Branch Circuit Design Calculations Part Three


In the previous article " Branch Circuit Design Calculations Part Two " in our new
course " Course EE-3: Basic Electrical design course Level II ", I explained some
Additional definitions and features of Branch circuits.
Also, I listed the (5) categories of Lighting Branch circuits, which were:
1.
2.
3.
4.
5.

General lighting.
Show-window lighting.
Track lighting.
Sign and outline lighting.
Other lighting.

Today I will explain the design calculations for the general lighting branch circuits as
follows.
You can review the following previous articles for more information:

Branch Circuit Design Calculations Part One

1- General lighting branch circuit


1.1 Definition:

General lighting outlets are those Outlets intended for general use for fixed-in-place
luminaires (lighting fixtures). They are only used for lighting for the normal use of the
occupants and Its intensity should be adequate for any type of work performed in the
area.

1.2 Lighting fixtures not included in this category:


Specialized task lighting (Show-window lighting, Track lighting, accent, specialty,
or display lighting).

Any special lighting for workshops, photography labs, or studios that may be
located in the dwelling.

1.3 Calculation Method


Determining the general lighting load as per NEC will be based on the load per area
method as follows:

The NEC cod introduce minimum general lighting loads (in VA/ft2) for various types
of buildings in Table 220.12.

Within the same building, there are normally several different types of areas like
storage, office, hallways, and cafeterias, these areas must be considered separately if
their (VA/ft2) values are available in table 220.12.

The general lighting load is calculated by multiplying the floor area (in ft2) of a
building by its unit load (in VA/ft2) derived from the above table.

If the load is continuous (as in Most commercial structures), the calculated load is
multiplied by 1.25 (the inverse of 80%) to determine the circuit requirements. (Please
review the definition for the term continuous loads in Article)

How to calculate the Floor area?


The floor area for each floor shall be calculated from the outside dimensions of
the building, dwelling unit, or other area involved.

For dwelling units, the calculated floor area shall not include open porches,
garages, or unused or unfinished spaces not adaptable for future use (like some attics,
cellars, and crawl spaces).

Example#1:
A 25,000 ft2 office building is being designed. What is the general lighting load and what
load does the circuit need to supply?
Solution:
From Table 220.12, the unit load for an office building is 3.5 VA/ft2.
The general lighting load is determined by multiplying this value by the square footage of
the building:
The general lighting load = 3.5 VA/ft2 x 25,000 ft2 = 87,500 VA
So, the general lighting load is 87,500 volt-amperes.
However, the load is continuous and can only be 80% of the load supplied by the circuit.
This value must be multiplied by 1.25 to determine the circuit requirements:
the circuit rating = 87,500 VA x 1.25 = 109,375 VA
so, The circuit is designed to supply 109.375 KVA

1.4 Notes for table 220.12:

Important!!!
Dont apply the values of table 220.12 before reviewing the following notes.

The unit values herein are based on minimum load conditions and 100 percent
power factor (i.e. Load in VA = Load in Watt) and may not provide sufficient lighting for
the installation contemplated. So, the designer can choose a higher value based on the
existing design conditions.

Under any conditions, dont use values less than that specified in table 220.12,
there are no exceptions.

The general lighting load unit values specified in table 220.12 includes the
following loads:

1.
All general-use receptacle outlets of 20-ampere rating or less, including
receptacles connected to Bathroom Branch Circuits,
2.
The outdoor receptacle outlets,
3.
general-use receptacle Outlets used in Basements, Garages, and Accessory
Buildings.
4.
Wall lighting outlet used in Habitable Rooms,
5.
Wall lighting outlets used in hallways, stairways, attached garages, and
detached garages,
6.
Wall lighting outlet used in Storage or Equipment Spaces (like attics, underfloor spaces, utility rooms, and basements),
7.
Wall lighting outlet used in Guest Rooms or Guest Suites In hotels, motels,
or similar occupancies.
So, no need to add the above outlets in load calculations per NEC method.
The NEC method and table 220.12 are applied for any Additions to Existing
Installations for both dwelling and non-dwelling installations.

Energy savingtype calculations (which used to reduce the connected lighting load
and actual power consumption) are not permitted to be used to determine the minimum
calculated lighting load if they produce loads less than the load calculated according to
220.12.

Example#2:
A (2) floors (basement and main) dwelling unit have dimensions as show in below image.
Calculate the total general lighting load for this unit and the Minimum Number of General

Lighting Branch Circuits.

Solution:
Step#1: Calculate the total area of the dwelling unit as follows:
a- Basement area:
area A = 17 FT 9 IN. X (4 FT 4 IN. + 18 FT 6 IN. + 6 FT 0 IN.) = 17 FT 9 IN. X 28 FT 10 IN.
= 512.0 FT2
Note that as mentioned in notes for table 220.12, the crawl space and garage areas are
not considered as they are included in the NEC method calculation.
b- Main floor area:
AREA A= 6 FT 0 IN. X (11 FT 0 IN. + 17 FT 1 IN.) = 6 FT 0 IN. X 28 FT 1 IN. = 168.5 FT2
AREA B= 18 FT 6 IN. X (6 FT 3 IN. + 3 FT 8 IN. + 11 FT 0 IN. + 17 FT 1 IN.) = 18 FT 6 IN. X
38 FT 0 IN. = 730.0 FT2
AREA C= 4 FT 4 IN. X (3 FT 8 IN. + 11 FT 0 IN. + 17 FT 1 IN.) = 4 FT 4 IN. X 31 FT 9 IN. =
137.5 FT2
AREA D= 20 FT 2 IN. X (3 FT 8 IN. + 11 FT 0 IN.) = 20 FT 2 IN. X 14 FT 8 IN. = 295.5 FT2
Total main floor area (IN FT2) = 1304.5 FT2

So, Total area of the dwelling unit = 512.0 FT2 + 1304.5 FT2 = 1816.5 ft2

Step#2: The unit load listed in Table 220.12 shows 3 volt-amperes per ft2 for dwelling
units.
The general lighting load for the dwelling unit = 1816.5 ft2 x 3 watts per ft2 = 5449.5
watts

1.5 Notes for NEC method for calculation of lighting branch circuit load

Important!!!
The NEC doesnt introduce a procedure for calculating the actual full load for
the individual lighting fixtures in a general lighting branch circuit.

If the required information for calculating the actual full load for every individual
lighting fixture in the circuit is available, in this time, you can calculate the actual load
for the lighting branch circuit by summing of actual full load for its individual lighting
fixtures.

In this case, you need to compare the values obtained from NEC method with that
obtained from actual load method and select the greater load value to be used in the
design.

But actually, The NEC method for calculation of lighting load is not required if the
actual full load for every individual lighting fixture in the circuit is determined.

Methods for determining the actual full load for every individual lighting fixture in
the circuit is explained in our course " Advanced Course for Lighting Design - Level I "
and I recommend reviewing these methods very well.

Section 220.18 (b) states that For circuits supplying lighting units that have
ballasts, transformers, autotransformers, or LED drivers, the calculated load shall be
based on the total ampere ratings of such units and not on the total watts of the lamps.
This means that we must take into account the losses in light fixture switchgear (ballast,
internal wiring, etc.) so, you must use the current rating of the ballast, not the tube
wattage.

Example#3:
A fluorescent lighting fixtures with 4 numbers 2 feet lamps, 18 watt/ lamp. Calculate the
actual load for this lighting fixture.
Solution:
The actual total load of fixture = 4 lamps x 18 watt/lamp + losses
So, we cant know the actual losses, we will use the same equation in another form
The actual total load of fixture = 4 ballast x watt/ballast = 4 x 20 w = 80 watt

1.6 Determining the Minimum Number of General Lighting Branch Circuits


Example#4:
For the dwelling unit in example# 2 above, Calculate the Minimum Number of General
Lighting Branch Circuits.
Solution:
From example#2, the general lighting load for the dwelling unit = 5449.5 watts
However, the load is continuous and can only be 80% of the total load. This value must be
multiplied by 1.25 to determine the circuits requirements:
the Load Rating = 5449.5 watts x 1.25 = 6811.9 watts
The total ampere = 6811.9 watts / 120 V = 56.77 A (note that , NEC method assumed that
PF=1)
If we design 15-ampere circuits:
The number of the general lighting circuits = 56.77/ 15 = 3.78 circuits.

If we design 20-ampere circuits:

The number of the general lighting circuits = 56.77/ 20 = 2.84 circuits


Because it is not possible to have a partially powered electrical circuit that operates
properly, and because these are minimum units, the total number of branch circuits with
use of 15-ampere circuits is (4) circuits (3.78 circuits rounded up to 4 circuits) and (3)
circuits with use of 20-ampere branch circuits (2.84 circuits rounded up to 3 circuits).

1.7 Determination of maximum Permissible number of lighting fixtures on a general


lighting branch circuit
You need to review the definition for branch circuit rating explained in the previous
article " Branch Circuit Design Calculations Part Two ".
Rules to be applied are as follows:
Section 210.23 states that:
1.
In no case shall the load exceed the branch-circuit ampere rating.
2.
An individual branch circuit shall be permitted to supply any load (any
number of outlets) for which it is rated.

Section 210.23(A)(2) permits a 15- or 20-ampere branch circuit supplying lighting


outlets to also supply utilization equipment fastened in place, such as appliances or an air
conditioner. Under the conditions specified in this requirement, the utilization equipment
load must not exceed 50 % of the branch-circuit ampere rating (7.5 amperes on a 15ampere circuit and 10 amperes on a 20-ampere circuit).

Note: according to 210.52(B), such fastened-in-place equipment is not permitted on the


small-appliance branch circuits required in a kitchen, dining room, and so on.

Example#5:
A 4 feet long, two-lamp fluorescent fixture ballast draws 0.7 amps at 120 volts. How
many of these fixtures can be connected on a 20-amp circuit?
Solution:
This is a continuous load, so the current used by the lights can only be 80% of the circuit
current rating:
Allowable current = 20 A x 0.80 = 16 A

By dividing the allowable load by the load of each lamp, the total number of Fixtures is
determined:
the total number of Fixtures = 16 A /0.7 A = 22.8 fixtures
So, the maximum number of fixtures on the circuit is 22.

Example#6:
In example#5, If some utilization equipment fastened in place will be added to the circuit
How many of these fixtures can be connected to the circuit?
Solution:
This is a continuous load, so the current used by the lights can only be 80% of the circuit
current rating:
Allowable current = 20 A x 0.80 = 16 A
By following section 210.23(A)(2), the Allowable current = 16 A x 50% = 8 A
By dividing the allowable load by the load of each lamp, the total number of lamps is
determined:
the total number of Fixtures = 8 A /0.7 A = 11.4 fixtures
So, the maximum number of fixtures on the circuit is 11.

Important!!
For good design, usually assume that the general lighting branch circuits will
have some utilization equipment fastened in place and must be derated to 50%
of its rating.

Special Rules In non-dwelling buildings:


Lighting branch circuits that supply fixed lighting units with heavy-duty
Lampholders can have 30 A or 40 A ratings.

Lighting Outlets for heavy-duty Lampholders shall be calculated at a minimum of


600 volt-amperes.

Use The above rules when it is applicable.

In the next article, I will explain design calculations for other categories of Lighting
Branch circuits. so, please keep following.

Email ThisBlogThis!Share to TwitterShare to FacebookShare to Pinterest

5 comments:
1.
NAVEEN SJune 16, 2013 at 6:14 AM
Hello
Eng.
Ali,
An industrial information has been conveyed with every minute detail. Contents are
mind
blowing
for
any
practicing
professional.
Heads
up.
Lastly, not trying to point out the mistake here but there was confusion in the
mismatch of data provided in the Example-2. Hoping this would clear for the other
readers,
this
is
being
pointed
out:
1) Dimension in the pictorial representation has 10 FT 6 IN in the place of 18 FT 6 IN.
2) In Main Floor area calculation for Area-B, computed total area would be 703 FT2 in
the place of 730 FT2 (Total Area has no mismatch though).
Once

Naveen
Reply
Replies

again,

thanks

for

the

priceless

contribution

of

information.

1.
Ali HassanJune 17, 2013 at 1:32 PM
Hi

Naveen,

thanks for your cooperation for highlighting any mistakes, and i think
that your note#1 is not accurate the two lengths are identical in the
figure of example#2. but your note#2 is accurate , the area "B" must
equal 703 ft2, i think it was a typing error. thanks again.
2.
NAVEEN SJune 19, 2013 at 2:28 AM
I downloaded the image & viewed in PICASA. I may be wrong though.
Thanks for responding.
Reply

2.
Anteneh NebyuDecember 24, 2014 at 4:24 PM
nice
Reply

3.
Anteneh NebyuDecember 24, 2014 at 4:25 PM
nice
Reply
Leave a comment to help all for better understanding

<< Branch Circuit Design Calculations Part FourBranch Circuit Design Calculations
Part Two >>Home
Subscribe to: Post Comments (Atom)
Search

ELECTRICAL LIBRARY

Electrical Design Criteria


Electrical Works Method Statements

Manufacturers Lists for Electrical Products


Electrical Drawing Details

PDF COURSES

Electrical Load Estimation Course


An Introduction to Heating, Ventilation and Air Conditioning (HVAC) Systems
An Introduction to Lighting Design
An Introduction to Electrical Motor Basics

ELECTRICAL BOOKS

Electrical Books & Design Guides


Code of Practice for Energy Efficiency of Electrical Installations
Guide for electrical design engineers
Maintenance Manager's Guide to Power Quality
Power Quality & Utilization Guide
Engine Application and Installation Guide
Liquid Cooled Genset Application Manual
MV Design & Technical Guide
MV Application catalogue
Electrical and Traffic Engineering Manual

ELECTRICAL SOFTWARE

Electrical Software Programs


Riesgo Software For Performing The Risk Assessment Study
StrikeRisk V5.0 for performing the Risk Assessment Study
RAPAL Software for performing the Risk Assessment Study
Erico-GEM Software Program for Earthing Calculations
Visual Professional Edition Software (6) - Print the Results by Using the Print Editor
Visual Professional Edition Software (5) - Inserting Calculation Planes
Visual Professional Edition Software (4) - Inserting Luminaires
Visual Professional Edition Software (3) - Starting Steps
Visual Professional Edition Software (2) - Checking the Default Settings
Visual Professional Edition Software (1) Understanding the Program Interface
CalcuLux Software(1) - Main Window and Bar Menus
CalcuLux Software(2) - Checking The Default Settings
CalcuLux Software(3) - Example for Ligthing design of an Office
CalcuLux Software - Part Four
CalcuLux Software - Part Five
CalcuLux Software - Part Six
CalcuLux Software-Part Seven
ID-Spec Software
DIALux Lighting Software Program-Blue Version
DIALux Lighting Software Program - Red Version
DIALux - Indoor Lighting Calculations Menu Options

HOW TO

Write Technical Specifications for Lightning Protection Systems


Determine The Number Of Down Conductors of LPS
Perform Need for Lightning Protection Calculations by (4) Different Methods
Perform Grounding Calculations by (6) Different Methods
Size Earthing Conductors Using NEC Tables
Size Earthing Conductors Using BS 7671
Select the Best Earthing System
Calculate Voltage Drop as per U.S. and European Methods
Use NEC Annex B Tables in Conductor Ampacity Calculations
Perform Conductor Ampacity Calculations Using NEC under Engineering Supervision
Method
Perform Conductor Ampacity Calculations Using NEC Section 310.15 Tables
Size Overcurrent Protection Devices
Calculate the Total Demand Electrical Load for Non-Dwelling Buildings
Calculate Electrical Demand Load for Dwelling Buildings as per NEC Optional Method
Calculate Electrical Demand Load for Dwelling Buildings as per NEC Standard Method
Calculate general-use receptacles load in a dwelling unit
Calculate Maximum Permissible Number Of Lighting Fixtures On A General Lighting Branch
Circuit
Calculate Track Lighting Load
Calculate The Minimum Number Of General Lighting Branch Circuits For Any Building
Calculate General Lighting Branch Circuit Load For Any Building
Calculate Sign And Outline Branch Circuits Load
Calculate Show Window Lighting Load
Calculate The Minimum number of receptacle branch circuits for bank or office buildings
Calculate the Maximum allowable number of receptacles on a branch circuit in a dwelling
unit
Estimate Preliminary Load By Using Area Method
Estimate Preliminary Load By Using The Building Area Method
Estimate Preliminary Load By Using Space-By-Space Method (Functional Area Method)
Design Outdoor Lighting By Using Isolux Diagram Method
Design Outdoor Lighting By Using The Beam-Lumen Method As Per IES
Design Outdoor Lighting By Using The Beam-Lumen Method As Per CIE
Design Outdoor Lighting By Using Point-By-Point Method
Design Interior Lighting By Using By Using Quick Estimate Charts
Design Interior Lighting By Using Watt Per Square Feet Method
Design Interior Lighting By Using Point By Point Method
Design Interior Lighting By Using The Zonal Cavity (Lumen) Method
Build Preliminary Single Line Diagram Like Professionals
Make A Preliminary Design Like Professionals
Write Electrical Design Criteria Like Professionals
Specify The Required Type Of General-Use Receptacles For Each Area In A Dwelling Unit
Distribute General-Use Receptacle Loads In A Dwelling Unit
Select Receptacle Rating For A Branch Circuit In A Dwelling Unit
CONTACT FORM

Name
Email *
Message *

HOW TO JOIN OUR SITE?

Follow Us on
Share on facebookShare on twitterShare on linkedinShare on google_followShare on rss
Enter your email address:

Subscribe for New Articles

ELECTRICAL CALCULATORS

Electrical Calculations Spreadsheets

(3) Online Calculators Method Used for Need for Lightning Protection
NFPA 780 Simplified Method Excel Sheet

IEC62305-2 Need for Lightning Protection Excel Sheet

Excel Spreadsheets for Grounding System Design Calculations of AC Substation


Electrician2 Online Grounding Calculators

Loresco Online Earthing Calculators

LPI Online Earthing Calculator

Excel Spreadsheet for Earthing system Design - Non Substation Buildings

(5) nos. Excel Spreadsheets for Voltage Drop Calculations

(8) nos. Online Voltage Drop Calculators

Electrical Demand Load Calculator for Non-Dwelling Buildings

Electrical Load Calculator for Dwelling Units as per NEC Optional Method

Electrical Load Calculator for Dwelling Units as per NEC Standard Method

Visual Interior Lighting Design Tool

The Lighting Calculator Ver.2.20

GE Lighting Assistant Calculator 3.0

Siemens Selective Coordination Calculator

Selective Coordination by using Charts/Tables

Selective coordination by Using Time - Current Curves

Power Factor Table Calculator

AccuSine Power Correction Calculator

NEMA Motor Data Calculator

Transformer Harmonic Calculators

Transformer Rating Calculators

GE Transformer & Short Circuit Calculator

Internal Lighting calculator

Siemens Lighting Calculator

GE Fixture Count Estimator

Short Circuit Calculations Spreadsheets No.1

Residential Load Calculations Spreadsheet Part Three

Residential Load Calculation Spreadsheet-Part Two

Residential Load Calculation Spreadsheet-Part One

Siemens Voltage Drop Calculations Spreadsheet

IEC Motor Data Calculator

BEST OF OUR BEST ARTICLES

(4) Different Methods for Need for Lightning Protection Calculations


(6) Different Methods for Grounding Design Calculations

(8) different Methods for Voltage Drop Calculations

Conductor Amapcity Calculations by Using NEC Annex B Tables


Conductor Ampacity Calculations by Using NEC 310.15 Tables
Locating of the Overcurrent Protection Devices OCPDs

How to Select the Best Earthing System

Selecting the Proper Overcurrent Protection for Certain Applications


Sizing Overcurrent Protective Devices OCPD

Calculation of Total Demand Load for Non-Dwelling Buildings


Electrical Demand Load Calculation for Non-Dwelling Buildings
Electrical Demand Load Calculation by NEC Standard Method
Electrical Demand Load Calculation by NEC Optional Method
(12) Calculation Methods for Indoor Lighting Design

Electrical Design Steps - Part One

Electrical Design Steps - Part Two

Electrical Load Estimation Basics

Electrical Load Estimation by Using Space-By-Space Method

Electrical Load Estimation by Using Building Area Method


Electrical Load Estimation by Using Area Method
Single Line Diagram Types and Method

How to write the Electrical Design Criteria?

Electrical Design Philosophy

Electrical Design Requirements for Industrial Buildings


Electrical Design Requirements for Commercial Buildings
Electrical Design Requirements for Health Care Buildings
Checklist for Electrical Distribution Design

ELECTRICAL CHECKLISTS

Electrical Checklists

Checklist
for
Electrical
Distribution Architecture Design

Checklist
for
Liquid
Cooled Generator

Checklists
for
Home
Electrical Safety

Checklists for Design, Construction, Commissioning and Maintenance of Project's Electrical


Works

ELECTRICAL COURSES
On-Line Electrical Courses

Course Lightning-2: Lightning Protection System Design and Calculations


Course Lightning-1: Introduction to Lightning Protection System Design

Course EE-1: Beginners' Electrical design course

Course EE-2: Basic Electrical design course Level I

Course EE-3: Basic Electrical design course Level II

Course EE-4: Basic Electrical design course Level III

Course EE-5: Grounding System Design Calculations

Course Light-1: An Introduction to Lighting Design

Course Lighting-2: Advanced Course for Lighting Design - Level I

Course Motor-1: An Introduction to Electrical Motors Basics

Course ELEV-1: An Introduction to Elevators, Escalators and Moving Walkways

Course HVAC-1: An Introduction to Heating, Ventilation and Air Conditioning (HVAC)

Systems
Course EP-3: Electrical procurement transformers course

Course ED-1: Electrical drawings course

Course PM-1: Tender Documents Preparation Course

Course EC-1: Understanding NFPA 70 (National electrical code) course

Course LV-1: Basic Sound system design course

NEW ARTICLES

Electrical Rules and Calculations for Air-Conditioning Systems

Part Five
Electrical Rules and Calculations for Air-Conditioning Systems
Part Four
Electrical Rules and Calculations for Air-Conditioning Systems
Part Three
Electrical Rules and Calculations for Air-Conditioning Systems
Part Two
Electrical Wiring Diagrams for Air Conditioning Systems Part
Three
Electrical Wiring Diagrams for Air Conditioning Systems Part
Two
Electrical Wiring Diagrams for Air Conditioning Systems Part
One
Electrical Rules and Calculations for Air-Conditioning Systems
Part One
Course Lightning-2: Lightning Protection System Design and
Calculations
Course Lightning-1: Introduction to Lightning Protection System
Design
CopyRight @ 2013 Electrical Knowhow - Privacy Policy

FacebookTwitterEmailPrintMore
Recommended for you

Course HVAC-1: An Introduction to Heating, Ventilation and Air Conditioning (HVAC) Systems ~
Elect...
www.electrical-knowhow.com
AddThis

Das könnte Ihnen auch gefallen