Sie sind auf Seite 1von 9

MEDICAL CLINIC AND RESIDENTIAL BUILDING

JEDDAH, SAUDI ARABIA


BILL OF QUANTITIES FOR ELECTRICAL INSTALLATION WORKS
ITEM
DESCRIPTION
NO.
C) LOW VOLTAGE SWITCHGEARS AND PANEL
BOARDS:
1

Supply and installation of main distribution board (MDB)


with 14 Nos. branches, as shown and described on
drawings and specifications with individual mounted
main and group mounted feeders and short circuit level
of 65 KA, RMS, symetrical at 220/380V. Minimum. The
switchboard shall be free standing floor mounted type
(40" deep minimum) top entry main and top entry
outgoing feeders and shall be front access and include
the following mian/sub-main breakers.

Main Circuit Breaker:


600A.MCCB with magnetic and thermal trip adjustable
type with interrupting capacity of 25 KA, RMS,
symetrical at 220/380V, minimum. The breaker shall be
suitable for connection of the required numbers of
feeders. (No.1)

Branch Breaker:

i)

250A, 3P, moulded case circuit breaker magnetic &


thermal trip, adjustable type with interrupting capacity of
25 KA, RMS, Symetrical at 220/380V (No.1)

ii)

150A, 3P, moulded case circuit breaker, magnetic and


thermal triup with interrupting capacity of 42 KA, RMS,
symetrical at 220/380V. (No.1)

iii)

100A, 3P, moulded case circuit breaker, magnetic and


thermal triup with interrupting capacity of 25 KA, RMS,
symetrical at 220/380V. (Nos.4)

iv)

60A, 3P, moulded case circuit breaker, magnetic and


thermal trip with interrupting capacity of 42 KA, RMS,
symetrical at 220/380V. (Nos.8)

Indicating Panel : (3 Nos. indicating lamps, 3 Nos.


Ammeters, 1 No. Voltmeter and 1 No. Selector Switch)

UNIT

The switch board shall be floor mounted type, ABB


No.
Make.

1329/1433-J
1/5/2015

2 of 25

QTY.

UNIT
RATE

AMOUNT
IN (SR)

MEDICAL CLINIC AND RESIDENTIAL BUILDING


JEDDAH, SAUDI ARABIA
BILL OF QUANTITIES FOR ELECTRICAL INSTALLATION WORKS
ITEM
DESCRIPTION
UNIT
NO.
2 Supply and installation of sub distribution Panel board
(SDB ) with 11 Nos. branches, as shown and described
on drawings and specifications with individual mounted
main and group mounted feeders and short circuit level
of 25 KA, RMS, Symetrical at 220/380V. minimum. The
Panel board shall be wall mounted bottom entry main
and outgoing feeders and shall be front access and
include the following main/sub-main breakers

QTY.

a) Main breaker
250A, 3P, moulded case circuit breaker magnetic &
thermal trip, adjustable type with interrupting capacity of
35 KA, RMS, Symetrical at 220/380V (No.1)

b) Branches:
i)

100A, 3P, moulded case circuit


breaker, magnetic and thermal trip
type with interrupting capacity of 18 KA,
RMS, symetrical at 220/380V. (Nos.3)

ii)

60A, 3P, moulded case circuit


breaker, magnetic and thermal trip
with interrupting capacity of 18 KA,
RMS, symetrical at 220/380V. (Nos.4)

iii)

32A, 3P, moulded case circuit


breaker, magnetic and thermal trip
with interrupting capacity of 18 KA,
RMS, symetrical at 220/380V. (Nos.4)

The sub distribution board shall be wall mounted type


ABB make.
3

Supply and installation of typical sub distribution Panel


board (SDB-M, SDB-R-MC2, SDB-R-MC3 ) with 2 Nos.
branches, as shown and described on drawings and
specifications with individual mounted main and group
mounted feeders and short circuit level of 18 KA, RMS,
Symetrical at 220/380V. minimum. The Panel board
shall be wall mounted bottom entry main and outgoing
feeders and shall be front access and include the
following main/sub-main breakers
a) Main breaker

1329/1433-J
1/5/2015

3 of 25

No.

UNIT
RATE

AMOUNT
IN (SR)

MEDICAL CLINIC AND RESIDENTIAL BUILDING


JEDDAH, SAUDI ARABIA
BILL OF QUANTITIES FOR ELECTRICAL INSTALLATION WORKS
ITEM
NO.

DESCRIPTION

UNIT

QTY.

Nos.

300AF (250AT), 3P, moulded case circuit breaker


magnetic & thermal trip, adjustable type with
interrupting capacity of 35 KA, RMS, Symetrical at
220/380V (No.1)
b) Branches:
i)

150A, 3P, moulded case circuit


breaker, magnetic and thermal trip
with interrupting capacity of 18 KA,
RMS, symetrical at 220/380V. (No.1)

iii)

60A, 3P, moulded case circuit


breaker, magnetic and thermal trip
with interrupting capacity of 18 KA,
RMS, symetrical at 220/380V. (No.1)

The sub distribution board shall be wall mounted type


ABB make.
4

Supply and installation of typical sub distribution Panel


board (SDB-F-MC1, SDB-F-MC2, SDB-F-MC3,SDB-FMC4,SDB-S-MC1,SDB-S-MC2, SDB-S-MC3, SDB-SMC4, SDB-T-MC1,SDB-T-MC2,SDB-T-MC3,SDB-TMC4 ) with 2 Nos. branches, as shown and described
on drawings and specifications with individual mounted
main and group mounted feeders and short circuit level
of 18 KA, RMS, Symetrical at 220/380V. minimum. The
Panel board shall be wall mounted bottom entry main
and outgoing feeders and shall be front access and
include the following main/sub-main breakers
a) Main breaker
300AF (250AT), 3P, moulded case circuit breaker
magnetic & thermal trip, adjustable type with
interrupting capacity of 35 KA, RMS, Symetrical at
220/380V (No.1)
b) Branches:
i)

1329/1433-J
1/5/2015

150A, 3P, moulded case circuit


breaker, magnetic and thermal trip
with interrupting capacity of 18 KA,
RMS, symetrical at 220/380V. (No.1)

4 of 25

UNIT
RATE

AMOUNT
IN (SR)

MEDICAL CLINIC AND RESIDENTIAL BUILDING


JEDDAH, SAUDI ARABIA
BILL OF QUANTITIES FOR ELECTRICAL INSTALLATION WORKS
ITEM
NO.

DESCRIPTION
iii)

QTY.

Nos.

12

Nos.

125A, 3P, moulded case circuit


breaker, magnetic and thermal trip
with interrupting capacity of 18 KA,
RMS, symetrical at 220/380V. (No.1)

The sub distribution board shall be wall mounted type


ABB make.
5

UNIT

Supply and installation of sub distribution Panel board


(SDB-R-MC1 ) with 2 Nos. branches, as shown and
described on drawings and specifications with individual
mounted main and group mounted feeders and short
circuit level of 18 KA, RMS, Symetrical at 220/380V.
minimum. The Panel board shall be wall mounted
bottom entry main and outgoing feeders and shall be
front access and include the following main/sub-main
breakers
a) Main breaker
300AF (250AT), 3P, moulded case circuit breaker
magnetic & thermal trip, adjustable type with
interrupting capacity of 35 KA, RMS, Symetrical at
220/380V (No.1)
b) Branches:
i)

150A, 3P, moulded case circuit


breaker, magnetic and thermal trip
with interrupting capacity of 18 KA,
RMS, symetrical at 220/380V. (Nos.2)

The sub distribution board shall be wall mounted type


ABB make.
6

Supply and installation of branch panel board type PBB1, with 24 Nos. branches and 7 nos. sub branches , as
shown and described on drawings and specification
including the following:
60A, 3P, main MccB, 18 KA, RMS, Symetrical, IC at
220/380V
Branches :
25A. TP # 1 No.
32A. SP # 2 Nos.
20A. SP # 21 Nos.
Sub-Branches :

1329/1433-J
1/5/2015

5 of 25

UNIT
RATE

AMOUNT
IN (SR)

MEDICAL CLINIC AND RESIDENTIAL BUILDING


JEDDAH, SAUDI ARABIA
BILL OF QUANTITIES FOR ELECTRICAL INSTALLATION WORKS
ITEM
NO.

DESCRIPTION
20A,

SP

UNIT

QTY.

No.

No.

No.

# 7Nos.

Contactors :
32A, 4P, Contractor # 1 No.
The branch panel board shall be surface mounted type
with bolt-on breakers, ABB make.
7

Supply and installation of branch panel board type PB2,


with 11 Nos. branches and 7 nos. sub branches , as
shown and described on drawings and specification
including the following:
60A, 3P, main MccB, 18 KA, RMS, Symetrical, IC at
220/380V
Branches :
25A. TP # 1 No.
32A. SP # 1 Nos.
20A. SP # 10 Nos.
Sub-Branches :
20A, SP # 7Nos.
Contactors :
32A, 4P, Contractor # 1 No.
The branch panel board shall be flush mounted type
with bolt-on breakers, ABB make.

Supply and installation of typical branch panel board


type PB3, with 18 Nos. branches as shown and
described on drawings and specification including the
following:
100A, 3P, main MccB, 18 KA, RMS, Symetrical, IC at
220/380V
Branches :
40A. TP # 1 Nos.
32A. TP # 1 No.
32A. SP # 1 Nos.
20A. SP # 11 Nos.
The branch panel board shall be flush mounted type
with bolt-on breakers, ABB make .

1329/1433-J
1/5/2015

6 of 25

UNIT
RATE

AMOUNT
IN (SR)

MEDICAL CLINIC AND RESIDENTIAL BUILDING


JEDDAH, SAUDI ARABIA
BILL OF QUANTITIES FOR ELECTRICAL INSTALLATION WORKS
ITEM
DESCRIPTION
UNIT
NO.
9 Supply and installation of branch panel board type PBG1, with 34 Nos. branches and 8 nos. sub branches as
shown and described on drawings and specification
including the following:

QTY.

100A, 3P, main MccB, 18 KA, RMS, Symetrical, IC at


220/380V
Branches :
25A. TP # 1 No.
20A. SP # 33 Nos.
Sub-Branches :
20A, SP # 8 Nos.
Contactors :
32A, 4P, Contractor # 1 No.
The branch panel board shall be surface mounted type
with bolt-on breakers, ABB make .
10

No.

No.

Supply and installation of branch panel board type PBGU, with 25 Nos. branches and 5 nos. sub branches as
shown and described on drawings and specification
including the following:
100A, 3P, main MccB, 18 KA, RMS, Symetrical, IC at
220/380V
Branches :
25A. TP # 1 No.
32A. SP # 6 Nos.
20A. SP # 19 Nos.
Sub-Branches :
20A, SP # 5 Nos.
Contactors :
32A, 4P, Contractor # 1 No.
The branch panel board shall be flush mounted type
with bolt-on breakers, ABB make .

11

1329/1433-J
1/5/2015

Supply and installation of branch panel board type PBF, with 18 Nos. branches as shown and described on
drawings and specification including the following:

7 of 25

UNIT
RATE

AMOUNT
IN (SR)

MEDICAL CLINIC AND RESIDENTIAL BUILDING


JEDDAH, SAUDI ARABIA
BILL OF QUANTITIES FOR ELECTRICAL INSTALLATION WORKS
ITEM
NO.

DESCRIPTION

UNIT

QTY.

No.

No.

No.

60A, 3P, main MccB, 18 KA, RMS, Symetrical, IC at


220/380V
Branches :
20A. SP # 18 Nos.
The branch panel board shall be flush mounted type
with bolt-on breakers, ABB make .
12

Supply and installation of branch panel board type PBS, with 12 Nos. branches as shown and described on
drawings and specification including the following:

60A, 3P, main MccB, 18 KA, RMS, Symetrical, IC at


220/380V
Branches :
20A. SP # 12 Nos.
The branch panel board shall be flush mounted type
with bolt-on breakers, ABB make .
13

Supply and installation of branch panel board type PBT, with 12 Nos. branches as shown and described on
drawings and specification including the following:

60A, 3P, main MccB, 18 KA, RMS, Symetrical, IC at


220/380V
Branches :
20A. SP # 12 Nos.
The branch panel board shall be flush mounted type
with bolt-on breakers, ABB make .
14

Supply and installation of branch panel board type PBR, with 18 Nos. branches as shown and described on
drawings and specification including the following:

60A, 3P, main MccB, 18 KA, RMS, Symetrical, IC at


220/380V
Branches :
20A. SP # 18 Nos.

1329/1433-J
1/5/2015

8 of 25

UNIT
RATE

AMOUNT
IN (SR)

MEDICAL CLINIC AND RESIDENTIAL BUILDING


JEDDAH, SAUDI ARABIA
BILL OF QUANTITIES FOR ELECTRICAL INSTALLATION WORKS
ITEM
NO.

DESCRIPTION

UNIT

QTY.

No.

The branch panel board shall be flush mounted type


with bolt-on breakers, ABB make .

No.

Supply and installation of 600A. TPN + G heavy duty


circuit breaker (CB) with surface mounted indoor
enclosure in meter room. ABB make

No.

Supply and installation of 200A. TPN + G circuit breaker


Nos.
(CB) heavy duty with surface mounted indoor type
enclosure in meter room. ABB make.

16

Supply and installation of 150A. TPN + G circuit breaker


(CB) heavy duty with surface mounted indoor or
Nos.
outdoor type enclosure as applicable for fire pump and
pacu-r-mc1. ABB make

Supply and installation of 100A. TPN + G circuit breaker


Nos.
(CB) with surface mounted indoor type ready made
enclosure for elevator-1,2. ELETRA make

Supply and installation of 60A. TPN + G circuit breaker


(CB) with ready made enclosure outdoor type for fan
coil unit's and elevator-2,3. ELETRA make

Nos.

29

Supply and installation of 32A. TPN + G circuit breaker


(CB) with surface mounted indoor ready made
enclosure for fan coil unit's . ELETRA make

Nos.

The branch panel board shall be flush mounted type


with bolt-on breakers, ABB make .
15

Supply and installation of l branch panel board type PBMC, with 18 Nos. branches as shown and described on
drawings and specification including the following:

60A, 3P, main MccB, 18 KA, RMS, Symetrical, IC at


220/380V
Branches :
32A. SP # 4 Nos.
20A. SP # 14 Nos.

16

17

18

19

20

21

1329/1433-J
1/5/2015

9 of 25

UNIT
RATE

AMOUNT
IN (SR)

MEDICAL CLINIC AND RESIDENTIAL BUILDING


JEDDAH, SAUDI ARABIA
BILL OF QUANTITIES FOR ELECTRICAL INSTALLATION WORKS
ITEM
DESCRIPTION
UNIT
NO.
22 Supply and installation of bus bar chamber equipped
with 5 nos. bus bar 150A. Continuous load suitable for
70 mm2 cable termination inside enclosure with No.
surface mounted outdoor type IP65 enclosure . ABB
make.

TOTAL CARRIED TO SUMMARY

1329/1433-J
1/5/2015

10 of 25

QTY.

12

UNIT
RATE

AMOUNT