F500

QUICK-REFERENCE
FR-F520-11K to 55K-NA
FR-F540-11K to 55K-NA

F500 Specifications
3-phase 200V Class
Model FR-F520-___K-NA
Applicable motor capacity
Normal
(kW) *1
Rated capacity (HP) *2
Normal
Rated Current (A)
Normal
Overload capacity *3
Normal

Duty

Duty
Duty
Duty
Max. value/time
Regenerative braking torque
Tolerable work rate

11K

15K

18.5K

22K

30K

37K

45K

55K

11

15

18.5

22

30

37

45

55

15
45

20
58

Rated input AC voltage, frequency *4


Tolerable AC voltage fluctuation
Tolerable frequency fluctuation
Power capacity (KVA) *6

No DC Reactor
DC Reactor Present

Protective structure
Cooling method
Ambient temperature
Approx. mass (Kg (lb))

3-phase 400V Class


Model FR-F540-___K-NA
Applicable motor capacity
Normal
(kW) *1
Rated capacity (HP) *2
Normal
Rated Current (A)
Normal
Overload capacity *3
Normal

Duty

Duty
Duty
Duty
Max. value/time
Regenerative braking torque
Tolerable work rate
Rated input AC voltage, frequency *4
Tolerable AC voltage fluctuation
Tolerable frequency fluctuation
Power capacity (KVA) *6
Protective structure
Cooling method
Ambient temperature
Approx. mass (Kg (lb))

Notes:

No DC Reactor
DC Reactor Present

20

25
30
40
50
60
70
85
114
140
170
120% 60 sec. (inverse-time characteristics)
15% *5
Continuous *5
3 phase, 200V to 240V, 60 Hz
3 phase, 200-230V, 60Hz
170 to 264V, 60Hz
170 to 253V, 60 Hz
+/- 5%
27

32

41

52

65

79

16
19
24
31
41
50
61
Fully enclosed type ( IP20, NEMA 1)
Open type ( IP00 )
Forced air cooling
50 degrees C ( 122 F ), no frost or condensation
8.0
13.0
13.0
13.0
21.0
30.0
40.0
17.6
28.7
28.7
28.7
46.3
66.1
88.2

75
212

99
74

55.0
121.3

11K

15K

18.5K

22K

30K

37K

45K

55K

11

15

18.5

22

30

37

45

55

15
23

20
29

25
30
40
50
60
35
43
57
70
85
120% 60 sec. (inverse-time characteristics)
15% *5
Continuous *5
Three phase, 380V to 480V, 60 Hz
323 to 528V, 60Hz
+/- 5%
20
27
32
41
52
65
79
16
19
24
31
41
50
61
Fully enclosed type ( IP20, NEMA 1)
Open type ( IP00 )
Forced air cooling
50 degrees C ( 122 F ), no frost or condensation
7.0
13.0
13.0
13.0
24.0
24.0
35.0
15.4
28.7
28.7
28.7
52.9
52.9
77.2

75
106

99
74

36.0
79.4

*1 The applicable motor capacity indicated is the maximum capacity based upon NEC standards for induction type motors.
*2 The rated output capacity is 220V for the 200V class and 440V for the 400V class.
*3 The percentage given for the overload current indicates the ratio with respect to the inverter's rated current. In case of repeated use, it is
essential to wait until the inverter and the motor has cooled to below the ambient temperature.
*4 The maximum output voltage cannot exceed the power supply voltage, but can be set as desired below the incoming power supply voltage.
*5 Indicate the average torque for decelerating to stop from 60Hz. Changes according to motor loss.
*6 The power supply capacity changes with the values of the power supply side inverter impedances (including those of the input reactor and
cables).

F500 Common Specifications


Control system
Output frequency range
Frequency
Analog input
setting
resolution
Digital input
Analog input
Output
frequency
Digital input
accuracy
(using keypad)
Voltage/frequency characteristic
Torque boost

DC injection brake
Stall prevention operation level
Analog input
Frequency setting signal
Digital input
Start signal
Multi-speed selection
2nd accel/decel selection
Jog operation selection
Current input selection
Selection of auto restart after
instantaneous power failure
Thermal relay input
FR-HC connection
External DC dynamic braking start
signal
PID control valid
PU operation-external operation
switching
PU operation external interlock
Output stop
Alarm reset
User definable input signals

Control specifications

Acceleration/deceleration time setting

Operation functions

Output signals

Operating status

Alarm (inverter trip)


For meter

Display

PU (FR-DU04/ FR-PU04)

Operating
status
Alarm
definition

LED display

Additional display on
FR-PU04 only

Operating
status
Alarm
definition
Interactive
guidance

Environment

Protective/alarm functions

Ambient temperature
Ambient humidity
Storage temperature (Note 2)
Ambience
Altitude, vibration

Notes:

Soft PWM control/high carrier frequency PWM control (V/F control), Optimum excitation control.
0.5 to 120Hz
0.015Hz/60Hz(Terminal 2 input: 12 bits/0 to 10V, 11 bits/0 to 5V,
terminal 1 input: 12 bits/10 to +10 V, 11 bits/ -5 to +5V)
0.01Hz
0.2% of maximum output frequency (25C 10C (77F18F))
0.01% of commanded output frequency
Base frequency setting range: 0 - 120Hz.
Constant torque or variable torque patterns may be selected.
Manual and automatic torque boosts.
0 to 3600 s (acceleration and deceleration set independently), Linear or S-pattern accel/decel curves may be
selected.
Operation frequency (0 to 120Hz), operation time (0 to 10s), voltage (0 to 30%) variable
Operation current level can be set (0 to 150% variable); presence or absence can be selected.
0 to 5VDC, 0 to 10VDC, 0 to 10VDC, 4 to 20mADC.
3-digit BCD or 12-bit binary using operation panel or parameter unit (when the FR-A5AX option is used.)
Forward and reverse rotation, start signal self-holding input (3-wire input) may be selected.
Up to 7speeds can be defined
0 to 3600s. (Up to 2 different accel and decel times can be set individually)
Provided with jog operation mode select terminal (Note 1)
Used to select input of frequency setting signal 4 to 20mADC (terminal 4).
Selection of whether automatic restart is make or not after an instantaneous power
failure.
Used to provide interface to external thermal relay
Use
VFD operation enable input and instantaneous power failure detection input
Pr. 180 to
Pr. 186 for
External input for DC dynamic brake start.
selection.
Selection for exercising PID control
Used to remotely switch the VFD between PU operation and external operation
External interlock switch-over of PU operation.
Instantaneous shut-off of inverter output (frequency, voltage).
Used to reset alarm output after alarm condition.
Maximum/minimum frequency setting, frequency jump operation, external thermal relay input selection,
polarity reversible operation, automatic restart operation after instantaneous power failure, commercial
power supply-inverter switch-over operation, forward/reverse rotation prevention, slip compensation,
operation mode selection, PID control, computer link operation (RS-485)
5 different signals can be selected from: inverter running, up to frequency, instantaneous power failure
(undervoltage), frequency detection, 2nd frequency detection, during PU operation, overload alarm, electronic
overcurrent protection pre-alarm, zero current detection, PID upper limit, PID lower limit, PID forward/reverse
rotation, commercial power supply invert switch over MC1/2/3, operation ready, fan fault and fin overheat
pre-alarm minor fault, and 1 contact output (230VAC 0.3A, 30VDC 0.3A) can be selected.
Contact output, change over contact (230VAC 0.3A, 30VDC 0.3A) open collector, Alarm code (4-bit)
1 signal can be selected from output frequency, motor current (steady or peak), output voltage, frequency
setting, running speed, converter output voltage (steady or peak), electronic overcurrent protection load
factor, input power, output power, load meter and reference voltage output.
Pulse train output (1440 pulses/s full scale) and analog output (0 to 10VDC)
Selection can be made from output frequency, motor current (steady or peak), output voltage, frequency
setting, running speed, overload, converter output (steady or peak), electronic overcurrent load factor, input
power, output power, load meter, total energization time, actual operation time, total power and motor load
factor.
Alarm definition is displayed when protective function is activated. 8 alarm definitions are stored.
(4 alarm definitions are only displayed on the operation panel (FR-DU04)).
Power application (POWER), Alarm (ALARM)
Input terminal signal states, output terminal signal states, option fitting status, terminal assignment status
Output voltage/current/frequency/cumulative ON time immediately before activation of protective function.
Operation guide and trouble shooting by help function.
Overcurrent shut-off (during accel, decel, constant speed), regenerative overvoltage shut-off, undervoltage,
instantaneous power failure, overload shut-off (electronic overcurrent protection), ground fault current, output
short circuit, stall prevention, overload alarm, fin overheat, fan fault, option fault, parameter error, PU
disconnection, retry count exceeded, output phase failure, CPU fault, 24VDC power output short circuit,
operation panel power supply short circuit.
-10C to +50C (14F to 122F) (non-freezing)
(-10C to +40C (14F to 122F) with FR-A5CV attachment)
90%RH or less (non-condensing)
-20C to +65C (-4F to 149F)
Indoors (no corrosive and flammable gases, oil mist, dust and dirt.)
Maximum 1000m (3280.80 feet) above sea level for standard operation. After that derate by 3% for every
extra 500m (1640.40 feet) up to 2500m (8202.00 feet) (91%). 5.9 m/s2 or less (conforming to JIS C0911)

1.

JOG operation may also be performed from the operation panel or parameter unit.

2.

Temperature applicable for a short period in transit, etc.

F500 Terminal Definitions

F500 Terminal Definitions


Symbol
R, S, T
U, V, W
R1, S1
P , PR
P,N
P , P1

Type

Discrete
Analog

Connection for the optional brake unit or high power factor converter.
Connection for the optional power factor improving DC reactor.

Ground

For grounding the inverter chassis.

Symbol

Terminal Name

Description
Connect to line power supply.
Connect to three-phase squirrel-cage motor.
Connected to AC power input terminals R and S. To retain alarm display
and alarm output, remove the jumpers from terminals R-R1 and S-S1.
Connection for the optional brake resistor

Description

When the STF and


Turn on the STF signal to start forward rotation and
STR signals are
turn it off to stop.
turned on
simultaneously, the
Reverse rotation
Turn on the STR signal to start reverse rotation
stop command is
STR
start
and turn it off to stop.
given.
Multi-speed
Combine the RH, RM and RL signals as
RH, RM, RL
selection
appropriate to select multiple speeds.
Turn on the JOG signal to select jog operation
JOG mode
JOG
(factory default). JOG operation can be performed Input terminal function
selection
choices (Pr. 180 to
with the start signal (STF or STR).
nd
Turn on the RT signal to select the 2 accel/decel Pr. 186) alter terminal
nd
nd
functions.
time. When the 2 functions such as 2 torque
Second accel/decel
nd
RT
boost, and 2 V/F functions have been set,
time selection
these functions can also be selected by turning on
the RT signal
MRS
Output stop
Turn on the MRS signal (20ms or longer) to stop the inverter output.
Turn on the RES signal for more than 0.1 sec to reset VFD after activation
RES
Reset
of protective functions.
Current input
Turn on the AU signal so that the inverter can be
AU
selection
operated with 4-20mA(dc) frequency setting signal.
Input terminal function
With the CS signal on, restart can be made
choices (Pr. 180 to
Automatic restart
automatically when the power is restored after an
Pr. 186) alter terminal
after instantaneous
CS
instantaneous power failure. Note this operation
functions.
power failure
requires restart parameters to be set. Factory
selection
default setting disallows automatic restart.
Contact input
Common to the contact input terminals and terminal FM. Common output
SD
common (sink)
terminal for 24VDC 0.1A power output (PC terminal).
Connect the external power supply common for transistor outputs to this
Contact input
terminal to prevent a fault caused by leakage current. This terminal can be
PC
common (source)
used as a 24VDC, 0.1A power output. When source logic is selected, this
terminal serves as a contact input common.
Factory logic default to terminal 10.
10E
10VDC, permissible load 10mA max When connecting to terminal 10E,
Analog speed ref.
power supply
change terminal 2s input
10
5VDC, permissible load10mA max
specifications.
Selectable 0 to 5VDC (factory setting) or 0 to 10VDC analog speed
Analog speed ref.
2
(voltage)
reference input. Input resistance 10k. Maximum permissible voltage 20V.
4 20mADC analog speed reference Input. This input signal is valid only
when one of the discrete input terminals is configured as AU and is
Analog speed ref.
4
(current)
jumped to SD terminal. Input resistance 250. Maximum permissible
current 30mA.
Analog speed ref.
Common to the frequency setting signals (terminal 2, 1 or 4).
5
input common
Do not connect to the earth.
STF

Input signals

Terminal Name
AC power input
Inverter output
Power supply for
control circuit
Brake resistor
connection
Brake unit connection
DC reactor connection

Forward rotation
start

F500 Terminal Definitions

Discrete

RS-485
Serial
Comm.

Analog

Output signals

A, B, C

Alarm output

RUN

Inverter running

SU

Up to Frequency

OL

Overload Alarm

IPF

Instantaneous
Power Failure

FU

Frequency
detection

SE

Open collector
output common

FM
AM

1 contact output indicating that the output has been stopped by


the inverter protective function activating.
Form C contact output: 230VAC 0.3A, 30VDC 0.3A.
Normal state (VFD pwr on): B-C continuity, (A-C discontinuity)
Alarm state (VFD pwr on): A-C continuity, (B-C discontinuity)
Closed when the VFD output frequency is equal to or higher
than starting frequency. Open during stop or DC dynamic brake
operation. Permissible load: 24VDC @ 0.1A max.
Switched low when output frequency has reached +/- 10% of
the set frequency. Switched high during accel, decel, or stop.
Permissible load: 24VDC @ 0.1A max.
Switched low when the stall prevention function had caused
stall prevention to be activated. Switched high when stall
prevention is reset. Permissible load: 24VDC @ 0.1A max.
Switched low when the instantaneous power failure or
undervoltage protection is activated.
Permissible load: 24VDC @ 0.1A max.
Closed when the output frequency has reached or exceeded
the defined detection frequency.
Permissible load: 24VDC @ 0.1A max.

Output
terminal
function
choices
(Pr. 190
to Pr.
195)
change
terminal
functions.

Common to the RUN, SU, OL, IPF, and FU terminals.

Factory default: Output Frequency


One may be selected from 16
Pulse signal output monitoring items is output.
Permissible load current 1mA
1440 pulses/second at 60Hz
The output signal is proportional
to the magnitude of each
Analog signal
Factory default: Output Frequency
monitored item.
output
Output signal 0 to 10 VDC (1mA max)
RS-485 serial communication is standard via the keypad connector:
! Conforming Standard
: EIA Standard RS-485
PU connector
! Transmission format
: Multi-drop link
! Communication speed
: Maximum 19200 baud rate
! Overall length
: 500m (1640.40 feet)

F500 Parameter Set

Other

Protective

Monitoring

Application Specific

General Operation

VFD Functions
Switch-over to full parameter settings from
simple mode operation
Switch-over to optimum excitation control
operation
Adjustment to accel/decel time and pattern
Selection of optimum output characteristic for
load
Limit of output frequency
Operation over 60Hz
Adjustment of frequency setting signal and
output
Adjustment of motor output torque
Adjustment of brake operation
Multi-speed operation
JOG operation
Frequency jump operation
Automatic restart after instantaneous power
failure
Optimum accel/decel within continuous rating
range
Ready to run signal
To perform commercial power supply inverter
switch-over operation
Timing of magnetic brake operation
Reversible operation according to analog signal
polarity
Sub-motor operation
To set desired output characteristics
Operation via communication with personal
computer

Associated Parameter Numbers


Pr. 160
Prs. 14, 60
Prs. 7, 8, 20, 21, 160
Prs. 3, 14, 19, 60
Prs. 1, 2
Prs. 903, 905
Prs. 73, 74, 902 to 905
Pr. 0
Prs. 10, 11, 12
Prs. 1, 2, 4, 5, 6, 15, 24, 25, 26, 27, 160
Prs, 15, 16
Prs. 31, 32, 33, 34, 35, 36
Prs. 57, 58
Pr. 60
Prs. 190 to 195, setting 11
Prs. 135 to 139, 160, 180 to 186, 190 to 195
Prs. 42, 160, 190 to 195
Prs. 28, 73
Prs. 0, 3, 7, 8, 44 to 47
Prs. 100 to 109
Prs. 117 to 124, 160

Operation under advanced PID control


To set backlash compensation
To suppress noise
Calibration of frequency meter
Adjustment of digital frequency meter
Display of speed, etc.
Clearing of inverters actual operation time
Alarm code output selection

Prs. 73, 79, 128 to 134, 160, 180 to 186, 190 to


195
Prs. 128 to 134, 500 to 516, 180 to 186, 190 to 195
Prs. 140 to 143
Prs. 72, 240
Prs. 54 to 56, 158, 160, 900, 901
Prs. 54 to 56, 900
Prs. 37, 52, 53, 160
Pr. 171
Pr. 76

Function rewrite protection


Reverse rotation protection
To group parameters
To set initial values for parameter groups
Assignment of input terminal functions
Assignment of output terminal functions
To increase cooling fan life
Motor overheat protection
Automatic restart after alarm stop
Selection of key beep
Inverter reset selection

Pr. 77
Pr. 78
Prs. 160, 173 to 176
Pr. 199
Prs. 180 to 186
Prs. 190 to 195
Pr. 244
Prs. 9, 71
Prs. 65, 67 to 69
Pr. 990
Pr. 75

Operation under PID control

F500 Advanced PID

Advanced PID Control


PID control function may be used for pumps and fans with multiple motors (max. 4)

1. Action outline
" Use Pr.500 Auxiliary Motor Action Selection to select the number of commercially powered motors to be
operated.
Use Pr.501 Motor Switching Selection to set switching mode for the motors.
Pr.
No.

Function

Range

Unit

Factory
setting

500

Auxiliary Motor
Action Selection

0~3

501

Motor Switching
Selection

0~2

Description
Number of auxiliary operated motors (1~3).
0: Auxiliary motors are inactive.
0: Basic mode.
1: Alternating mode.
2: Direct mode.

F lo w R a te

Q m ax
Q

T im e

(1 ) P r .5 0 1 = 0
M o to r1 (M 1 )
M o to r2 (M 2 )
M o to r3 (M 3 )
M o to r4 (M 4 )
N o te 1

N o te 1

(2 ) P r .5 0 1 = 1
M o to r1 (M 1 )
M o to r2 (M 2 )
M o to r3 (M 3 )
M o to r4 (M 4 )

(3 )P r.5 0 1 = 2
M o to r1 (M 1 )
M o to r2 (M 2 )
M o to r3 (M 3 )
M o to r4 (M 4 )
V F D C o n tro lle d O p e ra tio n

L in e P o w e r O p e ra tio n

S to p

F500 Advanced PID


(1) Pr.501 Motor Switch Select = 0 (Basic mode)
The VFD controlled motor is normally fixed based upon output frequency. By opening or closing the MC between the
input line power and the motor, the number of motors operated via commercial power can be increased or decreased.

(2) Pr.501 Motor Switch Select = 1 (Alternate mode)


While running the operation is the same as basic mode (Pr.501=0).
The VFD controlled motor is normally fixed based upon output frequency, and the number of commercially powered
motors can be changed.
During transition from stopping function to output stop the motor that is VFD controlled can be switched by opening or
closing the MC between VFD and motor.
(Note 1) If the motor start sequence was M1M2M3. The sequence becomes M2M3M1, after
switching the MC. (Total = 3 motors)

(3) Pr.501 Motor Switch Select = 2 (Direct mode)


When inputting STF/STR to motor, the motor starts up by VFD control. If the start-up condition is true for the next
motor, switch MC between VFD and motor, and switch MC between commercial power and the motor. The VFD
controlled motor is switched to commercially powered operation, the next motor starts-up by VFD control.
Consequently, if multiple motors are running and condition for stopping is true, the motor started first (via commercially
powered operation) is stopped first.
(Note) If the VFD is reset, the motor start sequence returns to its initial state (Pr.501=1 or 2).
During running, Pr.500 and Pr.501 cannot be changed.
During stop, if Pr.500 and Pr.501 settings are changed, the motor starting sequence returns to its
initial state.

F500 Advanced PID


2. System Structure
(1) Pr.501 Motor Switch Select = 0 (Basic mode)
Flow out

MC
M4

R04

Pump 4
M3

R03

Pump 3
M2

R02

Pump 2

VFD
Power

RST

UVW

M1
Pump 1

FWD

STF

REV

STR

Advanced PID
Control Selection
PID Fwd/Rev
Switch select

Potentiometer
(Set target value)

X14
X24

RT
JOG

FU

SD

OL

10

IPF

R02
R03
R04

MC
R02
MC
R03
MC
R04

Sink Logic
Pr.183=14, Pr.185=24
Pr.194=42, Pr.193=43, Pr.192=44

1
4

(Measured value) 4~20mA

24V
Power

10

DC24

2-line
case

Sensor

SE

5
Deviation
signal

Flow in

F500 Advanced PID


(2) Pr.501 Motor Switch Select = 1 (Alternate mode), or 2 (Direct mode).

VFD
UVW

RST

Power

REV
X14

Advanced PID
Control select

X24

PID Fwd/Rev
Switch select

RI01

MC

STF

FWD

STR

FU

RT

OL

RI01
R01
RI02

IPF

JOG

SD

R02

SU

RI03

RU

10
2

Pump 4
R01

RI02

Pump 3

R02

R02

RI03

SE

5
Deviation

1A

1C
2A

M3

Pump 2

MC

Option (Note 1)

M2

RI02

RI03

FR-A5AR

M1

R01

RI01

Potentiometer

(Set target value)

Flow out

MC(Note2)

R03

DC24

R03

R03
M4
RI04

RI04

RI04

R04

2C
3A

R04

Flow in

R04

Pump 1
2 line
case
-

3C
(Measured value)4~20mA

24V
Power

Sink logic
Pr.183=14, Pr.185=24
Pr.194=45, Pr.193=41, Pr.192=46
Pr.191=42, Pr.190=47, Pr.320=43
Pr.321=48, Pr.322=44

(Note) 1. If controlling 3 or more motors, option FR-A5AR must be used.


2. MC must be mechanically inter-locked.
" For Advanced PID control select signal X14, use any terminal function Pr.180 ~ Pr.186 (input terminal function select).
X14 (PID control valid

ON

Advanced PID Control - Activated

terminal)

OFF

Advanced PID Control Not Activated

11

Sensor

F500 Dimensions
" FR-F520-11K-NA, FR-F540-11K-NA

" FR-F520-15K,18.5K,22K-NA, FR-F540-15K,18.5K,22K-NA

12

F500 Dimensions
" FR-F520-30K-NA

"

FR-F520-37K/45K/55K-NA

FR-F540-30K/37K/45K/55K-NA

13

F500 Accessories
EMC Filters
Applicable Inverter
FR-F520-11K-NA
FR-F520-15K-NA
FR-F520-18.5K-NA
FR-F520-22K-NA
FR-F520-30K-NA
FR-F520-37K/45K/55K-NA

EMC Filter
240V
SF1260
SF1261
SF1262
SF1262
SF1263
SF1265

Applicable Inverter
FR-F540-11K-NA
FR-F540-15K-NA
FR-F540-18.5K-NA
FR-F540-22K-NA
FR-F540-30K-NA
FR-F540-37K/45K-NA
FR-F540-55K-NA

EMC Filter
480V
SF1175
SF1175
SF1176
SF1176
SF1177
SF1178
SF1179

Dynamic Braking
Standard Resistor and Brake Unit Selection
Dynamic Braking for 240 VAC
Braking torque = 100%
Resistance

Rated power

Motor size

(Ohms)

(W)

(HP)

FR-F520

% ED

4000

FR-BR-30K-UL

8000

FR-BR-55K-UL

16000

15
20
15
20
25
30
40
25
30
40
50
60
75

11K
15K
11K
15K
18.5K
22K
30K
18.5K
22K
30K
37K
45K
55K

15%
10%
65%
30%
25%
15%
10%
90%
60%
30%
20%
15%
10%

Braking Unit Kit

Resistor Kit

FR-BU-15K-UL

FR-BR-15K-UL

FR-BU-30K-UL

FR-BU-55K-UL

Drive Model :

Dynamic Braking for 480 VAC


Braking torque = 100%
Braking Unit Kit

Resistor Kit

Resistance

Rated Power

Motor Size

(Ohms)

(Watts)

(HP)

FR-F540

% ED

15
20
15
20
25
30
40
25
30
40
50
60
75

11K
15K
11K
15K
18.5K
22K
30K
18.5K
22K
30K
37K
45K
55K

15%
10%
65%
30%
25%
15%
10%
90%
60%
30%
20%
15%
10%

FR-BU-H15K-UL

FR-BR-H15K-UL

32

4000

FR-BU-H30K-UL

FR-BR-H30K-UL

16

8000

FR-BU-H55K-UL

FR-BR-H55K-UL

16000

Drive Model :

Note: Refer to Mitsubishi Technical Notes No.22 through 25 for detailed information on sizing and selecting dynamic braking systems.

Interchange Adapters
Installation Model
FR-F500 Series
200V

Attachment type

400V
FR-A5AT03
FR-F540-11K-NA
FR-A5AT04
FR-F520-22K-NA
FR-F540-22K-NA
FR-A5AT09
FR-F540-37K-NA
FR-A5AT05
FR-F540-55K-NA
Note: For the models not shown, there is a direct attachment between footprint sizes
When the attachment is used, the depth will increase by 12-15mm.

14

Convention Model
FR-A100E Series
200V
400V
FR-A140E-11K
FR-A120E-22K
FR-A140E-22K
FR-A140E-37K
FR-A140E-55K

F500 Accessories
Heat Sink Adapters
Applicable Inverter

Model
FR-A5CN03
FR-A5CN04
FR-A5CN05
FR-A5CN06
FR-A5CN07
FR-A5CN08

200V Class
FR-F520-11K-NA
FR-F520-15K~22K-NA
FR-F520-37K-NA
FR-F520-45K-NA
FR-F520-55K-NA
FR-F520-30K-NA

400V Class
FR-F540-11K-NA
FR-F540-15K~22K-NA
FR-F540-30K~37K-NA
FR-F540-45K~55K-NA
-

IP40 Adapters
Applicable Inverter

Model
FR-A5CV02

200V Class

400V Class

FR-F520-11K-NA

FR-F540-11K-NA

Plug-in Options
Plug-in Options for FR-F500 (Choose up to 3)
Kit
Model No.

Description

FR-A5AR

Relay Output Module allows 3 of 26 output signals to be pointed to terminals.

FR-A5AX

12 Bit Digital Input to set frequency reference with 3 digit BCD or 12 bit binary input. Gains and offsets can
also be set. Required for orintation control.

FR-A5AY

Digital/Analog Output Expansion Module allows 7 of 26 output signals to be pointed to terminals. 16 analog
output signals can be pointed to terminals.

FR-A5NC

Allows CC-Link (Control and Communication) communication with the drive to operate, monitor, and change
parameters.

FR-A5ND

Allows Device Net communication with the drive to operate, monitor, and change parameters. For
configuration files see page B-80.

FR-A5NM

Allows Modbus Plus communication with the drive to operate, monitor, and change parameters.

FR-A5NP

Allows Profibus DP communication with the drive to operate, monitor, and change parameters. For
configuration files see page B-80.

FR-A5NR

Allows RS-485 communication with the drive to operate, monitor, and change parameters.

Only One communication option can be mounted in a single drive.

Conduit Adapter
Model
FR-A5FN01
FR-A5FN02
FR-A5FN03
FR-A5FN04

Applicable Inverter
200V Class
FR-F520-37K-NA
FR-F520-45K-NA
FR-F520-55K-NA
FR-F520-30K-NA

400V Class
FR-F540-37K-NA
FR-F540-45K~55K-NA
-

Instruction Manual
Model #: IB(NA)66868

Description: FR-F500 Instruction manual.

Available as .PDF format: R:\INV_MKTG\Documentation\F500\F500 (IB(NA)66866).pdf

15

F500 Revision History


Date
01/05/01

Revision
R0 First edition

This document is available only in PDF format and


cannot be ordered from literature fulfillment. Please
contact your Mitsubishi Electric Automation, Inc.
sales office to obtain a copy.