305 B 00/09 B
Date: September 2000
Supersedes: none
McQuay International introduces their newest air cooled chillers ALZ HA equipped with scroll compressors and
electronic control system. McQuay have once again succeded in developing a high quality product with
extraordinary performance which is able to satisfy HVAC applications.
McQuay units are completely factory assembled, piped, wired and charged with refrigerant and shipped ready for
the installation.
Each unit consists of scroll compressors, condenser coils with independent subcooler circuits, multiple propeller
type direct drive condenser fans with independent fan motors, heavy-gauge weatherproof casing and weatherproof
electrical control centre containing all necessary and operating controls and motor starting equipment.
ALZ / ALP HA units are high thermodynamic engineering products, studied with high accuracy in balancing
compressors, condensers and evaporators in order to offer high performances and wide safety margins. The
choose of the materials and the equipments adopted for the products has been made without any compromises,
taking care of quality and long life purposes. The products meet ISO 9001 requirements, an assurance, beyond
any doubts, of the high producing standards followed by McQuay.
Code requirements
All units are designed and manufactured in accordance with applicable selections of the following which are
equivalent to American Air-conditioning industry applicable codes:
Rating of chillers: UNI 9018.
Construction of pressure vessel: TUV Standards (optional).
Electrical codes: IEC 204-1 CEI 44-5 Elect. & Safety Codes.
Safety Codes: CEI-EN 602041 Codes.
Manufacturing Quality Stds: ISO 9001.
Refrigerant
As the HCFC phase out will occur more quickly than currently legislated, the designers, owners and operators
should only evaluate equipment using chlorine free refrigerants. ALZ / ALP HA units are supplied with ecological
refrigerant HFC 407C. Studied and used by McQuay for several years, it offers the same garancies of
performance, costs and reliability of refrigerant HCFC 22.
Factory testing
Each unit is pressure tested, vacuum tested, evacuated and charged with refrigerant requested. It is then tested at
the factorys test bench under the design conditions specified by the customer. Upon request, a second series of
tests can be carried out witnessed by the customer. Before shipment, each unit is re-checked for pressure and
refrigerant charge control.
General characteristics
Cabinet and structure
The cabinet is made of galvanized steel sheet and painted to provide a high resistance to corrosion. The unit base
frame has holes to lift the unit with ropes for an easy installation. The weight is uniformly distributed along the
profiles of the base and this facilitates the arrangement of the units bases and the support structures. The
electrical and control equipment is located inside a panel which can be accessed by key locked doors complete
with door interlocking on the power cabinet.
The unit cabinet can be sound insulated (as an option) in order to reduce the noise of the compressors.
Scroll compressors
The scroll compressors achieve a high volumetric efficiency, due to constant contact with the sides of the scroll
spirals and the total absence of discharge and suction valves. This compressor is not only extremely reliable
thanks to the reduced number of moving parts, but has an exceptionally low noise level because of the absence of
suction and discharge valves and hence of the reduced pulsations of the discharge gas. The reduction in moving
parts means a very low level of vibration. Each compressor is equipped with a check valve on the discharge to
mantain the pump-down condition and hence avoid the migration of the refrigerating gas from the condenser to the
evaporator.
Condenser coils
ALZ HA condenser coils are constructed with internally enhanced seamless copper tubes arranged in a staggered
row pattern and mechanically expanded into McQuay lanced and rippled aluminium condenser fins with full fin
collars.
The multifunctional microprocessor control device has contacts for remote on/off control and remote signal of
general failure.
On request, remote programming radio-control and remote PC board are available as option.
Refrigerant circuit
The ALZ HA units are equipped with a complete refrigerant charge. The ALP HA units are equipped only by a
holding charge to keep the circuit in pression and to avoid moisture infiltration.
The ALZ HA circuits consist of insulated copper pipes on the suction line and is complete with suction shut-off
valves, filter driers, moisture indicators, liquid sight glass, thermostatic expansion valves and drain valves.
ALP HA motocondensing units are not equipped by liquid and suction lines. Customer will have to provide:
antivibration isolators, filter driers, solenoid valves, moisture indicators, thermostatic expansion valves.
NOTE: one and two pumps options always include inertial tank.
Microprocessor program remote infrared-control Infrared-control to remote program data.
Wooden box packing - Self-supporting wooden box internally insulated and suitable for shipment by sea.
Open Cage packing - Protection with polythene and wooden cage for transport and protection before the
installation.
Rubber type antivibration mounts - Supplied separately, these will be positioned under the base of the unit
during installation. Ideal to reduce the vibrations when the unit is floor mounted.
Spring type antivibration mounts - Supplied separately, these will be positioned under the base of the unit
during installation. Ideal for dampening vibrations for installation on roofs and metallic structures.
Low noise version For this version internal side of the steel cabinet is covered by soundproof material to allow
compressor sound insulation.
Entering evaporator
water temperature
Min (C)
Max (C)
8
8
8
8
8
8
8
8
20
20
20
20
20
20
15
15
4
4
4
4
4
4
4
4
Evaporator water t
Ambient temperature
Min (C)
Max (C)
Min (C)
4
4
4
4
4
4
4
4
8
8
8
8
8
8
8
8
10
10
10
10
10
10
10
10
15
15
14
12
15
13
12
10
Max (C)
50
49
49
48
50
48
47
47
0
1013
1,000
300
977
0,991
600
942
0,981
900
908
0,972
1200
875
0,962
1500
843
0,953
1800
812
0,943
-3
10
0,986
1,023
1,061
-8
20
0,980
1,054
1,114
-15
30
0,973
1,092
1,190
-23
40
0,966
1,140
1,244
-35
50
0,960
1,200
1,310
2
0,942
0,950
10
40
0
0.783
0,934
20
40
-2
0,725
0,918
20
38
-6
0,615
0,870
30
34
-8
0,562
0,845
30
32
Cooling capacity
correction factor
0,044
0,132
0,308
1,000
0,986
0,939
(1)
Q=
Pxp
25
where:
Q = minimum content of the plant expressed in litres.
P = cooling capacity of the plant expressed in W
p = minimum unloading capacity percentage
For a more accurate determination of the quantity of water, it is advisable to contact the designer of the plant.
When the sum of the water content of the evaporator, the pipes of the hydraulic circuit and the terminals (coils,
exchangers, etc.) is lower than the value obtained, it would be better to opt for a ALZ/ALP HA McQuay cooling unit
equipped with inertial tank (optional).
Installation notes
Handling
All moving and handling may damage the unit if some conditions are not scrupulously observed. The units should
be lifted with a crane using long ropes anchored to the holes on the frame of the units base and by using the
upper spacer bars to prevent the ropes from damaging the condenser coils.
Location
The ALZ/ALP HA units are produced for outside installation on roofs, floors or below ground level on condition that
the area is free from obstacles for the passage of the condensation air. The unit should be positioned on solid
foundations and perfectly level; in the case of installation on roofs or floors, it may be advisable to arrange the use
of suitable weight distribution beams. When the units are installed on the ground, a concrete base at least 250 mm
wider and longer than the units footprint should be laid. Furthermore, this base should be sufficiently robust to
withstand the unit weight mentioned in the technical data table. When the units are positioned in areas which are
easily accessible by persons or animals, it is advisable to fit guards (option) to protect the condenser and the
compressors.
Space requirements
The ALZ/ALP HA units are air-cooled, hence it is important to observe the minimum distances which guarantee the
best ventilation of the condenser coils. Limitations of space reducing the air flow could cause significant reductions
in cooling capacity, and increase in electricity consumption. The fans do not allow the use of ducts which have
high flow resistance, hence is should be ensured that the output air cannot recycle itself inside the condenser
coils. The units should be positioned such that there is sufficient distance between the coils and any obstacles to
improve ventilation and also to facilitate inspection (fig.1).
When two or more units are positioned side by side it is recommended that the condenser coils are at least 2500
mm distance from one another (fig. 2). Smaller distances could cause the recirculation of hot air. If the units are
positioned in places surrounded by walls or obstacles of the same height as the units, the units should be at least
2000 mm from said obstacles (fig. 3). In the event the obstacles are higher than the units, the units should be at
least 2500 mm from the obstacle (fig. 4). For other installation solutions, consult McQuay technicians.
Acoustic protection
The low noise levels of the ALZ/ALP HA units means that they meet most of the most restrictive regulations. When
the noise level must meet special requirements it will be necessary to pay the maximum attention to ensure the
perfect insulation of the unit from the support base by applying appropriate vibration-dampening devices, applying
vibration-dampening mounts on the water pipes and on the electrical connections (by the customer).
Nomenclature
ALZ HA 025 . 2 407
ALZ
ALP
011033
Unit size
1
2
N of tandem scroll
407
011.1
013.1
017.1
020.1
38,5
17,2
46,6
57,7
12,5
11,0
14
43,8
20,8
54,5
68,1
15,1
12,8
18
54,3
26,3
65,6
83,5
20,0
15,7
15
65,2
31,8
82,4
104,1
24,1
17,1
20
1 Tandem / 1
6,5
2
5,5
1 Tandem / 1
6,5
2
6
1 Tandem / 1
10,4
2
7
1 Tandem / 1
13,2
2
8,5
2,6
30
2,9
30
3,6
30
4,4
30
2 / 630
1,9 / 1360
2 / 630
1,9 / 1360
2 / 630
1,9 / 1360
2 / 630
1,9 / 1360
2780
1200
1400
400
662
2780
1200
1400
520
676
2780
1200
1400
530
740
2780
1200
1400
560
804
022.2
025.2
029.2
033.2
76,1
35,2
91,6
115,7
26,9
21,4
18
85,9
42,9
106,5
135,2
32,1
24,4
20
98,8
47,9
125,1
157,2
36,5
28,1
19
105,9
54,9
134,9
171,5
41,7
30,0
24
2 Tandem / 2
6,5+6,5
2
11
2 Tandem / 2
6,5+6,5
2
13
2 Tandem / 2
6,5+10,4
2
16
2 Tandem / 2
10,4+10,4
2
18
5,2
30
5,8
30
6,8
30
7,6
30
3 / 630
1,9 / 1360
3 / 630
1,9 / 1360
3 / 630
1,9 / 1360
3 / 630
1,9 / 1360
3530
1200
1400
630
834
3530
1200
1400
750
958
3530
1200
1400
760
992
3530
1200
1400
940
1040
(1) Nominal cooling capacity and power input are based on: 12/7 C entering/leaving evaporator water temperature;
46C ambient temperature;
(2) Nominal cooling capacity, power input and heating capacity are based on: 12/7 C entering/leaving evaporator
water temperature; 45C leaving HR water temperature.
(3) Desuperheaters heating capacity and pressure drops are based on: 12/7C entering/leaving evaporator water
temperature; 40/45C entering/leaving desuperheater water temperature; 46C ambient temperature.
Electrical data
ALZ / ALP HA Unit size
Standard voltage (1)
Max tandem 1 absorbed current
Max tandem 1 absorbed current
Max total compressors abs. current
Max fans absorbed current
Max unit absorbed current
Max inrush current (2)
A
A
A
A
A
A
011.1
013.1
029.2
033.2
37,0
37,0
6,8
43,8
134,5
42,4
42,4
6,8
49,2
148,2
52,0
52,0
6,8
58,8
185,0
52,0
42,4
94,4
10,2
104,6
227,4
52,0
52,0
104,0
10,2
114,2
237,0
64,0
64,0
6,8
70,8
224,0
37,0
37,0
74,0
10,2
84,2
171,5
42,4
42,4
84,8
10,2
95,0
190,6
63 Hz
75,0
75,0
75,0
75,0
77,0
77,0
77,0
77,0
Sound pressure level at 1 m from the unit in free field ( rif. 2 x 10-5 )
125 Hz
250 Hz
500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
75,0
75,0
75,0
75,0
76,5
76,5
76,5
76,5
72,0
72,0
72,0
72,0
73,5
73,5
73,5
73,5
71,5
71,5
71,5
71,5
73,0
73,0
73,0
73,0
71,0
71,0
71,0
71,0
72,5
72,5
72,5
72,5
65,5
65,5
65,5
65,5
67,0
67,0
67,0
67,0
58,0
58,0
58,0
58,0
59,5
59,5
59,5
59,5
50,5
50,5
50,5
50,5
52,0
52,0
52,0
52,0
dBA
74,5
74,5
74,5
74,5
76,0
76,0
76,0
76,0
Note: Average sound pressure level rated in accordance to ISO 3744, free field conditions.
63 Hz
72,5
72,5
72,5
72,5
74,5
74,5
74,5
74,5
Sound pressure level at 1 m from the unit in free field ( rif. 2 x 10-5 )
125 Hz
250 Hz
500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
72,5
72,5
72,5
72,5
74,0
74,0
74,0
74,0
69,5
69,5
69,5
69,5
71,0
71,0
71,0
71,0
69,0
69,0
69,0
69,0
70,5
70,5
70,5
70,5
68,5
68,5
68,5
68,5
70,0
70,0
70,0
70,0
63,0
63,0
63,0
63,0
64,5
64,5
64,5
64,5
55,5
55,5
55,5
55,5
57,0
57,0
57,0
57,0
48,0
48,0
48,0
48,0
49,5
49,5
49,5
49,5
dBA
72,0
72,0
72,0
72,0
73,5
73,5
73,5
73,5
Note: Average sound pressure level rated in accordance to ISO 3744, free field conditions.
1
0
5
-9
10
-14,1
15
-17,3
20
-19,7
25
-21,5
5
-8,7
10
-13,8
15
-16,9
20
-19,3
25
-21,1
1
0
ALZ HA
unit
size
HFC
407C
011.1
013.1
017.1
020.1
022.2
025.2
029.2
033.2
Evaporator
leaving
temp. (C)
4
5
6
7
8
9
10
4
5
6
7
8
9
10
4
5
6
7
8
9
10
4
5
6
7
8
9
10
4
5
6
7
8
9
10
4
5
6
7
8
9
10
4
5
6
7
8
9
10
4
5
6
7
8
9
10
AMBIENT TEMPERATURE - C
30
35
40
43
46
Cooling
capacity
(kW)
Power
input
(kW)
Cooling
capacity
(kW)
Power
input
(kW)
Cooling
capacity
(kW)
Power
input
(kW)
Cooling
capacity
(kW)
Power
input
(kW)
Cooling
capacity
(kW)
Power
input
(kW)
41,7
43,0
44,3
45,7
47,0
48,4
49,8
47,8
49,2
50,7
52,2
53,8
55,1
56,9
59,6
61,3
63,1
65,0
66,9
68,8
70,7
71,2
73,3
75,5
77,7
80,0
82,1
84,4
83,0
85,5
88,1
90,8
93,5
96,1
98,9
94,2
96,9
99,8
102,7
105,7
108,7
111,6
108,0
111,3
114,7
118,1
121,6
125,1
128,6
116,8
120,3
123,8
127,3
130,9
134,7
138,4
12,1
12,2
12,3
12,5
12,6
12,5
12,6
14,6
14,7
14,9
15,0
15,1
15,2
15,3
18,6
18,7
18,9
19,1
19,1
19,3
19,6
22,7
23,0
23,2
23,4
23,6
23,8
23,9
25,1
25,3
25,5
25,7
25,9
26,0
26,2
30,2
30,5
30,7
31,0
31,3
31,5
31,8
34,2
34,5
34,8
35,0
35,3
35,6
35,8
39,1
39,3
39,7
40,1
40,4
40,8
41,2
40,2
41,5
42,8
44,1
45,4
46,7
48,1
46,0
47,4
48,8
50,3
51,8
53,2
54,8
57,3
59,0
60,8
62,6
64,4
66,3
68,1
68,5
70,6
72,7
74,8
77,0
79,1
81,3
79,9
82,4
84,9
87,5
90,1
92,7
95,4
90,5
93,2
96,0
98,8
101,7
104,6
107,5
103,8
107,0
110,3
113,6
116,9
120,3
123,7
112,1
115,5
118,9
122,3
125,8
129,4
133,0
13,2
13,3
13,4
13,5
13,6
13,6
13,7
15,9
16,0
16,2
16,3
16,4
16,5
16,6
20,2
20,3
20,5
20,7
20,8
21,0
21,2
24,6
24,9
25,1
25,3
25,5
25,7
25,9
27,2
27,4
27,6
27,8
28,0
28,2
28,4
32,9
33,2
33,4
33,7
34,0
34,2
34,5
37,1
37,4
37,7
38,0
38,3
38,6
38,9
42,4
42,7
43,1
43,5
43,9
44,3
44,7
38,0
39,2
40,5
41,7
43,0
44,2
45,5
43,3
44,7
46,0
47,4
48,8
50,3
51,7
53,9
55,6
57,3
59,0
60,7
62,5
64,2
64,5
66,5
68,5
70,5
72,5
74,6
76,7
75,3
77,7
80,1
82,6
85,0
87,6
90,1
85,0
87,7
90,3
93,0
95,7
98,5
101,3
97,5
100,6
103,7
106,8
109,9
113,1
116,4
105,1
108,3
111,5
114,8
118,1
121,5
124,9
14,8
14,9
15,0
15,0
15,1
15,2
15,3
17,9
18,0
18,1
18,2
18,3
18,5
18,6
22,6
22,7
22,9
23,1
23,3
23,5
23,6
27,5
27,7
27,9
28,2
28,4
28,6
28,9
30,4
30,6
30,8
31,0
31,2
31,5
31,7
36,9
37,2
37,5
37,7
38,0
38,3
38,6
41,5
41,8
42,1
42,5
42,8
43,1
43,5
47,4
47,8
48,2
48,6
49,1
49,5
49,9
36,6
37,8
38,9
40,1
41,4
42,6
43,9
41,6
42,9
44,2
45,5
46,9
48,3
49,7
51,7
53,3
55,0
56,6
58,3
60,0
61,7
61,9
63,8
65,7
67,7
69,6
71,7
73,7
72,4
74,6
77,0
79,4
81,8
84,2
86,7
81,5
84,1
86,6
89,2
91,9
94,5
97,2
93,4
96,3
99,3
102,4
105,4
108,5
111,6
100,5
103,6
106,7
109,9
113,1
116,3
119,6
15,8
15,9
16,0
16,1
16,2
16,3
16,4
19,2
19,3
19,4
19,5
19,6
19,8
19,9
24,2
24,4
24,5
24,7
24,9
25,1
25,3
29,4
29,6
29,8
30,1
30,3
30,6
30,9
32,6
32,8
33,0
33,2
33,4
33,7
33,9
39,6
39,9
40,2
40,5
40,7
41,0
41,3
44,5
44,8
45,2
45,5
45,9
46,2
46,6
50,8
51,2
51,6
52,1
52,5
53,0
53,4
35,1
36,3
37,4
38,5
39,7
40,9
42,2
39,9
41,2
42,5
43,8
45,2
46,5
47,8
49,6
51,1
52,7
54,3
56,0
57,6
59,3
59,5
61,4
63,3
65,2
67,1
69,1
71,0
69,3
71,5
73,8
76,1
78,4
80,8
83,2
78,4
80,9
83,4
85,9
88,5
91,1
93,6
90,1
92,9
95,8
98,8
101,8
104,7
107,7
96,8
99,7
102,8
105,9
109,0
112,2
115,3
16,9
17,0
17,1
17,2
17,3
17,4
17,5
20,4
20,6
20,7
20,8
20,9
21,1
21,2
25,8
26,0
26,1
26,3
26,5
26,7
26,9
31,0
31,3
31,5
31,8
32,0
32,3
32,6
34,8
35,0
35,2
35,5
35,7
35,9
36,1
42,0
42,3
42,6
42,9
43,1
43,4
43,7
46,9
47,2
47,6
47,9
48,3
48,6
49,0
53,5
53,9
54,4
54,9
55,3
55,8
56,3
Notes: (1) Rating based on: evaporator fouling factor of 0,044 m C/ kW, evaporator temperature drop of 5C and sea level altitude.
(2) Interpolation is allowed, extrapolation is not permitted. Please contact McQuay for performance outside the standard ratings.
(3) The power input values are referred to compressor only.
(4) To know the units functioning maximum air ambient temperature consult the operating limits table.
ALZ HA
unit
size
HFC
407C
011.1
013.1
017.1
020.1
022.2
025.2
029.2
033.2
Evaporator
leaving
temp. (C)
4
5
6
7
8
9
10
4
5
6
7
8
9
10
4
5
6
7
8
9
10
4
5
6
7
8
9
10
4
5
6
7
8
9
10
4
5
6
7
8
9
10
4
5
6
7
8
9
10
4
5
6
7
8
9
10
45
50
Cooling
capacity
(kW)
Power
input
(kW)
Heating
capacity
(kW)
Cooling
capacity
(kW)
Power
input
(kW)
Heating
capacity
(kW)
Cooling
capacity
(kW)
Power
input
(kW)
Heating
capacity
(kW)
46,8
48,2
49,8
52,4
54,2
56,5
58,3
54,5
56,2
57,4
59,1
60,8
64,4
66,0
65,2
67,3
69,5
71,3
73,3
75,7
77,6
77,7
80,2
82,5
85,0
87,4
89,8
92,3
90,1
93,0
95,6
96,0
98,6
99,0
101,6
100,2
103,4
106,4
109,5
113,8
115,9
117,2
121,6
125,4
126,1
129,4
129,9
133,6
147,5
131,6
135,4
136,0
139,9
146,5
154,6
159,0
12,3
12,3
12,3
12,2
12,3
12,3
12,2
14,6
14,6
14,5
14,6
14,6
14,6
14,6
18,4
18,4
18,5
18,6
18,8
19,0
19,0
22,2
22,3
22,3
22,6
22,5
22,6
22,6
25,0
25,2
25,4
25,5
25,7
25,7
25,8
32,2
32,2
32,5
32,4
32,5
32,6
32,5
34,6
34,7
35,1
35,4
36,0
36,3
36,7
39,5
39,8
40,1
40,7
41,0
41,6
42,0
57,7
59,2
60,6
63,1
64,9
67,2
68,5
67,2
69,0
70,4
72,1
73,3
76,9
78,7
81,5
83,7
85,7
87,6
89,8
92,2
96,3
97,5
100,0
102,5
105,1
106,7
109,4
112,1
112,3
115,2
117,9
118,7
120,9
121,9
124,1
129,1
132,3
135,4
138,6
142,3
145,2
145,9
152,3
156,2
158,8
160,3
162,5
164,4
178,6
166,8
170,9
173,8
175,3
184,3
190,0
194,5
44,0
45,3
46,3
46,6
47,7
48,9
52,4
49,9
51,5
53,0
54,5
56,2
59,0
60,5
60,0
62,0
63,7
65,6
68,7
70,9
72,7
76,1
78,5
80,7
82,4
84,8
87,1
89,5
83,8
86,4
88,8
91,6
96,4
95,1
97,6
96,2
100,5
103,4
106,5
108,1
110,1
111,3
113,3
116,7
120,4
125,1
126,0
129,6
137,4
122,5
126,1
129,9
134,9
138,8
144,1
148,2
12,3
12,4
12,6
12,5
12,6
12,8
12,8
14,8
14,9
15,1
15,1
15,1
15,3
15,3
19,6
19,7
19,8
20,0
20,2
20,3
20,3
23,5
23,7
23,8
24,1
24,0
24,2
24,2
26,4
26,6
26,8
26,9
27,1
27,4
27,6
31,6
31,9
32,1
32,1
32,3
32,2
32,5
36,0
36,2
36,1
36,5
36,7
36,6
36,7
41,3
41,5
41,5
41,7
41,9
41,7
42,1
55,0
56,4
57,4
57,7
58,9
60,3
63,3
63,0
64,9
66,6
68,1
69,2
72,3
74,0
77,6
79,7
81,4
83,5
86,7
88,8
92,7
97,2
99,7
102,2
104,1
105,6
108,3
110,9
107,4
110,1
112,7
115,7
120,2
119,7
121,9
124,6
129,1
132,2
135,2
136,6
139,1
140,2
145,5
149,1
154,2
157,2
159,5
160,8
168,8
159,7
163,4
169,1
171,5
177,6
179,9
184,2
41,1
42,4
43,7
44,9
47,3
48,8
50,0
47,1
49,0
52,9
53,1
54,6
54,8
56,2
57,1
59,0
60,7
62,5
64,2
67,6
69,3
71,7
76,2
78,5
77,3
79,5
81,8
85,6
78,9
81,4
83,7
86,3
90,9
89,9
92,3
89,0
93,0
95,7
99,6
99,1
101,1
104,2
106,9
112,4
116,0
119,3
120,1
120,2
128,4
115,7
119,2
125,1
128,9
132,4
135,0
138,7
13,1
13,1
13,1
13,0
13,0
13,1
13,1
16,0
16,1
16,1
16,3
16,2
16,3
16,5
20,6
20,8
20,9
21,0
21,1
21,2
21,3
24,7
24,9
25,1
25,9
25,0
25,3
24,9
27,7
28,0
28,2
28,3
28,2
28,5
28,7
33,3
33,5
33,5
33,7
33,7
33,9
33,9
37,9
38,1
38,5
38,5
38,7
38,6
39,0
43,4
43,7
44,0
44,1
44,4
44,4
44,8
52,9
54,3
55,4
56,6
58,9
60,5
61,3
61,5
63,6
67,5
67,8
68,8
69,1
70,9
75,8
77,8
79,5
81,4
83,1
86,4
90,2
94,1
98,7
101,3
100,9
101,4
104,1
107,8
104,0
106,6
109,0
111,9
115,9
115,7
117,9
119,2
123,4
126,0
130,1
129,3
131,9
134,6
141,2
146,7
152,2
153,4
155,7
153,6
162,4
155,2
158,8
166,9
167,9
173,8
173,7
177,5
011.1
013.1
017.1
020.1
022.2
025.2
029.2
033.2
AMBIENT TEMPERATURE - C
35
40
43
Evaporation
temperature
C
Unit
Size
ALP
HA
HFC
407C
Cooling
capacity
(kW)
Power
input
(kW)
Cooling
capacity
(kW)
Power
input
(kW)
Cooling
capacity
(kW)
Power
input
(kW)
Cooling
capacity
(kW)
Power
input
(kW)
Cooling
capacity
(kW)
Power
input
(kW)
0
2
4
6
8
10
0
2
4
6
8
10
0
2
4
6
8
10
0
2
4
6
8
10
0
2
4
6
8
10
0
2
4
6
8
10
0
2
4
6
8
10
0
2
4
6
8
10
42,3
45,0
47,8
50,8
53,9
56,8
47,9
50,9
54,1
57,5
61,1
64,4
60,0
63,8
67,8
72,0
76,1
80,3
71,3
76,3
81,0
86,1
91,2
96,3
83,1
88,9
94,5
100,0
105,5
111,3
93,9
100,4
106,7
112,9
119,5
126,0
108,2
115,6
122,9
130,5
136,5
143,3
116,8
124,8
132,7
140,6
149,1
156,5
13,3
13,7
14,2
14,7
15,1
15,5
15,9
16,4
17,0
17,5
18,1
18,8
20,3
20,9
21,6
22,3
23,0
23,8
24,9
25,7
26,5
27,4
28,2
29,2
27,3
28,2
29,1
30,2
31,1
32,2
33,1
34,2
35,3
36,7
37,8
39,1
37,4
38,6
39,9
41,2
42,2
43,0
43,0
44,4
45,8
47,3
48,6
50,1
39,4
41,9
44,5
47,4
50,4
53,2
44,7
47,6
50,5
53,7
57,1
60,4
55,9
59,4
63,1
67,2
71,2
75,2
66,4
71,0
75,4
80,4
85,2
90,3
77,4
82,8
88,0
93,3
98,7
104,1
87,4
93,4
99,3
105,4
111,7
118,0
100,7
107,7
114,4
121,8
129,0
136,7
108,7
116,2
123,5
131,2
138,9
146,9
13,7
14,2
14,6
15,2
15,6
16,1
16,5
17,0
17,6
18,2
18,8
19,5
20,9
21,6
22,3
23,1
23,9
24,7
25,7
26,5
27,4
28,3
29,3
30,3
28,5
29,4
30,4
31,5
32,7
33,8
34,6
35,7
36,9
38,4
39,6
41,0
39,2
40,4
41,8
43,2
43,9
44,6
44,9
46,4
47,9
49,5
50,4
51,3
37,6
39,9
42,4
45,3
48,4
51,1
42,9
45,6
48,5
51,5
54,8
58,0
53,2
56,5
60,1
64,2
68,2
72,4
63,2
67,6
71,8
76,8
81,7
86,8
72,9
78,0
82,9
88,0
92,9
98,1
82,3
88,0
93,6
99,3
105,2
111,1
94,9
101,5
107,9
114,8
121,2
127,3
102,5
109,6
116,5
123,7
131,5
136,3
14,1
14,5
15,0
15,6
16,0
16,5
16,9
17,5
18,0
18,6
19,2
20,0
21,5
22,2
22,9
23,7
24,5
25,3
26,4
27,2
28,1
29,1
30,0
31,1
29,2
30,2
31,2
32,3
33,5
34,6
35,5
36,6
37,8
39,4
40,6
42,0
40,2
41,5
42,8
44,2
45,0
45,7
46,1
47,6
49,1
50,8
51,7
52,6
36,3
38,6
41,0
43,9
47,2
49,9
41,7
44,4
47,2
50,1
53,3
56,5
51,4
54,7
58,1
62,3
66,4
70,7
61,1
65,3
69,4
74,4
79,5
84,7
69,7
74,5
79,2
84,2
88,7
93,8
78,8
84,2
89,5
95,0
100,6
106,1
90,8
97,1
103,2
109,8
115,5
120,3
98,1
104,9
111,5
118,4
126,3
128,3
14,4
14,9
15,4
16,0
16,4
16,9
17,3
17,9
18,5
19,1
19,7
20,5
22,0
22,7
23,5
24,3
25,2
25,9
27,0
27,9
28,8
29,8
30,8
31,9
30,0
30,9
32,0
33,1
34,3
35,5
36,4
37,6
38,8
40,4
41,6
43,1
41,2
42,5
43,9
45,4
46,1
46,9
47,2
48,8
50,4
52,0
53,0
53,9
35,1
37,3
39,7
42,5
46,0
48,7
43,0
45,7
48,6
50,2
51,9
55,0
49,7
52,8
56,2
60,4
64,6
69,0
59,0
63,1
67,1
72,2
77,4
82,6
66,7
71,3
75,7
80,6
84,6
89,7
75,4
80,6
85,6
90,8
96,1
101,4
86,9
92,9
98,7
105,1
110,2
113,8
93,9
100,4
106,7
113,3
121,4
120,9
14,8
15,3
15,8
16,4
16,8
17,3
17,8
18,4
19,0
19,6
20,2
21,0
22,6
23,3
24,1
24,9
25,8
26,6
27,7
28,6
29,5
30,6
31,6
32,7
30,7
31,7
32,8
34,0
35,2
36,4
37,3
38,5
39,8
41,4
42,7
44,2
42,2
43,6
45,0
46,5
47,3
48,1
48,4
50,0
51,7
53,4
54,4
55,2
30
46
013.1
Flow rate
Pressure
(l/s)
drop (kPa)
017.1
Flow rate
Pressure
(l/s)
drop (kPa)
020.1
Flow rate
Pressure
(l/s)
drop (kPa)
1,02
10
1,18
10
1,44
10
1,71
10
1,31
1,72
15
28
1,45
1,75
15
21
1,61
2,03
14
20
2,02
2,42
14
20
2,02
2,51
2,94
36
52
74
2,12
2,71
3,20
30
47
72
2,51
3,23
4,00
31
50
78
3,10
3,83
4,50
34
49
70
3,24
100
3,74
100
4,56
100
5,42
100
10
15
2
32
54
78
100
025.2
Flow rate
Pressure
(l/s)
drop (kPa)
2,38
2,81
3,23
4,11
5,12
6,42
7,51
10
14
18
30
45
72
100
029.2
Flow rate
Pressure
(l/s)
drop (kPa)
2,94
3,42
4,13
5,09
6,23
7,65
9,28
10
14
19
29
44
68
100
033.2
Flow rate
Pressure
(l/s)
drop (kPa)
2,94
3,41
4,12
5,02
6,21
7,62
9,28
10
14
19
29
44
68
100
200
190
180
170
160
150
140
130
120
110
100
0,50
1,00
1,50
2,00
2,50
3,00
3,50
4,00
4,50
190
180
170
160
150
140
130
120
110
100
90
80
70
60
3,00
4,00
5,00
6,00
7,00
8,00
9,00
N.B. In order to get the net hydraulic lift, subtract the evaporator pressure drop from diagram value.
When you order the unit with the water pump and tank, you must specify the selected type: A or B.
10,00
Fans Arrangement
We reserve the right to make changes in design and construction at any time without notice, thus the cover picture is not binding.