B.effective depth
C.effective area
D.effective invert
6. Suspended cast iron soil pipe shall be supported at not more
than ____m intervals, except that pipe exceeding 1.5m length
may be supported at not more than _____m intervals.
Supports shall be adequate to maintain alignment & to
prevent sagging & shall be placed within 0.45m of the hub or
joint.
A.1.5/ 3
B.1.5/ 4
C.3/ 1.5
D.4/ 1.5
7. No water closet or bidet shall be set closer than ______m
from its center to any side of the wall or obstruction or closer
than ______m center to center to any similar fixture.
A..375 / 0.75
B..375 / 0. 70
C..40 / 0.70
D..50 / 0.60
- shall be supported at by____________for
8. Lead Pipe
entire length with hangers properly spaced.
A.Stiff aluminum or wooden backing
B.stiff metal or wooden backing
C.stiff plastic or metal sheet
9. Fixtures having concealed slip joint connections shall be
provided with an access panel or utility at least ______m in its
least dimension for inspection & repair.
A.0.30
B.0.20
C.0.10
D.0.40
10. Excessive water pressure water pressure greater than
____ Kpa
A.551
B.552
C.553
D.554
11. drains shall have a waterway equivalent area of the
tailpiece meaning, the sum of all the areas of the
perforation of the strainer is equivalent to the outlet area.
A.Strainers serving bathub
B.Strainers serving shower
C.Strainers serving lavatory
D.none of the above
12. Copper Tubing - shall be supported at approximately
________m intervals for piping 38mm diameter & smaller &
_______m intervals for piping 51mm & larger in dia.
A.1.8/ 3.0
B.1.9/ 3.5
C.1.5 / 2.5
D.none of the above
13. Continuous waste fixture tailpiece connections were
exposed or accessible may be of seamless drawn brass not
less than Ga. 20 B&S or ______mm thk.
A.0.90
B.0.80
C.0.70
D.0.60
14. All porcelain enamel surfaces on plumbing fixtures shall be
__________
A.mold resistant
B.acid resistant
C.corrosion resistant
D.none of the above
15. All pipe determinations shall be based on eighty percent
(___) the reduced pressure.
A.70%
B.60%
C.80%
D.90%
16. ______________ must be supported at least every other
joint except that when the developed length between
supports exceeds 1.2m, they shall be provided at each joint.
19.
A.WASTE TANK
B.SEPTIC TANK
C.SEWAGE DISPOSAL SYSTEM
D.NONE OF THE ABOVE
20.
A.20mm/m or 2%
B.30mm/m or 3%
C.40mm/m or 4 %
D.10mm/m or 1 %
21.
A.22 degrees bend
B.45 degrees bend
C.60 degrees bend or other approved fittings of longer sweeps
D.30 degress bend
22.
A.NAMPAP
B.DILG
C.DPWH
D.DENR
23.
A.AIR SEPARATION
B.AIR BREAK
C.AIR DEVISOR
D.NONE OF THE ABOVE
24.
A.BRANCH INTERVAL
B.INTERVAL
C.BRANCH
D.LENGTH
25.
A.1,2
B.1,1
C.2,1
D.2,3
26.
A.45 wye branches
B.combination wye & 1/8 bend branches
C.30 wye bend
D.or other approved fittings of longer sweeps.
27.
A.45 wye branches
B.combination wye & 1/8 bend branches
C.or other approved fittings of longer sweeps.
D.30 wye bend
28.
A.INTRAMUROS
B.BARASOAIN
C.BATAAN
D.CEBU
29.
A.45 wye branches
B.or other approved fittings of longer sweeps.
C.60 degree branches or offsets (only for pipes installed in true
vertical position
D.45 degree branches
30.
A.Double hub fitting for leak-caulked joint in vertical position
B.Single or double tee branch
C.Single or double tapped tee branch
D.Side inlet quarter bend, Running thread, band or saddle
E.all of the above
31.
A.single hub sanitary tapped tee
B.double hub sanitary tapped tee
C.triple hub sanitary tapped tee
D.none of the above
32.
A.plumbing unit
B.plumbing fixtures
C.plumbing system
D.plumbing minimum
33.
A.GI soil pipe
B.cast iron soil pipe
C.PVC soil Pipe
D.none of the above
34.
A.SINK
B.LAVATORY
C.BASIN
D.NONE OF THE ABOVE
35.
A.VENTILATING SYSTEM
B.WATER-SEALED TRAP
C.SOIL PIPES
D.WASTE PIPES
36.
A.100 mm
B.102 mm
C.101 mm
D.104 mm
37. Water pipes & fittings with a lead content that exceed
____ shall be prohibited & shall not be used in potable
piping systems.
A.8%
B.9%
C.10%
D.11%
38. Water Closet & Urinal Tanks shall be equipped with a listed
________ & shall be installed with the critical level at least
25mm above the full opening of the overflow pipe.
A.corporation cock
B.gatevalve
C.ballcock
D.none of the above
39. THE TOTAL NUMBERS OF SET OF SANITARY/
PLUMBING PLANS REQUIRED BY THE BUILDING
OFFICIAL WHEN APPLYING FOR PERMIT
A.4
B.5
C.3
D.6
40. THE SANITARY AND PLUMBING PERMIT WILL BE
REVOKE IF THE PROJECT HAS BEEN ABANDONED OR
SUSPENDED FOR HOW MANY DAYS
A.120
B.60
C.30
D.100
41. The quantity of water required to be supplied to every
plumbing fixture shall be represented by ____________
A.Fixture Units FU
B.Fixture drain FD
C.Fixture Trap FT
D.none of the above
42. The minimum airgap for Effective openings not greater than
D.22
48. The minimum air gap for Lavatories & other fixtures with
effective openings not greater than 13mm in diameter if
affected by walls
A.36mm
B.37mm
C.38mm
D.39mm
49. The minimum air gap for Sinks, laundry trays, goosenecks
bath faucets & other fixtures with effective openings not
greater than 19mm in diameter. if not affected by wall
A.40mm
B.39mm
C.38mm
D.37mm
50. The minimum air gap for Sinks, laundry trays, goosenecks
bath faucets & other fixtures witheffective openings not
greater than 19mm in diameter. if affected by wall
A.56mm
B.57mm
C.58mm
D.59mm
51. THE EXPIRATION OF THE PERMIT FOR SANITARY /
PLUMBING WILL BE EXPIRED AFTER HOW MANY
YEARS FROM THE DATE OF ISSUANCE
A.2
B.1
C.1.5
D.3
52. THE DRAWINGS, SPECIFICATION, CALCULATIONS AND
ETC FOR PLUMBING / SANITARY PERMIT WILL BE
SIGNED BY A a Registered & Licensed
A.DRAINAGE ENGINEER
B.MASTER PLUMBER
C.SANITARY ENGINEER
D.ARCHITECT
53. Restaurant kitchen & other special-use sink may be made of
C.3.6/ 3.0
D.3.0 / 3.6
- piping buried on the ground shall be laid on
59. In Ground
the ______ for its entire length, except where concrete
cradle support is provided which is adequate & approved by
the Administrative Authority.
A.firm bed
B.strata
C.compacted earth
D.none of the above
60. For EXCRETA DRAINAGE SYSTEM No Vitrified Clay
Pipes or Fittings for building drain or sewer shall be used
above ground or whenever piping is pressurized by a pump
or ejector. They shall be kept ______m below finish ground
level.
A.0,30
B.0.40
C.0.50
D.0.60
61. For EXCRETA DRAINAGE SYSTEM No Galvanized
Wrought Iron orGalvanized Steel Pipe shall be used
underground & shall be kept at least _____mm above
ground.
A.155
B.152
C.153
D.154
62. For vertical piping, Screwed Pipe - Iron Pipe Size (IPS)
shall be supported at not less than every other storey
A.drift
B.height
C.level
D.dimension
63. For vertical piping, _________ - shall be supported at each
storey or at a maximum intervals of 3m o.c.
A.lead tubing
B.copper tubing
C.steel tubing
D.g.i. tubing
64. For vertical piping, cast iron pipes- Bell & Spigot & Hubless
pipe shall be supported at_____ or closer.
A.every 2 storey
B.every storey
C.every 3 storey
D.every 4 storey
65. FOR THE SET OF SANITARY/ PLUMBING PLANS
REQUIRED BY THE BUILDING OFFICIAL WHEN
APPLYING FOR PERMIT HOW MANY SET OF
DRAWINGS WILL BE RETURNED ON THE APPLICANT
A.1
B.2
C.3
D.4
66. FOR THE SET OF SANITARY/ PLUMBING PLANS
REQUIRED BY THE BUILDING OFFICIAL WHEN
APPLYING FOR PERMIT HOW MANY SET OF
DRAWINGS WILL BE PROVIDED FOR THE
ADMINISTRATIVE AUTHORITY
A.1
B.4
C.3
D.2
67. FOR THE SET OF SANITARY/ PLUMBING PLANS
REQUIRED BY THE BUILDING OFFICIAL WHEN
APPLYING FOR PERMIT HOW MANY SET OF
DRAWINGS WILL BE KEPT IN THE JOB SITE
A.2
B.3
C.1
D.4
68. Fixture unit Lawn Sprinklers (standard type, each head)
A.1
B.2
C.1.5
D.2.0
69. Fixture unit Water Closet (economical flush) private use
A.5
B.4
C.3
D.2.5
E.2
70. Fixture unit of Urinal (stall & wall)
A.5
B.4
C.3
D.2
71. Fixture unit of Urinal (pedestal or similar type)
A.10
B.15
C.12
D.9
72. Fixture unit of Urinal (flush tank)
A.2
B.3
C.4
D.5
73. Fixture unit of Water Closet (flush tank & flushometertank),Hose Bibb or Sill Cock (standard type) private use
A.2
B.3
C.4
D.5
74. Fixture unit of Water Closet (flush tank & flushometer-tank),
A.5
B.4
C.3
D.2
75. Fixture unit of Water Closet (economical flush) public use
A.5
B.4
C.3
D.2
B.LAVATORY
C.BIBB
D.WATER CLOSET
92. If it is impracticable to obtain such slope due to the following
conditions except,
A.Excessive depth of the proposed drainage line
B.Structural and/or geological features of the terrain
C.Existing adverse in arrangements of building structure
D.Reasonable change because of existing weather