Beruflich Dokumente
Kultur Dokumente
OMICRON PTL
Protection Test Template PTT
Transformer Differential Protection
ABB RET 670 V1.1 A32
User Manual
V1.000
1/18
OMICRON PTL
Contents
2/18
OMICRON PTL
1 General Information
The RET 670 transformer differential template is used for testing the current differential, overcurrent and
thermal overload protection functions of the RET 670 relays. This template comprehends different
modules for testing the main protection functions and the most important backup protection functions. The
template is used for testing 3-winding or 2-winding transformer differential protection function. It is
designed and configured for use with the ABB RET 670 V1.1 XRIO converter which is included in this
template. For more information about the converter, see the ABB RET 670 XRIO Converter User Manual.
Note: The template is designed and built for use with the Test Universe 2.22 SR2 software.
The template is tested on the following relay:
Manufacturer: ABB
Serial no: T0802056
Firmware Version: V 1.1
Notes:
The OMICRON PTTs are designed for an experienced OMICRON user. The user should be
familiar with the Test Universe software and the XRIO technology (see
http://www.omicron.at/products/training/ for training information).
3/18
OMICRON PTL
Double click the file RET 670.occ to start the template-based procedure.
Open the test object.
Load (Import) the latest XRIO converter version for the RET 670.
Enter your relay settings in the Relay Parameter Section, Additional Information General
Information Hardware Configuration Analog modules Transformer Configuration Side1
(Side2 and Side3), and then click OK.
7.
8.
9.
10.
General
Analog Outputs
Binary Outputs
DC Analog Inputs
Click OK.
Follow the wiring instructions.
Start testing.
Evaluate and archive the results.
4/18
OMICRON PTL
5/18
OMICRON PTL
6/18
OMICRON PTL
7/18
OMICRON PTL
In the Analog Outputs dialog box, the current outputs have to be routed to the name variables. Figure 4
shows the Analog Output configuration.
8/18
OMICRON PTL
The necessary signals, trip signal, starting signal and circuit breaker auxiliary contacts (CB aux.), have to
be routed to the following binary inputs:
Relay TRIP W1 to:
binary input 1
Relay TRIP W2 to:
binary input 2
Relay TRIP W3 to:
binary input 3
Relay Start General to:
binary input 5
Thermal Overload Warning to:
binary input 6
CB aux. W1 to:
binary input 7
CB aux. W2 to:
binary input 8
CB aux. W3 to:
binary input 9
Note: The circuit breaker auxiliary contact is required for the trip test with the circuit breaker. If the circuit
breaker auxiliary contact cannot be connected to the binary inputs, the trip test with the circuit breaker
cannot be performed.
Control Center
Ramping
State Sequencer
Advanced Differential (Diff Configuration, Diff Operating and Diff Trip Time Charactreistic)
Overcurrent
6 Functional Range
The test modules are grouped according to the protection function to be tested. The template includes test
modules for the following protection functions:
The test modules are activated and deactivated automatically according to the corresponding protection
function status in the test object.
9/18
OMICRON PTL
10/18
OMICRON PTL
9 Template Structure
The structure of the RET 670 differential test template is shown below.
11/18
OMICRON PTL
12/18
OMICRON PTL
13/18
OMICRON PTL
14/18
OMICRON PTL
The diff trip time characteristic is tested with a single test shot at Idiff = 2 Iref.
Note: The 2
15/18
OMICRON PTL
16/18
OMICRON PTL
9.11 Thermal Overload Trip Time and Thermal Overload Warning Signal Test
The thermal overload warning and trip times signal of the relay is tested with the OMICRON Overcurrent
test modules by simulating a three-phase fault.
Generally the thermal overload warning and trip times tests start with the simulation of a cold start resetting the thermal overload memory, i.e. the fault begins without pre-fault state. The test shot for both
tests is set to 1.15 IN.
The only difference between the thermal overload warning and trip times test is the monitored binary
input. The trip times test is routed to the trip signal, while the warning input of the relay is triggerd in the
test of the thermal overload warning.
Note: The memory of the relay's thermal overload model has to be reset prior each thermal overload test.
For testing the thermal overload functionality behind the IHighTau threshold the OMICRON State
Sequencer test module is used by simulating a three-phase fault. For more information see the relay
manual.
Note: The thermal overload warning can only be tested if the warning signal of the thermal overload
function is routed to one of the relay's outputs.
Note: The Thermal Overload parameters ENMULTTTRn and FORCED COOL TTRn can be activated in
Additional Information -> Relay Information -> Configurations -> Thermal Overload. Also the side of TTRn
can be set there.
9.12 CB Test
For testing the trip time with circuit breaker contacts test, an OMICRON State Sequencer test module is
used. This test is divided into three sequencer states: pre-fault, fault and post-fault. The fault is a threepole fault with Idiff = 2 Inom. The time elapse between the trip command and the circuit breaker open is
evaluated.
17/18
OMICRON PTL
9.15 Using the RET 670 Transformer Differential Template for Two Winding Tests
If you want to use the RET 670 transformer differential template for testing two-winding transformers with
a relay similar to the RET 670 relay, connect the "Relay Trip W3" signal to the "Relay Trip W1" signal.
This ensures that all trip signals routed in the test modules are available.
18/18