.
Possible combinations of Normal and Replacement Compact source circuit breakers

Normal N

Interlocking of two electrically-operated Compact NS circuit


breakers using a base plate.

NS100
Ratings 12,5... 100 A
NS160
Ratings 12,5...160 A
NS250
Ratings 12,5...250 A
NS400
Ratings 160... 400 A
NS630
Ratings 250... 630 A

Replacement R
NS100

NS160

NS250

NS400

NS630

DB101572

Interlocking of two Compact NS630b to 1600 or two Masterpact


NT and NW devices using connecting rods
The two devices must be mounted one above the other (either 2 fixed or 2
withdrawable/drawout devices).
Combinations are possible between Compact NS630b to NS1600 devices and
between Masterpact NT and Masterpact NW devices.
Installation
This function requires:
b an adaptation fixture on the right side of each circuit breaker or switchdisconnector
b a set of connecting rods with no-slip adjustments.
The adaptation fixtures, connecting rods and circuit breakers or switchdisconnectors are supplied separately, ready for assembly by the customer.
The maximum vertical distance between the fixing planes is 900 mm.
Possible combinations of Normal and Replacement source circuit breakers

Normal N

Replacement R
NS630b to
NS1600

Interlocking of two Masterpact NT or NW circuit breakers using


connecting rods.

NS630b to NS1600
Ratings 250... 1600 A
NT06 to NT16
Ratings 250... 1600 A
NW08 to NW40
Ratings 320... 4000 A
NW40b to NW63
Ratings 4000... 6300 A

NT06 to NT16

NW08 to
NW40

NW40b to
NW63

A-10

Livre 1.indb 10

08/10/2008 18:38:53

Functions
and characteristics

Remote-operated
source-changeover systems
Mechanical interlocking

PB100842

Interlocking of two Compact NS630b to 1600 or two Masterpact


NT/NW or up to three Masterpact NW devices using cables
For cable interlocking, the circuit breakers may be mounted one above the other or
side-by-side.
The interlocked devices may be fixed or drawout, three-pole or four-pole, and have
different ratings and sizes.
Interlocking between two devices (Compact NS630b to 1600 or Masterpact NT
and NW)
This function requires:
b an adaptation fixture on the right side of each device
b a set of cables with no-slip adjustments.
The maximum distance between the fixing planes (vertical or horizontal) is 2000mm.

Interlocking of two Masterpact circuit breakers using cables.

Interlocking between three devices (Masterpact NW only)


This function requires:
b a specific adaptation fixture for each type of interlocking, installed on the right side
of each device
b two or three sets of cables with no-slip adjustments.
The maximum distance between the fixing planes (vertical or horizontal) is 1000mm.
Installation
The adaptation fixtures, sets of cables and circuit breakers or switch-disconnectors
are supplied separately, ready for assembly by the customer.
Installation conditions for cable interlocking systems:
b cable length: 2.5 m
b radius of curvature: 100 mm
b maximum number of curves: 3.
Possible combinations of Normal and Replacement source circuit breakers

Normal N

Replacement R
NS630b to
NS1600

NS630b to NS1600
Ratings 250... 1600 A
NT06 to NT16
Ratings 250... 1600 A
NW08 to NW40
Ratings 320... 4000 A
NW40b to NW63
Ratings 4000... 6300 A

NT06 to NT16

NW08 to
NW40

NW40b to
NW63

It is not possible to combine Compact NS630b to 1600 and Masterpact NT


(orMasterpact NW) devices.
All combinations of two Masterpact NT and Masterpact NW devices are possible,
whatever the rating or size of the devices.
Possible combinations of three device

Normal N

Replacement R
NS630b to
NS1600

NS630b to NS1600
Ratings 250... 1600 A
NT06 to NT16
Ratings 250... 1600 A
NW08 to NW40
Ratings 320... 4000 A
NW40b to NW63
Ratings 4000... 6300 A

NT06 to NT16

NW08 to
NW40

NW40b to
NW63

Only Masterpact NW may be used for three-device combinations.

Types of mechanical interlocking and combinations


See page A-4 to page A-9.

A-11

Livre 1.indb 11

08/10/2008 18:38:55

Remote-operated
source-changeover systems

Functions
and characteristics

General characteristics
Range

Compact

Types of devices
Types of circuit breakers
Switch-disconnector version
Mixing possibilities

Electrical characteristics
Rating
Insulating voltage Ui (V AC)
Positive break indication
Number of poles
(N and R devices must have the same number of poles)
Electrical durability
Operating temperature
Control characteristics
Control voltage

Maximum consumption

NS100 to NS250
N/H/L
NA
all devices
NS100 to NS250
N/H/L/NA
fixed or plug-in

NS400 to NS630
N/H/L
NA
all devices
NS100 to NS630
N/H/L/NA
fixed or plug-in

15 to 250 A
750
b
3, 4

15 to 630 A
750
b

See page A-14


25 C to +70 C (50 C for 440 V - 60 Hz)
AC
DC
AC
DC

Minimum switching time


Interlocking
Mechanical (see page A-10)
Electrical
by diagram (without IVE)
with IVE unit
auxiliary contacts used by circuit breaker
Protection and measurement
Overload protection
long time
Short-circuit protection
short time
instantaneous
Earth-fault protection
Zone selective interlocking (ZSI)
Earth-leakage protection
by Vigi module
by control unit
by add-on Vigirex relay
Current measurements
Voltage, frequency, power measurements, etc.
Indication and control auxiliaries
Available auxiliary indication contacts
Voltage releases
MX shunt
MN undervoltage
Voltage presence indicator
Voltage transformer
Ammeter module
Insulation monitoring module
Source-changeover controller
With permanent replacement source
With standby generator set
Remote communication via bus
Device status indications
Device remote control
Transmission of settings
Indication and identification of protection status and alarms
Transmission of measurements
Installation and connection
Fixed front connected
Fixed rear connected
Withdrawable, plug-in or drawout
Installation and connection accessories
Downstream coupling accessory
Bare-cable connectors
Terminal extensions
Terminal shields and inter-phase barriers
Locking
by padlock
by keylock
Front panel escutcheons

48 to 415 V - 50/60 Hz
440 V - 60 Hz
24-250 V
500 VA
500 W
800 ms

500 VA
500 W
800 ms

b
b
1 OF + 1 SDE

b
b
1 OF + 1 SDE

b
b
b

b
b
b
b
b
b

OF + SD (+ SDV)
b
b
b
b
b
b

2 OF + SD (+ SDV)
b
b
b
b
b
b

b BA controller
b UA controller
b

b (long rear connections)


b (plug-in on base)

b (long rear connections)


b (plug-in on base)

b
b
b

b
b
b
b
b
b
b

b
b
b

A-12

Livre 1.indb 12

08/10/2008 18:38:55

Functions
and characteristics

Remote-operated
source-changeover systems
General characteristics
Masterpact

NS630b to NS1600
N/H/L
NA
all devices
NS630b to 1600
N/H/L/NA
fixed or plug-in

NT06 to 16
N1 / H1 / H2 / H3 / L1
NA / HA / HF
all mixing possibilities
(fixed, drawout or fixed + drawout)
N1/H1/H2/H3/L1/NA/HA/HF

NW08 to 63
N1 / H1 / H2 / H3 / L1
NA / HA / HF
all mixing possibilities
(fixed, drawout or fixed + drawout)
N1/H1/H2/H3/L1/NA/HA/HF

250 to 1600 A
750

600 to 1600 A
1000
b
3, 4

800 to 6300 A
1000
b

See page A-14


25 C to +70 C (50 C for 440 V - 60 Hz)

180 VA
180 W
800 ms

48 to 415 V - 50/60 Hz
440 V - 60 Hz
24-250 V
180 VA
180 W
800 ms

180 VA
180 W
800 ms

b
b
1 OF + 1 CE (+ SDE)

b
only with UA or BA
1 OF + 1 CE + 1 PF

b
only with UA or BA
1 OF + 1 CE + 1 PF

b
b
b
b
b

b
b
b
b
b

b
b
b
b
b

b
b
b

b
b
b
b

b
b
b
b

2 OF + SD
b
b

2 OF + SD
b
b
b
b
b
b

2 OF + SD
b
b
b
b
b
b

b BA controller
b UA controller
b

b
b
b

b
b
b

b
b
b

b (vertical or horizontal)
b (drawout)

b (vertical or horizontal)
b (drawout)

b (vertical or horizontal)
b (drawout)

b
b
b

b
b
b

b
b
b
b
b

A-13

Livre 1.indb 13

08/10/2008 18:38:56

Remote-operated
source-changeover systems

Functions
and characteristics

Mechanical and electrical durability


Interpact INS switch-disconnectors
INS250-100
INS250-160
INS250-200
Number of poles
Conventional thermal current (A)
Rated operational current (A)

lth
Ie

Durability (category A)
(ON-CR-OR-CN cycles)

Number of poles
Conventional thermal current (A)
Rated operational current (A)

Durability (category A)
(ON-CR-OR-CN cycles)

lth
Ie

At 60 C
Electrical AC, 50/60 Hz
440-480 V
660-690 V
Mechanical
Electrical AC, 50/60 Hz
440-480 V
660-690 V

INS320

INS400

INS500

INS630

at 60 C
Electrical AC, 50/60 Hz
440-480 V
660-690 V
Mechanical
Electrical AC, 50/60 Hz
440-480 V
660-690 V

3, 4
320
AC22A
320
320
10000
AC22A
1500
1500

3, 4
400
AC22A
400
400
10000
AC22A
1500
1500

3, 4
500
AC22A
500
500
10000
AC22A
1500
1500

3, 4
630
AC22A
630
630
10000
AC22A
1500
1500

AC23A
100
100
AC23A
1500
1500

AC23A
320
320
AC23A
1500
1500

3, 4
160
AC22A
160
160
15000
AC22A
1500
1500

AC23A
160
160
AC23A
1500
1500

AC23A
400
400
AC23A
1500
1500

Compact NS100-NS1600
NS100-250
Number of poles
Rated current In (A)
Mechanical durability
(ON-CR-OR-CN cycles)

3, 4
100 to 250
10000

Electrical durability at In 10000


(ON-CR-OR-CN cycles)
for y 440 V and 480 V
NEMA (2)
Electrical durability at In 1500
(ON-CR-OR-CN cycles)
for U = 500 V to 690 V (2)

3, 4
200
AC22A
200
200
15000
AC22A
1500
1500

INS250

3, 4
100
AC22A
100
100
15000
AC22A
1500
1500

AC23A
200
200
AC23A
1500
1500

AC23A
500
500
AC23A
1500
1500

3, 4
250
AC22A
250
250
15000
AC22A
1500
1500

AC23A
250
250
AC23A
1500
1500

AC23A
630
630
AC23A
1500
1500

NS400-630

NS630bNS1600

3, 4
400 to 630
8000

3, 4
630 to 1600
8000

3000

2000

1500

1500

Masterpact NT06-NT16/NW08-NW63 (1)


NT06- NT12- NW08- NW20 NW25- NW50NT10 NT16
NW16
NW40 NW63
Number of poles
Rated current In (A)
Mechanical durability
(ON-CR-OR-CN cycles)

3, 4
630 to
1600
8000

3, 4
1250 to
1600
8000

3, 4
800 to
1600
10000

3, 4
2000
10000

3, 4
2500 to
4000
10000

3, 4
5000 to
6300
5000

8000
5000
1500
6000
10000
Electrical durability at In 6000
NT16:
(ON-CR-OR-CN cycles)
for y 440 V and 480 V
3000
NEMA (2)
Electrical durability at In 3000
2000
10000
6000
2500
1500
(ON-CR-OR-CN cycles)
NT16:
(2)
for U = 500 V to 690 V
1000
(1) Mechanical and electrical durability not applicable to Masterpact H3 and L versions.
(2) Electrical durability tests carried out with a power factor of 0.8 as per IEC 947-2.
Note:
ON: opening of Normal source
CR: closing of Replacement source
OR: opening of Replacement source
CN: closing of Normal source

A-14

Livre 1.indb 14

08/10/2008 18:38:56

Functions
and characteristics

Remote-operated

Connection and insulation accessories for


Compact NS and INS y 630 A

DB101605

Downstream coupling accessory


This accessory simplifies connection to bars and cables with lugs.
It may be used to couple two circuit breakers (Compact NS100 to 630) or switchdisconnectors (Interpact INS/INV100 to 630) of the same size.
Pitch between outgoing terminals:
b Interpact INS250 and INV100 to 250: 35 mm
b Interpact INS/INV320 to 630: 52.5 mm
b Compact NS100 to 250: 35 mm
b Compact NS400 to 630: 52.5 mm.
For Compact NS circuit-breakers, the downstream coupling accessory can be used
only with fixed versions.

Connection and insulation accessories


The coupling accessory can be fitted with the same connection and insulation
accessories as the circuit breakers and switch-disconnectors.

Possible uses

Downstream coupling
Possible

Outgoing pitch
(mm)

b
b
b
b
b
b

35
35
35
52.5
52.5
52.5

b
b

35
52.5

b
b

35
52.5

Manual source-changeover systems


INS250 (100 to 250 A) with rotary handle
NS100/250 with rotary handle
NS100/250 on base plate with toggle control
INS400/630 (320 to 630 A) with rotary handle
NS400/630 with rotary handle
NS400/630 on base plate with toggle control

Complete source-changeover assembly


INS250 (100 to 250 A)
INS400/630 (320 to 630 A)

Remote-operated source-changeover systems


NS100/250
NS400/630

A-15

Livre 1.indb 15

08/10/2008 18:38:57

Remote-operated
source-changeover systems

Functions
and characteristics

Electrical interlocking
Electrical interlocking is used with the mechanical
interlocking system. It electrically interlocks the two
circuit breakers and implements the time delays
required for proper operation of the system.
An automatic controller may be added to take into
account information from the distribution system.

Electrical interlocking is carried out by an electrical control device.


For Compact NS up to 630 A, electrical interlocking is implemented by the IVE unit
integrating control circuits and an external terminal block. The integrated control
circuits implement the time delays required for correct source transfer.
For Compact NS630b to 1600 and Masterpact, this function can be implemented in
one of two ways:
b using the IVE unit
b by an electrician based on the diagrams presented in the Electrical diagrams part
of this catalogue.

Characteristics of the IVE unit

DB101573

b external connection terminal block:


v inputs: circuit breaker control signals
v outputs: status of the SDE contacts on the Normal and Replacement source
circuit breakers
b 2 connectors for the two Normal and Replacement source circuit breakers:
v inputs:
- status of the OF contacts on each circuit breaker (ON or OFF)
- status of the SDE contacts on the Normal and Replacement source circuit
breakers
v outputs: power supply for operating mechanisms
b control voltage:
v 24 to 250 V DC
v 48 to 415 V 50/60 Hz - 440 V 60 Hz.
The IVE unit control voltage must be same as that of the circuit breaker operating
mechanisms.

IVE unit.

Necessary equipment
For Compact NS100 to 630, each circuit breaker must be equipped with:
b a motor mechanism
b an OF contact
b an SDE contact.
The components are supplied ready for assembly and the circuit breakers prewired.
The prewiring must not be modified.
For Compact NS630b to 1600, each circuit breaker must be equipped with:
b a motor mechanism
b an available OF contact
b a CE connected-position contact (carriage switch) on withdrawable circuit
breakers
b an SDE contact.
For Masterpact NT and NW, each circuit breaker must be equipped with:
b a remote-operation system made up of:
v MCH gear motor
v MX or MN opening release
v XF closing release
v PF ready to close contact
b an available OF contact
b one to three CE connected-position contacts (carriage switches) on drawout circuit
breakers (depending on the installation).

A-16

Livre 1.indb 16

08/10/2008 18:38:57

Functions
and characteristics

Remote-operated
source-changeover systems
Standard configurations

Compact NS, Masterpact NT and NW


Types of mechanical interlocking

Possible combinations Typical electrical diagrams

Diagram no.

QN
0
1
0

51201177
51201178

DB101574

2 devices
QR
0
0
1

Compact NS100 to 630:


b electrical interlocking without emergency
power off (EPO) auxiliaries:
v with EPO by MN
v with EPO by MX
Compact NS630b to 1600:
b electrical interlocking with lockout after fault:
v permanent replacement source (without IVE)
v with EPO by MX (without IVE)
v with EPO by MN (without IVE)
v permanent replacement source (with IVE)
v with EPO by MX (with IVE)
v with EPO by MN (with IVE)
b automatic control without lockout after fault:
v permanent replacement source (without IVE)
v engine generator set (without IVE)
Masterpact NT and NW:
b electrical interlocking with lockout after fault:
v permanent replacement source (without IVE)
v with EPO by MX (without IVE)
v with EPO by MN (without IVE)
v permanent replacement source (with IVE)
v with EPO by MX (with IVE)
v with EPO by MN (with IVE)
b automatic control without lockout after fault:
v permanent replacement source (without IVE)
v engine generator set (without IVE)
b automatic control with lockout after fault:
v permanent replacement source (with IVE)
v engine generator set (with IVE)
b BA/UA controller (with IVE)

51201179

51201180
51201181
51201182
51201183
51201184
51201185
51201186
51201187

51201139
51201140
51201141
51201142
51201143
51201144
51156226
51156227
51156904
51156905
51156903

Masterpact NW only
Types of mechanical interlocking

Possible combinations Typical electrical diagrams

Diagram no.

3 devices: 2 Normal sources and 1 Replacement source

DB101576

DB101575

QN1
0
1
0

QN2
0
1
0

QR
0
0
1

3 devices: 2 Normal sources and 1 Replacement source with source selection


QN1
QN2
QR
0
0
0
1
0
0
0
0
1
1
1
0
0
1
0

b electrical interlocking:
v without lockout after fault
v with lockout after fault

51156906
51156907

b automatic control with engine generator set:


v without lockout after fault (with MN)
v with lockout after fault (with MN)

51156908
51156909

b electrical interlocking:
v without lockout after fault
v with lockout after fault

51156910
51156911

3 devices: 3 sources, only one device


DB101577

QS1
0
1
0
0

QS2
0
0
1
0

QS3
0
0
0
1

DB101578

3 devices: 2 sources + 1 coupling


QS1
QC
QS2
b electrical interlocking:
0
0
0
v without lockout after fault
1
0
1
v with lockout after fault
1
1
0
b automatic control with lockout after fault
0
1
1
(1)
1
0
0
(1)
0
0
1
(1) possible by forcing
operation
Lockout after fault option. This option makes it necessary to manually reset the device following fault tripping.

51156912
51156913
51156914

A-17

Livre 1.indb 17

08/10/2008 18:38:58

Functions
and characteristics

By combining a remote-operated source-changeover


system with an integrated BA
or UA automatic controller, it is possible to
automatically control source transfer according to userselected sequences.
These controllers can be used on source-changeover
systems comprising 2 circuit breakers.
For source-changeover systems comprising 3 circuit
breakers, the automatic control diagram must be
prepared by the installer as a complement to to
diagrams provided in the electrical diagrams section
of this catalogue.

Associated controllers
Controller selection

Controller

BA

Compatible circuit breakers

UA

All Compact NS and


Masterpact circuit breakers

4-position switch
Automatic operation
Forced operation on Normal source
Forced operation on Replacement source
Stop (both Normal and Replacement sources off)

b
b
b
b

b
b
b
b

b
b
b
b
b

Automatic operation
Monitoring of the Normal source and automatic transfer
Generator set startup control
Delayed shutdown (adjustable) of generator set
Load shedding and reconnection of non-priority circuits
Transfer to the Replacement source if one of the phases
of the Normal phase is absent

Test
By opening the P25M circuit breaker supplying the controller
By pressing the test button on the front of the controller

b
b

PB100855

Indications
Circuit breaker status indication on the front of the controller:
on, off, fault trip
Automatic mode indicating contact

Other functions

BA controller.

Selection of type of Normal source


(single-phase or three-phase) (1)
Voluntary transfer to Replacement source (e.g. energy
management commands)
During peak-tariff periods (energy management commands)
forced operation on Normal sourceif Replacement source not
operational
Additional contact (not part of controller).
Transfer to Replacement source only if contact is closed. (e.g.
used to test the frequency of UR).
Setting of maximum startup time for the replacement source

b
b

b
b

Options
Communication option
PB100856

Power supply
Control voltages (2)

110 V
220 to 240 V 50/60 Hz
380 to 415 V 50/60 Hz
and 440 V 60 Hz

b
b
b

b
b
b

0.35 Un y voltage y 0.7 Un


0.5 Un y voltage y 0.7 Un
voltage u 0.85 Un

b
b
b

Operating thresholds
Undervoltage
Phase failure
Voltage presence

IP degree of protection (EN 60529) and IK degree of protection against


external mechanical impacts (EN 50102)

UA controller.

Front
Side
Connectors
Front

IP40
IP30
IP20
IK07

b
b
b
b

b
b
b
b

Characteristics of output contacts (dry, volt-free contacts)


Rated thermal current (A)
8
Minimum load
10 mA at 12 V
Output contacts:
Position of the Auto/Stop switch
Load shedding and reconnection order
Generator set start order.

b
b
b
AC
DC
Utilisation category (IEC 947-5-1)
AC12 AC13 AC14 AC15 DC12 DC13
Operational current (A)
24 V
8
7
5
5
8
2
48 V
8
7
5
5
2
110 V
8
6
4
4
0.6
220/240 V
8
6
4
3
250 V
0.4
380/415 V
5
440 V
4
660/690 V
(1) For example, 220 V single-phase or 220 V three-phase.
(2) The controller is powered by the ACP auxiliaries control plate. The same voltage must be used
for the ACP plate, the IVE unit and the circuit-breaker operating mechanisms. If this voltage is the
same as the source voltage, then the Normal and Replacement sources can be used directly
for the power supply. If not, an isolation transformer must be used.

A-18

Livre 1.indb 18

08/10/2008 18:38:59

Associated controllers

Functions
and characteristics

Controller installation

ACP auxiliaries control plate


PB100857

The auxiliaries control plate provides in a single unit:


b protection for the BA or UA controller with two highly limiting P25M circuit breakers
(infinite breaking capacity) for power drawn from the AC source
b control of circuit-breaker ON and OFF functions via two relay contactors
b connection of the circuit breakers to the BA or UA controller via a built-in terminal
block.
Control voltages
b 110 V 50/60 Hz
b 220 to 240 V 50/60 Hz
b 380 to 415 V 50/60 Hz and 440 V 60 Hz.
The same voltage must be used for the ACP plate, the controller and the circuitbreaker operating mechanisms.
Installation
Connection between the ACP auxiliaries control plate and the IVE electricalinterlocking unit may use:
b wiring done by the installer
b prefabricated wiring (optional).

Installation of the BA and UA controllers


The BA and UA controllers may be installed in one of two manners:
b directly mounted on the ACP auxiliaries control plate
b mounted on the front panel of the switchboard.
The length of the connection between the ACP plate and the controller must not
exceed two metres. Wiring is done by the installer.

DB101579

ACP auxiliaries control plate.

DB101580

Mounting on the ACP plate.

Mounting on the front panel of the switchboard.

A-19

Livre 1.indb 19

08/10/2008 18:39:01

Functions
and characteristics

Associated controllers

The BA controller is used to create simple sourcechangeover systems that switch from one source to
another depending on the presence of voltage UN on
the Normal source.
It is generally used to manage two permanent sources
and can control Compact NS and Masterpact NT/NW
circuit breakers and switch-disconnectors.

Operating modes

BA controller

A four-position switch may be used to select:


b automatic operation
b forced operation on the Normal source
b forced operation on the Replacement source
b stop (both Normal and Replacement sources off).

Setting the time delays

PB100858

Time delays are set on the front of the controller.


t1. delay between detection that the Normal source has failed and the transmission
of the order to open the Normal source circuit breaker (adjustable from 0.1 to 30
seconds).
t2. delay between detection that the Normal source has returned and the
transmission of the order to open the Replacement source circuit breaker
(adjustable from 0.1 to 240 seconds).

Circuit breaker commands and status indications


The status of the circuit breakers is indicated on the front of the controller.
b ON, OFF, fault.
A built-in terminal block may be used to connect the following input/output signals:
b inputs:
v voluntary order to transfer to source R (e.g. for special tariffs, etc.)
v additional control contact (not part of the controller). Transfer to the Replacement
source takes place only if the contact is closed (e.g. used to test the frequency of UR,
etc.)
b outputs:
indication of operation in automatic or stop mode via changeover contacts.

Test

DB101779

It is possible to test the operation of the BA controller by turning OFF (opening) the
P25M circuit breaker for the Normal source and thus simulating a failure of voltage
U N.

Front of the BA controller.

A-20

Livre 1.indb 20

08/10/2008 18:39:02

Functions
and characteristics

Associated controllers
BA controller
operating sequences

Switch set to the N position (forced


operation on the Normal source)
DB101584

DB101582

Switch set to Auto (automatic operation and special-tariff mode)

Switch set to the Stop position

DB101588

DB101586

Switch set to the R position (forced operation on the


Replacement source)

Key
UN : Normal source voltage
UR : Replacement source voltage
N : Normal source circuit breaker
R : Replacement source circuit breaker

WAITING The system exits this mode when the operating mode is modified or
when an external event occurs (e.g. failure or return of UN).

1 The number sends to the indicated step when


the condition is true.

A-21

Livre 1.indb 21

08/10/2008 18:39:03

Associated controllers

The UA controller is used to create a sourcechangeover system integrating the following automatic
functions:
b transfer from one source to another depending on
the presence of voltage UN on the Normal source
b startup of an engine generator set
b shedding and reconnection of non-priority circuits
b transfer to the Replacement source if one of the
phases on the Normal source fails.
The UA controller can control Compact NS and
Masterpact NT/NW devices.

Operating modes

PB100858

Functions
and characteristics

UA controller

A four-position switch may be used to select:


b automatic operation
b forced operation on the Normal source
b forced operation on the Replacement source
b stop (both Normal and Replacement sources off, then manual operation).

Setting the time delays


Time delays are set on the front of the controller.
t1. delay between detection that the Normal source has failed and the transmission
of the order to open the Normal source circuit breaker (adjustable from 0.1
to 30 seconds).
t2. delay between detection that the Normal source has returned and the
transmission of the order to open the Replacement source circuit breaker
(adjustable from 0.1 to 240 seconds).
t3. delay following opening of QN with load shedding and before closing of QR
(adjustable from 0.5 to 30 seconds).
t4. delay following opening of QR with load reconnection and before closing of QN
(adjustable from 0.5 to 30 seconds).
t5. delay for confirmation that UN is present before shutting down the engine
generator set (adjustable from 60 to 600 seconds).
t6. delay before startup of the engine generator set (120 or 180 seconds).

Commands and indications


Circuit breaker status indications on the front of the controller:
b ON, OFF, fault.
A built-in terminal block may be used to connect the following input/output signals:
b inputs:
v voluntary order to transfer to source R (e.g. for special tariffs, etc.)
v additional control contact (not part of the controller). Transfer to the Replacement
source takes place only if the contact is closed (e.g. used to test the frequency of UR,
etc.)
b outputs:
v control of an engine generator set (ON / OFF)
v shedding of non-priority circuits
v indication of operation in automatic mode via changeover contacts.

Distribution-system settings

DB101778

Three switches are used to:


b select the type of Normal source, whether single-phase or three-phase
(e.g. 240 V single-phase or 240 V three-phase)
b select whether to remain (or not) on the Normal source if the Replacement
source is not operational during operation on special tariffs
b select the maximum permissible startup time for the engine generator set during
operation on special tariffs (120 or 180 seconds).

Test
A pushbutton on the front of the controller may be used to test transfer from the
Normal source to the Replacement source, then the return to the Normal source.
The test lasts approximately three minutes.

COM communications option

Front of the UA controller.

Using the internal bus protocol, this option may be used to remote the following
information:
b circuit breaker status (ON, OFF, fault trip)
b presence of the Normal and Replacement voltages
b presence of an order for forced operation (e.g. special tariffs)
b settings and configuration information
b status of non-priority circuits (loads shed or not)
b position of the switch (stop, auto, forced operation on the Normal source, forced
operation on the Replacement source).

A-22

Livre 1.indb 22

08/10/2008 18:39:04

Functions
and characteristics

Associated controllers
UA controller
operating sequences

Switch set to the N position (forced operation on


the Normal source)

DB101590

DB101592

Switch set to the R position (forced operation on the Replacement source)

DB101594

Switch set to the Stop position

WAITING The system exits this mode when the


operating mode is modified or when an
external event occurs (e.g. failure or return
of UN).
When the UA controller is not energised, the output for
generator set startup is activated).
Key
UN : Normal source voltage
UR : Replacement source voltage
N : Normal source circuit breaker
R : Replacement source circuit breaker

A-23

Livre 1.indb 23

08/10/2008 18:39:05

Functions
and characteristics

Associated controllers
UA controller
Operating sequences

DB117634

Switch set to the Auto position (special-tariff mode)


WAITING The system exits this mode when the
operating mode is modified or when an
external event occurs (e.g. failure or return
of UN).
When the UA controller is not energised, the output for
generator set startup is activated).

Key
UN : Normal source voltage
UR : Replacement source voltage
N : Normal source circuit breaker
R : Replacement source circuit breaker
B : Penalties accepted (N ON), i.e. B = 1

The number sends to the indicated step when


the condition is true.

A-24

Livre 1.indb 24

08/10/2008 18:39:06

Functions
and characteristics

Associated controllers
UA controller
Operating sequences

DB101598

Switch set to the Auto position (automatic operation and test mode).

WAITING The system exits this mode when the


operating mode is modified or when an
external event occurs (e.g. failure or return
of UN).
When the UA controller is not energised, the output for
generator set startup is activated).
Key
UN : Normal source voltage
UR : Replacement source voltage
N : Normal source circuit breaker
R : Replacement source circuit breaker
B : Penalties accepted (N ON), i.e. B = 1
(*) The test lasts 180 seconds.

The number sends to the indicated step when


the condition is true.

A-25

Livre 1.indb 25

08/10/2008 18:39:06

Functions
and characteristics

Operating sequences

DB101600

IVE unit

Symbols
QN : Normal Compact C circuit breaker equipped
for remote operation (motor mechanism)
QR : Replacement Compact C circuit breaker
equipped for remote operation (motor
mechanism)
ON : Circuit breaker QN opening order
OR : Circuit breaker QR opening order
IN : Circuit breaker QN closing order
IR : Circuit breaker QR closing order
L1 : Faulty Normal indication LED
L2 : Faulty Replacement indication LED

Key
O: OFF (circuit open)
I: ON (circuit closed
: either ON or OFF.

Note:
Following all trips (overload, short-circuit, earth-leakage fault, voluntary trip), a manual reset on
the front of the motor mechanism is required.

A-26

Livre 1.indb 26

08/10/2008 18:39:07

Functions
and characteristics

Operating sequences

DB101602

BA controller

Inputs
UN : Normal source voltage
UR : Replacement source voltage
KT : order for forced-operation on R
KR : additional check before transfer
Outputs
QN : Normal source circuit breaker
QR : Replacement source circuit breaker

DB101604

UA controller

Inputs
UN : Normal source voltage
UR : Replacement source voltage
KT : order for forced-operation on R
KR : additional check before transfer
Outputs
KG : order to the genset
SH : load-shedding order
QN : Normal source circuit breaker
QR : Replacement source circuit breaker

Key
O: OFF (circuit open)
I: ON (circuit closed
: either ON or OFF.

Important
If UR is not ON when the transfer order is issued (KT or UN), the sequence is not carried out.
If KR status is not ON when the transfer order is issued (KT or UN), the transfer sequence is
carried out later when KR status becomes I.

A-27

Livre 1.indb 27

08/10/2008 18:39:08

Functions
and characteristics

COM communications option

DB101928

Communications option for Compact NS


and Masterpact NT/NW
The COM communications option is compatible with all the source-changeover
systems for Compact NS100 to 1600 and Masterpact NT/NW circuit breakers and
switch-disconnectors.
It can be used to remote status information. It may not be used to operate the circuit
breakers (only possible locally on the front of the UA150 controller).
Masterpact and Compact NS630b to 1600 circuit breakers and switch-disconnectors
are compatible with the Modbus ECO COM option.
Depending on the trip units or control units used, the COM option may also be used
to analyse distribution-system parameters required for the operating and
maintenance assistance.

Circuit breaker communication


SwitchCircuit
disconnector breaker

Compact NS100/1600 status indications


ON / OFF
Fault trip
Connected / disconnected position

b
b

b
b
b

Masterpact NT/NW status indications


ON / OFF
Fault trip
Connected / disconnected position

b
b

b
b
b

Operating and maintenance assistance


STR53UE trip unit for Compact NS400/630
Current readings
Phase and neutral rms currents
Current on the most heavily loaded phase
Alarm readings
Overload
Tripping cause (overload, short-circuit, etc.)
Positions of setting dials

Operating and maintenance aids

b
b
b
b
b

Digipact

Modbus

Measurement
Current
A
P
H
A
P
H
Voltages, frequency, power, etc.
P
H
P
H
Power quality: fundamental, harmonics
H
Programming of demand metering
P
H
Fault readings
Type of fault
A
P
H
Interrupted current
P
H
Waveform capture
On faults
H
On demand or programmed
H
Histories and logs
Trip history
P
H
Alarm history
P
H
Event logs
P
H
Indicators
Counter operation
A
P
H
A
P
H
Contact wear
P
H
Maintenance register
P
H
Note:
see the description of the Micrologic control units for further details on protection and alarms,
measurements, waveform capture, histories, logs and maintenance indicators.

A-28

Livre 1.indb 28

08/10/2008 18:39:11

Functions
and characteristics

COM communications option

Automatic source-changeover controller


UA150

Status indications
Normal source
ON / OFF
Circuit breaker ON
Fault trip (SDE)
Voltage presence
Replacement source
Circuit breaker ON
Fault trip (SDE)
Voltage presence
Status of R voltage contact
Controller
Automatic mode
Normal mode
Replacement mode
Stop mode
Testing
Replacement engine generator set
Genset failure
Genset OFF
Genset ON
Shedding of non-priority circuits
Reconnection of non-priority circuits

b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b

Settings
Time delay t1 for validation of UN absence

Time delay t2 for validation of UN return


Time delay t3 for wait between opening of N and closing of R
Time delay t4 for wait between opening of R and closing of N
Time delay t5 for wait between return of UN and order for genset shutdown
Time delay t6 for wait before declaring genset failure
Penalties accepted to avoid special tariff transfer

b
b
b
b
b
b

A-29

Livre 1.indb 29

08/10/2008 18:39:12

TOOLS
schneider-electric.com

CAD software and tools

This international site allows you


to access all the Schneider Electric
products in just  clicks
via comprehensive range datasheets, with direct links to:
p complete library: technical
documents, catalogs, FAQs,
brochures
p selection guides from
the e-catalog.
p product discovery sites and
their Flash animations.
You will also find illustrated
overviews, news to which you
can subscribe, the list of country
contacts

The CAD software and tools


enhance productivity
and safety. They help you create
your installations by simplifying
product choice through easy
browsing in the Schneider Electric
offers.
Last but not least, they optimise
use of our products while also
complying with standards and proper
procedures.

Livre 1.indb 2

08/10/2008 18:39:13

Source-changeover systems

Dimensions

Presentation
Functions and characteristics

2
A-1

Manual source-changeover systems

B-2

Remote-operated source-changeover systems

B-9

Interlocking of direct rotary handles


Interlocking of extended rotary handles
Interlocking of toggles
Complete source-changeover assembly
Downstream coupling accessory

Interlocking on a base plate


Interlocking using connecting rods
Interlocking using cables
IVE electrical-interlocking unit BA and UA automatic controllers
Electrical diagrams
Catalogue numbers and order forms

B-2
B-3
B-5
B-6
B-7

B-9
B-13
B-15
B-20
C-1
D-1

B-1

312E3100TDM.indd 1

22/10/2008 15:27:35

Manual source-changeover
systems

Dimensions

Interlocking of direct rotary handles


Compact NS100 to 1600

DB101608

Front-panel cutout
DB101607

DB101606

Dimensions

Dimensions (mm)
Type
NS100/160/250N/H/L
NS400/630N/H/L

A
325
416

B
90
115

C
87.5
100

D
175
200

F
156
210

G
133
157

H
9.25
5

J
9
24.6

K
295
386

L
75.5
100

M
150
175

N
75
74.5

P
155
179

Interpact INS/INV250 100 to 250 A / Interpact INS/INV320/400/500/630

DB101611

Front-panel cutout
DB101610

DB101609

Dimensions

Dimensions (mm)
Type
A
B
C
90
87.5
INS/INV250 100/160/250 A
325
115
100
INS/INV320/400/500/630
416
Note: X et Y are the symmetry planes for a 3-pole device.

D
175
200

F
156
210

G
106
130

H
17.5
22.5

K
295
386

L
75.5
100

M
150
175

N
75
74.5

P
131
160.4

B-2

Livre 1.indb 2

08/10/2008 18:39:15

Manual source-changeover
systems

Dimensions

Interlocking of extended rotary handles


Compact NS100 to 630

DB107757

Front-panel cutout
DB101607

DB101612

Dimensions

Dimensions (mm)
Type
NS100/160/250N/H/L
NS400/630N/H/L

A
325
416

B
90
115

C
87.5
100

D
175
200

F
156
210

G min
185
204

G max
600
600

H
9.25
5

J
9
24.6

P
25.5
30.8

Q
25.5
30.8

Interpact INS40/63/80/100/125/160 / Interpact INS/INV250 100 to 250 A / Interpact INS/INV320/400/500/630

DB107756

Front-panel cutout
DB101615

DB101614

Dimensions

Dimensions (mm)
Type
INS40/63/80
INS100/125/160
INS/INV250 100/160/250 A
INS320/400/500/630

A
325
325
325
416

B
90
90
90
115

C
87.5
87.5
87.5
100

D
175
175
175
200

F
156
156
156
210

G min
155
200
185
204

G max
396
441
600
600

H
0
0
17.5
22.5

P
25.5
25.5
25.5
30.8

Q
25.5
25.5
25.5
30.8

B-3

Livre 1.indb 3

08/10/2008 18:39:16

Manual source-changeover
systems

Dimensions

Interlocking of extended rotary handles


Compact NS630b to 1600

DB101618

DB101617

Dimensions

DB101619

Front-panel cutout

Dimensions (mm)
Type
NS630b/800/1000/1200/1600

A
411

B
63.5

C
98

D
175

F
280

G min
218

G max
605

H
25

J
24

P
25.5

Q
25.5

R
64

B-4

Livre 1.indb 4

08/10/2008 18:39:17

Manual source-changeover
systems

Dimensions

Interlocking of toggles
Compact NS100 to 630
4 poles

4 poles on left

DB101623

3 poles on left
DB101624

DB101620

Front-panel cutout

DB101622

3 poles
DB101621

Dimensions

Dimensions (mm)
Type
NS100/160/250N/H/L
NS400/630N/H/L

C2
54
92.5

C3
108
184

L
52.5
70

L16
140
185

L17
245
325

L18
280
370

R2
54
71.5

R18
89
116.5

R19
140
185

P5
83
107

P
115
144

B-5

Livre 1.indb 5

08/10/2008 18:39:18

Manual source-changeover
systems

Dimensions

Complete source-changeover assembly


Assembly for INS250 100 to 250 A / Assembly for INS320/400/500/630
DB101626

DB101625

Dimensions

DB101627

Front-panel cutout

Dimensions (mm)
Type
INS250
INS320/630

A
60.4
82.5

B
130.4
175

C
296
395

D
68
102.5

E
136
205

F
131
155

G
61.8
87

H
279.3
383.7

I
42
64

J
84
128

K
156
210

L
186.5
213

M
5.5
8

N
50
50

DB101651

DB101650

Dimensions of the complete source-changeover assembly with an extended handle

Dimensions (mm)
DB107743

Type
INS250
INV100/250
INS320/630
INV320/630

A
60.4

B
130.4

C
295

E
136

K
156

L
138.5

M
631

N
50

82.5

175

395

205

210

162.5

658

75

P
100

Mmax
567.5

Mmin
195

Q
64

150

593

220.5

64

Dimensions (mm)
Type
INS250
INV100/250
INS320/630
INV320/630

Note: Lines X and Y indicate the axes of symmetry of the switch-disconnector.


Reference plane Z corresponds to the back of the switch-disconnector.

B-6

Livre 1.indb 6

08/10/2008 18:39:20

Manual source-changeover
systems

Dimensions

Downstream coupling accessory


Compact NS100 to NS630 (only for Compact NS fixed devices)

DB101629

DB101628

Dimensions

Connection

DB101630

DB101631

Dimensions

Dimensions (mm)
Type
NS100/160/250
NS400/630

G2
118
165.9

G3
181.5
265.7

G28
238
339.5

G29
96
143.5

G30
140
188.5

G52
156
227.5

K1
35
45

K2
35
52.5

K3
51
75

K4
156
210

K8
70
113.5

K9
170
250.7

K16
8
3.75

L28
320
420

L29
99.5
127.5

L30
300
400

L31
89.5
117.5

L32
1
11.2

L33
123
187.5

L34
139.5
-

L35
74.5
96.5

L36
19.5
26

L37
87.5
115

L39
9.5
22.5

L40
140
210

T
6
6

Dimensions (mm)
Type
NS100/160/250
NS400/630

Note: coupling accessory: only for changeover systems using fixed versions of Compact NS circuit breakers.

B-7

Livre 1.indb 7

08/10/2008 18:39:21

Manual source-changeover
systems

Dimensions

Downstream coupling accessory


Interpact INS250 100 to 250 A / Interpact INS320/400/500/630

DB101633

DB101632

Dimensions

DB101902

Connection

DB101901

Dimensions

Dimensions (mm)
Type
INS250-100/160/200/250
INS320/400/500/630

G2
105.5
141

G3
169
240.7

G28
225.5
315

G29
83.5
119

G30
127.5
163.5

G52
143.5
202.5

K1
35
45

K2
35
52.5

K3
51
75

K4
156
210

K8
57.5
88.5

K9
157.5
225.7

K16
25.5
26.25

L28
320
420

L29
82
105

L30
300
400

L31
72
95

L32
16.5
11.2

L33
123
187.5

L34
139.5
-

L35
74.5
98.5

L36
21.5
26

L37
70
92.5

L39
8.5
0

L40
140
210

T
6
6

Dimensions (mm)
Type
INS250-100/160/200/250
INS320/400/500/630

B-8

Livre 1.indb 8

08/10/2008 18:39:22

Remote-operated
source-changeover systems

Dimensions

Interlocking on a base plate


Compact NS100 to 250

DB101636

Withdrawable device

DB101635

Fixed device

DB101634

Dimensions, 3 or 4 poles

(*) Short terminal shields are


mandatory.

DB101638

Horizontal mounting

DB101637

Vertical mounting

Dimensions (mm)
Type
NS100/160/250N/H/L
NS400/630N/H/L

G50
137.5
180

G51
285
360

H20
62.5
100

H21
97
152

H22
45.5
83

H23
73
123

H42
60
60

H43
120
120

H44
144.5
189

H45
300
378

H46
37
77

K25
156
210

K35
210.5
282.5

L31
110.5
150.5

L32
354
466

P7
25
25

P8
45
45

P9
75
100

P32
178
250

P33
143
215

P50
25
25

P52
99.5
123

P54
21
21

T9
9
9

T10
6
6

U
y 32
y 32

K36
300
400

Dimensions (mm)
Type
NS100/160/250N/H/L
NS400/630N/H/L

Note: coupling accessory: only for changeover systems using fixed versions of Compact NS circuit breakers.

B-9

Livre 1.indb 9

08/10/2008 18:39:24

Remote-operated
source-changeover systems

Dimensions

Interlocking on a base plate


Compact NS400 to 630
DB101640

Fixed device

DB101639

Dimensions, 3 or 4 poles

DB101641

Withdrawable device

Note: coupling accessory: only for changeover systems using fixed versions of Compact NS
circuit breakers.

Horizontal mounting
DB101638

DB101637

Dimensions
Vertical mounting

(*) Short terminal shields are mandatory.

Note: dimensions see p.B-9.

B-10

Livre 1.indb 10

08/10/2008 18:39:25

Remote-operated
source-changeover systems

Dimensions

Interlocking on a base plate


Normal and Replacement source devices: NS100 to NS250
Front-panel cutout
DB107744

DB101642

Dimensions

Normal and Replacement source devices: NS400 to NS630


Front-panel cutout
DB107745

DB101644

Dimensions

Note for Compact NS:


For dimensions with the accessories (IP40 escutcheons and Vigi escutcheon protection collars), see Catalogue Compact.

B-11

Livre 1.indb 11

08/10/2008 18:39:26

Remote-operated
source-changeover systems

Dimensions

Interlocking on a base plate

NS400 to NS630 as the Normal device, NS100 to NS250 as the Replacement device
Front-panel cutout
DB107746

DB101646

Dimensions

B-12

Livre 1.indb 12

08/10/2008 18:39:26

Dimensions

Remote-operated
source-changeover systems
Interlocking using connecting rods

Two Compact NS630b to NS1600 devices one above the other


Withdrawable devices
DB101655

DB107747

Fixed devices

Two Masterpact NT devices one above the other


Withdrawable devices
DB101655

DB101656

Fixed devices

B-13

Livre 1.indb 13

08/10/2008 18:39:27

Dimensions

Remote-operated
source-changeover systems
Interlocking using connecting rods

Two Masterpact NW devices one above the other


Withdrawable devices
DB107749

DB107748

Fixed devices

B-14

Livre 1.indb 14

08/10/2008 18:39:28

Dimensions

Remote-operated
source-changeover systems
Interlocking using cables

Two Compact NS630b to NS1600 devices side-by-side


Withdrawable devices
DB101662

DB101661

Fixed devices

Two Masterpact NT devices side-by-side


Drawout devices

DB101663

DB101662

Fixed devices

Combination of two Masterpact NT and NW devices side-by-side


Drawout devices
DB101665

DB101664

Fixed devices

B-15

Livre 1.indb 15

08/10/2008 18:39:30

Dimensions

Remote-operated
source-changeover systems
Interlocking using cables

Two Masterpact NW devices side-by-side


Drawout devices
DB101667

DB101666

Fixed devices

Three Masterpact NW devices side-by-side

DB101668

Fixed devices

DB101669

Drawout devices

B-16

Livre 1.indb 16

08/10/2008 18:39:31

Dimensions

Remote-operated
source-changeover systems
Interlocking using cables

Two Compact NS630b to NS1600 devices one above the other


Withdrawable devices

DB107750

DB101671

Fixed devices

Two Masterpact NT devices one above the other


Drawout devices
DB101671

DB101672

Fixed devices

B-17

Livre 1.indb 17

08/10/2008 18:39:32

Dimensions

Remote-operated
source-changeover systems
Interlocking using cables

Two Masterpact NW devices one above the other


Drawout devices
DB107752

DB107751

Fixed devices

Two Masterpact NT and NW devices one above the other


Drawout devices
DB107752

DB107753

Fixed devices

B-18

Livre 1.indb 18

08/10/2008 18:39:34

Dimensions

Remote-operated
source-changeover systems
Interlocking using cables

Three Masterpact NW devices one above the other


Drawout devices
DB107755

DB107754

Fixed devices

B-19

Livre 1.indb 19

08/10/2008 18:39:35

Remote-operated
source-changeover systems

Dimensions

IVE electrical-interlocking unit


BA and UA automatic controllers

DB101678

Door cutout for BA/UA controllers


DB101682

DB101680

DB101681

ACP auxiliaries control plate and BA/UA controller

DB101683

DB101679

IVE electrical-interlocking unit

(1) Cutout according DIN 43700 standard.

B-20

Livre 1.indb 20

08/10/2008 18:39:36

B-21

Livre 1.indb 21

08/10/2008 18:39:36

TOOLS
schneider-electric.com

Training

This international site allows you


to access all the Schneider Electric
products in just  clicks
via comprehensive range datasheets, with direct links to:
p complete library: technical
documents, catalogs, FAQs,
brochures
p selection guides from
the e-catalog.
p product discovery sites and
their Flash animations.
You will also find illustrated
overviews, news to which you
can subscribe, the list of country
contacts

Training allows you to acquire


the Schneider Electric expertise
(installation design, work with power
on, etc.) for increased efficiency
and a guarantee of improved
customer service.
The training catalogue includes
beginners courses in electrical
distribution, knowledge
of MV and LV switchgear, operation
and maintenance of installations,
design of LV installations to give
but a few examples.

Livre 1.indb 2

08/10/2008 18:39:38

Source-changeover systems

Electrical diagrams

Presentation
Functions and characteristics
Dimensions

2
A-1
B-1

Remote-operated source-changeover systems

C-2

2 Compact NS100/1600 or Masterpact NT/NW devices


2 Compact NS100/630 devices
2 Compact NS630b/1600 devices
2 Masterpact NT or NW devices
3 Masterpact NW devices

C-2
C-3
C-6
C-14
C-24

Source-changeover systems with automatic controllers C-33


2 Compact NS100/1600 or Masterpact NT/NW devices
2 Masterpact NT or NW devices
Catalogue numbers and order forms

C-33
C-36
D-1

C-1

Livre 1.indb 1

08/10/2008 18:39:38

Electrical diagrams

Remote-operated
source-changeover systems
2 Compact NS100/1600 or
Masterpact NT/NW devices

Electrical interlocking by the IVE unit

DB101689

Recommended electrical control system

(1) The normal and replacement source transfer orders must be interlocked electrically.
(2) Operating diagram: the SDE fault-trip signals are transmitted to the IVE unit. The SDE
auxiliary contacts are mounted in the circuit breakers.

Legends
ON Normal source opening order
OR Replacement source opening order
FN Normal source closing order
FR Replacement source closing order
L1 Normal source fault-trip signal
L2 Replacement source fault-trip signal
N Normal source auxiliary wiring connector
R Replacement source auxiliary wiring connector

Note:
diagram shown with circuits de-energised, circuit breakers open
and relays in normal position.

C-2

Livre 1.indb 2

08/10/2008 18:39:39

Electrical diagrams

Remote-operated
source-changeover systems
2 Compact NS100/630 devices
Diagram no. 51201177

Source-changeover system without automatic-control system


Local reset
DB101659

DB101686

Without auxiliaries for emergency off

DB101660

Voluntary remote reset

Automatic reset

ATTENTION

(1) Prefabricated wiring: cannot be modified.

The diagram shows the electrical wiring for circuit breakers.


When wiring the SDE with switch-disconnectors, reverse
the wires connected to terminals 82 and 84.
Legends
QN Normal source Compact NS equipped with motor mechanism
QR Replacement source Compact NS equipped with motor

mechanism
SDE fault-trip indication contact
IVE electrical interlocking and terminal block unit
MT motor mechanism
OF2 breaker ON/OFF indication contact
RN reset order for breaker QN
RR reset order for breaker QR

States permitted by mechanical interlocking system


Normal
Replacement
0
0
1
0
0
1
Note:
diagram shown with circuits de-energised, circuit breakers open
and relays in normal position.

C-3

Livre 1.indb 3

08/10/2008 18:39:39

Electrical diagrams

Remote-operated
source-changeover systems
2 Compact NS100/630 devices
Diagram no. 51201178

Source-changeover system without automatic-control system

DB112553

With emergency off by MN release and automatic reset

Automatic reset

ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, reverse
the wires connected to terminals 82 and 84.

Legends
QN Normal source Compact NS equipped with motor

mechanism
QR Replacement source Compact NS equipped with motor

mechanism
MN undervoltage release
OF2 breaker ON/OFF indication contact
SDE fault-trip indication contact
MT motor mechanism
IVE electrical interlocking and terminal block unit
BP emergency off button with latching
KA3 auxiliary relay
F1 auxiliary power supply circuit breaker

(1) Prefabricated wiring supplied.


(2) Independent auxiliary source.

States permitted by mechanical interlocking system


Normal
Replacement
0
0
1
0
0
1
Note:
after a fault trip, the breaker must be reset manually by pressing
its reset button.
Diagram shown with circuits de-energised, circuit breakers open
and relays in normal position.

C-4

Livre 1.indb 4

08/10/2008 18:39:40

Electrical diagrams

Remote-operated
source-changeover systems
2 Compact NS100/630 devices
Diagram no. 51201179

Source-changeover system without automatic-control system

DB101691

With emergency off by MX release and automatic reset

Automatic reset

ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, reverse
the wires connected to terminals 82 and 84.

Legends
QN Normal source Compact NS equipped with motor

mechanism
QR Replacement source Compact NS equipped with motor

mechanism
SDE fault-trip indication contact
OF2 breaker ON/OFF indication contact
MX shunt release
MT motor mechanism
IVE electrical interlocking and terminal block unit
KA1 time-delayed auxiliary relays
KA2 time-delayed auxiliary relays
F1 auxiliary power supply circuit breaker
F2 auxiliary power supply circuit breaker

(1) Prefabricated wiring supplied


(2) This source can be:

b the source present in the case of voltage monitoring

b an independent source.
In this case, the MX release must be protected.
(3) The reset orders must be delayed by 0.3 seconds.

States permitted by mechanical interlocking system


Normal
Replacement
0
0
1
0
0
1
Note:
after a fault trip, the breaker must be reset manually by pressing
its reset button.
Diagram shown with circuits de-energised, circuit breakers open
and relays in normal position.

C-5

Livre 1.indb 5

08/10/2008 18:39:41

Electrical diagrams

Remote-operated
source-changeover systems
2 Compact NS630b/1600 devices
Diagram no. 51201180

DB101693

Electrical interlocking

ATTENTION

(1) Not to be wired on fixed version.

The diagram shows the electrical wiring for circuit breakers.


When wiring the SDE with switch-disconnectors, connect
the SDE to terminals 81 and 84.

States permitted by mechanical interlocking system


Legends
QN Normal source Compact NS630b to 1600
QR Replacement source Compact NS NS630b to 1600
OF... breaker ON/OFF indication contact
SDE1fault-trip indication contact
CE1 connected-position indication contact (carriage switch)
F1 auxiliary power supply circuit breaker
ON Normal source opening order
OR Replacement source opening order
FN Normal source closing order (0.25 second delay)
FR Replacement source closing order (0.25 second delay)
MT Motor Mechanism

Normal
Replacement
0
0
1
0
0
1
Note:
after a fault trip, the breaker must be reset manually by pressing
its reset button.
Diagram shown with circuit breakers in connected position, open,
charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MX, MN...).

C-6

Livre 1.indb 6

08/10/2008 18:39:41

Electrical diagrams

Remote-operated
source-changeover systems
2 Compact NS630b/1600 devices
Diagram no. 51201181

DB101695

Electrical interlocking with emergency off by shunt release

ATTENTION

(1) Not to be wired on fixed version.

The diagram shows the electrical wiring for circuit breakers.


When wiring the SDE with switch-disconnectors, connect
the SDE to terminals 81 and 84.

Legends
QN Normal source Compact NS630b to 1600
QR Replacement source Compact NS NS630b to 1600
OF... breaker ON/OFF indication contact
SDE1fault-trip indication contact
CE1 connected-position indication contact (carriage switch)
F1 auxiliary power supply circuit breaker
MX shunt release
BP emergency off button with latching
KA3 auxiliary relay
ON Normal source opening order
OR Replacement source opening order
FN Normal source closing order (0.25 second delay)
FR Replacement source closing order (0.25 second delay)
MT Motor Mechanism

States permitted by mechanical interlocking system


Normal
Replacement
0
0
1
0
0
1
Note:
after a fault trip, the breaker must be reset manually by pressing
its reset button.
Diagram shown with circuit breakers in connected position, open,
charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MX, MN...).

C-7

Livre 1.indb 7

08/10/2008 18:39:42

Remote-operated
source-changeover systems

Electrical diagrams

2 Compact NS630b/1600 devices


Diagram no. 51201182

DB101697

Electrical interlocking with emergency off by undervoltage

(1) Not to be wired on fixed version.

ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
the SDE to terminals 81 and 84.

Legends
QN Normal source Compact NS630b to 1600
QR Replacement source Compact NS NS630b to 1600
OF... breaker ON/OFF indication contact
SDE1fault-trip indication contact
CE1 connected-position indication contact (carriage switch)
F1 auxiliary power supply circuit breaker
MN undervoltage release
BP emergency off button with latching
KA3 auxiliary relay
ON Normal source opening order
OR Replacement source opening order
FN Normal source closing order (0.25 second delay)
FR Replacement source closing order (0.25 second delay)
MT Motor Mechanism

Wiring colour codes


RD
red

GN
green

BK
black

VT
violet

YE
GY
yellow grey

WH
white

BN
brown

States permitted by mechanical interlocking system


Normal
Replacement
0
0
1
0
0
1
Note:
after a fault trip, the breaker must be reset manually by pressing
its reset button.
Diagram shown with circuit breakers in connected position, open,
charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MX, MN...).

C-8

Livre 1.indb 8

08/10/2008 18:39:43

Remote-operated
source-changeover systems

Electrical diagrams

2 Compact NS630b/1600 devices


Diagram no. 51201183

DB112554

Electrical interlocking by IVE

ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
wire BK to terminal 82.

Legends
QN Normal source Compact NS630b to 1600
QR Replacement source Compact NS NS630b to 1600
OF... breaker ON/OFF indication contact
SDE1fault-trip indication contact
CE1 connected-position indication contact (carriage switch)
F1 auxiliary power supply circuit breaker
IVE electrical interlocking and terminal block unit
ON Normal source opening order
OR Replacement source opening order
FN Normal source closing order (0.25 second delay)
FR Replacement source closing order (0.25 second delay)
MT Motor Mechanism

Wiring colour codes


RD
red

GN
green

BK
black

VT
violet

YE
GY
yellow grey

WH
white

BN
brown

(1) Not to be wired on fixed version.


(2) Prefabricated wiring supplied.

States permitted by mechanical interlocking system


Normal
Replacement
0
0
1
0
0
1
Note:
after a fault trip, the breaker must be reset manually by pressing
its reset button.
Diagram shown with circuit breakers in connected position, open,
charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MX, MN...).

C-9

Livre 1.indb 9

08/10/2008 18:39:44

Remote-operated
source-changeover systems

Electrical diagrams

2 Compact NS630b/1600 devices


Diagram no. 51201184

DB112555

Electrical interlocking by IVE with emergency off by shunt release

ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
wire BK to terminal 82.

Legends
QN Normal source Compact NS630b to 1600
QR
Replacement source Compact NS NS630b to 1600
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
CE1 connected-position indication contact (carriage switch)
auxiliary power supply circuit breaker
F1
electrical interlocking and terminal block unit
IVE
shunt release
MX
BP
emergency off button with latching
KA3 auxiliary relay
ON
Normal source opening order
Replacement source opening order
OR
Normal source closing order (0.25 second delay)
FN
Replacement source closing order (0.25 second delay)
FR
MT
Motor Mechanism

Wiring colour codes


RD

GN

BK

VT

YE

red

green

black

violet

yellow grey

GY

WH

BN

white

brown

(1) Not to be wired on fixed version.


(2) Prefabricated wiring supplied.

States permitted by mechanical interlocking system


Normal
Replacement
0
0
1
0
0
1
Note:
after a fault trip, the breaker must be reset manually by pressing
its reset button.
Diagram shown with circuit breakers in connected position, open,
charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MX, MN...).

C-10

Livre 1.indb 10

08/10/2008 18:39:45

Remote-operated
source-changeover systems

Electrical diagrams

2 Compact NS630b/1600 devices


Diagram no. 51201185

DB112556

Electrical interlocking by IVE with emergency off by undervoltage release

ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
wire BK to terminal 82.

Legends
QN Normal source Compact NS630b to 1600
QR
Replacement source Compact NS NS630b to 1600
MCH spring-charging motor
MX
standard opening release
standard closing release
XF
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
CE1 connected-position indication contact (carriage switch)
F1
auxiliary power supply circuit breaker
electrical interlocking and terminal block unit
IVE
undervoltage release
MN
BP
emergency off button with latching
KA3 auxiliary relay
ON
Normal source opening order
Replacement source opening order
OR
Normal source closing order (0.25 second delay)
FN
Replacement source closing order (0.25 second delay)
FR
MT
Motor Mechanism

Wiring colour codes


RD
red

GN
green

BK
black

VT
violet

YE
GY
yellow grey

WH
white

BN
brown

(1) Not to be wired on fixed version.


(2) Prefabricated wiring supplied.

States permitted by mechanical interlocking system


Normal
Replacement
0
0
1
0
0
1
Note:
after a fault trip, the breaker must be reset manually by pressing
its reset button.
Diagram shown with circuit breakers in connected position, open,
charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MX, MN...).

C-11

Livre 1.indb 11

08/10/2008 18:39:46

Electrical diagrams

Remote-operated
source-changeover systems

2 Compact NS630b/1600 devices


Diagram no. 51201186

DB101705

Automatic-control system without IVE for permanent replacement source

ATTENTION

(1) Not to be wired on fixed version.

The diagram shows the electrical wiring for circuit breakers.


When wiring the SDE with switch-disconnectors, connect
the SDE to terminals 81 and 84.

Legends
QN Normal source Compact NS630b to 1600
QR
Replacement source Compact NS NS630b to 1600
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
CE1 connected-position indication contact (carriage switch)
F1
auxiliary power supply circuit breaker
F2/F3 circuit breaker (high breaking capacity)
S1
control switches
KA1 auxiliary relays - UN presence detection
KA2 auxiliary relays - UR presence detection
KM1 contactors with 0.25 second delay (for transfer

to Replacement source)
KM2 contactors with 0.25 second delay (for transfer to Normal

source)
MT
Motor Mechanism

States permitted by mechanical interlocking system


Normal
Replacement
0
0
1
0
0
1
Note:
after a fault trip, the breaker must be reset manually by pressing
its reset button.
Diagram shown with circuit breakers in connected position, open,
charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MX, MN...).

C-12

Livre 1.indb 12

08/10/2008 18:39:46

Remote-operated
source-changeover systems

Electrical diagrams

2 Compact NS630b/1600 devices


Diagram no. 51201187

DB101707

Automatic-control system for replacement source generator set

(1) Not to be wired on fixed version.

ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
the SDE to terminals 81 and 84.

Legends
QN Normal source Compact NS630b to 1600
QR
Replacement source Compact NS NS630b to 1600
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
CE1 connected-position indication contact (carriage switch)
auxiliary power supply circuit breaker
F1
F2/F3 circuit breaker (high breaking capacity)
S1
control switches
KA1 auxiliary relays - UN presence detection
KA2 auxiliary relays - UR presence detection
KA3 auxiliary relays - generator set startup if UN absent
KM1 contactors with 0.25 second delay (for transfer

to Replacement source)
KM2 contactors with 0.25 second delay (for transfer to Normal

source)
MT
Motor Mechanism

Wiring colour codes


RD
red

GN
green

BK
black

VT
violet

YE
GY
yellow grey

WH
white

BN
brown

States permitted by mechanical interlocking system


Normal
Replacement
0
0
1
0
0
1
Note:
after a fault trip, the breaker must be reset manually by pressing
its reset button.
Diagram shown with circuit breakers in connected position, open,
charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MX, MN...).

C-13

Livre 1.indb 13

08/10/2008 18:39:47

Electrical diagrams

Remote-operated
source-changeover systems
2 Masterpact NT or NW devices
Diagram no. 51201139

DB101709

Electrical interlocking with lockout after a fault

ATTENTION

(1) Not to be wired on fixed version.

The diagram shows the electrical wiring for circuit breakers.


When wiring the SDE with switch-disconnectors, connect
the SDE to terminals 81 and 84.

Legends
Normal source Masterpact NT or NW
QN
Replacement source Masterpact NT or NW
QR
MCH spring-charging motor
standard opening voltage release
MX
standard closing voltage release
XF
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
ready-to-close contact
PF
CE1 connected-position indication contact (carriage switch)
CH
springs charged indication contact
auxiliary power supply circuit breaker
F1
Normal source opening order
ON
Replacement source opening order
OR
Normal source closing order (0.25 second delay)
FN
Replacement source closing order (0.25 second delay)
FR

States permitted by mechanical interlocking system


Normal
Replacement
0
0
1
0
0
1
Note:
diagram shown with circuit breakers in connected position, open,
charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MX, MN...).

C-14

Livre 1.indb 14

08/10/2008 18:39:48

Electrical diagrams

Remote-operated
source-changeover systems
2 Masterpact NT or NW devices
Diagram no. 51201140

DB101711

Electrical interlocking with lockout after a fault and emergency off by shunt release

ATTENTION

(1) Not to be wired on fixed version.

The diagram shows the electrical wiring for circuit breakers.


When wiring the SDE with switch-disconnectors, connect
the SDE to terminals 81 and 84.

Legends
KA3 time delay for genset startup order to avoid starting

the genset for transient UN disturbances
QN
Normal source Masterpact NT or NW
Replacement source Masterpact NT or NW
QR
MCH spring-charging motor
standard opening voltage release
MX
standard closing voltage release
XF
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
ready-to-close contact
PF
CE1 connected-position indication contact (carriage switch)
CH
springs charged indication contact
auxiliary power supply circuit breaker
F1
MX2 shunt release
BP
emergency off button with latching
Normal source opening order
ON
Replacement source opening order
OR
Normal source closing order (0.25 second delay)
FN
Replacement source closing order (0.25 second delay)
FR
BP
emergency off button with latching

States permitted by mechanical interlocking system


Normal
Replacement
0
0
1
0
0
1
Note:
diagram shown with circuit breakers in connected position, open,
charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MX, MN...).

C-15

Livre 1.indb 15

08/10/2008 18:39:49

Electrical diagrams

Remote-operated
source-changeover systems

2 Masterpact NT or NW devices
Diagram no. 51201141

DB101713

Electrical interlocking with lockout after a fault and emergency off by undervoltage release

ATTENTION

(1) Not to be wired on fixed version.

The diagram shows the electrical wiring for circuit breakers.


When wiring the SDE with switch-disconnectors, connect
the SDE to terminals 81 and 84.

Legends
QN Normal source Masterpact NT or NW
QR
Replacement source Masterpact NT or NW
MCH spring-charging motor
MX
standard opening voltage release
standard closing voltage release
XF
undervoltage release
MN
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH
springs charged indication contact
auxiliary power supply circuit breaker
F1
BP
emergency off button with latching
control switches
S1
KA3 auxiliary relay
ON
Normal source opening order
Replacement source opening order
OR
Normal source closing order (0.25 second delay)
FN
Replacement source closing order (0.25 second delay)
FR

States permitted by mechanical interlocking system


Normal
Replacement
0
0
1
0
0
1
Note:
diagram shown with circuit breakers in connected position, open,
charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MX, MN...).

C-16

Livre 1.indb 16

08/10/2008 18:39:50

Remote-operated
source-changeover systems

Electrical diagrams

2 Masterpact NT or NW devices
Diagram no. 51201142

DB101715

Electrical interlocking by IVE with lockout after a fault

ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
wire BK to terminal 82.

Legends
QN Normal source Masterpact NT or NW
QR
Replacement source Masterpact NT or NW
MCH spring-charging motor
MX
standard opening voltage release
standard closing voltage release
XF
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH
springs charged indication contact
electrical interlocking and terminal block unit
IVE
auxiliary power supply circuit breaker
F1
Normal source opening order
ON
Replacement source opening order
OR
Normal source closing order (0.25 second delay)
FN
Replacement source closing order (0.25 second delay)
FR

Wiring colour codes


RD
red

GN
green

BK
black

VT
violet

YE
GY
yellow grey

WH
white

BN
brown

(1) Not to be wired for the without lockout after a fault solution.
(2) Not to be wired on fixed version.
(3) Prefabricated wiring supplied.

States permitted by mechanical interlocking system


Normal
Replacement
0
0
1
0
0
1
Note:
diagram shown with circuit breakers in connected position, open,
charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MX, MN...).

C-17

Livre 1.indb 17

08/10/2008 18:39:51

Remote-operated
source-changeover systems

Electrical diagrams

0=

2 Masterpact NT or NW devices
Diagram no. 51201143

DB101717

Electrical interlocking by IVE with lockout after a fault and emergency off by shunt release

ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
wire BK to terminal 82.

Legends
QN Normal source Masterpact NT or NW
QR
Replacement source Masterpact NT or NW
MCH spring-charging motor
MX
standard opening voltage release
standard closing voltage release
XF
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH
springs charged indication contact
electrical interlocking and terminal block unit
IVE
auxiliary power supply circuit breaker
F1
BP
emergency off button with latching
KA3 auxiliary relay
ON
Normal source opening order
Replacement source opening order
OR
Normal source closing order (0.25 second delay)
FN
Replacement source closing order (0.25 second delay)
FR

Wiring colour codes


RD
red

GN
green

BK
black

VT
violet

YE
GY
yellow grey

WH
white

BN
brown

(1) Not to be wired for the without lockout after a fault solution.
(2) Not to be wired on fixed version.
(3) Prefabricated wiring supplied.

States permitted by mechanical interlocking system


Normal
Replacement
0
0
1
0
0
1
Note:
diagram shown with circuit breakers in connected position, open,
charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MX, MN...).

C-18

Livre 1.indb 18

08/10/2008 18:39:52

Remote-operated
source-changeover systems

Electrical diagrams

2 Masterpact NT or NW devices
Diagram no. 51201144

DB101719

Electrical interlocking by IVE with lockout after a fault and emergency off by undervoltage release

ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
wire BK to terminal 82.

Legends
QN Normal source Masterpact NT or NW
QR
Replacement source Masterpact NT or NW
MCH spring-charging motor
MX
standard opening voltage release
standard closing voltage release
XF
undervoltage release
MN
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH
springs charged indication contact
electrical interlocking and terminal block unit
IVE
auxiliary power supply circuit breaker
F1
BP
emergency off button with latching
control switches
S1
KA3 auxiliary relay
ON
Normal source opening order
Replacement source opening order
OR
Normal source closing order (0.25 second delay)
FN
Replacement source closing order (0.25 second delay)
FR

Wiring colour codes


RD
red

GN
green

BK
black

VT
violet

YE
GY
yellow grey

WH
white

BN
brown

(1) Not to be wired for the without lockout after a fault solution.
(2) Not to be wired on fixed version.
(3) Prefabricated wiring supplied.

States permitted by mechanical interlocking system


Normal
Replacement
0
0
1
0
0
1
Note:
diagram shown with circuit breakers in connected position, open,
charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MX, MN...).

C-19

Livre 1.indb 19

08/10/2008 18:39:53

Electrical diagrams

Remote-operated
source-changeover systems
2 Masterpact NT or NW devices
Diagram no. 51156226

DB101721

Automatic-control system without IVE for permanent replacement source with lockout after a fault

ATTENTION

(1) Not to be wired on fixed version.

The diagram shows the electrical wiring for circuit breakers.


When wiring the SDE with switch-disconnectors, connect
the SDE to terminals 81 and 84.

Legends
QN Normal source Masterpact NT or NW
QR
Replacement source Masterpact NT or NW
MCH spring-charging motor
MX
standard opening voltage release
standard closing voltage release
XF
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH
springs charged indication contact
auxiliary power supply circuit breaker
F1
F2/F3 circuit breaker (high breaking capacity)
S1
control switches
KA1 auxiliary relays - UN presence detection
KA2 auxiliary relays - UR presence detection
KM1 contactors with 0.25 second delay (for transfer to

Replacement source)
KM2 contactors with 0.25 second delay (for transfer to Normal

source)

States permitted by mechanical interlocking system


Normal
Replacement
0
0
1
0
0
1
Note:
diagram shown with circuit breakers in connected position, open,
charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MX, MN...).

C-20

Livre 1.indb 20

08/10/2008 18:39:54

Electrical diagrams

Remote-operated
source-changeover systems
2 Masterpact NT or NW devices
Diagram no. 51156227

DB101723

Automatic-control system for replacement source generator set with lockout after a fault

ATTENTION

(1) Not to be wired on fixed version.

The diagram shows the electrical wiring for circuit breakers.


When wiring the SDE with switch-disconnectors, connect
the SDE to terminals 81 and 84.

Legends
QN Normal source Masterpact NT or NW
QR
Replacement source Masterpact NT or NW
MCH spring-charging motor
MX
standard opening voltage release
standard closing voltage release
XF
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
ready-to-close contact
PF
CE1 connected-position indication contact (carriage switch)
CH
springs charged indication contact
auxiliary power supply circuit breaker
F1
F2/F3 circuit breaker (high breaking capacity)
S1
control switches
KA1 auxiliary relays - UN presence detection
KA2 auxiliary relays - UR presence detection
KA3 auxiliary relays - generator set startup if UN absent
KM1 contactors with 0.25 second delay (for transfer to

Replacement source)
KM2 contactors with 0.25 second delay (for transfer to Normal

source)

States permitted by mechanical interlocking system


Normal
Replacement
0
0
1
0
0
1
Note:
diagram shown with circuit breakers in connected position, open,
charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MX, MN...).

C-21

Livre 1.indb 21

08/10/2008 18:39:55

Remote-operated
source-changeover systems

Electrical diagrams

2 Masterpact NT or NW devices
Diagram no. 51156904

DB112557

Automatic-control system for permanent replacement source with lockout after a fault (with MN)

ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
wire BK to terminal 82.

Legends
QN Normal source Masterpact NT or NW
QR
Replacement source Masterpact NT or NW
MCH spring-charging motor
standard closing voltage release
XF
undervoltage release
MN
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH
springs charged indication contact
electrical interlocking and terminal block unit
IVE
auxiliary power supply circuit breaker
F1
circuit breaker (high breaking capacity)
F2
control switches
S1
KA1 auxiliary relays
KA2 auxiliary relays
KA3 auxiliary relays

Wiring colour codes


RD
red

GN
green

BK
black

VT
violet

YE
GY
yellow grey

WH
white

BN
brown

(1) Not to be wired for the without lockout after a fault solution.
(2) Not to be wired on fixed version.
(3) Prefabricated wiring supplied.

States permitted by mechanical interlocking system


Normal
Replacement
0
0
1
0
0
1
Note:
diagram shown with circuit breakers in connected position, open,
charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MX, MN...).

C-22

Livre 1.indb 22

08/10/2008 18:39:56

Remote-operated
source-changeover systems

Electrical diagrams

2 Masterpact NT or NW devices
Diagram no. 51156905

DB112558

Automatic-control system for replacement source generator set with lockout after a fault (with MN)

ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
wire BK to terminal 82.

Legends
QN Normal source Masterpact NT or NW
QR
Replacement source Masterpact NT or NW
MCH spring-charging motor
XF
standard closing voltage release
undervoltage release
MN
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH
springs charged indication contact
electrical interlocking and terminal block unit
IVE
auxiliary power supply circuit breaker
F1
circuit breaker (high breaking capacity)
F2
control switches
S1
KA1 auxiliary relay
KA2 time delay for genset startup order to avoid starting

the genset for transient UN disturbances
KA3 auxiliary relay

Wiring colour codes


RD
red

GN
green

BK
black

VT
violet

YE
GY
yellow grey

WH
white

BN
brown

(1) Not to be wired for the without lockout after a fault solution.
(2) Not to be wired on fixed version.
(3) Prefabricated wiring supplied.

States permitted by mechanical interlocking system


Normal
Replacement
0
0
1
0
0
1
Note:
diagram shown with circuit breakers in connected position, open,
charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MX, MN...).

C-23

Livre 1.indb 23

08/10/2008 18:39:57

Electrical diagrams

Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156906

DB101734

2 Normal sources and 1 Replacement source: electrical interlocking without lockout after a fault

Legends
QN... Normal source Masterpact NW
QR
Replacement source Masterpact NW
MCH spring-charging motor
MX
standard opening voltage release
XF
standard closing voltage release
OF... breaker ON/OFF indication contact
PF
ready-to-close contact
connected-position indication contact (carriage switch)
CE
springs charged indication contact
CH
F1
auxiliary power supply circuit breaker
t1
order for transfer from R to N1 + N2

(QN1 and QN2 closing time delay = 0.25 sec. minimum)
t2
order for transfer from N1 + N2to R

(QR closing time delay = 0.25 sec. minimum)

States permitted by mechanical interlocking system


Normal 1
Normal 2
Replacement
0
0
0
1
1
0
0
0
1
1
0
0
0
1
0
Note:
diagram shown with circuit breakers in connected position, open,
charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MX, MN...).

C-24

Livre 1.indb 24

08/10/2008 18:39:59

Electrical diagrams

Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156907

DB101766

2 Normal sources and 1 Replacement source: electrical interlocking with lockout after a fault

ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
the SDE to terminals 81 and 84.

Legends
QN... Normal source Masterpact NW
Replacement source Masterpact NW
QR
MCH spring-charging motor
MX
standard opening voltage release
XF
standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH
springs charged indication contact
auxiliary power supply circuit breaker
F1
control switches
S1
S2
source selection switches
t1
order for transfer from R to N1 + N2

(QN1 and QN2 closing time delay = 0.25 sec. minimum)
t2
order for transfer from N1 + N2to R

(QR closing time delay = 0.25 sec. minimumm)

States permitted by mechanical interlocking system


Normal 1
Normal 2
Replacement
0
0
0
1
1
0
0
0
1
1
0
0
0
1
0
Note:
diagram shown with circuit breakers in connected position, open,
charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MX, MN...).

C-25

Livre 1.indb 25

08/10/2008 18:40:00

Electrical diagrams

Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156908

DB101737

2 Normal sources and 1 Replacement source: automatic-control system for generator set without lockout
after a fault (with MN)

Legends
QN... Normal source Masterpact NW
QR
Replacement source Masterpact NW
MCH spring-charging motor
XF
standard closing voltage release
undervoltage release
MN
OF... breaker ON/OFF indication contact
PF
ready-to-close contact
CE... connected-position indication contact (carriage switch)
CH
springs charged indication contact
F1
auxiliary power supply circuit breaker
F2/F3 circuit breaker (high breaking capacity)
S1
control switches
S2
source selection switches
KA1 auxiliary relay
KA2 auxiliary relays with 10 to 180 sec. time delay
KA3 auxiliary relays with 0.1 to 30 sec. time delay
KA4 auxiliary relay
KA5 auxiliary relays with 0.25 sec. time delay
KA6 auxiliary relays with 0.25 sec. time delay

States permitted by mechanical interlocking system


and with associated automatism
Normal 1
Normal 2
Replacement
0
0
0
1
1
0
0
0
1
1
0
0
0
1
0
Note:
diagram shown with circuit breakers in connected position, open,
charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MX, MN...).

C-26

Livre 1.indb 26

08/10/2008 18:40:01

Electrical diagrams

Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156909

DB101739

2 Normal sources and 1 Replacement source: automatic-control system for generator set with lockout
after a fault (with MN)

ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
the SDE to terminals 81 and 84.

Legends
QN... Normal source Masterpact NW
Replacement source Masterpact NW
QR
MCH spring-charging motor
XF
standard closing voltage release
undervoltage release
MN
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
ready-to-close contact
PF
CE... connected-position indication contact (carriage switch)
CH
springs charged indication contact
F1
auxiliary power supply circuit breaker
F2/F3 circuit breaker (high breaking capacity)
S1
control switches
S2
source selection switches
KA1 auxiliary relay
KA2 auxiliary relays with 10 to 180 sec. time delay
KA3 auxiliary relays with 0.1 to 30 sec. time delay
KA4 auxiliary relay
KA5 auxiliary relays with 0.25 sec. time delay
KA6 auxiliary relays with 0.25 sec. time delay
KA7 auxiliary relay
KA8 auxiliary relay

States permitted by mechanical interlocking system


and with associated automatism
Normal 1
Normal 2
Replacement
0
0
0
1
1
0
0
0
1
1
0
0
0
1
0
Note:
diagram shown with circuit breakers in connected position, open,
charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MX, MN...).

C-27

Livre 1.indb 27

08/10/2008 18:40:03

Electrical diagrams

Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156910

DB101741

3 sources with only 1 device closed: electrical interlocking without lockout after a fault

Legends
QS... Source Masterpact NW
MCH spring-charging motor
MX
standard opening voltage release
XF
standard closing voltage release
OF... breaker ON/OFF indication contact
PF
ready-to-close contact
CE... connected-position indication contact (carriage switch)
CH
springs charged indication contact
auxiliary power supply circuit breaker
F1
t1
order for transfer to Source 1

(QS1 closing time delay = 0.25 sec. minimum)
t2
order for transfer to Source 2

(QS2 closing time delay = 0.25 sec. minimum)
t3
order for transfer to Source 3

(QS3 closing time delay = 0.25 sec. minimum)

States permitted by mechanical interlocking system


Source 1
Source 2
Source 3
0
0
0
1
0
0
0
1
0
0
0
1
Note:
diagram shown with circuit breakers in connected position, open,
charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MX, MN...).

C-28

Livre 1.indb 28

08/10/2008 18:40:04

Electrical diagrams

Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156911

DB101743

3 sources with only 1 device closed: electrical interlocking with lockout after a fault

ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
the SDE to terminals 81 and 84.

Legends
QS... Source Masterpact NW
MCH spring-charging motor
MX
standard opening voltage release
standard closing voltage release
XF
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE... connected-position indication contact (carriage switch)
CH
springs charged indication contact
F1
auxiliary power supply circuit breaker
t1
order for transfer to Source 1

(QS1 closing time delay = 0.25 sec. minimum)
t2
order for transfer to Source 2

(QS2 closing time delay = 0.25 sec. minimum)
t3
order for transfer to Source 3

(QS3 closing time delay = 0.25 sec. minimum)
KA1 auxiliary relays
KA2 auxiliary relays
KA3 auxiliary relays

States permitted by mechanical interlocking system


Source 1
Source 2
Source 3
0
0
0
1
0
0
0
1
0
0
0
1
Note:
diagram shown with circuit breakers in connected position, open,
charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MX, MN...).

C-29

Livre 1.indb 29

08/10/2008 18:40:05

Electrical diagrams

Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156912

DB101745

2 sources and 1 coupling: electrical interlocking without lockout after a fault

Legends
QS... Source Masterpact NW
QC
Coupling Masterpact NW
MCH spring-charging motor
MX
standard opening voltage release
XF
standard closing voltage release
OF... breaker ON/OFF indication contact
PF
ready-to-close contact
CE... connected-position indication contact (carriage switch)
CH
springs charged indication contact
auxiliary power supply circuit breaker
F1
coupling order for Source 1 failure
t1

(QC closing time delay = 0.25 sec. minimum)
t2
coupling order for Source 2 failure

(QC closing time delay = 0.25 sec. minimum)
t3
coupling order for Source 1 restored

(QS1 closing time delay = 0.25 sec. minimum)
t4
coupling order for Source 2 restored

(QS2 closing time delay = 0.25 sec. minimum)

States permitted by mechanical interlocking system


Source 1
Source 2
Coupling
0
0
0
1
1
0
1
0
1
0
1
1
1
0
0
0
1
0
0
0
1
Note:
diagram shown with circuit breakers in connected position, open,
charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MX, MN...).

C-30

Livre 1.indb 30

08/10/2008 18:40:06

Electrical diagrams

Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156913

DB101747

2 sources and 1 coupling: electrical interlocking with lockout after a fault

ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
the SDE to terminals 81 and 84.

Legends
QS... Source Masterpact NW
QC
Coupling Masterpact NW
MCH spring-charging motor
standard opening voltage release
MX
standard closing voltage release
XF
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE... connected-position indication contact (carriage switch)
CH
springs charged indication contact
auxiliary power supply circuit breaker
F1
t1
coupling order for Source 1 failure

(QC closing time delay = 0.25 sec. minimum)
t2
coupling order for Source 2 failure

(QC closing time delay = 0.25 sec. minimum)
t3
coupling order for Source 1 restored

(QS1 closing time delay = 0.25 sec. minimum)
t4
coupling order for Source 2 restored

(QS2 closing time delay = 0.25 sec. minimum)
KA1 auxiliary relays
KA2 auxiliary relays
KA3 auxiliary relays

States permitted by mechanical interlocking system


Source 1
Source 2
Coupling
0
0
0
1
1
0
1
0
1
0
1
1
1
0
0
0
1
0
0
0
1
Note:
diagram shown with circuit breakers in connected position, open,
charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MX, MN...).

C-31

Livre 1.indb 31

08/10/2008 18:40:08

Electrical diagrams

Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156914

DB101749

2 sources and 1 coupling: automatic-control system with lockout after a fault

ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
the SDE to terminals 81 and 84.

Legends
QS... Source Masterpact NW
QC
Coupling Masterpact NW
MCH spring-charging motor
MX
standard opening voltage release
standard closing voltage release
XF
OF... breaker ON/OFF indication contact
SDE1 fault trip indication contact
ready-to-close contact
PF
CE... connected-position indication contact (carriage switch)
CH
springs charged indication contact
auxiliary power supply circuit breaker
F1
F2/F3 circuit breaker (high breaking capacity)
S1
control switches
source selection switches
S2
KA1 auxiliary relays with 10 to 180 sec. time delay
KA2 auxiliary relays with 0.1 to 30 sec. time delay
KA3 auxiliary relays with 10 to 180 sec. time delay
KA4 auxiliary relays with 0.1 to 30 sec. time delay
KA5 auxiliary relays with 0.25 sec. time delay
KA6 auxiliary relays with 0.25 sec. time delay
KA7 auxiliary relays with 0.25 sec. time delay

States permitted by mechanical interlocking system


and with associated automatism
Source 1
Source 2
Coupling
0
0
0
1
1
0
1
0
1
0
1
1
1
0
0
0
1
0
0
0
1
Note:
diagram shown with circuit breakers in connected position, open,
charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MX, MN...).

C-32

Livre 1.indb 32

08/10/2008 18:40:09

Electrical diagrams

Source-changeover systems
with automatic controllers
2 Compact NS100/1600 or
Masterpact NT/NW devices

Source-changeover system with BA controller

DB101753

DB101751

Coupling

DB101755

Transfer conditions

Terminals 20 and 21:


additional control contact (not part of
controller).

Tests on Normal and Replacement


source voltages
The single-phase check for UN and UR
is implemented across terminals 1 and 5
of circuit breakers Q1 and Q2.

Legends
Q1
circuit breaker supplying and protecting the automatic
control circuits for the Normal source
Q2
circuit breaker supplying and protecting the automatic
control circuits for the Replacement source
ACP auxiliaries control plate
BA
automatic controller
IVE
electrical interlocking and terminal block unit

Note:
diagram shown with circuits de-energised, circuit breakers open
and relays in normal position.

C-33

Livre 1.indb 33

08/10/2008 18:40:10

Electrical diagrams

Source-changeover systems
withautomaticcontrollers
2 Compact NS100/1600 or
Masterpact NT/NW devices

Source-changeover system with UA controller

DB101758

DB101757

Load shedding and genset management

DB101759

Transfer conditions

Terminals 20 and 21:


additional control contact (not part of
controller).

DB101761

Tests on Normal and Replacement


source voltages
Normal source voltage UN test

Replacement source voltage UR test


The single-phase check for UR is
implemented across terminals 1 and 5
of circuit breaker Q2.

Legends
Q1
circuit breaker supplying and protecting the automatic
control circuits for the Normal source
Q2
circuit breaker supplying and protecting the automatic
control circuits for the Replacement source
ACP auxiliaries control plate
UA
automatic controller
IVE
electrical interlocking and terminal block unit

Note:
diagram shown with circuits de-energised, circuit breakers open
and relays in normal position.

C-34

Livre 1.indb 34

08/10/2008 18:40:11

Source-changeover systems
withautomaticcontrollers

Electrical diagrams

2 Compact NS100/1600 or
Masterpact NT/NW devices
Using communication functions
DB101763

DB101762

Controller settings

Tests on Normal source voltage


A = 0 single-phase test,
A = 1 three-phase test.

The address of the UA controller is set using


the two BBus dials.

Voluntary transfert (e.g. for energy management)


b action in the event of genset failure
B = 0 circuit breaker N opens,
B = 1 circuit breaker N remains closed.
b maximum permissible genset startup time (T6)
C = 0 T = 120 s,
C = 1 T = 180 s.
After this time has elapsed, the genset is considered to
have failed.

C-35

Livre 1.indb 35

08/10/2008 18:40:13

Source-changeover systems
withautomaticcontrollers

Electrical diagrams

2 Masterpact NT or NW devices
Diagram no. 51156903

DB101765

Electrical interlocking with lockout after a fault

ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
wire BK to terminal 82.

Legends
QN Normal source Masterpact NT or NW
QR
Replacement source Masterpact NT or NW
MCH spring-charging motor
MX
standard opening voltage release
standard closing voltage release
XF
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH
springs charged indication contact
electrical interlocking and terminal block unit
IVE

Wiring colour codes


RD
red

GN
green

BK
black

VT
violet

YE
GY
yellow grey

WH
white

BN
brown

(1) Not to be wired for the without lockout after a fault solution.
(2) Not to be wired on fixed version.
(3) Prefabricated wiring supplied.

States permitted by mechanical interlocking system


Normal
Replacement
0
0
1
0
0
1
Note:
diagram shown with circuit breakers in connected position, open,
charged, and ready to close.

C-36

Livre 1.indb 36

08/10/2008 18:40:14

C-37

Livre 1.indb 37

08/10/2008 18:40:14

TOOLS
schneider-electric.com

The electrical
installation guide

This international site allows you


to access all the Schneider Electric
products in just  clicks
via comprehensive range datasheets, with direct links to:
p complete library: technical
documents, catalogs, FAQs,
brochures
p selection guides from
the e-catalog.
p product discovery sites and
their Flash animations.
You will also find illustrated
overviews, news to which you
can subscribe, the list of country
contacts

According to IEC 60364


This guide, part of the
Schneider Electric offer, is
the essential tool to "guide"
you any time in your business:
p design office, consultant
p contractor, panelbuilder
p teacher, trainer.
Comprehensive
and concrete information on:
p all the new technical solutions
p all the components
p of an installation from a global
point of view
p all the IEC standards modifications
p all the fundamental
electrotechnical knowledge
p all the design stages, from medium
to low voltage.

Livre 1.indb 2

08/10/2008 18:40:29

Source-changeover systems

Catalogue numbers
and order forms

Presentation
Functions and characteristics
Dimensions
Electrical diagrams

Source-changeover systems for2devices


Interpact INS40 to INS2500 and INV100 to INV2500
Compact NS100 to NS630
Compact NS630b to NS1600 circuit breakers and switch-disconnectors
Masterpact NT circuit breakers and switch-disconnectors

Source-changeover systems for2or 3devices

2
A-1
B-1
C-1

D-2
D-2
D-3
D-5
D-7

D-8

Masterpact NW circuit breakers andswitch-disconnectors

D-8

Source-changeover systems for2devices

D-10

Interpact INS40 to INS630 Switch-disconnectors


Compact NS100 to NS630 / Circuit breakers and switch-disconnectors
Compact NS630b to NS1600 / Circuit breakers and switch-disconnectors
Masterpact NT or NW / Circuit-breakers and switch-disconnectors

Source-changeover systems for 3 devices


Masterpact NW / Circuit breakers and switch-disconnectors

D-10
D-12
D-14
D-16

D-18
D-18

D-1

Livre 1.indb 1

08/10/2008 18:40:30

Catalogue numbers
and order forms

Source-changeover systems
for2devices
Interpact INS40 to INS2500
and INV100 to INV2500

Manual source-changeover systems Interpact INS40 to INS630 and INV100 to INV630


Interlocking for rotary handle
3/4P
28953

E89624

DB107710

Mechanical device for INS40 to INS160


equipped with an extended rotary handle

5...8

Mechanical device for INS250-100 to INS250/INV100 to INV250


equipped with a direct or extended rotary handle
Mechanical device for INS/INV320 to INS/INV630
equipped with a direct or extended rotary handle

31073
31074

Complete assembly source-changeover systems Interpact INS250 to INS630

DB107711

E89638

3P
With Interpact INS250-100A
31140
With Interpact INS250-160A
31144
31142
With Interpact INS250-200A
31146
With Interpact INS250
31148
With Interpact INS320
With Interpact INS400
31150
With Interpact INS500
31152
With Interpact INS630
31154
Locking for INS complete source changeover assembly
Handle locking by 1 to 3 padlocks (in OFF position)
By keylock
Keylocking device
+ Ronis 1351B.500 keylock
or + Profalux KS5 B24 D4Z keylock

4P
31141
31145
31143
31147
31149
31151
31153
31155
Built in
31097
41940
42888

E89617

Rotary handle
Extended front control for complete source changeover assembly

31055

Manual source-changeover systems Interpact INS250 to INS2500 and INV250 to INV2500 by keylock

E89626

DB101549

Interlocking
Locking device for Ronis/Profalux keylocks
on INS250-100 to INS250/INV100 to INV250
Locking device for Ronis/Profalux keylocks
on INS/INV320 to INS/INV630

2x

3/4P
31087

2x

31088

Locking device for Ronis/Profalux keylocks


on INS/INV630b to INS/INV2500

2x

31291

+ Ronis 1351B.500 keylock (2 keylocks / 1 key)


or + Profalux KS5 B24 D4Z keylock (2 keylocks / 1 key)

41950
42878

Connection accessories
Downstream coupling accessories
INS250 (1 pair)
INS320 to INS630 (1 pair)

3P
29322
32563

4P
29322
32563

Normal source /
replacement source

INS250
INS320 to INS630

29358
32619

29359
32620

Long terminal shields

INS250 (1 pair)
INS320 to INS630 (1 pair)

29324
32583

29324
32583

DB101063

E50998

DB101062

Short terminal shields

D-2

Livre 1.indb 2

08/10/2008 18:40:33

Source-changeover systems
for 2 devices (cont.)

Catalogue numbers
andorderforms

Compact NS100 to NS630


Manual source changeover
Mechanical interlocking
NS100...250
NS400...630

29354
32614

For rotary handled circuit breakers

NS100...250
NS400...630

29369
32621

E18780

E21288

For toggle controlled circuit breakers

Key lock interlocking


E23851

For rotary handled or remote controlled circuit breakers


2 locks, 1 key
Ronis 1351B.500
Profalux KS5 B24 D4Z

41950
42878

Remote controlled source changeover


Plate + IVE
E33419

Source normal/source replacement (identical voltages)


NS100...250/NS100...250
Plate + IVE (1)
Plate
IVE
Auxiliary switches 2 OF + 2 SDE
Spare wiring system (device/IVE)
Back sockets option add:
Only long RC
Plug in base option add:
Plug in kit
NS400...630/NS100...630
Plate + IVE (1)
Plate
IVE
Auxiliary switches 2 OF + 2 SDE
Spare wiring system (device/IVE)
Back sockets option add:
Only long RC
Plug in base option add:
Plug in kit
Adaptator kit for NS100...250

24 to 250 V DC

48 to 415 V AC 50/60 Hz
440 V 60 Hz

29351
29349
29356
4 x 29450
29365

29350
29349
29352
4 x 29450
29365

(2)

(2)

(2)

(2)

32611
32609
29356
4 x 29450
29365

(2)

(2)

(2)

1 x 32618

32610
32609
29352
4 x 29450
29365
(2)

1 x 32618

Control unit option


E33420

110/127 V AC 50/60 Hz
GERIN
MERLIN
multi

220/240 V AC 50/60 Hz

0 . OFF

P25M

GERIN
MERLIN
multi

0 . OFF

660V
AC3-IEC292-1

P25M
660V
AC3-IEC292-1

Test

Test

ACP + control unit BA (1)


Plate ACP
Control unit BA
ACP + control unit UA (1)
29448
Plate ACP
29447
Control unit UA 29446
ACP + control unit UA150 (1) (communication option)
Plate ACP
Control unit UA150

29470
29363
29376
29472
29363
29378
29474
29363
29379

380/415 V AC 50/60 Hz
440 V 60 Hz
29471
29364
29377
29473

29364
29380

29475
29364
29381

Wiring cable between BA/UA and ACP/IVE


29368
29368
(1) The supply voltages BA/UA control unit, ACP plate, IVE and the remote control must be identical whatever the source changeover type.
(2) See products pages.

D-3

Livre 1.indb 3

08/10/2008 18:40:36

Catalogue numbers
andorderforms

Source-changeover systems
for 2 devices (cont.)
Compact NS100 to NS630 (cont.)

Connection accessories
Downstream coupling accessories
NS100...250/NS100...250
NS400...630/NS400...630

Source normal/source
replacement

NS100...250/
NS100...250
NS400...630/
NS400...630

E50998

DB101062

Short terminal shields (1 pair)

DB101063

Long terminal shields (1 pair)

3P
29321
32562

4P
29322
32563

250 A

29358

29359

630 A

32619

32620

NS100...250/NS100...250
NS400...630/NS400...630

29324
32565

Typical composition of remote controlled source changeover


Remote controlled source changeover
E33422

1 normal device N (1)


+ 1 replacement device R (2)
+ 2 remote controls (3)
+ 1 plate with interlocking (4) with IVE (5) and its wiring (8)
+ 2 plug-in kits (if plug-in version)
+ 1 adaptor kit for NS100...250 plug-in (if NS400...630 with NS100...250)
+ auxilary switches (6)
2 x (1 OF + 1 SDE) for Compact NS100...630
+ 1 downstream coupling accessory (7) for Compact NS100...630 (option)
+ long RC (if back connection)

IVE voltages and remote controls are identical.

E33423

Associated control unit


GERIN
MERLIN
multi

P25M

GERIN
MERLIN
multi

0 . OFF

660V
AC3-IEC292-1

P25M
660V
AC3-IEC292-1

Test

Test

0 . OFF

1 source changeover without associated control unit


+ 1 ACP (9) with BA control unit (10)
Or + 1 ACP (9) with UA control unit (11)
Or + 1 ACP (9) with UA150 control unit (11)
+ extension (12) for remote UA/BA connection on front of switchboard

IVE voltages + remote control + ACP + BA or UA are identical.

D-4

Livre 1.indb 4

08/10/2008 18:40:38

Catalogue numbers
andorderforms

Source-changeover systems
for2devices (cont.)

Compact NS630b to NS1600


circuit breakers and switch-disconnectors
Interlocking for source-changeover systems
Mechanical interlocking
33890

E70744

For 2 devices with extended rotary handles

Interlocking using connecting rods for Compact electrically-operated devices


E72941

Complete assembly with 2 adaptation fixtures + rods


2 Compact fixed devices
2 Compact withdrawable devices

33910
33913

FFO
hsup

NO h
sup

FFO

O
degr

ahcs

id

FFO
hsup

NO h
sup

FFO

O
degr

ahcs

id

Interlocking using cables for Compact electrically-operated devices


E72942

Complete assembly with 2 adaptation fixtures + cables


2 Compact fixed devices
2 Compact withdrawable devices
1 Compact fixed + 1 Compact withdrawable device

33911
33914
33915

FFO
hsup

NO h
sup

FFO

O
degr

ahcs

id

FFO
hsup

NO h
sup

FFO

O
degr

ahcs

id

D-5

Livre 1.indb 5

08/10/2008 18:40:39

Catalogue numbers
andorderforms

Source-changeover systems
for2devices (cont.)

Compact NS630b to NS1600 circuit


breakers and switch-disconnectors (cont.)
Associated controller
The automatic-control option includes:
b an IVE electrical-interlocking unit
b an ACP auxiliaries control plate
b a BA or UA controller, depending on the required functions
b a UA/BA adapter kit.
Note: the circuit breaker auxiliaries (MCH, MX, XF) and the automatic-control components (IVE, ACP, UA or BA) must have the same voltages.

IVE electrical-interlocking unit

E88714

For 2 devices
Wiring kit for connection of 2 fixed/withdrawable devices to the IVE unit

Control unit option

E33420

48/415 V AC 50/60 Hz
440 V 60 Hz

110/127 V AC 50/60 Hz

220/240 V AC 50/60 Hz

29352
54655

380/415 V AC 50/60 Hz
440 V 60 Hz

ACP + control unit BA (1)


29470
29471
Plate ACP
29363
29364
Control unit BA
29376
29377
29448
29472
29473
ACP + control unit UA (1)
Plate ACP
29447
29363
29364
Control unit UA 29446
29378
29380
29474
29475
ACP + control unit UA150 (1) (communication option)
Plate ACP
29363
29364
29379
29381
Control unit UA150
(1) The supply voltages of the BA/UA controller, ACP plate, IVE unit and circuit breaker operating mechanism must be identical whatever the type of sourcechangeover system.
GERIN

MERLIN
multi

0 . OFF

P25M

GERIN

MERLIN
multi

0 . OFF

660V
AC3-IEC292-1

P25M

660V
AC3-IEC292-1

Test

Test

D-6

Livre 1.indb 6

08/10/2008 18:40:40

Catalogue numbers
andorderforms

Source-changeover systems
for2devices (cont.)
Masterpact NT circuit breakers
and switch-disconnectors

interlocking for source-changeover systems


Interlocking using connecting rods
E47760

Complete assembly with 2 adaptation fixtures + rods


2 Masterpact NT fixed devices
2 Masterpact NT drawout devices

33912
33913

Interlocking using cables (*)


Choose 2 adaptation fixtures (1 for each breaker + 1 set of cables)
1 adaptation fixture for Masterpact NT fixed devices
1 adaptation fixture for Masterpact NT drawout devices
1 set of 2 cables
(*) Can be used with any combination of NT or NW, fixed or drawout devices.

33200
33201
33209

Associated controller
The automatic-control option includes:
b an IVE electrical-interlocking unit
b an ACP auxiliaries control plate
b a BA or UA controller, depending on the required functions
b a UA/BA adapter kit.
Note: the circuit breaker auxiliaries (MCH, MX, XF) and the automatic-control components (IVE, ACP, UA or BA) must have the same voltages.

IVE electrical-interlocking unit

E88714

for 2 devices
wiring kit for connection of 2 fixed/drawout devices to the IVE unit

Control unit option

E33420

48/415 V AC 50/60 Hz
440 V 60 Hz

110/127 V AC 50/60 Hz

29352
54655

220/240 V AC 50/60 Hz

380/415 V AC 50/60 Hz
440 V 60 Hz

ACP + control unit BA (1)


29470
29471
Plate ACP
29363
29364
Control unit BA
29376
29377
29448
29472
29473
ACP + control unit UA (1)
Plate ACP
29447
29363
29364
Control unit UA 29446
29378
29380
29474
29475
ACP + control unit UA150 (1) (communication option)
Plate ACP
29363
29364
29379
29381
Control unit UA150
(1) The supply voltages of the BA/UA controller, ACP plate, IVE unit and circuit breaker operating mechanism must be identical whatever the type
of source-changeover system.
GERIN

MERLIN
multi

0 . OFF

P25M

GERIN

MERLIN
multi

0 . OFF

660V
AC3-IEC292-1

P25M

660V
AC3-IEC292-1

Test

Test

D-7

Livre 1.indb 7

08/10/2008 18:40:42

Catalogue numbers
andorderforms

Source-changeover systems
for2or 3devices
Masterpact NW circuit breakers
andswitch-disconnectors

Interlocking for source-changeover systems for 2 devices


Interlocking of 2 devices using connecting rods
E47762

Complete assembly with 2 adaptation fixtures + rods


2 Masterpact NW fixed devices
2 Masterpact NW drawout devices
Can be used with 1 NW fixed + 1 NW drawout.

48612
48612

Interlocking of 2 devices using cables (*)


Choose 2 adaptation fixtures (1 for each breaker + 1 set of cables)
1 adaptation fixture for Masterpact NW fixed devices
1 adaptation fixture for Masterpact NW drawout devices
1 set of 2 cables
(*) Can be used with any combination of NT or NW, fixed or drawout devices.

47926
47926
33209

Associated controller for 2 devices


The automatic-control option includes:
b an IVE electrical-interlocking unit
b an ACP auxiliaries control plate
b a BA or UA controller, depending on the required functions
b a UA/BA adapter kit.
Note: the circuit breaker auxiliaries (MCH, MX, XF) and the automatic-control components (IVE, ACP, UA or BA) must have the same voltages.

IVE electrical-interlocking unit

E88714

for 2 devices
wiring kit for connection of 2 fixed/drawout devices to the IVE unit

Control unit option

E33420

48/415 V AC 50/60 Hz
440 V 60 Hz

110/127 V AC 50/60 Hz

29352
54655

220/240 V AC 50/60 Hz

380/415 V AC 50/60 Hz
440 V 60 Hz

ACP + control unit BA (1)


29470
29471
Plate ACP
29363
29364
Control unit BA
29376
29377
29448
29472
29473
ACP + control unit UA (1)
Plate ACP
29447
29363
29364
Control unit UA 29446
29378
29380
29474
29475
ACP + control unit UA150 (1) (communication option)
Plate ACP
29363
29364
29379
29381
Control unit UA150
(1) The supply voltages of the BA/UA controller, ACP plate, IVE unit and circuit breaker operating mechanism must be identical whatever the type of sourcechangeover system.
GERIN

MERLIN
multi

0 . OFF

P25M

GERIN

MERLIN
multi

0 . OFF

660V
AC3-IEC292-1

P25M

660V
AC3-IEC292-1

Test

Test

Interlocking for source-changeover systems for 3 devices


Interlocking of 3 devices using cables
Choose 3 adaptation fixtures (1 complete set with 3 adaptation fixtures + cables)
3 sources, only 1 device closed, fixed or drawout devices
2 sources, 1 coupling, fixed or drawout devices
2 normal, 1 replacement source, fixed or drawout devices

48610
48609
48608

D-8

Livre 1.indb 8

08/10/2008 18:40:43

D-9

Livre 1.indb 9

08/10/2008 18:40:44

Catalogue numbers
and order forms

Source-changeover systems
for2devices
Interpact INS40 to INS630
Switch-disconnectors

To indicate your choices, check the applicable square boxes


appropriate information in the rectangles
.

and enter the

Mechanical interlocking of two INS40 to INS630 devices


Devices with front rotary handles, mounted side by side
Two devices with direct rotary handles
INS320/400/500/630
INS250
Two devices with extended rotary handles
INS40/63/80
INS100/125/160
INS250
INS320/400/500/630
Downstream coupling
accessory
Long terminal shields

INS250

INS320/400/500/630

INS250

INS320/400/500/630

Complete source-changeover assembly


INS250-100 A

INS250-160 A

INS250-200 A

INS250-250 A

INS320

INS400

INS500

INS630

D-10

Livre 1.indb 10

08/10/2008 18:40:44

Source-changeover systems
for2devices

Catalogue numbers
and order forms

Interpact INS40 to INS630


Switch-disconnectors
To indicate your choices, check the applicable square
boxes
and enter the appropriate information in the
rectangles
.

Indication and measurements


4P ammeter module

For INS250

Rating

100 A
150 A
250 A

(one sheet per device, make copies if necessary)

Device identification:
Q 1 - NORMAL SOURCE
Q 2 - REPLACEMENT SOURCE
Switch-disconnector
Interpact type

Adaptation kit required for direct handles


For INS320/630

400 A
600 A

INS40/63/80
INS100/125/160
INS250
INS320/400/500/630
A
3 or 4

Rating
Number of poles

Rating

4P current-transformer
module

Auxiliary contact

Connections

For INS250

Rating

100 A

For INS320/630

Rating

For INS40/160

1OF/CAF/CAO

For INS250/630

1 OF/CAM

Front connection Standard

150 A
250 A
400 A
600 A
Standard
Low level
Standard
Low level

Rotary handles
Rear connection
INS40/80
connectors
INS100/160
connectors
INS250

2 short
2 long
Distribution 3x16v rigid/10v flexible

connectors

Snap-on 10v to 185v (< 250 A)


Voltage tap connector for 185v
connector

Snap-on y 95v
Distribution 4x25v rigid/16v flexible
Snap-on 1.5v to 95v (< 160 A)

Clips for connectors

Set of 10

Distribution 6x1.5v to 35v rigid


with interphase barriers
INS320/630
connectors

Extended front handles

INS40 to INS160
Black
INS250
Black
Black
INS320 to INS630
For complete changeover assembly

Red on yellow front


Red on yellow front
Red on yellow front
INS250
INS320/630

Locking of rotary handles


Padlocking
Keylocking

1 to 3 padlocks (in OFF position)


Keylock adapter (keylock not included)
Keylocks Ronis 1351B.500
Profalux KS5 B24 D4Z

Installation accessories
Front-panel escutcheon

For switch-disconnectors
For ammeter module, IP40

1 cable 35v to 300v


2 cables 35v to 240v
Voltage tap connector for 185v
connector

Distribution
blocks

Distribloc
125 A
160 A
160 A
Multi-stage
125 A
250 A
Polybloc
160 A
630 A
Rt-angle extension Set of 3 or 4
250 A
Straight extension INS250
Edgewise ext.
INS630
Spreader
INS250 (45 mm)
Front alignment base
70 mm
INS320/630 52.5 mm
INS630
One-piece
INS250
For 95v cable
CU cable lugs
INS100/160
For 120v cable
supplied with
INS250
2 or 3 inter-phase
For 150v cable
barriers
For 185v cable
INS320/630
For 240v cable
For 300v cable
For 150v cable
AL cable lugs
INS250
supplied with
For 185v cable
2 or 3 inter-phase INS320/630
For 240v cable
barriers
For 300v cable
Terminal shrouds INS40/63/80
INS100/125/160
Terminal shields
INS40/63/80
INS100/125/160
Long
INS250
Short
Long
INS320/630
Short
Long for 52.5 mm spreaders
Set of 6
Interphase
INS100/160
Set of 6
barriers
INS250
INS320/630
Set of 6

D-11

Livre 1.indb 11

08/10/2008 18:40:44

Catalogue numbers
and order forms

Source-changeover systems
for 2 devices
Compact NS100 to NS630 / Circuit
breakers and switch-disconnectors
To indicate your choices, check the applicable square boxes
appropriate information in the rectangles
.

and enter the

Diagram for two Compact NS devices


Without automatic control, without emergency off auxiliaries
Without automatic control, with emergency off by MN
Without automatic control, with emergency off by MX

(no. 51201177)
(no. 51201178)
(no. 51201179)

Mechanical interlocking of two NS100 to NS630 devices


(fixed, plug-in or withdrawable)
Manually operated devices, mounted side by side:
Two devices with toggles
Two devices with rotary handles

Mechanical and electrical interlocking of two NS100 to NS630 devices


(fixed or plug-in)
Electrically operated devices, mounted side by side:
Select 1 base plate + IVE, the 4 auxiliary contacts and the options / accessories
Base plate + IVE
Identical voltages:
48 to 415 V AC 50/60 Hz
440/480 V AC 60 Hz
24 to 250 V DC
Replacement NS100/250
Normal NS100/250
Replacement NS400/630
Normal NS400/630
Replacement NS100/250
Normal NS400/630
Adapter kit for NS400/630 with NS100/250 (plug-in)
Auxiliary contacts
2 OF + 2 SDE (mandatory)
Quantity
Options
Long rear connections
Plug-in base
Downstream coupling accessory
3P
NS100/250
4P
NS400/630
Prefabricated wiring
Between device and IVE
Quantity

Automatic-control option
Power supply 220/240 V - 50/60 Hz:

Power supply 380/415 V - 50/60 Hz and 440 V - 60 Hz:

ACP + BA controller
ACP + UA controller
ACP + UA150 controller
ACP + BA controller
ACP + UA controller
ACP + UA150 controller

D-12

Livre 1.indb 12

08/10/2008 18:40:44

Source-changeover systems
for 2 devices

Catalogue numbers
and order forms

Compact NS100 to NS630 / Circuit


breakers and switch-disconnectors
To indicate your choices, check the applicable square
boxes
and enter the appropriate information in the
rectangles
.
(one sheet per device, make copies if necessary)

Device identification:
Q 1 - NORMAL SOURCE
Q 2 - REPLACEMENT SOURCE
Circuit breaker or switch-disconnector
Compact type
Rating
Circuit breaker
Switch-disconnector

Ammeter module

Electronic

Withdrawable
ME, MH, MB, MHM
Voltage
V
4p MB option on 3p NS

Plug-in kit
Compact
Withdrawable Compact
kit

4P

3P

4P

Standard

Low level

Motor mechanism
Instantaneous

AC
MX AC
MN AC
MN AC

DC
DC
DC
DC

V
V
V
V

Rotary handles

Indication auxiliary

Black
Red on yellow front
MCC conversion access.
CNOMO conversion access.
Black
Red on yellow front
Telescopic handle for withdrawable device
1 early-break switch
2 early-break switches
Wiring accessory for early-make switches

Locking
ME
SV F
FTI
A

F
FI
110/240 V AC/DC
24/48 V AC/24/72 V DC

Connections
Short

3P

Extended

COM wiring
Spare battery for STR43 and STR53
Rearconnect. kit

4P

Insulation-monitoring module
Voltage-presence indicator
Auxiliary contact
OF, SD, SDE or SDV
SDE adapter (TM or MA trip units)

Direct

TMD rating (16 250 A)


TMG rating (16 63 A)

STR43ME
Option STDAM

3P

Delayed

Mixed rear conn.

MA rating (2.5 220 A)


STR22
SE
GE
STR23
SE
SV
STR53 (basic)
UE F
STR53UE
FT
FI
ZSI wiring
Option T (rating 150630 A)

3P

I max
Current-transformer module

Electrical operation
Voltage releases

Thermal-magnetic or electronic trip unit


Thermalmag.

standard

Remote operation

Number of poles
2, 3 or 4
Number of poles tripped
2d, 3d, 3dN/2 or 4d
Fixed device
Front
Long rear conn.
connections
Plug-in/withdr. Plug-in
Earth-leakage protection

220-240 V 50/60 Hz

Indication and measurements

NS100/160/250
NS400/630
A
N, H, L
NA

Short rear conn.

Communication
Communicating OF, SD, SDE or SDV auxiliary contacts
Connected/disconnected position indication contacts
Motor mechanism + communicating OF, SD, SDE contacts

Mixed

Toggle (1 to 3 padlocks) Removable


Rotary handle
Keylock adapter (keylock not included)
Keylocks Ronis 1351B.500
Motor mechanism
Keylock adapter + Keylocks Ronis (special)
Keylock adapter (keylock not included)
Keylocks Ronis 1351B.500

Profalux KS5 B24 D4Z


NS100/250
NS400/630
Profalux KS5 B24 D4Z

Installation accessories
Front-panel escutcheon Toggle
Rotary handle, motor mechanism, escutcheon collar; IP40
Vigi module or ammeter IP40
Vigi module
Toggle cover
Sealing accessories
DIN rail adapter NS100/250

Plug-in / withdrawable configuration accessories


Auxiliary connections

Vigicompact
Vigicompact

Long terminal-shield kit for plug-in or withdr. NS400/630


Interphase-barrier kit for plug-in or withdr. NS400/630
NS100/250 connectors
Snap-on 1.5v to 95v (< 160 A)
Snap-on 10v to 185v (< 250 A)
Distribution 6 x 1.5v to 35v
NS1400/630 connectors
1 cable 35v to 300v
2 cables 35v to 240v
Right-angle terminal extensions
Straight extensions
NS100/250
Edgewise extensions
NS400/630
Spreader
NS100/250 (one piece)
(45 mm)
NS400/630 (52.5 mm)
(70 mm)
CU cable lugs NS100/250 120v
150v
185v
NS400/630 240v
300v
AL cable lugs NS100/250 150v
185v
NS400/630 240v
300v
Voltage measurement input for lugs NS100/250 y 185v
for connector
for lugs NS400/630
Short
Long
Terminal
NS100/250
shields
NS400/630
Short
Long
Long for 52.5 mm spreaders
Interphase barriers
Set of 6
Insulation kit > 600 V
Without spreaders
NS400/630
With 52.5 mm spreaders
2 insulating
NS100/250
screens:
NS400/630
52.5 pitch
70 pitch

Fixed

Plug-in base
accessories
Chassis accessories

Parts of plug-in

1 automatic connector fixed part with 9 wires (for base)


1 auto. conn. moving part with 9 wires (for circuit breaker)
1 support for 3 automatic connector moving parts
9-wire manual auxiliary connector (fixed + moving)
Long insulated terminals
Set of 3
Set of 4
2 IP4 shutters for base
Escutcheon collar
Toggle
Vigi
Locking kit (keylock not included)
2 carriage switches (conn./disconnected position indication)
Plug-in base FC/RC
2P
3P
4P
Set of two power connections
Standard
Vigi
Safety trip for advanced opening
For 3P/4P chassis
Moving part
Fixed part

D-13

Livre 1.indb 13

08/10/2008 18:40:45

Catalogue numbers
and order forms

Source-changeover systems
for 2 devices

Compact NS630b to NS1600 / Circuit


breakers and switch-disconnectors
To indicate your choices, check the applicable square boxes
appropriate information in the rectangles
.

and enter the

Diagram for two Compact NS devices


Electrical interlocking with lockout after fault:
Permanent replacement source (without IVE)
With emergency off by MX (without IVE)
With emergency off by MN (without IVE)
Permanent replacement source (with IVE)
With emergency off by MX (with IVE)
With emergency off by MN (with IVE)
Automatic control without lockout after fault:
Permanent replacement source (without IVE)
Engine generator set (without IVE)

(no. 51201180)
(no. 51201181)
(no. 51201182)
(no. 51201183)
(no. 51201184)
(no. 51201185)
(no. 51201186)
(no. 51201187)

Interlocking using connecting rods between two NS630b to NS1600 devices


Manually operated devices installed side-by-side:
For two fixed NS devices with extended rotary handles
Electrically operated devices installed one above the other:
Select a complete set including two adaptation fixtures and the connecting rods
Complete set for:
2 fixed NS devices
2 withdrawable NS devices

Interlocking using cables between two NS630b to NS1600 devices


Electrically operated devices installed one above the other or side-by-side:
Select a complete set including two adaptation fixtures and the cables
Complete set for:
2 fixed NS devices
2 withdrawable NS devices
1 fixed NS device + 1 withdrawable NS device

Electrical interlocking between two NS630b to NS1600 devices


1 IVE unit 48/415 V - 50/60 Hz and 440 V - 60 Hz
1 wiring kit for connection between 2 fixed / withdrawable devices to the IVE unit

Automatic-control option
Power supply 110 V - 50/60 Hz:

Power supply 220/240 V - 50/60 Hz:

Power supply 380/415 V - 50/60 Hz and 440 V - 60 Hz:

ACP + BA controller
ACP + UA controller
ACP + UA150 controller
ACP + BA controller
ACP + UA controller
ACP + UA150 controller
ACP + BA controller
ACP + UA controller
ACP + UA150 controller

D-14

Livre 1.indb 14

08/10/2008 18:40:45

Source-changeover systems
for 2 devices

Catalogue numbers
and order forms

Compact NS630b to NS1600 / Circuit


breakers and switch-disconnectors
To indicate your choices, check the applicable square
boxes
and enter the appropriate information in the
rectangles
.
(one sheet per device, make copies if necessary)

Device identification:
Q 1 - NORMAL SOURCE
Q 2 - REPLACEMENT SOURCE
Circuit breaker or switch-disconnector
Compact type
Rating
Circuit breaker
Switch-disconnector
Number of poles
Device

Indication contacts
SD trip indication (maximum 1)
6 A-240 V AC
Low level
SDE fault-trip indication (maximum 1) (SDE integrated in electrically operated devices)
6 A-240 V AC
Low level
OF ON/OFF indication contacts (maximum 3)
6 A-240 V AC

NS630b to NS1600
A
N, H, L
NA
3 or 4
Fixed

qty
CE - connected position
6 A-240 V AC
qty
CD - disconnected position
6 A-240 V AC
qty
CT - test position
6 A-240 V AC
Auxiliary terminals for chassis alone
3-wire terminal (30 parts)

Withdr. chassis
Withdr. without chassis
(moving part only)

Electrical operation

Remote operation

Voltage releases

Chassis alone without connections

Micrologic control unit


Basic protection
A - ammeter

2.0

Direct
Extended
Indication auxiliary

Communicating
AC
AC
AC

DC
DC
DC
Adjustable

V
V
V
Nonadjustable

Manual operation
Electrical operation
Manual operation
Electrical operation

For electrically operated


devices

Modbus Eco COM module


(for switchboard display units)

Connections
Horizontal rear
connections

Top

Bottom

Vertical rear connections


Front connections
4x240v bare cable
connectors + shields

Top
Top
NS - FC fixed

Bottom
Bottom

Long connection shields


Vertical-connection
adapters

NS - FC fixed
NS - FC fixed, withdr.

Cable-lug adapters
Arc chute screen
Interphase barriers
Spreaders

NS - FC fixed, withdr.
NS - FC fixed
NS - FC fixed, withdr.
NS - FC fixed, withdr.

VO - safety shutters on
chassis

NS - FC fixed

Black

Red on yellow front


CNOMO conversion access.
Black
Red on yellow front
Telescopic handle for withdrawable device
6 A-240 V AC
2 early-make switches
2 early-break switches

Locking
Toggle (1 to 3 padlocks)
Rotary handle using
a keylock

Communication

Digipact

Standard
Power supply
MX
MN
MN delay unit

qty
Low level
qty
Low level
qty
Low level
Jumpers (set of 10)
6-wire terminal (10 parts)

Rotary handles for fixed and withdrawable device

High setting 0.8 to 1 Ir


LT OFF
Jbus/
Modbus

qty

Low level

5.0

2.0
5.0
6.0
7.0
V
AD - external power-supply module
TCE - external sensor (CT) for neutral protection
Rectangular sensor
280 x 115 mm
TCW - external sensor for SGR protection
LR - long-time rating plug Standard 0.4 to 1 Ir
Low setting 0.4 to 0.8 Ir

COM module

qty

Carriage switches (possible combinations: 3 CE, 2 CD, 1 CT)

Removable system
OFF position
Ronis 1351B.500

Keylock kit (without keylock)


VBP - ON/OFF pushbutton locking
OFF position locking:
VCPO - by padlocks
VSPO - by keylocks
Keylock kit (w/o keylock)
Profalux
1 keylock
Profalux

2 identical keylocks, 1 key


Chassis locking in disconnected position:
VSPD - by keylocks
Keylock kit (w/o keylock)

VPEC - door interlock

Fixed system
ON and OFF positions
Profalux KS5 B24 D4Z

Profalux

Ronis
Ronis
Ronis

Profalux
Ronis
Kirk
Castell
1 keylock
Profalux
Ronis
2 identical keylocks, 1 key
Profalux
Ronis
2 keylocks, different keys
Profalux
Ronis
Optional connected/disconnected/test position locking
On right-hand side of chassis
On left-hand side of chassis

VPOC - racking interlock


VDC - mismatch protection

Accessories
CDM - mechanical operation counter
CDP - escutcheon
CP - transparent cover for escutcheon
OP - blanking plate for escutcheon
Mounting brackets for fixed NS
Test kits

Mini test kit

for mounting on horizontal


plane
Portable test kit

D-15

Livre 1.indb 15

08/10/2008 18:40:46

Catalogue numbers
and order forms

Source-changeover systems
for 2 devices

Masterpact NT or NW / Circuit breakers


and switch-disconnectors
To indicate your choices, check the applicable square boxes
appropriate information in the rectangles
.

and enter the

Diagram for 2 Masterpact NT/NW devices


Electrical interlocking with lockout after fault:
Permanent replacement source (without IVE)
With emergency off by MX (without IVE)
With emergency off by MN (without IVE)
Permanent replacement source (with IVE)
With emergency off by MX (with IVE)
With emergency off by MN (with IVE)
Automatic control without lockout after fault:
Permanent replacement source (without IVE)
Engine generator set (without IVE)
Automatic control with lockout after fault:
Permanent replacement source (with IVE)
Engine generator set (with IVE)
BA/UA controller (with IVE)

(no. 51201139)
(no. 51201140)
(no. 51201141)
(no. 51201142)
(no. 51201143)
(no. 51201144)
(no. 51156226)
(no. 51156227)
(no. 51156904)
(no. 51156905)
(no. 51156903)

Interlocking using connecting rods (NT/NW devices one above the other)
Select a complete set including two adaptation fixtures and the connecting rods
2 fixed NT devices
Complete set for:
2 drawout NT devices
2 drawout NW devices
2 fixed NW devices
1 fixed NT device + 1 fixed NW devices
1 drawout NT device + 1 drawout NW device

Interlocking using cables (NT/NW devices one above the other or side-by-side)
Select two adaptation fixtures (one for each device) and a set of two cables
Adaptation fixture for:
1 fixed NT device
(NT/NW fixed and drawout 1 drawout NT device
devices may be mixed)
1 fixed NW device
1 drawout NW device
1 set of 2 cables (for two devices)

qty
qty
qty
qty

Electrical interlocking 2 appareils NT/NW


1 IVE unit 48/415 V - 50/60 Hz and 440 V - 60 Hz
1 wiring kit for connection between 2 fixed / withdrawable devices to the IVE unit

Automatic-control option
Power supply 220/240 V - 50/60 Hz:

Power supply 380/415 V - 50/60 Hz and 440 V - 60 Hz:

ACP + BA controller
ACP + UA controller
ACP + UA150 controller
ACP + BA controller
ACP + UA controller
ACP + UA150 controller

D-16

Livre 1.indb 16

08/10/2008 18:40:46

Source-changeover systems
for 2 devices

Catalogue numbers
and order forms

Masterpact NT or NW / Circuit breakers


and switch-disconnectors
To indicate your choices, check the applicable square
boxes
and enter the appropriate information in the
.
rectangles
(one sheet per device, make copies if necessary)

Device identification:
Q 1 - NORMAL SOURCE
Q 2 - REPLACEMENT SOURCE
Circuit breaker or switch-disconnector
Masterpact type
Rating
Sensor rating
Circuit breaker
Switch-disconnector

NT
A
A
N1, H1, H2, H3, L1
NA, HA, HF, ES,
HA10 (NW)

Number of poles
Option: neutral on right side
Device

3 or 4

Indication contacts
OF - ON/OFF indication contacts
Standard
4 OF 6 A-240 V AC (10 A-240 V AC and low-level for NW)
qty
Additional
1 block of 4 OF for NW
max. 2
EF - combined connected/closed contacts
1 EF 6 A-240 V AC for NW

max. 8

1 EF low-level for NW

max. 8

SDE - fault-trip indication contact


Standard
1 SDE 6 A-240 V AC
Additional
1 SDE 6 A-240 V AC
1 SDE Low level
Programmable contacts
2 M2C contacts
6 M6C contacts
Carriage switches
6 A-240 V AC
Low level
CE - connected position max. 3 for NW / NT
CD - disconnected position max. 3 for NW, 2 for NT
CT - test position
max. 3 for NW, 1 for NT
AC - NW actuator for 6 CE - 3 CD - 0 CT additionnal carriage switches

NW

Fixed

Remote ON/OFF

Chassis alone without connections

MCH - gear motor


XF - closing voltage release
MX - opening voltage release
PF - ready to close contact

Micrologic control unit


A - ammeter
5.0
6.0
P - power meter
5.0
6.0
H - harmonic meter
5.0
6.0
AD - external power-supply module
TCE - external sensor (CT) for neutral protection
Rectangular sensor
NT (280 x 115 mm)
for earth-leakage protection NW (470 x 160 mm)

qty
qty
qty
qty

Remote operation

Withdr. chassis
Withdr. without chassis
(moving part only)

2.0

qty
qty

7.0
7.0
7.0
V

Remote tripping

Standard 0.4 to 1 Ir
Low setting 0.4 to 0.8 Ir
High setting 0.8 to 1 Ir
LT OFF
PTE - external voltage measurement input (required for
reverse supply)

BPFE - electrical closing pushbutton


Res - electrical reset option
RAR - automatic reset option
MN - undervoltage release
R - delay unit (non-adjustable)
Rr - adjustable delay unit
2nd MX - shunt release

VBP - ON/OFF pushbutton locking (by transparent cover + padlocks)


OFF position locking:
VCPO - by padlocks
VSPO - by keylocks
Keylock kit (w/o keylock)
Profalux
Kirk
1 keylock
Profalux
2 identical keylocks, 1 key
Profalux
2 keylocks, different keys (NW) Profalux

BAT - battery module

Communication
Eco COM module
Modbus
(for switchboard display units)

Chassis locking in disconnected position:


VSPD - by keylocks
Keylock kit (w/o keylock)

Connections
Top
Bottom
Top
Bottom
Top
Bottom
NT - FC fixed, draw.
NT - FC fixed, draw.
NT - FC fixed
NT, NW fixed, draw.
NT fixed, drawout
NW fixed

Lugs for 240v or 300v cables


VO - safety shutters on
chassis

NT fixed, draw.
NT, NW

VIVC - shutter position


indication and locking

NW

Low level
6 A-240 V AC
V
V

Locking

LR - long-time rating plug

Horizontal
Vertical
Front
Vertical-connection adapters
Cable-lug adapters
Arc chute screen
Interphase barriers
Spreaders
Disconnectable front
connection adapter

V
V
V

VPEC - door interlock

Profalux
Kirk

Ronis
Castell
Ronis
Ronis
Ronis
Ronis
Castell

1 keylock
Profalux
Ronis
2 identical keylocks, 1 key
Profalux
Ronis
2 keylocks, different keys
Profalux
Ronis
Optional connected/disconnected/test position locking
On right-hand side of chassis
On left-hand side of chassis

VPOC - racking interlock


IPA - cable-type door interlock
IBPO - racking interlock between crank and OFF pushbutton for NW
DAE - automatic spring discharge before breaker removal for NW
VDC - mismatch protection

Accessories
CDM - mechanical operation counter
CB - auxiliary terminal shield for chassis
CDP - escutcheon
CP - transparent cover for escutcheon
OP - blanking plate for escutcheon
Brackets for mounting NW fixed
Test kits
Mini test kit

on backplates
Portable test kit

D-17

Livre 1.indb 17

08/10/2008 18:40:47

Catalogue numbers
and order forms

Source-changeover systems
for 3 devices
Masterpact NW / Circuit breakers
and switch-disconnectors
To indicate your choices, check the applicable square boxes
appropriate information in the rectangles
.

and enter the

Diagram for 3 Masterpact NW devices


2 Normal sources + 1 Replacement source:
Electrical interlocking without lockout after fault
(no. 51156906)
Electrical interlocking with lockout after fault
(no. 51156907)
2 Normal sources + 1 Replacement source with source selection:
Automatic control w/ engine generator set w/o lockout after fault
(no. 51156908)
Automatic control w/ engine generator set w/ lockout after fault
(no. 51156909)
3 sources, only 1 device ON:
Electrical interlocking without lockout after fault
(no. 51156910)
Electrical interlocking with lockout after fault
(no. 51156911)
2 Normal sources + 1 coupling:
Electrical interlocking without lockout after fault
(no. 51156912)
Electrical interlocking with lockout after fault
(no. 51156913)
Automatic control with lockout after fault:
(no. 51156914)

Interlocking using cables (NW devices one above the other or side-by-side)
Select a complete set including three adaptation fixtures and the cables
1 complete set for:
3 sources / 1 device ON, fixed or drawout
2 sources + 1 coupling, fixed or drawout
2 sources + 1 replacement source, fixed or drawout

D-18

Livre 1.indb 18

08/10/2008 18:40:47

Source-changeover systems
for 3 devices

Catalogue numbers
and order forms

Masterpact NW / Circuit breakers


and switch-disconnectors
To indicate your choices, check the applicable square
and enter the appropriate information in the
boxes
.
rectangles
(one sheet per device, make copies if necessary)

Device identification:
Q 1 - NORMAL SOURCE
Q 2 - REPLACEMENT SOURCE
Circuit breaker or switch-disconnector
Masterpact type
Rating
Sensor rating
Circuit breaker
Switch-disconnector
Number of poles
Option: neutral on right side
Device

Indication contacts
OF - ON/OFF indication contacts
Standard
4 OF 6 A-240 V AC (10 A-240 V AC and low-level)
Additional
1 block of 4 OF
max. 2
EF - combined connected/closed contacts
max. 8

1 EF low-level

max. 8

Standard
1 SDE 6 A-240 V AC
Additional
1 SDE 6 A-240 V AC
1 SDE Low level
Programmable contacts
2 M2C contacts
6 M6C contacts
Carriage switches
6 A-240 V AC
Low level
CE - connected position
max. 3
CD - disconnected position max. 3
CT - test position
max. 3
AC - NW actuator for 6 CE - 3 CD - 0 CT additionnal carriage switches

NW

Fixed
Drawout with chassis

Remote operation

Drawout without chassis


(moving part only)

Remote ON/OFF

Chassis alone without connections

Micrologic control unit


A - ammeter
7.0
7.0
7.0
V

Remote tripping

TCW - external sensor for SGR protection


Standard 0.4 to 1 Ir
Low setting 0.4 to 0.8 Ir
High setting 0.8 to 1 Ir
LT OFF
PTE - external voltage measurement input (required for
reverse supply)

MCH - gear motor


XF - closing voltage release
MX - opening voltage release
PF - ready to close contact

Communication
Eco COM module
Modbus
(for switchboard display units)

Low level

6 A-240 V AC
BPFE - electrical closing pushbutton
Res - electrical reset option
RAR - automatic reset option
MN - undervoltage release
R - delay unit (non-adjustable)
Rr - adjustable delay unit
2eme MX - shunt release

Chassis locking in disconnected position:


VSPD - by keylocks
Keylock kit (w/o keylock)

Connections

VO - safety shutters on chassis


VIVC - shutter position indication and locking

qty
qty
qty
qty
V
V
V

VBP - ON/OFF pushbutton locking (by transparent cover + padlocks)


OFF position locking:
VCPO - by padlocks
VSPO - by keylocks
Keylock kit (w/o keylock)
Profalux
Kirk
1 keylock
Profalux
2 identical keylocks, 1 key
Profalux
2 keylocks, different keys (NW) Profalux

BAT - battery module

Top
Top
Top
Fixed, drawout
Fixed

qty

V
V

Locking

LR - long-time rating plug

Horizontal
Vertical
Front
Interphase barriers
Disconnectable front
connection adapter

qty

SDE - fault-trip indication contact

A
A
N1, H1, H2, H3, L1
NA, HA, HF
3 or 4

2.0
5.0
6.0
P - power meter
5.0
6.0
H - harmonic meter
5.0
6.0
AD - external power-supply module
TCE - external sensor (CT) for neutral protection
Rectangular sensor
470 x 160 mm
for earth-leakage protection

1 EF 6 A-240 V AC

qty

Bottom
Bottom
Bottom
VPEC - door interlock

Profalux
Kirk

Ronis
Castell
Ronis
Ronis
Ronis
Ronis
Castell

1 keylock
Profalux
Ronis
2 identical keylocks, 1 key
Profalux
Ronis
2 keylocks, different keys
Profalux
Ronis
Optional connected/disconnected/test position locking
On right-hand side of chassis
On left-hand side of chassis

VPOC - racking interlock


IPA - cable-type door interlock
IBPO - racking interlock between crank and OFF pushbutton for NW
DAE - automatic spring discharge before breaker removal for NW
VDC - mismatch protection

Accessories
CDM - mechanical operation counter
CB - auxiliary terminal shield for chassis
CDP - escutcheon
CP - transparent cover for escutcheon
OP - blanking plate for escutcheon
Brackets for mounting NW fixed
Test kits
Mini test kit

on backplates
Portable test kit

D-19

Livre 1.indb 19

08/10/2008 18:40:48

Notes

D-20

312E5100.indd 20

09/10/2008 10:07:52

312E0100.indd 3

20/10/2008 10:12:30

89, boulevard Franklin Roosevelt


F - 92505 Rueil-Malmaison Cedex (France)
Tel : +33 (0)1 41 29 85 00

As standards, specifications and designs change from time to time, please ask for confirmation
of the information given in this publication.

http://www.schneider-electric.com

This document has been printed on ecological paper.


Design: Schneider Electric
Photos: Schneider Electric
Printed: Centre Impression - made in France

http://www.schneider-electric.co

LVPED208007EN

312E0100.indd 4

ART836795 2008 - Schneider Electric - All rights reserved

Schneider Electric Industries SAS

10-2008

20/10/2008 10:12:30

Das könnte Ihnen auch gefallen