Sie sind auf Seite 1von 37

High Voltage Engineering

UnitUnit-III

UNIT-III
GENERATION OF HV AC DC IMPULSE VOLTAGE & CURRENT
22. INTRODUCTION
A fundamental knowledge about generators and circuits which are in use for the
generation of high voltages belongs to the background of work on H.V. technology.
Generally commercially available H.V. generators are applied in routine testing
laboratories; they are used for testing equipment such as transformers, bushings, cables,
capacitors, switchgear, etc. The tests should confirm the efficiency and reliability of the
products and therefore the H.V. testing equipment is required to study the insulation behavior
under all conditions which the apparatus is likely to encounter. The amplitudes and types of
the test voltages, which are always higher than the normal or rated voltages of the apparatus
under test, are in general prescribed by national or international standards or
recommendations, and therefore there is not much freedom in the selection of the H.V.
testing equipment. Quite often, however, routine testing laboratories are also used for the
development of new products. Then even higher voltages might be necessary to determine the
factor of safety over the prospective working conditions and to ensure that the working
margin is neither too high nor too low. Most of the H.V. generator circuits can be changed to
increase the output voltage levels, if the original circuit was properly designed. Therefore,
even the selection of routine testing equipment should always consider a future extension of
the testing capabilities.
The work carried out in research laboratories varies considerably from one
establishment to another, and the type of equipment needed varies accordingly. As there are
always some interactions between the H.V. generating circuits used and the test results, the
layout of these circuits has to be done very carefully. The classes of tests may differ from the
routine tests, and therefore specially designed circuits are often necessary for such
laboratories. The knowledge about some fundamental circuits treated in this chapter will also
support the development of new test circuits.
Finally, high voltages are used in many branches of natural sciences or other technical
applications. The generating circuits are often the same or similar to those treated in the
following sections. It is not the aim, however, of this introductory text to treat the broad
variations of possible circuits, due to space limitation. Not taken into account are also the

57

Deependra Singh

High Voltage Engineering


UnitUnit-III
differing problems of electrical power generation and transmission with high voltages of A.C.
or D.C., or the pure testing technique of H.V. equipment, the procedures of which may be
found in relevant standards of the individual equipment. Power generation and transmission
problems are treated in many modern books, some of which are listed within the bibliography
of an earlier report.
This chapter discusses the generation of the following main classes of voltages: direct
voltages, alternating voltages, and transient voltages.

REFERENCE:

HVE FUNDAMENTALS: KUFFEL, ZAENGL & KUFFEL: P-8-9

Deependra Singh

58

High Voltage Engineering


UnitUnit-III

23. DIRECT VOLTAGES


In H.V. technology direct voltages are mainly used for pure scientific research work
and for testing equipment related to HVDC transmission systems. There is still a main
application in tests on HVAC power cables of long length, as the large capacitance of those
cables would take too large a current if tested with A.C. voltages Although such D.C. tests on
A.C. cables are more economical and convenient, the validity of this test suffers from the
experimentally obtained stress distribution within the insulating material, which may
considerably be different from the normal working conditions where the cable is transmitting
power at low-frequency alternating voltages. For the testing of polyethylene H.V. cables, in
use now for some time, D.C. tests are no longer used, as such tests may not confirm the
quality of the insulation.
High D.C. voltages are even more extensively used in applied physics (accelerators,
electron microscopy, etc.), electro-medical equipment (X-rays), industrial applications
(precipitation and filtering of exhaust gases in thermal power stations and the cement
industry; electrostatic painting and powder coating, etc.), or communications electronics (TV,
broadcasting stations). Therefore, the requirements on voltage shape, voltage level, and
current rating, short- or long-term stability for every HVDC generating system may differ
strongly from each other. With the knowledge of the fundamental generating principles it will
be possible, however, to select proper circuits for a special application.
In the International Standard IEC 60-1 or IEEE Standard 4-1995 the value of a direct
test voltage is defined by its arithmetic mean value, which will be designated as V .
Therefore, this value may be derived from:
T

V =

1
V (t )dt
T 0

2.1

Where T equals a certain period of time if the voltage V (t) is not constant, but periodically
oscillating with a frequency of f = 1/T. Test voltages as applied to test objects then deviate
periodically from the mean value. This means that a ripple is present. The amplitude of the
ripple, V, is defined as half the difference between the maximum and minimum values, or
V = 0.5(Vmax -Vmin)

2.2

The ripple factor is the ratio of the ripple amplitude to the arithmetic mean value, or V/V .
For test voltages this ripple factor should not exceed 3 percent unless otherwise specified by
the appropriate apparatus standard or be necessary for fundamental investigations. The D.C.

59

Deependra Singh

High Voltage Engineering


UnitUnit-III
voltages are generally obtained by means of rectifying circuits applied to A.C. voltages or by
electrostatic generation. A treatment of the generation principles according to this subdivision
is appropriate.

REFERENCE:

HVE FUNDAMENTALS: KUFFEL, ZAENGL & KUFFEL: 2.1 P-9-10.

Deependra Singh

60

High Voltage Engineering


UnitUnit-III

24. HVAC HV TRANSFORMER


Most of the present day transmission and distribution networks are operating on A.C.
voltages and hence most of the testing equipments relate to high A.C. voltages. Even though
most of the equipments on the system are 3-phase systems, a single phase transformer
operating at power frequency is the most common from of HVAC testing equipment.
Test transformers normally used for the purpose have low power rating but high
voltage ratings. These transformers are mainly used for short time tests on high voltage
equipments. The currents required for these tests on various equipments are given below:
Insulators, C.B., bushings, Instrument transformers
Power transformers, h.v. capacitors.
Cables

=
=
=

0.1 0.5 A
0.51 A
1 A and above

The design of a test transformer is similar to a potential transformer used for the
measurement of voltage and power in transmission lines. The flux density chosen is low so
that it does not draw large magnetizing current which would otherwise saturate the core and
produce higher harmonics.

REFERENCE:

HVE: C. L. WADHWA, 2.4; P-69

61

Deependra Singh

High Voltage Engineering


UnitUnit-III

25. NEED FOR CASCADE CONNECTION & WORKING OF


TRANSFORMERS UNITS CONNECTED IN CASCADE
For voltages higher than 400 KV, it is desired to cascade two or more transformers
depending upon the voltage requirements. With this, the weight of the whole unit is
subdivided into single units and, therefore, transport and erection becomes easier. Also, with
this, the transformer cost for a given voltage may be reduced, since cascaded units need not
individually possess the expensive and heavy insulation required in single stage transformers
for high voltages exceeding 345 kV. It is found that the cost of insulation for such voltages
for a single unit becomes proportional to square of operating voltage.

Fig. 2.9 shows a basic scheme for cascading three transformers. The primary of the
first stage transformer is connected to a low voltage supply. A voltage is available across the
secondary of this transformer. The tertiary winding (excitation winding) of first stage has the
same number of turns as the primary winding, and feeds the primary of the second stage
transformer. The potential of the tertiary is fixed to the potential V of the secondary winding
as shown in Fig. 2.9. The secondary winding of the second stage transformer is connected in
series with the secondary winding of the first stage transformer, so that a voltage of 2V is
available between the ground and the terminal of secondary of the second stage transformer.
Similarly, the stage-III transformer is connected in series with the second stage transformer.
With this the output voltage between ground and the third stage transformer, secondary is 3V.

Deependra Singh

62

High Voltage Engineering


UnitUnit-III
It is to be noted that the individual stages except the upper most must have three-winding
transformers. The upper most, however, will be a two winding transformer.
Fig. 2.9 shows metal tank construction of transformers and the secondary winding is
not divided. Here the low voltage terminal of the secondary winding is connected to the tank.
The tank of stage-I transformer is earthed. The tanks of stage-II and stage-III transformers
have potentials of V and 2V, respectively above earth and, therefore, these must be insulated
from the earth with suitable solid insulation. Through H.T. bushings, the leads from the
tertiary winding and the H.V. winding are brought out to be connected to the next stage
transformer.
However, if the high voltage windings are of mid-point potential type, the tanks are
held at 0.5 V, 1.5 V and 2.5 V, respectively. This connection results in a cheaper construction
and the high voltage insulation now needs to be designed for V/2 from its tank potential.
The main disadvantage of cascading the transformers is that the lower stages of the
primaries of the transformers are loaded more as compared with the upper stages.
The loading of various windings is indicated by P in Fig. 2.9. For the three-stage
transformer, the total output VA will be 3VI = 3P and, therefore, each of the secondary
winding of the transformer would carry a current of I = P/V. The primary winding of stage-III
transformer is loaded with P and so also the tertiary winding of second stage transformer.
Therefore, the primary of the second stage transformer would be loaded with 2P. Extending
the same logic, it is found that the first stage primary would be loaded with P. Therefore,
while designing the primaries and tertiaries of these transformers, this factor must be taken
into consideration.

The total short circuit impedance of a cascaded transformer from data for individual
stages can be obtained. The equivalent circuit of an individual stage is shown in Fig. 2.10.
Here Zp, Zs, and Zt, are the impedances associated with each winding. The
impedances are shown in series with an ideal 3-winding transformer with corresponding

63

Deependra Singh

High Voltage Engineering


UnitUnit-III
number of turns Np, Ns and Nt. The impedances are obtained either from calculated or
experimentally-derived results of the three short-circuit tests between any two windings taken
at a time.
Let

Zps = leakage impedance measured on primary side with secondary short circuited and
tertiary open.
Zpt = leakage impedance measured on primary side with tertiary short circuited and
secondary open.
Zst = leakage impedance on secondary side with tertiary short circuited and primary
open.

If these measured impedances are referred to primary side then


Zps = Zp + Zs, Zpt = Zp + Zt

and Zst = Zs + Zt

Solving these equations, we have


1
1
1
Z p = ( Z ps + Z pt Z st ) , Z s = ( Z ps + Z st Z pt ) and Z t = ( Z pt + Z st Z ps )
2
2
2

2.19

Assuming negligible magnetizing current, the sum of the ampere turns of all the windings
must be zero.
N p I p Ns I s Nt It = 0
Assuming lossless transformer, we have,

Zp = jXp,

Deependra Singh

Zs = jXs,

64

and

Zt = jXt

High Voltage Engineering


UnitUnit-III

Also let Np = Nt for all stages, the equivalent circuit for a 3-stage transformer would
be given as in Fig.2.11.
Fig. 2.11 can be further reduced to a very simplified circuit as shown in Fig. 2.12. The
resulting short circuit reactance Xres is obtained from the condition that the power rating of
the two circuits be the same. Here currents have been shown corresponding to high voltage
side.

I 2 X res = (3I ) 2 X p + (2 I ) 2 X p + I 2 X s + I 2 X s + I 2 X s + (2 I ) 2 X t + I 2 X t
X res = 14 X p + 3 X s + 5 X t

2.20

Instead of 3(Xp + Xs + Xt) as might be expected. Equation (2.20) can be generalized for an nstage transformer as follows:
n

Xres = [(n i + 1) 2 X pi + X si + (i + 1) 2 X ti
i =1

REFERENCE:
REFERENCE:

HVE: C. L. WADHWA, 2.4; P-69

HVE: C. L. WADHWA, 2.4; P-70-72

65

Deependra Singh

High Voltage Engineering


UnitUnit-III

26. SERIES RESONANT CIRCUIT


(PRINCIPLE OF OPERATION AND ADVANTAGES)
The equivalent circuit of a single-stage-test transformer along with its capacitive load
is shown in Fig. 2.15. Here L1 represents the inductance of the voltage regulator and the
transformer primary, L the exciting inductance
of the transformer, L2 the inductance of the
transformer secondary and C the capacitance
of the load. Normally inductance L is very
large as compared to L1 and L2 and hence its
shunting effect can be neglected. Usually the
load capacitance is variable and it is possible
that for certain loading, resonance may occur in the circuit suddenly and the current will then
only be limited by the resistance of the circuit and the voltage across the test specimen may
go up as high as 20 to 40 times the desired value.
Similarly, presence of harmonics due to saturation of iron core of transformer may
also result in resonance. Third harmonic frequencies have been found to be quite disastrous.
With series resonance, the resonance is controlled at fundamental frequency and
hence no unwanted resonance occurs.
The development of series resonance circuit for testing purpose has been very widely
welcome by the cable industry as they faced resonance problem with test transformer while
testing short lengths of cables.
In the initial stages, it was difficult to
manufacture

continuously

variable

high

voltage and high value reactors to be used in


the series circuit and therefore, indirect
methods to achieve this objective were
employed. Fig. 2.16 shows a continuously
variable reactor connected in the low voltage
winding of the step up transformer whose
secondary is rated for the full test voltage. C2
represents the load capacitance.
If N is the transformation ratio and L is the inductance on the low voltage side of the
transformer, then it is reflected with N2L value on the secondary side (load side) of the

Deependra Singh

66

High Voltage Engineering


UnitUnit-III
transformer. For certain setting of the reactor, the inductive reactance may equal the
capacitive reactance of the circuit, hence resonance will take place. Thus, the reactive power
requirement of the supply becomes zero and it has to supply only the losses of the circuit.
However, the transformer has to carry the full load current on the high voltage side. This is a
disadvantage of the method. The inductor are designed for high quality factors Q = L/R.
The feed transformer, therefore, injects the losses of the circuit only.

It has now been possible to manufacture high voltage continuously variable reactors
300 kV per unit using a new technique with split iron core. With this, the testing step up
transformer can be omitted as shown in Fig. 2.17. The inductance of these inductors can be
varied over a wide range depending upon the capacitance of the load to produce resonance.
Fig. 2.17 (b) represents an equivalent circuit for series resonance circuit. Here R is
usually of low value. After the resonance condition is achieved, the output voltage can be
increased by increasing the input voltage. The feed transformers are rated for nominal current
ratings of the reactor. Under resonance, the output voltage will be
V0 =

V 1
R C 2

Where V is the supply voltage.


Since at resonance

L =

Therefore,

V0 =

1
C 2

V
L = VQ
R

Where Q is the quality factor of the inductor which usually varies between 40 and 80.
This means that with Q = 40, the output voltage is 40 times the supply voltage. It also means
that the reactive power requirements of the load capacitance in kVA is 40 times the power to
be provided by the feed transformer in KW. This results in a relatively small power rating for
the feed transformer.

67

Deependra Singh

High Voltage Engineering


UnitUnit-III

ADVANTAGES:
The following are the advantages of series resonance circuit:
(i). The power requirements in KW of the feed circuit are (kVA)/Q where kVA is the
reactive power requirements of the load and Q is the quality factor of variable reactor
usually greater than 40. Hence, the requirement is very small.
(ii). The series resonance circuit suppresses harmonics and interference to a large extent.
The near sinusoidal wave helps accurate partial discharge of measurements and is also
desirable for measuring loss angle and capacitance of insulating materials using
Schering Bridge.
(iii). In case of a flashover or breakdown of a test specimen during testing on high voltage
side, the resonant circuit is detuned and the test voltage collapses immediately. The
short circuit current is limited by the reactance of the variable reactor. It has proved to
be of great value as the weak part of the isolation of the specimen does not get
destroyed. In fact, since the arc flash over has very small energy, it is easier to
observe where exactly the flashover is occurring by delaying the tripping of supply
and allowing the recurrence of flashover.
(iv). No separate compensating reactors (just as we have in case of test transformers) are
required. This results in a lower overall weight.
(v). When testing SF6 switchgear, multiple breakdowns do not result in high transients.
Hence, no special protection against transients is required.
(vi). Series or parallel connections of several units is not at all a problem. Any number of
units can be connected in series without bothering for the impedance problem which
is very severely associated with a cascaded test transformer. In case the test specimen
requires large current for testing, units may be connected in parallel without any
problem.

REFERENCE:

HVE: C. L. WADHWA, 2.4; P-73-76

Deependra Singh

68

High Voltage Engineering


UnitUnit-III

27. TESLA COIL


High frequency high voltages are required for rectifier D.C. power supplies. Also, for
testing electrical apparatus for switching surges, high frequency high voltage damped
oscillations are needed which need high voltage high frequency transformers. The advantages
of these high frequency transformers are:
(i)

The absence of iron core in transformers and hence saving in cost and size,

(ii)

Pure sine wave output,

(iii) Slow build-up of voltage over a few cycles and hence no damage due to switching
surges, and
(iv) Uniform distribution of voltage across the winding coils due to subdivision of coil
stack into a number of units.
The commonly used high frequency resonant transformer is the Tesla coil, which is a
doubly tuned resonant circuit shown schematically in Fig. 6.13a. The primary voltage rating
is 10 kV and the secondary may be rated to as high as 500 to 1000 kV. The primary is fed
from a D.C. or A.C. supply through the condenser C1. A spark gap G connected across the
primary is triggered at the desired voltage V1 which induces a high self-excitation in the
secondary. The primary and the secondary windings (L1 and L2) are wound on an insulated
former with no core (air-cored) and are immersed in oil. The windings are tuned to a
frequency of 10 to 100 kHz by means of the condensers C1 and C2.

Fig. 6.13 Tesla Coil equivalent circuit and its output waveform

The output voltage V2 is a function of the parameters L1, L2 C1, C2 and the mutual
inductance M. usually, the winding resistances will be small and contribute only for damping
of the oscillations.
The analysis of the output waveform can be done in a simple manner neglecting the
winding resistances. Let the condenser C1 be charged to a voltage V1 when the spark gap is

69

Deependra Singh

High Voltage Engineering


UnitUnit-III
triggered. Let a current i1 flow through the primary winding L1 and produce a current i2
through L2 and C2.
Then,
t

1
di
di
V1 = i1dt + L1 1 + M 2
C1 0
dt
dt

(6.9)

1
di
di
0=
i2 dt + L2 2 + M 1

C2 0
dt
dt

And,

The Laplace transformed equations for the above are,

V1
1
= L1s +
I1 + MsI 2
s
C1s

(6.10)

1
0 = [Ms ]I 2 + L2 s +
I2
C2 s

And,

Where I1 & I2 are the Laplace transformed values, of i1 and i2.


The output voltage V2 across the condenser C2 is
t

V2 =

1
i2 dt ;
C2 0

V2 (s ) =

Or its transformed equation is

1
C2 s

(6.11)

Where V2(s) is the Laplace transform of V2.


The solution for V2 from the above equations will be
V2 =

MV1
1
[cos 1t cos 2t ]
2
L1 L2C1 2 12

2 =1

Where,

(6.12)

M2
= 1 K 2
L1 L2

K = coefficient of coupling between the windings L1 and L2

1, 2 =
1 =

12 + 22
2
1
L1C1

2 + 22
1222 1 K 2
1
2

And

2 =

1
L2C2

The output waveform is shown in Fig. 6.13(b).


The peak amplitude of the secondary voltage V2 can be expressed as,

Deependra Singh

70

High Voltage Engineering


UnitUnit-III

V2 max = V1e

Where,

e=

L2
L1

(6.13)

2 (1 )
(1 + a ) 2 4a

L2C2 W12
a=
=
L1C1 W22
A more simplified analysis for the Tesla coil may be presented by considering that the
energy stored in the primary circuit in the capacitance C1 is transferred to C2 via the magnetic
coupling. If W1 is the energy stored in C1 and W2 is the energy transferred to C2 and if the
efficiency of the transformer is , then
1
1

W1 = C1V12 = C2V22
2
2

From which

V2 = V1

C1
C2

(6.14)

(6.14a)

It can be shown that if the coefficient of coupling K is large the oscillation frequency
is less, and for large values of the winding resistances and AT, the waveform may become a
unidirectional impulse. This is shown in the next sections while dealing with the generation
of switching surges.

REFERENCE:

HVE: KAMARAJU NAIDU; 6.2.3; P-126-128

71

Deependra Singh

High Voltage Engineering


UnitUnit-III

28. HVDC- VOLTAGE DOUBLER CIRCUIT

Both full wave and half wave rectifier circuits produce a D.C. voltage less than the
A.C. maximum voltage. When higher D.C. voltages are needed, a voltage doubler or
cascaded rectifier doubler circuits are used. The schematic diagram of voltage doublers are
given in Figs. 6.3a and b. In voltage doubler circuit shown in Fig. 6.3a, the condenser C1 is
charged through rectifier R to a voltage of +Vmax with polarity as shown in the figure during
the negative half cycle. As the voltage of the transformer rises to positive Vmax during the
next half cycle, the potential of the other terminal of C1 rises to a voltage of +2Vmax.

Fig. 6.2 Input and output waveforms of half and full wave rectifiers
(a) Input sine wave
(b) Output with half wave rectifier and condenser filter
(c) Output with full wave rectifier and condenser filter
(d) Vmax, Vmean and ripple voltage and 8V with condenser filter of a full
wave rectifier

Thus, the condenser C2 in turn is charged through R2 to 2Vmax. Normally the D.C. output
voltage on load will be less than 2Vmax, depending on the time constant C2RL and the forward
charging time constants. The ripple voltage of these circuits will be about 2% for RL/r 10
and X/r 0.25, where X and r are the reactance and resistance of the input transformer. The
rectifiers are rated to a peak inverse voltage of 2Vmax, and the condensers C1 and C2 must also
have the same rating. If the load current is large, the ripple also is more.

Deependra Singh

72

High Voltage Engineering


UnitUnit-III
Cascaded voltage doublers are used when larger output voltages are needed without
changing the input transformer voltage level. A typical voltage doubler is shown in Fig. 6.3b
and its input and output waveforms are shown in Fig. 6.3(c). The rectifiersR1 and R2 with
transformer T1 and condensers C1 and C2 produce an output voltage of 2V in the same way as
described above. This circuit is duplicated and connected in series or cascade to obtain a
further voltage doubling to 4V. T is an isolating transformer to give insulation for 2Vmax since
the transformer T2 is at a potential of 2Vmax above the ground. The voltage distribution along
the rectifier string R1, R2, R3 and R4 is made uniform by having condensers C1, C2, C3 and C4
of equal values. The arrangement may be extended to give 6V, 8V, and so on by repeating
further stages with suitable isolating transformers. In all the voltage doubler circuits, if valves
are used, the filament transformers have to be suitably designed and insulated, as all the
cathodes will not be at the same potential from ground. The arrangement becomes
cumbersome if more than 4V is needed with cascaded steps.

73

Deependra Singh

High Voltage Engineering


UnitUnit-III

(1) A.C. input voltage waveform, (2) A.C. output voltage waveform without condenser filter,
(3) A.C. output voltage waveform with condenser filter
Fig. 6.3 Voltage doubler circuits
R1, R2, R3, R4 - rectifiers;
T1, T2 - H.V. transformers;
C1, C2, C3- condensers;
RL - Load resistance; T- Isolating transformer

REFERENCE:

HVE: KAMARAJU NAIDU; 6.1.2; P-106-108

Deependra Singh

74

High Voltage Engineering


UnitUnit-III

29. COCK CROFT- WALTON TYPE HIGH VOLTAGE DC SET


In 1932, Cockroft and Walton suggested an improvement over the circuit developed by
Greinacher for producing high D.C. voltages. Fig. 2.3 shows a multistage single phase
cascade circuit of the Cockroft-Walton type.

No Load Operation: The portion


ABMMA is exactly indentical to Greinarcher
voltage doubler circuit and the voltage across
C becomes 2Vmax when M attains a voltage
2Vmax. During the next half cycle when B
becomes positive with respect to A, potential
of M falls and, therefore, potential of N also
falls becoming less than potential at

hence C2 is charged through D2. Finally all


the capacitors C1, C2, C3, C1, C2, and C3 are
charged. The voltage across the column of
capacitors consisting of C1, C2, C3, keeps on
oscillating as the supply voltage alternates.
This column, therefore, is known as oscillating column. However, the voltage across the
capacitances C1, C2, C3, remains constant and is known as smoothening column. The
voltages at M, N, and O are 2Vmax, 4Vmax
and 6Vmax. Therefore, voltage across all the
capacitors is 2Vmax except for C1 where it is
Vmax only. The total output voltage is
2nVmax where n is the number of stages.
Thus, the use of multistages arranged in the
manner shown enables very high voltage to
be obtained. The equal stress of the elements
(both capacitors and diodes) used is very
helpful and promotes a modular design of
such generators.
Generator

Loaded:

When

the

generator is loaded, the output voltage will

75

Deependra Singh

High Voltage Engineering


UnitUnit-III
never reach the value 2nVmax. Also, the output wave will consist of ripples on the voltage.
Thus, we have to deal with two quantities, the voltage drop V and the ripple V.
Suppose a charge q is transferred to the load per cycle. This charge is q = 1/f = 1T.
The charge comes from the smoothening column, the series connection of C1, C2, and C3. If
no charge were transferred during T from this stack via D1, D2, D3, to the oscillating column,
the peak to peak ripple would merely be
n

1
n = 0 Ci '

2V = 1T

(2.6)

But in practice charges are transferred.


Cascade generators of Cockcroft Walton type are used and manufactured today
worldwide. The D.C. voltages produced with this circuit may range from some 10 kV up to
more than 2 MV, with current ratings from some 10 A up to some 100 mA. Supply
frequencies of 50/60 Hz are heavily limiting the efficiency, and therefore higher frequencies
up to about 1000 Hz (produced by single-phase alternators) or some 10 kHz (produced by
electronic circuits) are dominating.

REFERENCE:

HVE: C L WADHWA; 2.2; P-59-60

HVE FUNDAMENTALS: KUFFEL, ZAENGL & KUFFEL; P-19

Deependra Singh

76

High Voltage Engineering


UnitUnit-III

30. INTRODUCTION TO STANDARD LIGHTNING AND SWITCHING


IMPULSE VOLTAGES
Disturbances of electric power transmission and distribution systems are frequently
caused by two kinds of transient voltages whose amplitudes may greatly exceed the peak
values of the normal A.C. operating voltage.
The first kind is lightning overvoltages, originated by lightning strokes hitting the
phase wires of overhead lines or the busbars
of outdoor substations. The amplitudes are
very high, usually in the order of 1000 kV or
more, as every stroke may inject lightning
currents up to about 100 kA and even more
into the transmission line; each stroke is
then followed by traveling waves, whose
amplitude is often limited by the maximum
insulation strength of the overhead line. The rate of voltage rise of such a traveling wave is at
its origin directly proportional to the steepness of the lightning current, which may exceed
100 kA/sec, and the voltage levels may simply be calculated by the current multiplied by
the effective surge impedance of the line. Too high voltage levels are immediately chopped
by the breakdown of the insulation and therefore traveling waves with steep wave fronts and
even steeper wave tails may stress the insulation of power transformers or other H.V.
equipment severely. Lightning protection systems, surge arresters and the different kinds of
losses will damp and distort the traveling waves, and therefore lightning overvoltages with
very different waveshapes are present within the transmission system.
The second kind is caused by switching phenomena. Their amplitudes are always
related to the operating voltage and the shape is
influenced by the impedances of the system as
well as by the switching conditions. The rate of
voltage rise is usually slower, but it is well known
that the waveshape can also be very dangerous to
different

insulation

systems,

especially

to

atmospheric air insulation in transmission systems


with voltage levels higher than 245 kV.

77

Deependra Singh

High Voltage Engineering


UnitUnit-III
Both types of overvoltages are also effective in the L.V. distribution systems, where
they are either produced by the usual, sometimes current-limiting, switches or where they
have been transmitted from the H.V. distribution systems. Here they may often cause a
breakdown of electronic equipment, as they can reach amplitudes of several kilovolts, and it
should be mentioned that the testing of certain L.V. apparatus with transient voltages or
currents is a need today.

REFERENCE:

HVE FUNDAMENTALS: KUFFEL, ZAENGL & KUFFEL; P-48-51

Deependra Singh

78

High Voltage Engineering


UnitUnit-III

31. ANALYSIS OF SINGLE STAGE IMPULSE GENERATOR


EXPRESSION FOR OUTPUT IMPULSE VOLTAGE
Two basic circuits for single-stage impulse generators are shown in Fig. 2.25. The
capacitor C1 is slowly charged from a D.C. source until the spark gap G breaks down. This
spark gap acts as a voltage-limiting and voltage-sensitive switch, whose ignition time (time to
voltage breakdown) is very short in comparison to T1.

As such single-stage generators may be used for charging voltages from some kV up
to about 1MV; the sphere gaps will offer proper operating conditions. An economic limit of
the charging voltage V0 is, however, a value of about 200 to 250 kV, as too large diameters
of the spheres would otherwise be required to avoid excessive inhomogeneous field
distributions between the spheres. The resistors R1, R2 and the capacitance C2 form the wave
shaping network. R1 will primarily damp the circuit and control the front time T1. R2 will
discharge the capacitors and therefore essentially control the wave tail. The capacitance C2
represents the full load, i.e. the object under test as well as all other capacitive elements
which are in parallel to the test object (measuring devices; additional load capacitor to avoid
large variations of T1/T2, if the test objects are changed). No inductances are assumed so far,

79

Deependra Singh

High Voltage Engineering


UnitUnit-III
and are neglected in the first fundamental analysis, which is also necessary to understand
multistage generators. In general this approximation is permissible, as the inductance of all
circuit elements has to be kept as low as possible.
Before starting the analysis, we should mention the most significant parameter of
impulse generators. This is the maximum stored energy:
W=

1
C1 (V0 MAX ) 2
2

(2.22)

Within the discharge capacitance C1.As C1 is always much larger than C2, this figure
determines mainly the cost of a generator.
For the analysis we may use the Laplace transform circuit sketched in Fig. 2.25(c),
which simulates the boundary condition, that for t 0, C1 is charged to V0 and for t> 0 this
capacitor is directly connected to the wave-shaping network. For the circuit Fig. 2.25(a) the
output voltage is thus given by the expression

V ( s) =
Where

By Substitution we find

Where

V0 Z 2
,
s Z1 + Z 2

Z1 =

1
+ R1 ;
C1 s

Z2 =

R2 / C 2 s
.
R2 + 1 / C 2 s

V ( s) =

V0
1
2
k s + as + b

1
1
1
a =
+
+
R1C1 R1C 2 R2 C 2

(2.23)

1
;
b =
R
R
C
C
1 2 1 2

k = R1C 2 .

(2.24)

For circuit Fig. 2.25(b) one finds the same general expression (eqn (2.23)), with the following
constants; however,

1
1
1
;
a =
+
+
R1C1 R1C 2 R2 C1

1
b =
R1 R2 C1C 2
k = R1C 2

Deependra Singh

;
as Above

(2.25)

80

High Voltage Engineering


UnitUnit-III
For both circuits, therefore, we obtain from the transform tables the same expression in the
time domain:

V (t ) =

V0
1
[exp(1t ) exp( 2 t ]
k ( 1 + 2 )

(2.26)

Where 1 and 2 are the roots of the equation s2+ab+b = 0, or


2

a
a
1 , 2 = m b
2
2

(2.27)

The output voltage V(t) is therefore the superposition of two exponential functions of
different signs. According to eqn (2.27), the negative root leads to a larger time constant 1/ 1
than the positive one, which are 1/ 2. A graph of the expression (eqn (2.26)) is shown in Fig.
2.26, and a comparison with Figs 2.23 and 2.24 demonstrates the possibility to generate both
types of impulse voltages with these circuits.

REFERENCE:

HVE FUNDAMENTALS: KUFFEL, ZAENGL & KUFFEL; 2.3.1; P-52-55

81

Deependra Singh

High Voltage Engineering


UnitUnit-III

32. MULTISTAGE IMPULSE GENERATOR


COMPONENTS OF MULTISTAGE IMPULSE GENERATOR
In order to obtain higher and higher impulse voltage, a single stage circuit is inconvenient for
the following reasons:
(i). The physical size of the circuit elements becomes very large.
(ii). High D.C. charging voltage is required.
(iii). Suppression of corona discharges from the structure and leads during the charging
period is difficult.
(iv). Switching of vary high voltages with spark gaps is difficult.
In 1923 E. Marx suggested a multiplier circuit which is commonly used to obtain impulse
voltages with as high a peak value as possible for a given D.C. charging voltage.
Depending upon the charging voltage available and the output voltage required a
number of identical impulse capacitors are charged in parallel and then discharged in series,
thus obtaining a multiplied total charging voltage corresponding to the number of stages. Fig.
3.7 shows a 3-stage impulse generator circuit due to Marx employing b circuit connections.
The impulse capacitors C1 are charged to the charging voltage V0 through the high charging
resistors RC in parallel. When all the gaps G break down, the C1 capacitances are connected
in series so that C2 is charged through the series connection of all the wave front resistances
R1 and finally all C1 and C2 will discharge through the resistors R2 and R1. Usually RC
>> R2 >> R1.
If in Fig. 3.7 the wave tail resistors R2 in each stage are connected in parallel to the
series combination of R1, G and C1, an impulse generator of type circuit a is obtained.

In order that the Marx circuit operates consistently it is essential to adjust the
distances between various sphere gaps such that the first gap G1 is only slightly less than that
of G2 and so on. If is also necessary that the axes of the gaps G be in the same vertical plane

Deependra Singh

82

High Voltage Engineering


UnitUnit-III
so that the ultraviolet radiations due to spark in the first gap G, will irradiate the other gaps.
This ensures a supply of electrons released from the gap electrons to initiate breakdown
during the short period when the gaps are subjected to overvoltages.
The wave front control resistance can have three possible locations (i) entirely within
the generator (ii) entirely outside the generator (iii) partly within and partly outside the
generator.
The first arrangement is unsatisfactory as the inductance and capacitance of the
external leads and the load form an oscillatory circuit which requires to be damped by an
external resistance. The second arrangement is also unsatisfactory as a single external front
resistance will have to withstand, even though for a very short time, the full rated voltage and
therefore, will turn out to be inconveniently long and would occupy much space. A
compromise between the two is the third arrangement as shown in Fig. 3.7 and thus both the
space economy and damping of oscillations are taken care of.
It can be seen that Fig. 3.7 can be reduced to the single stage impulse generator of Fig.
3.4 (b).
After the generator has fired, the total discharge capacitance C1 may be given as:
1 n 1
C '
C1
1
n

the equivalent front resistance

R1 = R1 '+ R1"
n

and the equivalent tail control resistance

R2 = R2 '

where n is the number of stages.

CONSTRUCTION OF IMPULSE GENERATOR:


An impulse generator requires a D.C. power supply for charging the impulse
capacitance C1 of the generator. The supply consists of a step-up transformer and rectifier.
The charging times should not be less than 3 to 10 seconds as every application of voltage
will leave behind pre-ionizing effects, so a time should be allowed between two successive
applications so that the pre-stressing effects within the insulations do not influence the
breakdown strength. These days thyristor controlled D.C. supply for charging is available.
The resistors may be made up of wire, liquid or composite (carbon etc.) resistive
materials. The liquid and carbon resistors even though have high heat capacity, these are

83

Deependra Singh

High Voltage Engineering


UnitUnit-III
invariably not used especially for wave front and tail control resistances as these are highly
unstable i.e. their value is not constant and may change with various factors. Therefore, noninductive wire would resistors are used for this purpose even though these are relatively
costly. It is found that for most of the circuits if the time constant of those resistances is less
than 0.1 micro se. they are considered quite satisfactory from the view point of oscillation in
the circuit. These resistors should be placed in such a way that they can be exchanged and
replaced easily as they must be charged as per the requirement of a particular wave shape.
The layout of an impulse generator is mainly decided by the type of capacitors used.
Oil paper insulated capacitors having low inductance and high rate of discharge are normally
employed. The material oil is often replaced by special fluids which are having higher
permittivity to reduce the size of the capacitor for the same capacitance. Some of the designs
use oil impregnated capacitors in insulating containers. These capacitors have the dielectric
assembled in an insulating cylinder of porcelain or varnished paper with plane metal plates.
An advantage of this form of capacitor is that successive stages of capacitors can be built up
in vertical columns, each stage being separated from the adjacent one by supports of the same
form as the capacitors but without the dielectric. Recently, modular constructions with simple
capacitor units within insulating cylinders or vessels or within metal tanks and bushings have
been recommended are in use. These designs were made possible due to the use of high
dielectric fluids (e.g. SF6) which could reduce the size of the capacitors significantly.
The coupling sphere gaps are arranged one above the other on horizontal arms and the
setting of the gaps is adjusted by a remotely controlled motor in conjunction with an
indicator. This arrangement with mutual irradiation ensures a perfect cascading of the spark
gaps. They are normally encapsulated in a chimney provided with dust free and dry air. The
use of proper gas mixtures gives good switching performance.
The impulse generator should have a device to earth the capacitors when it is not in
operation. The D.C. capacitors can build up high voltages after a short time of short circuit
due to the relaxation phenomenon. A series protective resistance should be included in this
earthing device to avoid too high discharge currents.
The front and tail resistors are fixed to the generator frame by means of resistor
carriers of bakelized paper tubes. The charging resistors are fixed along the sphere gap
column. All leads and electrodes within the generator should be dimensioned properly to
avoid too heavy corona discharges during the charging period.
A typical impulse generator circuit giving all details is shown in Fig. 3.9.

Deependra Singh

84

High Voltage Engineering


UnitUnit-III

REFERENCE:

HVE FUNDAMENTALS: C L WADHWA; 3.5; P-94-98

85

Deependra Singh

High Voltage Engineering


UnitUnit-III

33. TRIGGERING OF IMPULSE GENERATOR BY THREE ELECTRODE


GAP ARRANGEMENT
Impulse generators are normally operated in conjunction with cathode ray
oscillographs for measurement and for studying the effect of impulse waves on the
performance of the insulations of the equipments. Since the impulse waves are of shorter
duration, it is necessary that the operation of the generator and the oscillograph should be
synchronised accurately and if the wave front of the wave is to be recorded accurately, the
time sweep circuit of the oscillograph should be initiated at a time slightly before the impulse
wave reaches the deflecting plates.
If the impulse generator itself initiates the sweep circuit of the oscillograph, it is then
necessary to connect a delay cable between the generator or the potential divider and the
deflecting plates of the oscilloscope so that the impulse wave reaches the plates at a
controlled time after the sweep has been tripped. However, the use of delay cable leads to
inaccuracies in measurement. For this reason, some tripping circuits have been developed
where the sweep circuit is operated first and then after a time of about 0.1 to 0.5 sec. the
generator is triggered.

Fig. 3.11 shows a trigatron gap which is used as the first gap of the impulse generator
and consists essentially of a three-electrode gap. The high voltage electrode is a sphere and
the earthed electrode may be a sphere, a semi-sphere or any other configuration which gives
homogeneous electric field. A small hole is drilled into the earthed electrode into which a
metal rod projects. The annular gap between the rod and the surrounding hemisphere is about
1 mm. A glass tube is fitted over the rod electrode and is surrounded by a metal foil which is
connected to the earthed hemisphere. The metal rod or trigger electrode forms the third
electrode, being essentially at the same potential as the drilled electrode, as it is connected to

Deependra Singh

86

High Voltage Engineering


UnitUnit-III
it through a high resistance, so that the control or tripping pulse can be applied between these
two electrodes. When a tripping pulse is applied to the rod, the field is distorted in the main
gap and the latter breaks down at a voltage appreciably lower than that required to cause its
breakdown in the absence of the tripping pulse. The function of the glass tube is to promote
corona discharge round the rod as this causes photo-ionization in the annular gap and the
main gap and consequently facilitates their rapid breakdown.
REFERENCE:

HVE FUNDAMENTALS: C L WADHWA; 3.7; P-98-99

87

Deependra Singh

High Voltage Engineering


UnitUnit-III

34. TRIGGERING GAP AND OSCILLOGRAPH TIME SWEEP CIRCUITS


For single stage or multi-stage impulse generators the trigatron gaps have been found
quite satisfactory and these require a tripping voltage of about 5 kV of either polarity. The
tripping circuits used today are commercially available and provide in general two or three
tripping pulses of lower amplitudes. Fig. 3.12 shows a typical tripping circuit. The capacitor
C1 is charged through a high resistance R1. As the remotely controlled switch S is closed, a
pulse is applied to the sweep circuit of the oscillograph through the capacitor C3. At the same
time the capacitor C2 is charged up and a triggering pulse is applied to the trigger electrode of
the trigatron. The requisite delay in triggering the generator can be provided by suitably
adjusting the values of R2 and C2. The residual charge on C2 can be discharged through a high
resistance R3. Nowadays lasers are also used for tripping the spark gap.

The trigatron also has a phase shifting circuit associated with it so as to synchronise
the initiation time with an external alternating voltage. Thus, it is possible to combine high
alternating voltage tests with a superimposed impulse wave of adjustable phase angle.
The trigatron is designed so as to prevent the overcharging of the impulse capacitors
in case of an accidental failure of triggering. An indicating device shows whether the
generator is going to fire correctly or not. An additional feedback circuit provides for a safe
wave chopping and oscillograph release, independent of the emitted control pulse.

REFERENCE:

HVE FUNDAMENTALS: C L WADHWA; 3.7; P-100

Deependra Singh

88

High Voltage Engineering


UnitUnit-III

35. GENERATION OF SWITCHING IMPULSE VOLTAGE

The common impulse generator circuits discussed so far are well capable of
producing standard switching impulses with adequate voltage efficiency , if the circuit is
well designed and the ratio C2/C1 is kept adequately small.
Other methods, however, have taken advantage of utilizing testing transformers to
step up the amplitudes from impulse voltages also. One such circuit is shown in Fig. 2.31. An
initially charged capacitor C1 is discharged into the waveshaping circuit R1, C2 as well as into
the L.V. winding of the transformer. The elements R1 and C2 or other suitable components, in
the dotted rectangle, may be used to control the waveshape. The wave tail is not only
controlled by the resistive voltage divider included, but also from the main inductance of the
transformer equivalent circuit. The time to crest Tp is even without R1, C2 limited by the
series inductance of the transformer, LS, which forms a series resonant circuit in combination
with

C1

capacitance

and

the

load

C2 .

Neglecting

any losses within the circuit,


the voltage across the test
object would therefore start
with a (1-cost) function and
as Tp T/2 = /fr, fr being the
resonance frequency, the time
to crest is approximately
Tcr Ls C
where, neglecting transformer ratio,

C=

C1C 2 '
C1 + C 2 '

In general, low values of Tp are difficult to achieve, as Ls is quite large and also the
capacitance of the H.V. winding of the transformer contributes to the load C2. Further
problems arise with transient oscillations within the transformer windings, mainly if cascaded
testing transformers are used.
REFERENCE:

HVE FUNDAMENTALS: KUFFEL, ZAENGL & KUFFEL; 2.3.1; P-64-65

89

Deependra Singh

High Voltage Engineering


UnitUnit-III

36. ENERATION OF HIGH IMPULSE CURRENT

For producing impulse currents of large


value, a bank of capacitors connected in parallel
are charged to a specified value and are
discharged through a series R-L circuit as
shown in Fig. 6.20. C represents a bank of
capacitors connected in parallel which are
charged from a D.C. source to a voltage up to
200 kV. R represents the dynamic resistance of
the test object and the resistance of the circuit and the shunt L is an air cored high current
inductor, usually a spiral tube of a few turns. If the capacitor is charged to a voltage V and
discharged when the spark gap is triggered, the current im will be given by the equation

di
1
V = Rim + L m + im dt
dt C 0

(6.24)

The circuit is usually underdamped, so that


R
< L
C
2
Hence, im is given by
im =

Deependra Singh

V
[exp(t )]sin(t )
L

90

(6.25)

High Voltage Engineering


UnitUnit-III

Where

R
and =
2L

1
R2
2
LC 4 L

(6.25a)

The time taken for the current im to rise from zero to the first peak value is

t1 = t f =

sin 1

LC

tan 1

(6.26)

The duration for one half cycle of the damped oscillatory wave t2 is,

t2 =

1
R2
2
LC 4 L

(6.27)

REFERENCE:

HVE KAMARAJU NAIDU; 6.4.2; P-145

91

Deependra Singh

High Voltage Engineering


UnitUnit-III

PROBLEMS
Q. 1

Describe in brief, the generation of HVDC HVAC & Impulse voltages?

Q. 2

Explain and compare the performance of half wave rectifier and voltage doubler
circuits for generation of high D.C. voltages.

Q. 3

Define ripple voltage. Show that the ripple voltage in a rectifier circuit depends upon
the load current and the circuit parameters.

Q. 4

Explain with neat sketches Cockroft-Walton voltage multiplier circuit. Explain clearly
its operation when the circuit is (i) unloaded (ii) loaded.

Q. 5

Derive an expression for ripple voltage of a multistage Cockroft-Walton Circuit.

Q. 6

Derive an expression for the voltage output under load condition. Hence, deduce the
condition for optimal number of stage if a maximum value of output voltage is
desired.

Q. 7

Describe with neat diagram the principle of operation and application of a


symmetrical cascaded rectifier.

Q. 8

Explain clearly the basic principle of operation of an electrostatic generator. Describe


with neat diagram the principle of operation, application and limitations of Van de
Graf generator.

Q. 9

What is a cascaded transformer? Explain why cascading is done? Describe with neat
diagram a three stage cascaded transformer. Label the power ratings of various stages
of the transformer.

Q. 10 Draw equivalent circuit of a 3-stage cascaded transformer and determine the


expression for short circuit impedance of the transformer. Hence deduce an
expression for the short-circuit impedance of an n-stage cascaded transformer.
Q. 11 Explain with neat diagram the basic principle of reactive power compensation is high
voltage A.C. testing of insulating materials.
Q. 12 Explain with neat diagram the principle of operation of (i) series (ii) parallel resonant
circuits for generating high A.C. voltages. Compare their performance.
Q. 13 Explain the series-parallel resonant circuit and discuss its advantages and
disadvantages
Q. 14 Give the principle of operation of series resonant circuit along with advantages?
Q. 15 Define the terms:
(i) Impulse voltages
(iv) Impulse puncture voltage

Deependra Singh

(ii) Chopped wave


(v)

(iii) Impulse flash over voltage

Impulse ratio for flash over (vi) Impulse ratio for puncture

92

High Voltage Engineering


UnitUnit-III
Q. 16 Draw a neat exact equivalent circuit of an Impulse Generator and indicate the
significance of each parameter being used.
Q. 17 Draw and compare the two simplified equivalent circuits of the impulse generator
circuits.
Q. 18 Give complete analysis of circuit a and show that the wave front and wave tail
resistances are physically realizable only under certain condition. Derive the
condition.
Q. 19 Give complete analysis of circuit b and derive the condition for physical realization
of wave front and wave tail resistances.
Q. 20 Derive an expression for voltage efficiency of a single stage impulse generator.
Q. 21 Describe the construction, principle of operation and application of a multistage
Marx's Surge Generator.
Q. 22 Explain the Goodlet circuit of impulse voltage generation and compare its
performance with that of Marxs circuit.
Q. 23 Describe the construction of various components used in the development of an
impulse generator.
Q. 24 Explain with neat diagram triggering and synchronization of the impulse generator
with the CRO.
Q. 25 Draw a typical impulse current generator circuit and explain its operation and
application.
Q. 26 Draw a neat diagram of a high current generator circuit (equivalent circuit) and
through analysis of the circuit show how the wave form can be controlled.

93

Deependra Singh

Das könnte Ihnen auch gefallen