The light output of a luminaire decreases with age and use, and the energy input
may increase over time. Eventually, the reduction will affect the appearance of the
space and the productivity and safety of the occupants. Proper lighting maintenance
is essential to high quality and efficient lighting.
Group Relamping
o To ensure lighting levels are maintained, all lamps are replaced:
just prior to the time in their rated life
when burnouts begin to occur
When lamps are greatly depreciated in light output.
o The following should be done to determine when to replace lamps
Record and evaluate the lighting level in all areas, especially
after all new lamps are in place.
Conduct periodic light output checks with a lux meter to monitor
change in light levels.
Cleaning
o Even in areas where air is well filtered, enough dirt accumulates on
lamps, lenses or louvers and reflectors to reduce light significantly.
o Tips for cleaning fixtures:
Clean lighting fixtures whenever lamps are replaced.
In areas where doors allow outside air or filtering is not
adequate, clean at least twice a year.
Wipe plastic lenses with damp, not dry cloth (a mild detergent
may be needed).
Small cell louver panels, including parabolic wedge louvers,
should be removed and dipped in mild detergent solution, then
air-dried.
Do not wipe luminaire or lamps while fixture is energized.
Spot Relamping
To avoid damage to ballasts, lamps are replaced when
o It ceases operation unexpectedly
o Failed to light up after turning it on
If a lamp requires 5-6 seconds to start, one electrode may not be receiving
the cathode heating current. This usually results in excessive darkening of
that end of the lamp, which is visible after a short period of operation.
Procedure
o With lamps removed from the sockets, check heater voltages with
available testers, which have a flashlight lamp Mounted on a
fluorescent lamp base
o If a voltmeter is used, a 10-, 10-W resistor should be inserted in
parallel with the meter. The meter should measure at least 3 V.
o If proper voltage is found, check for poor contact between lamp holder
and base pins or contacts on the lamp. Also check for proper spacing of
lamp holders.
If multiple-tapped ballasts are used, check to be sure that the tap matches
the supply voltage to which the ballast tap is connected by:
Replace the lamp with one known to be operative. Be sure the operative lamp
is room temperature, as hot lamps will not restart immediately.
Check that the lamp is properly seated and that its base eyelet and shell
make proper contact in the lampholder.
Check the ballast nameplate. Make sure that ballast and lamp designations
match. Refer to the system of lamp and ballast designations developed by
the lamp industry and American National Standards Institute (ANSI).
Check the ballast wiring. If a multiple-tapped primary-winding ballast is used,
be sure the connected tap matches the supply voltage.
Check the supply circuit wiring for open circuit or incorrect connections.
Replace the ballast if no output voltage can be obtained and make sure that
line voltage is properly connected to the ballast input terminals. If you must
replace the ballast, it would be better to retrofit the fixture to a more efficient
HPS or Metal Halide equivalent, by changing the ballast and lamp (plus ignitor
and capacitor, as required).
If lamps fail prematurely, check for the following:
o Cracks or breaks in the bulb will allow air to enter the lamp and cause
arc tube shell failure. This can be caused
by rough handling,
by contact with metal surfaces of a bulb changer tool or metal
parts of the luminaire,
by water droplets falling on an operating lamp.
o Overly blackened or swollen arc tubes may indicate excessive lamp
current and over-wattage operation. Also, the ballast may have failed
due to a component failure, Such as a shorted capacitor or core
winding.
If multiple-tapped ballasts are used, check to be sure that the tap matches
the supply voltage to which the ballast tap is connected.
o Connecting a given line voltage to a tap marked for a higher voltage
will give low light output due to under-wattage operation.
o Connecting it to a tap marked for a lower voltage will cause, poor lamp
lumen maintenance and short lamp and ballast life due to overwattage operation.
The line voltage should be reasonably free of voltage fluctuations. A variety
of ballast types are available that provide an appropriate percentage of lamp
wattage regulation with respect to the percentage of line voltage variation.
Lamp-and-ballast combinations must be chosen by following the system of
lamp and ballast designations developed by the lamp industry and ANSI so
that their electrical characteristics match. Incorrect matching of lamp and
ballast may result in short life and equipment damage.
Lamps should be handled carefully. Rough handling can cause scratches or
cracks in outer glass envelopes, resulting in short lamp life and possible
injury.
High-pressure sodium lamps have a vacuum in the space between the
ceramic arc tube and the outer envelope. Handle these lamps carefully, since
vacuum lamps are known to make an inordinately loud noise if the glass
should break when dropped.
In case the outer envelope breaks during lamp operation, ultraviolet emission
is not a problem.
Caution: To prevent electric shock, always turn off the power before removing
or installing lamps. Exposed metal parts of the internal lamp structure will be
live, and touching them will cause an electric shock.
Replace the lamp with one known to be operative. Be sure the operative lamp
is room temperature, as hot lamps will not restart immediately.
Check that the lamp is properly seated and that its base eyelet and shell
make proper contact in the lampholder.
Check the ballast nameplate. Make sure that ballast and lamp designations
match. Refer to the system of lamp and ballast designations developed by
the lamp industry and American National Standards Institute (ANSI).
Check the ballast wiring. If a multiple-tapped primary-winding ballast is used,
be sure the connected tap matches the supply voltage.
Check the supply circuit wiring for open circuit or incorrect connections.
Replace the ballast if no output voltage can be obtained and make sure that
line voltage is properly connected to the ballast input terminals. If you must
replace the ballast, it would be better to retrofit the fixture to a more efficient
HPS or Metal Halide equivalent, by changing the ballast and lamp (plus ignitor
and capacitor, as required).
A high-pressure sodium lamp must be started with an igniter. If both the old
and a known good lamp fail to start, Determine if the igniter or the ballast or
perhaps both are defective.
o First make certain that the proper line voltage is correctly connected to
the ballast input.
o Obtain a ballast tester (a flashlight lamp mounted on a fluorescent
lamp base) or voltmeter and follow the manufacturer's instructions to
determine the defect.
Caution: Do not connect a voltmeter or multimeter to an open or inoperative
high-pressure sodium socket. The high-voltage pulse from the igniter will
damage the meter
Cracks or breaks in the bulb will allow air to enter the lamp and cause arc
tube shell failure which can be caused by the following.
o rough handling
o contact with metal surfaces of a bulb changer tool or metal parts of the
luminaire
o water droplets falling on an operating lamp.
Overly blackened or swollen arc tubes may indicate excessive lamp Current
and over-wattage operation. Also, the ballast may have failed due to a
component failure, Such as a shorted capacitor or core winding.
Excessive discoloration of the arc tube or a metallic deposit on the inside
walls of the outer envelope may indicate over wattage operation. See items
3, 4 and 5 under Mercury Lamps. Also, ballast components may have failed;
for example, a capacitor or the core winding may be shorted.
If multiple-tapped ballasts are used, check to be sure the tap matches the
supply voltage at the ballast. Low voltage will cause low light output, poor
lumen maintenance and reduced lamp life. High voltage will cause short lamp
life.
The circuit should be reasonably free from voltage fluctuations. Replacement
ballasts should match the particular voltage, frequency and lamp type.
The proper lamp type should be used for the ballast in installation. Incorrect
matching of lamp and ballast may result in short lamp life or lamps going on
and off repeatedly.
Lamps should be handled carefully to avoid breakage.
Lamp breakage. Check lamps for cracks or scratches in the outer bulb. These
can be caused by rough handling, by contact with metal surfaces in the bulb
changer or luminaire, or by moisture falling on an overheated bulb b.
Bulb touching the luminaire, the lampholder or any other hard surface.
If the arc tube is cracked, blackened or swollen early in life, or if the
connecting leads inside the outer bulb are damaged, check for the following:
Overwattage operation. Check the ballast rating, the voltage at the ballast
and whether the proper tap on the ballast is being used.
Excessive current. Check if the ballast is shorted. Check for possible voltage
surges or transients on the supply line.
Caution: Do not replace the bulb until the circuit is checked and the cause of