Tripping curve:
No.
Parameter Description
In
Trip unit setting range: The maximum setting corresponds to the trip unit In rating
Ir
tr
40
LV434104 09/2009
Preset Values of Ir (A) Depending on the Trip Unit In Rating and the Dial Position
40 A
18
18
20
23
25
100 A
40
45
50
55
63
70
80
90
100
160 A
63
70
80
90
100
110
125
150
160
250 A
100
110
125
140
150
175
200
225
250
400 A
160
180
200
230
250
280
320
360
400
630 A
250
280
320
350
400
450
500
570
630
28
32
36
40
Example:
A Micrologic 5.2 trip unit rated In = 250 A is preset by the dial at 140 A:
The minimum preset value is: 100 A
The fine-tuning range on the keypad is: 90...140 A
tr Time Delay Setting Value
The setting value displayed is the value of the trip time delay for a current of 6 Ir.
The default tr time delay setting value is 0.5 (minimum value) i.e. 0.5 seconds at 6 Ir.
The table below shows the value of the trip time delay (in seconds) according to the current in the load
for the setting values displayed on-screen:
Current in the Load
Setting Value
0.5
16
50
100
200
400
15
25
6 Ir
0.5
16
7.2 Ir
0.35
0.7
1.4
2.8
5.5
11
3
2
0
1
2
3
LV434104 09/2009
3
12
Trip unit without thermal image: On each current pulse, the trip unit only takes account of the thermal
effect on the pulse under consideration. No tripping occurs despite the build-up in conductor heat rise.
Trip unit with thermal image: The trip unit adds together the thermal effect of successive current
pulses. Tripping intervenes to take account of the actual thermal state of the conductor.
41
1
2
Thermal Memory
Micrologic 5 and 6 trip units incorporate the thermal memory function which ensures that the conductors
are cooled even after tripping: cooling lasts for 20 minutes before or after tripping.
42
LV434104 09/2009
Tripping curve:
No.
Parameter Description
Ir
Isd
tsd
2t
The tsd time delay setting incorporates activation/deactivation of the I2t option.
Setting the Short Time Protection (Micrologic 6)
The Isd pick-up and tsd time delay can be set as follows:
On the Micrologic trip unit, set on the keypad
Via the communication option using the RSU software
The tsd time delay setting incorporates activation/deactivation of the I2t option.
LV434104 09/2009
43
Preset by a dial
(Micrologic 5)
1.5
10
1.5/2
1.5...3
1.5...4
1.5...5
1.5...6
1.5...7
1.5...8
1.5...10
(1) For Micrologic 6 trip units, the setting range value on the keypad is: 1.5...10 Ir.
Value
0.1
0.2
0.3
0.4
I2
0.1
0.2
0.3
0.4
tsd with
t ON (s)
20
80
140
230
350
80
140
200
320
500
The default tsd time delay setting value is 0 s with I2t OFF.
I2t ON/OFF Function
The I2t inverse time curve function is used to improve circuit breaker discrimination. It is particularly
necessary when a protection device using inverse time only, for example a fuse protection device, is
installed downstream.
Example:
The figures below illustrate an example of discrimination between a Compact NSX630 upstream, and a
gG-250 A fuse downstream (calculation performed by the Ecodial software):
I2t OFF
I2t ON
t(s)
t(s)
gG - 250 A
gG - 250 A
I (A)
I (A)
44
2t
LV434104 09/2009
Instantaneous Protection
Presentation
Instantaneous protection on Micrologic 5 and 6 trip units is adapted to protecting all types of electrical
distribution application against very high intensity short-circuit currents.
It is identical for Micrologic 5 and 6 trip units.
Operating Principle
Instantaneous protection is definite time. It can be configured as Ii pick-up and without a time delay.
Tripping curve:
No.
Parameter Description
In
Trip unit setting range: The maximum setting corresponds to the trip unit In rating
Ii
Setting Range
Step
1.5....15 In
0.5 In
1.5....12 In
0.5 In
630 A
1.5....11 In
0.5 In
LV434104 09/2009
45