Sie sind auf Seite 1von 1

2 HOURS

30

20

7
8
9
10

10000
9000
8000
7000

Circuit Breaker Time / Current Curves (Phase Current)


Magnum DS and Magnum SB Power Circuit Breakers
Response: Long Delay & Short Delay Trip (FLAT & I2T)
This curve is for 50Hz or 60Hz applications.

Available Long Delay


Setting
0.4 to 1x In = Ir
In 0.1 increments

6000
5000

1 HOUR

.7
.8
.9
1

.6

.5

Digitrip 520 / 520M / 520MC / 520i / 520Mi / 520MCi


Long Delay & Short Delay Curves

4000

Notes:
3000

1. If Long Delay thermal memory is enabled, trip times may be shorter than indicated on
this chart.
2000

2. The end of the curve is determined by the interrupting rating of the circuit breaker.
3. The Long Delay Pickup Point (indicated by rapid flashing of Unit Status LED on the product)
occurs at 110%, with a 5% tolerance. The Instantaneous settings have conventional 100%
10% at the pick up points.

1000
900
800
700

4. With Zone Selective Interlocking enabled, max trip times w/o aux power are as follows:

600

3-phase fault
75ms
85ms

60 Hz
50 Hz

500
400

When only one pole is carrying current and a fault occurs, trip times increase to 90ms at 60Hz and
95ms at 50 Hz, however with Aux power these times would be reduced by 10%.

300

5. This curve is shown as a multiple of the Long Delay Setting.


200

Maximum Total
Clearing Time

6. Breakpoint back to FLAT response indicated by dots occurs @8x Ir for upper line of I T curve.
7. Additional available max M1 settings (all adjustable ranges are 2x to 10x Ir):

Minimum
Total
Clearing
Time

1 MINUTE

100
90
80
70

Narrow Frame:
200A through 1250A
1600A, 2000A
Standard Frame:
200A through 1250A
1600A, 2000A, 2500A
3000A, 3200A
Double Wide Frame:
2000A, 2500A
3200A, 4000A, 5000A
6000A, 6300A (IEC only)

60
50

40

Long Delay
Time curves
can extend
down to M1
(Max Short
Delay Setting)
See Note 7

30
24

20

15

10
9
8
7

Available Long
Delay Time
Shown @ 6x Ir
2,4,7,10,12,15,
20,24 Seconds
+0/-30%

6
5

M1 = 14x In
M1 = 12x In
M1 = 14x In
M1 = 12x In
M1 = 10x In
M1 = 14x In
M1 = 12x In
M1 = 10x In

8. Curve applies from -20C to +55C ambient. Temperatures above +85C cause automatic trip.
Breaker must be applied according to Continuous Rating at Different Ambient table.
9. These curves are comprehensive for the complete family of Magnum breakers, including all
frame sizes, ratings, and constructions. The total clearing times shown are conservative and
consider the maximum response times of the trip unit, the circuit breaker opening, and the
interruption of the current under factors that contribute to worst case conditions, like: maximum
rated voltages, single phase interruption, and minimum power factor. Faster clearing times are
possible depending on the specific system conditions, the type of Magnum Circuit Breaker applied,
and if any arc reduction settings are employed. Contact Eaton for additional information.

5
4

4
4

2.5 3

1
.9
.8
.7
.6

Available
Short Delay
Settings
2 to 10x Ir
5%
See Note 7

10
2.5

.5

8
3

TIME IN SECONDS

1
.9
.8
.7
.6

.5

.5*

.5

.4

.4
.4

.3

.3
.3*

.3

Available Flat
Short Delay
Time 0.1 to 0.5
Seconds

.2
.2

.2

.1

.1*

.1
.09
.08
.07
.06

.1
.09
.08
.07
.06

.05

.05

.04

.04

.03

.02

.03

Available I t Short
Delay Time Response
.1*, .3*, .5* seconds

Application
Determines
End of curve

.02

.01

60

70
80
90
100

50

40

30

20

7
8
9
10

50

60
70
80
90
100

40

30

20

7
8
9
10

.7
.8
.9
1

.6

.01
.5

TIME IN SECONDS

Current in Multiples of Long Delay Setting ( Ir )


Dwg. No: 70C1006
July 2012

Das könnte Ihnen auch gefallen