Sie sind auf Seite 1von 5

B- Series Diesel Fire Pump Start-up Check Off List

1
Battery 1
Battery 2
1
Date/Alarms 2
Pressure
O

Volts
4 .
3 .
6 : 3

Current
Mode
2 5
9 . 5
b u l
5 0
0 . 5
f l o
1 2 - 0 7
1 3 : 2
5
I : 2 5
P : 0

This is the Standard Display found on the Door of the


Fire Pump Controller. Alarms will flash on Line 3 in place
of the Date when trouble is detected.
Pressure: O = Cut Out (upper setting of pressure control)
I = Cut In (lower setting of pressure control)
For Discussion Purposes - Phase 1 has bell mounted on Door and Buttons below LED Display
P = Actual System Pressure
Phase 2 has bell mounted on Trim above Door.
Phase 3 has bell mounted on Door and Buttons on Left of LED Display.
Job Information:

k
a t
2 : 3 6
0 0 p s i

Controller Information:

Job Name:
Job Location:
Pump Mfg:
Pump Rep:
Sprinkler Co:
Sprinkler Rep:
Fire Dept Rep:
Insurance Rep:

Bulletin Number:
Catalog Number:
Serial Number:
Diesel MFG:
Battery Volts:
AC Voltage:
Date of Test:
Technician Name:

Engine Related Check Off Items :

1
2
3
4
5
6
7
8

These are the responsibility of others, but we should at least check to confirm they have been done.
Yes
No

Fill Cooling System with Antifreeze Solution


Fill Engine Crank Case with Lubricating Oil.
Fill Fuel Supply Tank with Fuel Oil ( at least enough to
run Diesel for required Test time
Connect The Batteries to the Engine
Fill Batteries with Electrolyte
Connect Wires between Engine and Controller
1-6,8-11 for most engines, 2-6,8-12 for Caterpillar
Connect Crank Case Heater to 120V (some 240V)
Connect Water Solenoid to terminals 1 and 11

______
______
______
______
______
______
______
______
______
______

______
______
______
______
______
______
______
______
______
______

The Pump Representative is our customer. The Electrical Contractor is either a sub to the Sprinkler Contractor or the General.
Either way, it is the electrical contractor's responsibility to complete the wiring connections.

B-Series Diesel Phase 3 Field Test Procedure


Controller Rep Responsibility to check
Yes

1
2
3
4
5
List :

6
7
8
9
10
11

Is Selector Switch in "Off" Position?


Does wiring agree with Connection Drawing?
Do Wire Sizes agree, especially 6, 8, and 11?
Are All Connections Tight?
What Alarms are connected?

No

______
______
______
______
______

______
______
______
______
______

Before Power is applied, all construction debris


______
and tools must be removed.
Locate CB3 and CB4 and turn on or confirm on.
______
Phase 2 units will be already on unless tripped.
Does voltage for batteries appear OK? See Display
______
If batteries are connected, Located CB1 and CB2
______
and turn "ON". Wait 5 seconds, Did "no ans" disappear?
Confirm Charging Currents are OK? No user adj.
______
Check for Jumper at Remote Start Input
______

______

Terminals:

______ Phase 1 CB's are located inside Top Left


Phase 2 CB's are not switchable

______
______ Both CB's are located in lower middle of
controller near AC Input Terminals

______
______ Phase 1 - Terminals 21 - 13
Phase 2 - Terminals 17 - 13
Phase 3 - Terminals J18-1 and J18-2

12

Check for Jumper at Deluge Valve Input

______ ______ Phase 1 - Terminals 23 - 25


Phase 2 - Terminals 23 - 42
Phase 3 - Terminals J19 or J4-25 and C

13

14

Check for Low Fuel Level Switch in Fuel Tank


Confirm landing of wires on proper Terminals

______ ______ Phase 1 - Terminals 23 - 24

Check for Jumper in place of High Fuel Level Sw

______ ______

Phase 2 - Terminals 23 - 43
Phase 3 - Terminals J4-24 and C
Phase 1 - Terminals 23 - 29
Phase 2 - Terminals 23 - 38
Phase 3 - Terminals J20 or J4-29 and C

15

Check Pressure Sensing Line to pressure Switch/Trans ______ ______


Be sure it is connected to system side of Check Valve.
FT-B10710-3001

Page 2

B-Series Diesel Phase 3 Field Test Procedure

Starting of the Pump

The following functions are only to be performed after the approval of the Pump Representative.
Yes
No
1
Place the Selector Switch in the Manual Position and Observe
_______ _______
that the Water Solenoid operated and cooling water is flowing.
2
Press the #1 Start Button and observe engine starting.
_______ _______
3
Move the Selector Switch to OFF to stop Engine
_______ _______
4
Press the #2 Start Button and observe engine starting.
_______ _______
5
Move the Selector Switch to OFF to stop Engine
_______ _______
6
Observe that the water solenoid closes off the cooling water flow.
_______ _______
7
Move the Selector Switch to AUTO
8
Relieve some water from the sensing line to drop the pressure
_______ _______
below the lower setpoint ( I = 25 psi). The pump should start.
9
Observe the Engine Running Light on the front of the Controller
_______ _______
confirm the engine speed switch closes at 15% of rated speed.
10
With Pressure above upper setting, press Red Stop button.
_______ _______
Engine should Stop and remain stopped unless pressure is low.
11
Move the Selector Switch to "OFF"

He must give the OK to proceed.

Phase 1&3 - Crank #1, Phase 2 Start #1


Phase 1&3 - Crank #2, Phase 2 Start #2

Phase 1&3 - Door Mounted, Phase 2 - Trim

Adjusting the Pressure Settings


Open the Door and look at the left edge of the Electronic Control Module.
You will find two DIP switch groupings. The upper switch group is S5 and should have all 4 switches "OFF"
The Second Group is S10 and controls several functions of the Fire Pump Controller.
#8, the top switch is for Factory Adjustment, Leave in OFF position
#7 and #6 should both be OFF to give a pressure reading interval of 5 PSI
#5 in the OFF position allows the controller to operate in PSI
#4 and #3 select the Delay Start timer setting, Both OFF give 0 Seconds delay.
#2 when OFF selects Manual Stop. Moving #2 to ON selects Automatic Stop set for 30 Min
#1 should be OFF for normal operation, Moving #1 to ON allows Pressure settings to be adjustable
Note: Alarm Display on Front of controller shows " DIP Switch Misset" while #1 is on to remind
you to Switch it OFF when pressures are set to prevent changes.
Move #1 to the ON position. Then observe front Display.
Press Cut Out until Desired Upper Pressure setting is reached. Push and hold will advance faster.
Value goes up until transducer limit is reached, the cycles back to 0 and up again.
Press Cut IN until Desired Starting Pressure setting is reached. Push and hold will advance faster.
Value goes up until CutOut limit is reached, the cycles back to 0 and up again.
Move #1 to the OFF position and unit has been set.

FT-B10710-3001

Page 3

B-Series Diesel Phase 3 Field Test Procedure


Engine Monitor Functions
1
With Engine Running from Auto Start position, Short Terminals
on Engine Temperature Switch. Observe light on Front of Control
2
With Engine Running from Auto Start position, Short Terminals
on Low Oil Pressure Switch. Hold for 10 seconds. Observe light
on Front of Controller.
3
Test Engine overspeed switch by using test switch on front of
engine panel or jumpering terminals on Speed Switch Relay.
Observe Engine Stop and proper light on front of controller.
4
Reset Engine Speed Switch, Turn Selector Switch to OFF to
Reset Controller.
5
Remove Battery Cable, Positive Terminal on Battery #1
Observe Battery 1 Failure and Red Light on Front of Controller
Re-install Battery Cable on Battery #1
6
Remove Battery Cable, Positive Terminal on Battery #2
Observe Battery 2 Failure and Red Light on Front of Controller
Re-install Battery Cable on Battery #2
7
Turn off CB1 inside controller. Observe AC Failure Light on
front of Controller. Note AC Failure in Display - Top Row.
Turn on CB1 inside controller.
8
Turn off CB1 inside controller. Observe AC Failure Light on
front of Controller. Note AC Failure in Display - Top Row.
Turn on CB1 inside controller.

Yes
_______

No
_______

_______

_______

_______

_______

_______

_______

_______

_______

_______

_______

_______

_______

_______

_______

Testing the Controller Starting


Bat Set 1
1
Turn the Selector Switch to Manual and using one of the
Manual Start Buttons, start the engine. When the
_______
engine speed stabilizes, Move the Selector Switch to OFF.
Manual
Let the engine come to a full stop and wait for Turbo charger
to stop rotating as well, then move Selector back to Manual.
2
Place a mark on the line above for the Battery Set used
During this start. Then use the other Manual Start Button
to perform the next Manual Start. Alternate Starts until
you have 3 starts on each battery set.
3
Now move the Selector Switch to the AUTO position.
_______
Using the hand valve on the sensing line just outside the
Automatic
controller, drain some pressure from the sensing line until
the pump starts. Observe the Pump Running LED and when engine
speed stabilizes, Push STOP Button on controller. Wait for engine
to stop as before and then drop pressure again. 3 times on each battery set.
FT-B10710-3001

Bat Set 2
_______
Manual

_______
Automatic

Page 4

B-Series Diesel Phase 3 Field Test Procedure


SetClock / Weekly Test Setup / Change
Hold "Print Events" Button for 6 Seconds
Display Changes to
T u
A u g
1 5 ,
0 6
1 3 : 4 1
W e e k l y
T e s t
: N
W e
1 4 : 2 2
1 4 : 2 3
E X I T
S t a r t
S t o p
S A V E

Set Clock Display


Choose Weekly Test: Y or N
Set Day, Start Time and Stop Time, Exit without changing
Save Changes

Use "Print Events" Button to move around display


Press "Engine Test" Button to Change an item.
When all changes are complete, Use "Print Events" button to get back to SAVE.
Then press "Engine Test" Button to SAVE the changes

Timer Setup, Sequence Start, RPT, AC Failure Start


Hold "Print Events" Button for 6 Seconds, Display Changes to Weekly Test Setup above
While still Holding "Print Events" Button, Press "Engine Test" three (3) times
Display Changes to
S e q u e n t .
T i m e : 1 5
S e c
Set Sequence Start timer here 0 - 99 Sec in 1 sec increments
R u n
P e r .
T i m e : 3 0
M i n
Set RPT here 1-60 Minutes in 1 minute increments
A C
F a i l
S t a r t
: N O
M
Set AC Fail Start Time Delay, 0 - 255 Minutes in 1 minute increments
S A V E
E X I T
Save Changes or Exit without saving
Pressure Transducer Calibration (Requires 2 Screens)
(Transducer Calibration only needed when replacing Transducers.)
Hold "Print Events" Button for 6 Seconds, Display Changes to Weekly Test Setup above
While still Holding "Print Events" Button, Press "Engine Test" four (4) times
Display Changes to
C U R
P R E S S U R E
0 P S I
Read Signal Pressure from Sensing Line Gauge, just outside the controller.
P R E S S 1
0 0 0 0
R E A D
Drop Signal pressure to near Zero- Enter Here, move to Read, Press Eng. Test
Increase Signal pressure to Maximum, Enter here, move to Read Press Eng. Test
P R E S S 2
0 5 0 0
R E A D
N E X T
E X I T
Exit if you do not wish to continue Calibration, otherwise, Choose Next
Pressing NEXT will get you to
O L D
N E W
G A I N
1 6 9 4 1
1 6 9 4 1
These are the calibration numbers that have been calculated based on the
O F F S E T
0 3 6 7
0 3 6 7
readings taken above. If you wish to save them choose Save, or
S A V E
E X I T
Exit without saving new calibration values.

FT-B10710-3001

Page 5

Das könnte Ihnen auch gefallen