Beruflich Dokumente
Kultur Dokumente
Configuration questions:
Enter METRIC or US to set the default units of measure. METRIC or US
If nothing is entered then US units are the default.
Please enter a sub-title to print on sizing sheets; ie. Natural Gas Systems Inc.
Please enter the initials of the default applications engineer 5 characters max.
Settings
The following files can be customized by the program user:
__SETTINGS.TXT
__By.TXT
__CAL FACILITY.TXT
__CAL FLUID.TXT
__NDT DYEPEN.TXT
__NDT HYDRO.TXT
__NDT XRAY.TXT
www.mccrometer.com/sizings
USA 1-909-652-6811
Page 1 of 8
Lit #24508-51 Rev. 1.4/11-01
File System
New
Open
Save
E-mail Print
Warnings
1. There are seven warning boxes:
Low Y Factor
The Y factor is less than 0.96, however the application may be acceptable
Low Dp
The minimum Dp is <= 0.1 inWC.
Low Re
The minimum Re is <= 8000, however the application may be acceptable.
Cavitation
Cavitation (flashing) may be present. Possible fix is to decrease the fs Dp.
High Dp The Dp fullscale is too high.
Gas at P,T
The fluid may be in a gas state at the pressure and temperature given. (check Pv)
Liquid at P,T
The fluid may be in a liquid state at the pressure and temperature given. (check Pv)
2. There are borders that appear around the density, viscosity, compressibility and isentropic exponent
field labels when a value is required.
Page 2 of 8
Lit #24508-51 Rev. 1.4/11-01
Calculation
1. After the last field is populated with data, select another field to execute the calculation.
If the sizing program does not solve for the target value please see the troubleshooting section.
2. The sizing can be solved for one of the following:
2a. fullscale flowrate (Q)
2b. fullscale differential pressure (Dp)
2c. meter inside diameter (ID)
2d. beta ratio (Beta)
*The solution for inside diameter is only intended to narrow the possible pipe sizes. Standard inside
diameters are solved for. Once the inside diameter is populated the user should change the solve method
to Dp or Q and then change the inside diameter to meet the application requirements. To change the
solve method click one of the radio buttons located left of 2a, 2b, 2c, and 2d.
Troubleshooting
If the sizing program does not solve for the target value:
(a) The density can not be calculated or was not entered.
(b) The flowrate entered causes the DP calculation to be so high that the DP calculation fails.
Try lowering the flowrate or increasing the line size.
(c) The flowrate unit of measure is inappropriate for the application.
(d) The density calculation may fail due to the entered operating temperature.
(e) Gas application.: Normal and Standard gas flows require values for Pb, Tb, and Zb.
(f) Gas application.: The isentropic exponent doesn't have a value and therefore the Y factor is zero.
Page 3 of 8
Lit #24508-51 Rev. 1.4/11-01
Tables
Range Beta vs. Dp (0.05 increments)
This table shows a range of beta ratios from 0.45 to 0.85 in 0.05 increments.
The user can click a row in the table to set the sizing beta ratio and Dp relationship.
Range Beta vs. Dp (0.01 increments)
This table shows a range of beta ratios from 0.45 to 0.85 in 0.01 increments.
The user can click a row in the table to set the sizing beta ratio and Dp relationship.
Turndown Table
The maximum flowrate divided by the minimum flowrate is the turndown.
Example: 1000 SCFM / 100 SCFM = 10:1 turndown
All three tables above require that all of the necessary data is present.
Sending Files
Receiving party has the sizing program:
1. E-Mail the file from the program.
Receiving party does not have the sizing program:
1. Copy the data to the clipboard and paste the text into a new notepad file. Email the file.
After the person receives the file it can be double clicked and should open in Notepad on their system.
2. Copy the data to the clipboard and paste the text directly into an email.
If this is done you should change the font to Courier New which is fixed size font.
3. Print and fax the sizing report.
4. Print the sizing directly to your fax server.
5. Print the sizing directly to Adobe Acrobat 3.0 writer and then email.
For more information on this method go to www.adobe.com/acrobat.
Special Models
If you require a special model please use the following syntax:
{series}{size}-xx ie. VS10-XX, VW04-XX
With any special model be specific regarding material grades and coatings.
Screen Colors
The color settings can be changed by the user.
Definitions:
FG - Foreground
BG Background
FG: units of measure
FG: labels which can be clicked
FG: labels for calculated only fields
FG: labels for general fields
FG: text boxes entered
FG: text boxes estimated
BG: text boxes estimated
Save Changes
Page 4 of 8
Lit #24508-51 Rev. 1.4/11-01
Fluid State
GAS or LIQUID
Fluid list selections: The fluid state is set by the program.
User entered fluid: The fluid state can be changed by clicking the fluid state label.
If the fluid state is GAS it will toggle to LIQUID and visa versa.
Fluid Selections
Fluid Selection
WATER
WATER BOILER FEED
STEAM
NATURAL GAS 17.4mw
NATURAL GA S 23.3mw
NATURAL GAS 19.7mw
AIR
NITROGEN
OXYGEN
CARBON DIOXIDE
METHANE
DIGESTER GAS 25.8mw
DIGESTER GAS 30.0mw
OVEN 11.294mw
GAS
HYDROGEN
PROPANE
CHLORINE
AMMONIA
ETHYLENE
OZONE
HELIUM
ARGON
HYDROGEN CHLORIDE GAS
CARBON MONOXIDE
SULFUR DIOXIDE
Fluid State
LIQUID
LIQUID
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
LIQUID OXYGEN
LIQUID PROPANE
KEROSENE 60F 0.8sg
NAPTHALENE
METHANOL
PROPYLENE
BENZENE
LIQUID
LIQUID
LIQUID *User must only use this selection at 60 F
LIQUID
LIQUID
LIQUID
LIQUID
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS
Page 5 of 8
Lit #24508-51 Rev. 1.4/11-01
Typical Sizing Process
1. Start a new record.
2. Select the desired units of measure.
3. Select a fluid from the fluid list.
Examples:
a. STEAM
b. NATURAL GAS 17.4 mW
c. TANK FEED WATER
d. TANK SUPPLY LINE (WATER)
In example c the properties of water are used even though there is a special name.
In example d the properties of water are used and the word WATER is not printed on reports.
4. Select a model number.
For standard meter tubes the meter inside diameter is set automatically.
5. Select meter tube and cone material thermal coefficients.
The aPE values are used to calculate the Fa term.
Click the pipe and cone buttons in the dialog to set the values to entered on the main screen.
6. Select the desired operating range; turn down.
The maximum flowrate divided by the minimum flowrate is the turndown.
7. Enter the line pressure, line temperature, full-scale flowrate, and inside pipe diameter: P, T, Q, I.D.
8. Adjust the fullscale Dp and beta ratio relationship until satisfactory.
A beta ratio can be selected by clicking the appropriate row in either of these two tables.
The beta ratio and Dp can also be entered directly.
Page 6 of 8
Lit #24508-51 Rev. 1.4/11-01
Fluid
Serial #
Job Ref.
used as required
Model
Description
Note
Fluid State
End User
Industry
fluid name
GAS or LIQUID
end user
select from a McCrometer list of industries
description of model: If model is from the literature then the description is entered by the program.
misc. note
Cf
coefficient of flow
max. Flowrate
McCrometer Cal.
Pf
line pressure
Re
max. Reynolds
Tf
line temperature
max. Velocity
density (rho)
max. Dp
Hydro. Test
viscosity (mu)
min. Dp
X-Ray Exam.
specific gravity
Meter I.D.
gas compressibility
Cone O.D.
Beta Ratio
isentropic exponent
Turn Down
CP
Mw
molecular weight
Pb
Tb
Zb
barometric pressure
Pc
critical pressure
Tc
critical temperature
Fa
Pv
vapor pressure
HL
estimated headloss
10
Pbaro
aPE
Entered Value
inside diameter
cone outside diameter
Re
Non Destructive -
Mag. Part.
Tests
PMI
NDT
CMTR Copies
max./min flow
NDT
Application Eng.
material cert.
sized by
Velocity
Gas Exp.
Flowrate
u/m
u/m
u/m
Page 7 of 8
Lit #24508-51 Rev. 1.4/11-01
The V-Cone Sizing Program can not be installed, copied nor used without permission from the sales and
marketing staff of McCrometer Inc.
Page 8 of 8
Lit #24508-51 Rev. 1.4/11-01