Special Requirements

of IEEE C37.013 for


Generator Circuit Breaker
Applications

November 20, 2009

Schutzvermerk / Copyright-Vermerk
Siemens AG 2009
Sector Energy, Business Unit Medium Voltage

Generator Circuit Breaker Applications


What is different about generator
circuit breakers?
Applicable standards
Special considerations
Vacuum versus SF6 technology
Questions.

Siemens AG 2009
Folie 2

November 09

Sector Energy, Business Unit Medium Voltage

Generator and Distribution Circuit Breakers


Generator circuit breaker

Distribution circuit breaker

Siemens AG 2009
Folie 3

November 09

Sector Energy, Business Unit Medium Voltage

Circuit Breakers for Distribution


Requirements
Standards:
IEEE C37.04
IEEE C37.09
IEEE C37.10

Rating structure for HV circuit breakers


Tests for HV circuit breakers
Application guide for HV circuit breakers.

X/R ratio:

17 (60 Hz).

Time constant of dc decay:

45 ms.

TRV typical values (15 kV, class S1 cable):


Peak voltage
(uc) = 25.7 kV
Time-to-peak
(t3) = 66 s
RRRV
0.39 kV/s.

Duty cycle:
Folie 4

November 09

O t CO t CO
t = 0.3 s for reclosing / 15 s for non-reclosing
Siemens AG 2009
t = 3 minutes.
Sector Energy, Business Unit Medium Voltage

Circuit Breakers for Generation


Requirements
Standards:
IEEE C37.013

Generator circuit breaker.

X/R ratio:

50 (60 Hz).

Time constant of dc decay:

133 ms.

TRV typical values (15 kV, 100 MVA machine):


Peak voltage
(E2) = 1.84 V = 1.84 x 15.0 = 27.6 kV
Time-to-peak
(T2) = 0.62 V = 0.62 x 15.0 = 9.3 s
RRRV
3.5 kV/s.

Duty cycle:

CO 30 min CO.
Siemens AG 2009

Folie 5

November 09

Sector Energy, Business Unit Medium Voltage

Notes on TRV Representation


IEEEC37.04 for distribution circuit
breakers expresses TRV in terms
harmonized with IEC with peak voltage
uc, and
time-to-peak t3.
IEEE C37.013 still uses old TRV
expressions with peak voltage E2 and
time-to-peak T2. Peak voltage is not
changed, but t3 is approximately 0.88 x
T2.
The physics are not changed, just the
representation.

Siemens AG 2009
Folie 6

November 09

Sector Energy, Business Unit Medium Voltage

IEEE C37.04-1999 Scope


IEEE Standard Rating Structure for AC High-Voltage Circuit Breakers

1. Scope
This standard establishes a symmetrical current rating structure and construction
requirements for all indoor and outdoor types of ac high-voltage circuit breakers
rated above 1000 V. It is only applicable to three-pole circuit breakers used in
three-phase systems and single-pole circuit breakers used in single-phase
systems.
This standard does not cover circuit breakers used at frequencies other than
50 Hz or 60 Hz, or generator circuit breakers that are covered in IEEE
Standard C37.013-1997.

Siemens AG 2009
Folie 7

November 09

Sector Energy, Business Unit Medium Voltage

IEEE C37.013-1997 Scope


IEEE Standard for AC High-Voltage Generator Circuit Breakers Rated on a
Symmetrical Current Basis
1. Scope
This standard applies to all ac high-voltage generator circuit breakers rated on a
symmetrical current basis that are installed between the generator and the
transformer terminals...
Note: Since no other national or international standard on generator circuit
breakers exists, this standard is used worldwide.

Siemens AG 2009
Folie 8

November 09

Sector Energy, Business Unit Medium Voltage

IEEE C37.013 the International Standard


for Generator Circuit Breakers
IEEE C37.013 Revision PAR (Project)
PAR approved by IEEE-SA
Standards Board, March, 2009
Joint development with IEC SC 17A
(HV Switchgear and Controlgear)
IEEE WG chair is convenor (WG chair) of
IEC working group.
IEC has no standard for a generator circuit breaker.
The IEEE and IEC intent has been that IEEE
C37.013 would be the global standard.
IEC SC 17A WG 52
WG scope: Joint IEC/IEEE revision of
IEEE C37.013: IEEE Standard for AC HighVoltage Generator Circuit Breakers Rated on a
Symmetrical Current Basis
Siemens AG 2009
Folie 9

November 09

Sector Energy, Business Unit Medium Voltage

X/R Ratio Determines %dc Component


X/R = 17, = 45 ms

X/R = 50, = 133 ms

%dc vs Contact Part for X/R = 17 and X/R = 50


120.0

%dc Component

100.0

80.0

60.0

40.0

20.0

0.0
0

10

15 20

25

30

35

40

45

50 55

60

Contact Part tim e (m s)

65

70

75

80 85

90

95 100
X/R = 17
X/R = 50

Siemens AG 2009
Folie 10

November 09

Sector Energy, Business Unit Medium Voltage

X/R Ratio Effect on Asymmetrical Interrupting

3.00

Instantaneous (total) current

2.50

S-factor (C37.04-1979)

dc component

dc component (in decimal form)


(multiply by 100 for %dc component)
(C37.04-1999)

Current (Isc = 1.00)

2.00
1.50
1.00
0.50
0.00
-0.50
-1.00
-1.50

Symmetrical current (ac component)

3600

3420

3240

3060

2880

2700

2520

2340

2160

1980

1800

1620

1440

1260

1080

900

720

540

360

180

-2.00

Time (in degrees)


Siemens AG 2009
Folie 11

November 09

Sector Energy, Business Unit Medium Voltage

X/R Ratio Effect on Asymmetrical Interrupting

S=

I total
I symmetrical

= 1 + 2(%dc / 100)

S factor (from IEEE C37.04-1979)


Ratio of rms asymmetrical current to rms symmetrical current
Assume contact part time of 55 ms, and 50 kA symmetrical current
X/R = 17

%dc = 29.5

S = 1.084

I = 54.2 kA

X/R = 50

%dc = 66.1

S = 1.369

I = 68.5 kA
over 26% higher

Siemens AG 2009
Folie 12

November 09

Sector Energy, Business Unit Medium Voltage

Short-Circuit Currents
Consider system shown:
Transformer
1,000 A full load (self-cooled)
impedance = 10%
Generator
1,000 A full load
Xd (subtransient reactance) = 20%
For fault at F2, circuit breaker sees transformer
fault current, roughly 1,000 A / 0.10 = 10 kA
For fault at F1, circuit breaker sees generator
fault current, roughly 1,000 A / 0.20 = 5 kA

F1

F2
G

Note:
Fault current for generator
source fault is only about
50% of fault current for
system (transformer)
source fault
Siemens AG 2009

Folie 13

November 09

Sector Energy, Business Unit Medium Voltage

Generator Circuit Breaker Ratings


Characteristic

Unit

Drawout
(Metal-Clad)

FixedMounted

Maximum voltage

kV

15.0

17.5

Dielectric 60 Hz / BIL

kV/kV

38 / 95

50 / 110

Short-circuit current
Transformer source
Generator source

kA
kA

40 / 63
20 / 31.5

50 / 63 / 72
25 / 31.5 / 36

%dc component

73 / 61

75 / 65 / 65

Delayed current zero*

ms

40 / 30

30 / 30 / 30

TRV parameters
Peak voltage (1.84 V)
RRRV transformer source
RRRV generator source

kV
kV/s
kV/s

27.6
3.5 / 4.5
1.6 / 1.8

32.2
4.5 / 4.5 / 4.5
1.4 / 1.8 / 1.8

* Higher values may be available


Folie 14

November 09

Siemens AG 2009
Sector Energy, Business Unit Medium Voltage

Generator Circuit Breakers

Siemens AG 2009
Folie 15

November 09

Sector Energy, Business Unit Medium Voltage

Generator Circuit Breakers

Siemens AG 2009
Folie 16

November 09

Sector Energy, Business Unit Medium Voltage

Out-of-Phase Switching
Circuit Breakers for Standard Applications:
IEEE C37.04 (clause 5.12):
Out-of-phase switching is optional, not required for general purpose circuit
breakers
If a rating is assigned, the preferred rating is 25% of the rated symmetrical
interrupting rating, with recovery voltage of (250% rated voltage / 1.732).
Therefore, out-of-phase ratings are not typically assigned to general purpose
circuit breakers rated per IEEE C37.04 and tested to IEEE C37.09.

Siemens AG 2009
Folie 17

November 09

Sector Energy, Business Unit Medium Voltage

Out-of-Phase Switching
Circuit Breakers for Generator Switching Applications:
IEEE C37.013 (clause 6.2.9):
Out-of-phase switching is optional, not required for generator circuit breakers
If a rating is assigned, the assigned rating is shall be 50% of the rated
symmetrical interrupting rating (transformer or system source).
Out-of-phase switching recovery voltage values are based on a maximum
out-of-phase condition of 90 degrees between generator and system. This is
reasonable as more extreme angles would result in damage to the machine.
The likelihood of out-of-phase switching is influenced by generator inertia, i.e.,
low-inertia machines are more likely to be subject to out-of-phase switching
conditions.
Generator circuit breakers should have an assigned out-of-phase switching
rating.
Siemens AG 2009
Folie 18

November 09

Sector Energy, Business Unit Medium Voltage

Other Differences
Reclosing:
Reclosing duty not required for generator circuit breakers.
Short-time current duration:
Normal circuit breakers
3 seconds (metal-clad switchgear = 2 seconds)
Generator circuit breakers
1.0 second (typically test to 3 seconds).
Closing & latching rating:
Normal circuit breakers
Peak current 260% of symmetrical short-circuit (60 Hz)
With X/R = 17, real peak is 259.3%
Generator circuit breakers
Peak current 274% of symmetrical short-circuit (60 Hz)
With X/R = 50, real peak is 274.2%.
Siemens AG 2009
Folie 19

November 09

Sector Energy, Business Unit Medium Voltage

160

150

140

130

120

110

100

90

80

70

60

50

40

30

20

10

Delayed Current Zero Example C37.013

0.500
0.000
-0.500

Current (unitized)

-1.000
-1.500
-2.000
-2.500
-3.000
-3.500
-4.000
Time (ms)

Siemens AG 2009
Folie 20

November 09

Sector Energy, Business Unit Medium Voltage

Delayed Zero Test Example

20.6 ms

30.0 ms

40.1 ms

57.7 ms
Siemens AG 2009

Folie 21

November 09

Sector Energy, Business Unit Medium Voltage

Generator Circuit Breaker Technologies


Vacuum
Well-suited to smaller units
(up to 6,000 A or so)

SF6
Only option for very large units

Most economic for small units

VERY expensive

Derived from proven distribution unit


operators and interrupters
High experience-base

Unlike distribution products

Very low arc voltage (20 - 50 V)


Little affect on X/R ratio
Lower arc voltage = less arc energy =
lower contact erosion

SF6 low arc voltage (several 100 V)


Somewhat higher impact on X/R ratio
Higher arc voltage = higher arc energy =
greater contact erosion

Lower experience-base

Extremely rapid recovery of dielectric


Less able to cope with high TRV levels
strength between contacts after
interruption good for extreme TRV levels
Siemens AG 2009
Folie 22

November 09

Sector Energy, Business Unit Medium Voltage