IPS-E-EL-100

3) Auto-Transformer starting (Preferably Korndorffer Type).


Tables A1 and A2 are typical examples of low voltage and medium voltage induction motors with
conventional rating and characteristics.
TABLE A1 - LOW VOLTAGE MOTORS IEC STANDARD WITH CONVENTIONAL RATINGS AND
CHARACTERISTICS
Rated Output
kW
Air Temperature
40C

 1.1
1.5
2.2
3
4
5.5
7.5
9
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200

Starting
Current
=
Times
F.L.
Current

4.7
5
5.2
6
6.3
6.5
6.5
6.5
6.5
7
7.2
7.2
7.2
7
7
7
7
7
7.5
7.5
7.5
7.5

COS

4/4

3/4

2/4

4/4

3/4

2/4

Starting

0.73
0.77
0.78
0.80
0.83
0.84
0.85
0.88
0.88
0.88
0.90
0.90
0.91
0.91
0.92
0.925
0.935
0.935
0.935
0.94
0.94
0.94

0.73
0.77
0.78
0.80
0.83
0.84
0.85
0.88
0.88
0.88
0.90
0.90
0.91
0.91
0.92
0.92
0.93
0.93
0.93
0.935
0.935
0.935

0.70
0.74
0.75
0.79
0.82
0.83
0.84
0.87
0.87
0.87
0.89
0.89
0.90
0.90
0.91
0.91
0.92
0.92
0.92
0.92
0.92
0.92

0.81
0.79
0.81
0.82
0.82
0.83
0.85
0.83
0.83
0.83
0.83
0.84
0.85
0.86
0.86
0.86
0.86
0.86
0.86
0.87
0.87
0.87

0.75
0.74
0.75
0.76
0.77
0.79
0.81
0.79
0.79
0.79
0.79
0.79
0.80
0.82
0.82
0.82
0.83
0.83
0.83
0.84
0.84
0.85

0.65
0.63
0.65
0.66
0.67
0.69
0.73
0.69
0.69
0.69
0.69
0.69
0.70
0.74
0.74
0.74
0.75
0.75
0.75
0.76
0.77
0.78

0.70
0.70
0.63
0.62
0.62
0.55
0.55
0.50
0.50
0.50
0.45
0.45
0.40
0.40
0.40
0.40
0.38
0.38
0.37
0.36
0.35
0.30

66

Dec. 1997

IPS-E-EL-100

TABLE A2 - MEDIUM VOLTAGE MOTORS IEC STANDARD WITH CONVENTIONAL RATINGS


AND CHARACTERISTICS
Rated Output
kW
Air Temperature
40C

50C

185
200
220
250
280
300
315
335
335
375
400
425
450
475
500
530
560
600
630
670
710
750
800
850
900
950
1000
1120
1250
1400
1600
1800
2000

166
180
198
225
252
270
283
301
320
337
360
382
405
427
450
477
504
540
567
603
639
675
720
765
810
855
900
1008
1125
1260
1440
1620
1800

Starting
Current
=
Times
F.L.
Current
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6
6

COS

4/4

3/4

2/4

4/4

3/4

2/4

Starting

0.93
0.93
0.93
0.93
0.93
0.93
0.94
0.94
0.94
0.94
0.94
0.94
0.94
0.94
0.94
0.94
0.94
0.94
0.94
0.95
0.95
0.95
0.95
0.95
0.96
0.96
0.96
0.96
0.96
0.96
0.96
0.96
0.96

0.928
0.928
0.928
0.928
0.928
0.928
0.94
0.94
0.94
0.94
0.94
0.94
0.94
0.94
0.94
0.94
0.94
0.94
0.94
0.945
0.945
0.945
0.945
0.945
0.955
0.955
0.955
0.955
0.955
0.955
0.955
0.955
0.955

0.915
0.915
0.915
0.915
0.915
0.915
0.925
0.925
0.925
0.925
0.925
0.925
0.925
0.925
0.925
0.925
0.925
0.925
0.925
0.93
0.93
0.93
0.93
0.93
0.94
0.94
0.94
0.94
0.94
0.94
0.94
0.94
0.94

0.865
0.865
0.865
0.865
0.865
0.865
0.865
0.875
0.875
0.875
0.875
0.875
0.875
0.875
0.875
0.875
0.875
0.875
0.885
0.885
0.885
0.885
0.885
0.885
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.895
0.895

0.82
0.82
0.82
0.82
0.82
0.82
0.825
0.825
0.84
0.84
0.84
0.84
0.84
0.84
0.84
0.84
0.84
0.84
0.86
0.86
0.86
0.86
0.86
0.86
0.87
0.87
0.87
0.87
0.87
0.87
0.87
0.87
0.87

0.74
0.74
0.74
0.74
0.74
0.74
0.75
0.75
0.755
0.755
0.755
0.755
0.755
0.755
0.755
0.755
0.755
0.755
0.77
0.77
0.77
0.77
0.77
0.77
0.78
0.78
0.78
0.78
0.78
0.78
0.78
0.78
0.78

0.20
0.20
0.20
0.20
0.20
0.20
0.18
0.18
0.18
0.18
0.18
0.18
0.18
0.18
0.18
0.18
0.18
0.18
0.18
0.16
0.16
0.16
0.16
0.15
0.15
0.15
0.15
0.15
0.15
0.15
0.16
0.16
0.16

3. RATING OF ELECTRICAL ROTATING MACHINES


The rating of a rotating machine implies the service conditions and loading conditions at which the
machine can operate indefinitely. In general, the rating of a machine is also associated with
warranties by the manufacturer for a certain period of time, although such warranties should be
always obtained in written form. Rotating machines are rated in terms of output capabilities, as are
most other types of rotating machines. The principal parameters used in rating a machine are listed
on the nameplate of the machine. These generally include:
1) Output (Kilovolt-amperes in a generator; horsepower in a motor).
2) Terminal voltage, line to line.
3) Frequency (in case of a.c.).
4) Speed.
5) Current.
6) Power factor (in case of a.c.).
7) Temperature rise at rated kilovolt-ampere (or horsepower) output.
8) Service conditions.
The rating of a machine on its nameplate is its continuous, or indefinite, rating. For short periods of
time, most rotating electric machines can operate at load conditions far exceeding these
continuous, or steady-state, ratings. Ratings for shorter time periods, such as 1 h down to 1 min.

67