Good cooling tower practises

Georges Hoeterickx
Evapco Europe

Good cooling tower practises


Design considerations

Approach :
Difference between cooling tower outlet temp.
and design entering wb temp.

Design considerations
Cooling tower size versus approach

Cooling Tower Size

6
5
4
3
2
1
0
3

Approach F

10

11

12

Design considerations
Minimum approach

CTI Certification under STD-201


Certification is limited to thermal operating
conditions.. and a cooling approach of
2.8C (5F) or greater.

Good cooling tower practises


Cooling tower range

Range :
Difference between cooling tower inlet and
cooling tower outlet temperature.

Design considerations
Cooling tower size versus range

C.T. Size

1,2
1
0,8
0,6
0,4
0,2
0
80%

90%

100%

110%

Range

120%

130%

140%

150%

Good cooling tower practises


Design considerations

Avoid recirculation :
Bypass of warm discharge air into the cooling
tower air inlet will cause capacity losses.

Design considerations
Avoid recirculation

Top of cooling tower should be at least level


with enclosure.

Design considerations
Avoid recirculation
Fan discharge velocity : min. 1200 fpm

(6 m/sec).
Downward velocity : max. 600 fpm
(3 m/sec).

Design considerations
Avoid recirculation

Limit downward velocity - two side air inlet units

Design considerations
Avoid recirculation

Limit downward velocity - single air inlet units

Good cooling tower practises


Design considerations

Use of VFDs for fan motors :


Allow to control air flow through the cooling
tower

Design considerations
VFDs for fan motors

Energy saving ?

Condenser water temp 1F


Chiller efficiency 3%

Cooling tower kW = ~ 5 %
Chiller kW.

Design considerations
VFDs for fan motors
Water consumption :

Air flow

Water consumption

Plume formation :

Air flow

Plume formation tendency

Noise control @ night

Fan @ half speed : 9 dBA fan noise


(60% capacity)

Design considerations
VFDs for fan motors
Min. RPM for gear

(motor speed 450 RPM)


Gear with mechanical oil pump for proper

lubrication

Design considerations
Cooling tower basins
Common basin

+ Easier basin and cooling tower construction.


+ No need for equalizing connection
- Maintenance sump cleaning

Good cooling tower practises


Design considerations

Cooling Tower Basin :


Hold circulating water of the tower.

Design considerations
Cooling Tower Basin
Individual Basin per Cell

+ Easier for maintance (water)


- Need equalizing between basins.
- More costly construction

Design considerations
Cooling Tower Basin

Sound mats to reduce water noise


Noise reduction function
number of layers
distance mats water in basin !
Sound mats will obstruct basin access :

maintenance !

Good cooling tower practises


Obtain the specified and correct
quality level !

Obtain the specified quality


Cost distribution main items
Fan
Gear & Motor
Fill
Structure
Louvers
DE
Water Dis.
Fan Stack
Other

Good cooling tower practises


Obtain the specified quality

Typical requirements:

Obtain the specified quality


FRP structure
Reputable manufacturers have their

components third party tested per


ASTM E 84 for strength values and
flamability
Ask if these evidences are part of contract

submittals !

Obtain the specified quality


FRP structure

Three factors influence life expectancy :


Creep : long term deformation of a member

under load

Shear : FRP strong in one direction


UV degradation

Obtain the specified quality


FRP structure : creep
Design structure loads primarily taken by

fiber unidirectional
Loads by resin to be maintained low
Correct design assures long life time

Obtain the specified quality


FRP structure : shear

Loads in plane of laminate by resin


Avoid water migration by proper sealing

all holes
Inspect on regular basis

Obtain the specified quality


FRP structure

UV protection
UV degradation and moisture penetration

will have influence life time of an FRP


cooling tower
The UV rays will cause the decomposition of

the polymers holding the fibre glass together

FRP structure
UV protection
Surface veil material of non woven polyester

fabric to prevent fiber blow out

Surface veil creates a resin rich surface area

to provide enhanced UV protection

One mil thickness of surface veil =

2 3 years life time

FRP structure
UV protection

STRUCTURAL
RESIN 55-25%
GLASS 45-75%
WOVEN ROVEN AND
CONTINUOUS GLASS
250 MILS OR MORE

CORROSION BARRIER
RESIN 60-70 %
GLASS 30-40%
MAT OR CLOTH
40-60 MILS

EXTERNAL LINER
RESIN RICH 80-90%
GLASS 10-20%
15-20 MILS
SURFACING VEIL TYPE C
10-20 MIL THICKNESS

FRP structure
UV protection

Useful life of UV projected components


80
70
60
50
Midde East Climate
European Climate

40
30
20
10
0
5

10

15

20

25

30
Years

FRP structure
UV protection

How to verify UV protection quality ?


Have samples of different weight veil

material for comparison.


Variation in the visibility of the Continious
Filament Mat.

Obtain the required quality


FRP structure

Fire retardancy
Fire resistance and damage control of the
FRP structure.

FRP structure
Fire retardancy
Design with high quality, heat resistant / fire

retardant resin systems, Class 1 type

Specify self extinguishing


High glass content = minimum burn rate
Addition Antimony Trioxide improves fire

retarding

Obtain the required quality


FRP structure
Major part of the cooling tower cost
Most critical item for the cooling tower life

time !

How to obtain the required quality ?

Obtain the required quality


FRP structure

1. Demand cooling tower supplier names the FRP


source and ask delivery certificates from the
FRP manufacturer.
2. Reserve the right to inspect before delivery to
verify Quality Process Map is complied with.

Obtain the best quality


Fans

Obtain the best quality


Fans
Fans are selected for a given airflow and

static pressure

Fan design parameters :

diameter speed nbr and shape of blades


blade width
Fan design parameters influence :

cost power consumption noise

Cooling tower fans


Noise definition

Specify sound pressure


in dB(A) measured 1,5 meter
above fan discharge
(per CTI std ATC 128)

Cooling tower fans


Noise

Cooling tower fans


Comparison - 2000 ton tower - 196 m/ sec @ 160 Pa pressure drop
Fan
dia

Nbr
Blades

Rpm

ft

Tip
speed

Sound
Power

Fan shaft
Power

Fan

m/sec

dB(A)

kW

US $

14

270.8

60.5

100.3

59.3

2100

16

193.9

49.5

95.6

53.2

3600

18

186.8

54.2

99

46

13500

18 *

137

40

86.3

54.9

45000

Cooling tower fans


Fan power vs cost 2000 ton tower 196 m/sec @ 160 Pa pressure
drop

Fan dia

Tower price

Fan Power

ft

kW

14

16

+ 1, 25 %

- 11 %

18

+8 %

- 22 %

Cooling tower fans


Comparison - 5000 ton tower - 375 m/ sec @
Fan
dia

Nbr
Blades

Rpm

ft

160 Pa pressure drop

Tip speed

Sound
Power

Fan shaft
Power

Fan

m/sec

dB(A)

kW

US $

22

226

44.2

106.3

106.3

9500

26

104.8

43.5

97.9

87.1

26000

26

89.7

37.2

90.6

104.2

60000

28

82.6

36.9

90

102.3

65000

Cooling tower fans


Fan power noise vs cost - 5000 ton tower
375 m/ sec @ 160 Pa pressure drop

Fan
dia

Tower
price

Power

Sound
Power

ft

kW

dB (A)

22

106.3

26

+7%

- 18 %

97.9

26

20%

-2%

90.6

28

+ 22%

-4%

90

Obtain the required quality


Fan stacks

Fan stacks
Material
Height : 6 8 10 ft -
Material : Class 1 flame spread rating 25

(Class II and Class III = Cheaper !)


UV resistance (gelcoat 20 mil).
Access door or removable panel
Assembly hardware SST

Fan stacks
Make sure fan deck floor opening matches

fan cylinder
Smooth air inlet
Fan tip clearance : 0,5% fan dia

Obtain the required quality


Air inlet louvers

Water stays in
Sunlight stays out!

Air inlet louvers


Single pass louvers
Waterdroplets tend to splash out when fans

are shut off.


Sunlight still enters the cooling tower basin !

Air inlet louvers


Two pass air inlet louvers
Minimise splashout
Direct sunlight is blocked from the water

inside the tower and reducing the potential


for algae formation !
Minimum pressure drop

Air inlet louvers


Two pass air inlet louvers

Typical two pass air inlet louvers

Obtain the required quality


Drift eliminators

Obtain the required quality


Drift eliminators
Drift rates : 0,01 to 0,0005 % of tower flow

rate
Drift rate function of type DE, air velocity,

water loading and spray nozzle types

Drift eliminators
Quality

Drift rate dependends on:

Waterloading
Air velocity
Spray nozzle arrangement

Drift eliminators
Efficiency confirmation

Ask your cooling tower supplier names

manufacturer of DE
Demand independent test certifications

according to accepted standards

Drift eliminators
Execution on site

Air passes through area with minimum resistance


Air bypass reduces cooling effect
Water loss because of higher air velocity

Drift losses
Design considerations : air seals

Good cooling tower practises


Design considerations

Mechanical equipment
Fill
Water distribution

Good cooling tower practises


Obtain the specified and correct
quality level !

Thank you
Georges Hoeterickx